Non Destructive / Semi Destructive Testing (for RCC Structure) Results
Name of Laboratory : SMVDSR GEOTECH RESEARCH & QUALITY CONTROL LAB
NABL Accreditation No : NA
Date of Survey : 14/09/2020
Facility Name : CHC KHALTSE, LEH
Facility Code : Block-A
Building Block Name : HOSPITAL BUILDING
Building Block Code : LA-LE-16-A
Block : LEH
District : LEH
State : LADAKH (UT)

1 Masonry Unit
Masonry Type –(ASHLAR STONE MASONRY)
Floor Sr. No. Tests
i. Dimensions (mm) MASONRY UNIT- Sample 1 310MMX325MM
ii. Dimensions (mm) MASONRY UNIT-Sample 2 225mmx367mm
iii. Water absorption (%) Sample 1 0.34%
Ground
iv. Water absorption (%)Sample 2 1.45%
v. Compressive strength (N/mm²) Sample 1 26
vi. Compressive strength (N/mm²) Sample 2 24
i. Dimensions (mm) MASONRY UNIT- Sample 1 410mmx321mm
ii. Dimensions (mm) MASONRY UNIT-Sample 2 370mmx235mm
iii. Water absorption (%) Sample 1 0.22%
First
iv. Water absorption (%)Sample 2 0.32%
v. Compressive strength (N/mm²) Sample 1 23
vi. Compressive strength (N/mm²) Sample 2 27

2 Mortar Composition (Based on chemical analysis) as per ASTM C-1084-97


Floor Sr. No. Tests Composition
i. Mortar Sample 1 1:2.4
Ground
ii. Mortar Sample 2 1:7.9
i. Mortar Sample 1 1:4.6
First
ii. Mortar Sample 2 1:7.8

3 Footing Pit
Sr. Nomenclature Dimension of Footing Depth of Footing Sectional Drawing Material of Footing
No. (in metre) (As- Built)
i. FP1 1.60*1.60 1.00 Section-A RCC
ii. FP2 1.60*1.60 1.00 Section-A RCC
FP- Footing Pit

Smvdsr
Page 1
Head office Dr.S R Singh complex.village Bhajmasta Distt. And Tehsil Ramban Jammu and Kashmir (INDIA)
Pin Code 182144 Tele,cell No:-9419900222,08803278230, E-mail.dr.srsbms@yahoo.in,smvdsr@gmail.com, Web.Site.www.smvdsr.devhub.com
Cooperate office:- smvdsr Udhampur,Sikkim,Rajastan, Punjab,Himichal, Maharastra,Goa Nepal,Bhutan,Srilanka,China,
AN ISO 9001-2015.ISO 17025 CERTIFIED COMPANY

Member of:-1-Canada’s Society of Petroleum and hydro Energy Geoscientist,


2- American Society for Testing and Material.
3- IPMS INDIA
4- American Society of Geology.
5- DRDO(SASE) defense Research and Development Origination Govt. Of India.

4 Rebound Hammer
Average Compressive
Inclination
Nomenclature Readings of 5 Strength
Floor Sr. No. Angle
readings (N/mm²)
Readings 1 2 3 4 5 6 7
i. RHF1 32 33 35 36 34 37 31 -45 34 28
ii. RHF2 48 30 21 39 33 32 36 -45 34 30
iii. RHC1 32 31 32 33 36 39 34 +90 33 28
iv. RHC2 43 44 45 46 47 40 41 +90 43 38
v. RHC3 32 34 36 38 30 32 22 +90 32 20
vi. RHC4 31 36 29 22 26 21 36 +90 28 14
Ground vii. RHC5 36 32 26 39 32 33 41 +90 33 20
viii. RHB1 41 36 38 41 38 39 40 +90 39 32
ix. RHB2 42 44 41 30 36 39 29 +90 37 28
x RHB3 28 31 39 37 32 31 32 +90 33 28
xi RHB4 31 33 40 36 41 33 36 +90 35 30
xii RHB5 25 28 31 34 40 41 26 +90 31 22
xiii. RHS1 27 29 36 39 33 39 45 -90 36 32
i. RHC1 41 44 45 31 34 41 43 +90 38 36
ii. RHC2 40 38 41 44 46 40 39 +90 40 38
iii. RHC3 29 36 37 36 39 42 21 +90 35 30
iv. RHC4 29 32 41 45 36 50 33 +90 37 28
v. RHC5 30 34 36 31 34 40 36 +90 34 30
vi. RHB1 31 33 39 32 31 29 39 +90 33 20
First vii. RHB2 33 32 35 36 34 41 41 +90 32 20
viii. RHB3 35 36 41 42 30 33 27 +90 35 30
ix. RHB4 42 44 35 39 38 36 36 +90 38 36
x. RHB5 38 36 40 44 41 45 45 +90 50 50
xi. RHS1 35 46 41 44 45 41 41 -90 42 42
xii. RHS2 41 45 32 38 36 39 36 -90 38 36
xiii. RHS3 38 37 34 39 42 38 32 -90 37 28

RHF- Rebound hammer footing; RHC- Rebound hammer at column; RHB- Rebound hammer at beam; RHS- Rebound hammer at
slab.

