You are on page 1of 1

ISO A1 594mm x 841mm

This drawing has been prepared for the use of AECOM’s client. It may not be used, modified, reproduced or relied upon by third parties, except as agreed by AECOM or as required by law. AECOM accepts no responsibility, and denies any liability whatsoever, to any party that uses or relies on this drawing without AECOM’s express written consent. Do not scale this document. All measurements must be obtained from the stated dimensions.
2
SPECIFIC NOTES:

1. STANDARD INSTALLATION FOR DB OUTGOING CIRCUITS


SHALL BE SINGLE CORE XLPE/LSZH INSULATED CABLE
UNLESS OTHERWISE SPECIFIED.

2. ALL OUTGOING CIRCUIT TO EXTERNAL & ROOF LEVEL


SHALL BE MULTICORE XLPE/LSZH INSULATED CABLE
INSTALLED ON CABLE TRAY.
Approved: MRS

Project

BAH053
Checked: YK

Notes
1. All dimensions shown in millimeters.
2. This drawing shall be read in conjunction with all
associated equipment schedules and mechanical,
1 08.09.17 CC/MS 1 08.09.17 CC/MS 1 08.09.17 CC/MS electrical, structural and architectural drawings.
Designer: MS

Location: Electrical Room -3/4 Rev Date By/Chk/App Location: Electrical Room -1/2 Rev Date By/Chk/App Location: Electrical Room -1/2 Rev Date By/Chk/App 3. All service routes, equipment locations &
service/maintenance space shall be checked
Distribution Board Ref: HUPP/4C4 Distribution Board Ref: HUPP/4C5 Distribution Board Ref: HUPP/4C6 against fully detailed architectural, structural &
Supply From:HUPP/4C (In Catcher Rm 4) Supply From: HUPP/4C (In Catcher Rm 4) Supply From:HUPP/4C (In Catcher Rm 4) specialist service drawings.
Woolverstone House Woolverstone House Woolverstone House 4. All dimensions shall be checked on site.
61 Berners Street 61 Berners Street 61 Berners Street
Number of TP Ways: 24 Volts: 415/240V Distribution board to have a
(access on Eastcastle Street) Number of TP Ways: 24 Volts: 415/240V Distribution board to have a
(access on Eastcastle Street) Number of TP Ways: 24 Volts: 415/240V Distribution board to have a
(access on Eastcastle Street)
5. The contractor shall fully comply with all relevant
minimum of 20% spare minimum of 20% spare minimum of 20% spare
Project Management Initials:

