You are on page 1of 1

Sl.

Description Details
No.
VI
Fans
I
Axial flow, Multi-blade construction with the blades of aero foil section
1 Type
propeller type and with adjustable pitch.
Drive motor shall have at least 10% margin over the shaft power
2 Drive arrived at considering the transmission efficiency. maximum fan
power consumption.
3 Drive motor suitable for VFD No
VIII Gear Box
1 Gear box service factor Minimum 2
2 Type of Gear Box Spiral bevel or Spiral bevel cum helical type
IX Material of Construction
1 Cold water basin / sump & Sludge pit RCC (Basin with partition wall for each cells)
2 Casing & superstructure Pultruded FRP
4 Aux. cooling tower roof (top deck) FRP
5 Fan stack Pultruded FRP
6 Supporting structures on fan Deck MSHDG
7 Hot water distribution header PVC
8 Hot water distribution spray nozzles Non clog type Poly Propylene / Aluminium alloy sprinkler
9 Fills PVC
10 Fill Support MSHDG / GRP Pultruded frames
11 Louvers FRP
12 Drift eliminators PVC
13 Fan blades FRP with epoxy resin
14 Fan hub Stainless steel Hot Dipped Galvanized (HDG) Steel
15 Fan drive shaft Carbon fibre material Stainless Steel
16 Oil Lines SS 304 gear reducer oil piping
17 CAT (Cage) ladder MSHDG / Pultruded FRP
Double handrail of Hot dipped galvanized steel pipe, 32 mm nominal
18 Handrails
diameter / Pultruded FRP
X Design parameters
1 Water Loading 15 TPH / sq.m.
2 Air exit velocity at stack inlet 4.5 m/sec.
3 Air exit velocity at stack outlet Minimum 6 m/sec.
4 L/G Ratio 1.5
5 Average fill air velocity Minimum 1.8 m/sec

You might also like