Saudi Aramco Inspection Checklist: Exhaust Fan Installation Inspection SAIC-K-4002 15-Dec-09 Hvac
Saudi Aramco Inspection Checklist: Exhaust Fan Installation Inspection SAIC-K-4002 15-Dec-09 Hvac
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
All exhaust fans shall have back draft dampers which shall close when SAES-K-001
A3
fan is off. Para 4.8.9.2
SAES-K-001
A4 All fans shall be isolated from their ducts by flexible connections.
Para 4.8.14.3
Exhaust fan used for ventilating the Battery Room shall have their
SAES-K-002
A7 exhaust point (air outlet) located in the ceiling or its upper edge flush with
Para 6.4
ceiling if it is located in a wall.
Fans and their Motors shall be accessible for servicing and maintenance SAES-K-100
A8
(UMC Para 503.1) Section 1
REMARKS:
REFERENCE DOCUMENTS:
1-SAES-K-001 -- Heating, Ventilating and Air Conditioning (HVAC), 25 November, 2006
2-SAES-K-002 -- Air Conditioning System for Essential Operating Facilities 31 May , 2004
3- Uniform Mechanical Code (UMC), 1997
Page 1 of 2