London W1T 3NJ UK London W1T 3NJ UK London W1T 3NJ UK standards, regulations, standard codes of practice,
capacity in the outgoing ways capacity in the outgoing ways capacity in the outgoing ways
Tel +44(0) 20 7299 8260 Tel +44(0) 20 7299 8260 Tel +44(0) 20 7299 8260 methods of working, and good practice.
at practical completion. at practical completion. at practical completion.
Incoming Device Rating/Type:100 A / MCB Phases: 3Ø
Fax +44(0) 20 7299 8294
Incoming Device Rating/Type:100 A / MCB Phases: 3Ø
Fax +44(0) 20 7299 8294
Incoming Device Rating/Type:100 A / MCB Phases: 3Ø
Fax +44(0) 20 7299 8294 6. Coordination working drawings, installation
www.red-eng.com www.red-eng.com www.red-eng.com drawings and buildswork drawing shall be prepared
by the contractor.
Notes: 1) 72Way Pan Assembly minimum. Contractors to be Notes: 1) 72Way Pan Assembly minimum. Notes:1) 72Way Pan Assembly minimum. Contractors to be 7. Dimensions shall not be scaled from the drawing.
provided for lighting circuits. Contractors to be provided for lighting circuits. provided for lighting circuits. The contractor shall be responsible for obtaining all
2) Emergency lighting circuits to be controlled via CTU 2) Emergency lighting circuits to be controlled 2) Emergency lighting circuits to be controlled via CTU
and in accordance with BS:5266 via CTU and in accordance with BS:5266 and in accordance with BS:5266 dimensions and levels on site for actual setting out
RED Job No:100103 RED Job No:100103 RED Job No:100103 of works.
CKT Load Name No of Elements Protective Device Category Protective Device Type Protective Device Rating CKT Load Name No of Elements Protective Device Category Protective Device Type Protective Device Rating CKT Load Name No of Elements Protective Device Category Protective Device Type Protective Device Rating
R1 Emergency Lighting Control MCB 1 C MCB 6A R1 Emergency Lighting Control MCB 1 C MCB 6A R1 Emergency Lighting Control MCB 1 C MCB 6A
Y1 Lights Electrical Room 8 C MCB 10 A Y1 Lights Electrical Room 8 C MCB 10 A Y1 Lights Electrical Room 8 C MCB 10 A
B1 Lights Battery Room 6 C MCB 10 A B1 Lights Battery Room 6 C MCB 10 A B1 Spare - C MCB 10 A
R2 Lights Electrical Room 8 C MCB 10 A R2 Lights Electrical Room 8 C MCB 10 A R2 Lights Electrical Room 9 C MCB 10 A
Y2 Lights Electrical Room 8 C MCB 10 A Y2 Lights Electrical Room 4 C MCB 10 A Y2 Spare - C MCB 10 A
B2 Spare - C MCB 10 A B2 Spare - C MCB 10 A B2 Spare - C MCB 10 A
R3 Spare - C MCB 10 A R3 CRAH E2-3 EPMS Elec. Rm. 1 C MCB 10 A R3 Spare - C MCB 10 A
Y3 CRAH E4-3 EPMS Elec. Rm. 1 C MCB 10 A Y3 CRAH E2-2 EPMS Elec. Rm. 1 C MCB 10 A Y3 CRAH E1-4 EPMS Elec. Rm. 1 C MCB 10 A
B3 CRAH E3-5 EPMS Elec. Rm. 1 C MCB 10 A B3 CRAH E2-1 EPMS Elec. Rm. 1 C MCB 10 A B3 CRAH E1-5 EPMS Elec. Rm. 1 C MCB 10 A CABLE SCHEDULE
R4 AMCOP B Elec. Rm. 1 C MCB 10 A R4 AMCOP B Elec. Rm. 1 C MCB 10 A R4 AMCOP B Elec. Rm. 1 C MCB 10 A
