II. DESIGN DATA
I. BUILING 1:
1 General data
Main frame type MS1
Height (m) 12m on 5m floor level Eave height Slope (%) 5%
Width (m) 97.5 Out to out of steel column Width module 97.5m
Lenght (m) 90 Center to center of steel column Bay spacing 9@10m
2 Design load
Dead load (kN/m2) Base on structure Collateral load (kN/m2) 0.2
Purlin liveload (kN/m2) 0.57 Area of Coll load Full
Area liveload (kN/m2) 0.3 Seismic load
Wind speed (km/h) 155
Area of Wind load B Rainfall (mm/h) 216
Other load
III. MATERIAL
4 Material Specifications:
Built up Q345B
Cold Formed Z275 G450
5 Anchorbolt See in structure
6 Purlin & Girt (FM Standard)
Roof Purlin: see Zone A1,A2,A3,A4
Wall Girt: Z30024 for 2 exterior bays, lap 705x2= 1410mm
Z30018 for remain bays, lap 500x2= 1000mm
7 Roof Structure
See detail in Autocad drawings
8 Downspout & Gutter
Gutter:- Min width-0.28m; Min height-0.32m
Downspout PVC: D200
9 Wall sheeting and Roof sheeting :
Roof sheeting: ATAD Span4 with insulation Glasswool Twiga
Wall sheeting: ATAD Span9 with Insulation Rockwool
Normal Concrete
Reverse Checkered plate
Grating