Professional Documents
Culture Documents
5B
LAB EXPERIMENT # 5B
Assembling the common current transformer circuit for measurement on three-phase network.
EQUIPMENT
THEORY
The Current Transformer ( C.T. ), is a type of “instrument transformer” that is designed to produce
an alternating current in its secondary winding which is proportional to the current being measured in
its primary. Current transformers reduce high voltage currents to a much lower value and provide a
convenient way of safely monitoring the actual electrical current flowing in an AC transmission line
using a standard ammeter. The principal of operation of a basic current transformer is slightly
different from that of an ordinary voltage transformer.
The secondary winding however, may have a large number of coil turns wound on a laminated core
of low-loss magnetic material. This core has a large cross-sectional area so that the magnetic flux
density created is low using much smaller cross-sectional area wire, depending upon how much the
current must be stepped down as it tries to output a constant current, independent of the connected
load.
The secondary winding will supply a current into either a short circuit, in the form of an ammeter, or
into a resistive load until the voltage induced in the secondary is big enough to saturate the core or
cause failure from excessive voltage breakdown.
Unlike a voltage transformer, the primary current of a current transformer is not dependent of the
secondary load current but instead is controlled by an external load. The secondary current is usually
rated at a standard 1 Ampere or 5 Amperes for larger primary current ratings.
41
Lab No. 5B
CURRENT TRANSFORMERS:
The following circuit in Figure 5B.1 is used to measure the conductor currents in a three-phase
system; this circuit is usually called a three-transformer three-phase system.
In order to maintain unambiguous potential relationships on the secondary side, one terminal
(usually terminal k) must be grounded.
42
Lab No. 5B
PROCEDURE:-
Assemble the circuit according to the foregoing topographic diagram in Figure 5B.2.
Do not forget that the current transformer may not be operated in open circuit on its secondary
side!
The resistive load, located in the primary circuit, is star connected and set to resistance value
R6 for every phase.
Connect the three-phase current transformer so that the resulting current transformation ratio
is 1:1.
Starting from 0 V, increase the value of the supply voltage to obtain 1 A on the primary
circuit.
Measure the three primary current alternately and read off the secondary currents with the
neutral conductor N connected or disconnected.
N connected N disconnected
N connected N disconnected
IL1 (A)
I1 (A)
IL2 (A)
I2 (A)
IL3 (A)
I3 (A)
The three measured currents must be approximately equal in both cases; slight deviations may be
explained by the components tolerances.
N connected N disconnected
I1 (A) ………… (1) …………(0.9)
I2 (A) …………(0.7) …………(0.75)
I3 (A) …………(0.7) …………(0.75)
Now, when the circuit is not alive, disconnect the conductor L3 at the output side of the three phase
power supply.
Repeat the above measurements.
N connected N disconnected
I1 (A) ………… (1) …………(0.68)
I2 (A) …………(0.7) …………(0.7)
I3 (A) …………(0) …………(0)
Note: The values in brackets are for information only.
43
Lab No. 5B
CONNECTION DIAGRAM:
CONCLUSION:
44
Lab No. 5B
Needs Total
Category Excellent 8 Good 6 Satisfactory 4
improvement 2 (40)
Clearly describes the Adequately Describes the Cannot describe
objectives of lab. describes the objectives but the objectives of
Understands possible objectives, but misses some the lab, or what
Objectives and sources of errors and cannot discuss details. Cannot was learnt,
Results their effects. possible sources discuss possible sources of errors
Suggests ways to of errors and their sources of error or and their effects
minimize them. effects their effects
Signature:
45