Cable Line CPC Cable Line
Y4 AMCOP A Elec. Rm. 1 C MCB 10 A Y4 AMCOP A Elec. Rm. 1 C MCB 10 A Y4 AMCOP A Elec. Rm. 1 C MCB 10 A MCB Rating Size Size
B4 Spare - C MCB 10 A B4 Door Magnetic Holds - Electrical Room 1 C MCB 10 A B4 Spare - C MCB 10 A
R5 EPMS Panel Elec. Rm. 1 C MCB 10 A R5 EPMS Panel Elec. Rm. 1 C MCB 10 A R5 EPMS Panel Elec. Rm. 1 C MCB 10 A 10A 2.5mm² 2.5mm²
Y5 VESDA Panel Elec. Rm. 1 C MCB 10 A Y5 VESDA Panel Elec. Rm. 1 C MCB 10 A Y5 VESDA Panel Elec. Rm. 1 C MCB 10 A
20A 4mm² 4mm²
B5 Spare - C MCB 10 A B5 Spare - C MCB 10 A B5 Spare - C 1A 10 A
R6 PURGE Panel DH 1 C MCB 10 A R6 PURGE Panel Elec. Rm. 1 C MCB 10 A R6 Spare 1 C MCB 10 A 32A 6mm² 6mm²
Y6 Generator xA ACB Panel EPMS 1 C MCB 10 A Y6 Generator xA ACB Panel EPMS 1 C MCB 10 A Y6 Generator xA ACB Panel EPMS 1 C MCB 10 A 40A 10mm² 10mm²
B6 Generator xB ACB Panel EPMS 1 C MCB 10 A B6 Generator xB ACB Panel EPMS 1 C MCB 10 A B6 Generator xB ACB Panel EPMS 1 C MCB 10 A
R7 PDP-A EPMS 1 C MCB 10 A R7 PDP-A EPMS 1 C MCB 10 A R7 PDP-A EPMS 1 C MCB 10 A 63A 16mm² 16mm²
Y7 PDP-B EPMS 1 C MCB 10 A Y7 PDP-B EPMS 1 C MCB 10 A Y7 PDP-B EPMS 1 C MCB 10 A
B7 HSDB-Mechanical Board EPMS Elec. Rm. 1 C MCB 10 A B7 HSDB-Mechanical Board EPMS Elec. Rm. 1 C MCB 10 A B7 HSDB-Mechanical Board EPMS Elec. Rm. 1 C MCB 10 A
R8 USS-B EPMS 1 C MCB 10 A R8 USS-B EPMS 1 C MCB 10 A R8 USS-B EPMS 1 C MCB 10 A
Y8 USS-A EPMS 1 C MCB 10 A Y8 USS-A EPMS 1 C MCB 10 A Y8 USS-A EPMS 1 C MCB 10 A
B8 BMS Panel DPU AC-01 1 C MCB 10 A B8 BMS Panel DPU AC-01 1 C MCB 10 A B8 BMS Panel DPU AC-01 1 C MCB 10 A
R9 BMS Panel DPU AC-02 1 C MCB 10 A R9 BMS Panel DPU AC-02 1 C MCB 10 A R9 BMS Panel DPU AC-02 1 C MCB 10 A
Y9 BMS Panel DPU AC-03 1 C MCB 10 A Y9 BMS Panel DPU AC-03 1 C MCB 10 A Y9 BMS Panel DPU AC-03 1 C MCB 10 A
B9 BMS Panel DPU AC-04 1 C MCB 10 A B9 BMS Panel DPU AC-04 1 C MCB 10 A B9 Spare - C MCB 10 A
R10 BMS Panel DPU AC-05 1 C MCB 10 A R10 BMS Panel DPU AC-05 1 C MCB 10 A R10 Spare - C MCB 10 A
Y10 Spare - C MCB 10 A Y10 Spare - C MCB 10 A Y10 Spare - C MCB 10 A
B10 VESDA Panel DH 1 C MCB 10 A B10 VESDA Panel DH 1 C MCB 10 A B10 Spare - C MCB 10 A
R11 VESDA Panel DH 1 C MCB 10 A R11 Spare - C MCB 10 A R11 Spare - C MCB 10 A
Y11 VESDA Panel DH 1 C MCB 10 A Y11 VESDA Panel DH 1 C MCB 10 A Y11 Spare - C MCB 10 A
B11 VESDA Panel DH 1 C MCB 10 A B11 Spare - C MCB 10 A B11 Spare - C MCB 10 A
R12 Spare - C MCB 10 A R12 Spare - C MCB 10 A R12 Spare - C MCB 10 A
Y12 UPS-A EPMS Elec. Rm. 1 C MCB 10 A Y12 UPS-B EPMS Elec. Rm. 1 C MCB 10 A Y12 UPS-A EPMS Elec. Rm. 1 C MCB 10 A
B12 UPS-B EPMS Elec. Rm. 1 C MCB 10 A B12 UPS-A EPMS Elec. Rm. 1 C MCB 10 A B12 UPS-A EPMS Elec. Rm. 1 C MCB 10 A
R13 Sounder Unit DH 1 C MCB 10 A R13 Sounder Unit DH 1 C MCB 10 A R13 Sounder Unit DH 1 C MCB 10 A
Y13 BMS Panel DPU AC-06 1 C MCB 10 A Y13 Spare - C MCB 10 A Y13 Spare - C MCB 10 A
