Calculations for Seismic Coefficient:

Horizontal Seismic Forces:


Feq = Ah x (Dead Load + Appropriate Live Load)
Ah = Horizontal Seismic Coefficient

Ah =

I= Importance factor
I= 1.2
Z= Zone Factor as given in table 5 (Interim Specifications)

Zone No = V Zone NoZone Factor


Z = 0.36 II 0.10
R = Response reduction factor III 0.16
R = 3 Table 9 note 4 IV 0.24
T = 2 D ^0,5 V 0.36
1000 F

F= Horizontal force in kN required to be applied at the centre of mass


of the superstructure for one mm.
Horizontal deflection at the top of the pier/abutment along the
direction
Calculation of Time period: of horizontal force

Calculation of stiffness for Pier:


Dimension of shaft in long. Direction = 12.50 m
Dimension of shaft in transverse Direction(outer to outer) = 1.30 m

76
Moment of inertia in transverse direction
M.I of the section about its C.G = 211.59 m4
M.I of overall section about its C.G = 211.59 m4

Moment of inertia in longitudinal direction


M.I of the section about its C.G = 2.29 m4
Grade of concrete = 30 grade
Young's modulus of elasticity of concrete E = 27386 N/mm2
Height of shaft above the foundation = 9.617 m
Distance of C.G. of superstructure to fixity point
= 3.96 x 1000 = 11307 mm
Deflection at the tip of Abutment/Pier F x=L^3/(3E x M.I.) Longitudanat direction
F = = 130.0674 KN (For one mm deflection)

Seismic Coefficient in Longitudinal Direction


Dead Load from Superstructure (DL + LL) = 4500 KN
Total load D = 4500 KN
Time period T = 0.37 sec
Sa/g = 2.500
Ah = 0.1800

Seismic Coefficient in Transverse Direction


Dead Load from Superstructure ( DL+SIDL ) = 2250 kN
shaft Cap Load = 1872 kN
20% of Live load from superstructure = 279 kN
Total Load D = 4401 kN
Time Period T = 0.37 sec
Sa/g = 2.500
Ah = 0.1800