Physical properties
Mass flow rate of gas in= mass flow rate of gas out= 33,424.8Kg/day = 0.386 Kg/sec
=282.82KJ/s
Cp of water= 4.2KJ/kgk
Q=mcΔT
282.82 KJ/s= m * 4.2* (313-298)
M = 4.51 kg/s
For this type of heat exchanger overall coefficient will be in the range of 20-250 W/m2k. so we start
at the trial value of heat transfer coefficient of 200 w/m2k
LMTD=
[ ( T 1−t 1 ) – ( T 2−t 2 ) ]
T 1−t 2
ln [ T 2−t 1 ]
T m= 111.84 K
400−25 40−25
R=
40−25
= 25 S=
400−25
=0.04
For the heat exchanger of this type the overall heat transfer coefficient will be in the range of 20-300
W/m2K. So we start at the trial value of heat transfer coefficient of 200 W/m2K
At,
Q=UA ΔT lm
282.82∗103
A¿ = 8.6m 2
200∗109.6
We are using the split- ring floating head exchanger for efficiency and ease of cleaning ,
Cupper nickel is opted as a material of construction for the shell and tubes.
The tubes are of length 4.5m, with outer diameter of 20mm and inner diameter of 16mm with
triangular pitch 1.25
Number of tubes
On neglecting thickness of tube sheets
Area of one tube= A=πdL = 4.5* 14¿ 10 = 0.282 m Number of tubes= 8.6/0.282= 30 tubes
−3 2
−3 2
Tube cross-sectional area= A=π r 2 =
[ π ( 16∗10 ) ] =201∗10 −6
4
hi=6706.4 W /m2 K
[ ( P t – d o ) D S Lb ] −3 2
Cross- sectional flow area As= = 2.04∗10 m
Pt
flowrate
∗1
Mass velocity (gas) = 3600
=186.2
m
As s
1.10
Equivalent diameter=
d o ( P −0.917 d 2o ) = 14.4mm
2
t
400+25
Mean shell side temperature= = 212.5 °C
2
G S∗d e
Re = = 115.5
μ
C p∗μ
Pr = = 1.25
kf
j h = 5.2¿ 10−2
h s=( k f Re P 0.33 2
r ) /d e = 450.6 W /m k
Overall Coefficient
Fouling coefficient
2
Tube side fouling coefficient= hid =3000W /m k
2
Shell side fouling coefficient = h od=500 W / m k
do
1 1 1
= + +
[ ( )]
do l n
di
+
do
di
∗1
+
do
di
∗1
U o ho h od 2 kw hid hi
U o =¿ 207.3¿
Pressure drop
From fig, for
G S∗d e
Re = = 29850
μ
j f =3.9∗10 −3
2
1 ¿∗ρ U t
Pt =N p 8 j f
( ( ))
di
+ 2.5
2
= 26.6 k pa
G S∗d e
Re = = 111720
μ
From fig, at Re
j f =3∗10 −2
DS L U 2s
Δ Pt =8 j h ρ = 25.90 N / m 2
D e Lb 2
Tube side fouling factor 3000 W /m 2 k Shell side fouling factor 500 W/m2K
Tube side heat transfer 6706.4 W /m 2 k Shell side heat transfer coefficient 450.6 W/m2K
coefficient
Tube side pressure drop 26.6 Pa Shell side pressure Drop 25.90 N/m2