B13 Security Panel DH 1 C MCB 10 A B13 Security Panel DH 1 C MCB 10 A B13 Security Panel DH 1 C MCB 10 A
R14 Spare - C MCB 10 A R14 Spare - C MCB 10 A R14 Spare - C MCB 10 A
Y14 High Temp Alarm Panel DH+Elec 1 C MCB 10 A Y14 High Temp Alarm Panel DH+Elec 1 C MCB 10 A Y14 High Temp Alarm Panel DH+Elec 1 C MCB 10 A
B14 AHU 3-14 EPMS 1 C MCB 10 A B14 AHU 2-7 EPMS 1 C MCB 10 A B14 AHU 1-1 EPMS 1 C MCB 10 A
R15 AHU 3-13 EPMS 1 C MCB 10 A R15 AHU 2-6 EPMS 1 C MCB 10 A R15 AHU 1-2 EPMS 1 C MCB 10 A
Y15 AHU 3-12 EPMS 1 C MCB 10 A Y15 AHU 2-5 EPMS 1 C MCB 10 A Y15 AHU 1-8 EPMS 1 C MCB 10 A
B15 AHU 3-11 EPMS 1 C MCB 10 A B15 AHU 2-4 EPMS 1 C MCB 10 A B15 AHU 1-9 EPMS 1 C MCB 10 A
R16 AHU 3-10 EPMS 1 C MCB 10 A R16 AHU 2-3 EPMS 1 C MCB 10 A R16 AHU 1-15 EPMS 1 C MCB 10 A
Y16 Spare - 2 C MCB 10 A Y16 Spare - 2 C MCB 10 A Y16 Spare - 2 C MCB 10 A
B16 Spare - C MCB 10 A B16 Spare - C MCB 10 A B16 Spare - C MCB 10 A
R17 Spare - C MCB 10 A R17 Spare - C MCB 10 A R17 Spare - C MCB 10 A
Y17 Spare - C MCB 10 A Y17 Spare - C MCB 10 A Y17 Spare - C MCB 10 A
B17 Spare - C MCB 10 A B17 Spare - C MCB 10 A B17 Spare - C MCB 10 A
R18 Spare - C MCB 10 A R18 Spare - C MCB 10 A R18 Spare - C MCB 10 A
2
Y18 Spare - C MCB 10 A Y18 Spare - C MCB 10 A Y18 Spare - C MCB 10 A
B18 Spare - C MCB 10 A B18 Spare - C MCB 10 A B18 Spare - C MCB 10 A Issue/Revision
R19 Spare - C MCB 10 A R19 Spare - C MCB 10 A R19 Spare - C MCB 10 A
Y19 Spare - C MCB 10 A Y19 Spare - C MCB 10 A Y19 Spare - C MCB 10 A
2 08/09/17 100% Design
B19 Spare - C MCB 10 A B19 Spare - C MCB 10 A B19 Spare - C MCB 10 A
R20 Spare - C MCB 10 A R20 Spare - C MCB 10 A R20 Spare - C MCB 10 A 1 11/08/17 100% Design
Y20 Spare - C MCB 10 A Y20 Spare - C MCB 10 A Y20 Spare - C MCB 10 A
B20 Spare - C MCB 10 A B20 Spare - C MCB 10 A B20 Spare - C MCB 10 A 0 31/07/17 100% Design
R21 Spare - C MCB 10 A R21 Spare - C MCB 10 A R21 Spare - C MCB 10 A
Rev Date Description
Y21 Spare - C MCB 10 A Y21 Spare - C MCB 10 A Y21 Spare - C MCB 10 A
B21 Spare - C MCB 10 A B21 Spare - C MCB 10 A B21 Spare - C MCB 10 A
R22 Spare - C MCB 10 A R22 Spare - C MCB 10 A R22 Spare - C MCB 10 A
Y22 Spare - C MCB 10 A Y22 Spare - C MCB 10 A Y22 Spare - C MCB 10 A
B22 Spare - C MCB 10 A B22 Spare - C MCB 10 A B22 Spare - C MCB 10 A
R23 Spare - C MCB 10 A R23 Spare - C MCB 10 A R23 Spare - C MCB 10 A
Y23 Spare - C MCB 10 A Y23 Spare - C MCB 10 A Y23 Spare - C MCB 10 A
B23 Spare - C MCB 10 A B23 Spare - C MCB 10 A B23 Spare - C MCB 10 A
R24 Spare - C MCB 10 A R24 Spare - C MCB 10 A R24 Spare - C MCB 10 A
Y24 Spare - C MCB 10 A Y24 Spare - C MCB 10 A Y24 Spare - C MCB 10 A
B24 Spare - C MCB 10 A B24 Spare - C MCB 10 A B24 Spare - C MCB 10 A

Purpose of Issue

100% Design
Project Number

100103
Sheet Title

BAH 053_Askar
Electrical Services
Panel Schedule
HUPP Panels (Sheet 2 of 3)
Agile Number
800-029798-001

Sheet Number

BAH053-RED-00-XX-DR-E-721
Scale: NTS @ A1 Rev: 2

You might also like