5 Ultrasonic Pulse Velocity

Nomencla Pulse Average


Sr. Readings Transmission Average of 5 Quality of
Floor ture Velocity Velocity
No. Method readings Concrete
(Km/sec) (Km/sec)
Readings 1 2 3 4 5
i UPVC1 3.03 2.94 3.12 3.22 3.03 Direct 3.06 3.06 3.06 Doubtful
ii. UPVC2 3.12 2.91 3.29 2.29 2.60 Direct 2.84 2.84 2.84 Doubtful
Ground
iii. UPVB1 3.03 2.88 3.15 2.58 2.83 Direct 2.89 2.89 2.89 Doubtful
Floor
iv. UPVB2 3.12 3.09 3.06 3.00 2.94 Direct 3.04 3.04 3.04 Doubtful
v. UPVS1 3.09 3.06 2.94 2.58 2.56 Indirect 2.84 2.84 2.84 Medium
i. UPVC1 3.12 3.22 3.21 2.88 2.98 Direct 3.08 3.08 3.08 Medium
ii. UPVC2 3.15 3.03 3.29 2.94 2.97 Direct 3.07 3.07 3.07 Doubtful
First
iii. UPVB1 3.26 3.22 3.12 3.19 1.71 Direct 2.90 2.90 2.90 Doubtful
Floor
iv. UPVB2 2.94 3.06 3.29 3.37 3.40 Direct 3.21 3.21 3.21 Doubtful
v. UPVS1 3.12 3.26 3.06 3.12 2.71 Indirect 3.05 3.05 3.05 Doubtful

UPVC- Ultrasonic pulse velocity at column; UPVB- Ultrasonic pulse velocity at beam; UPVS- Ultrasonic pulse velocity at slab.

Smvdsr
Page 2
Head office Dr.S R Singh complex.village Bhajmasta Distt. And Tehsil Ramban Jammu and Kashmir (INDIA)
Pin Code 182144 Tele,cell No:-9419900222,08803278230, E-mail.dr.srsbms@yahoo.in,smvdsr@gmail.com, Web.Site.www.smvdsr.devhub.com
Cooperate office:- smvdsr Udhampur,Sikkim,Rajastan, Punjab,Himichal, Maharastra,Goa Nepal,Bhutan,Srilanka,China,
AN ISO 9001-2015.ISO 17025 CERTIFIED COMPANY

Member of:-1-Canada’s Society of Petroleum and hydro Energy Geoscientist,


2- American Society for Testing and Material.
3- IPMS INDIA
4- American Society of Geology.
5- DRDO(SASE) defense Research and Development Origination Govt. Of India.

6 Core Test / CAPO Test


Compressive Strength
Floor Sr. No. Nomenclature
(N/mm2)
i CTF1 18
ii CTF2 21
Ground
iii CTC1 19
iv CTC2 18
First v CTB1 17
CTF- Core / Capo test at Footing; CTC- Core / Capo test at Column; CTB- Core / Capo test at Beam

7 Rebar Locator Test


Floor Sr. No. Nomenclature Rebar Locator Results Drawing / Sketch with details Remarks
i. RLF1 RCC Footing Found Section-A
Ground ii. RLF2 RCC Footing Found Section-A
Floor iii. RLC1 8 nos bar 16 mm Section-C 450 mm x 450 mm
iv. RLB1 4 nos bar 16 mm Section-B 300 mm x 300 mm
i. RLC1 6 nos bar 16 mm& 2 nos bar 12 mm Section-C 450 mm x 450 mm
First Floor
ii. RLB1 6 nos bar 16 mm& 2 nos bar 12 mm Section-B 300 mm x 300 mm

RLF- Rebar locator at footing; RLC- Rebar locator at column; RLB- Rebar locator at beam.

Smvdsr
Page 3
Head office Dr.S R Singh complex.village Bhajmasta Distt. And Tehsil Ramban Jammu and Kashmir (INDIA)
Pin Code 182144 Tele,cell No:-9419900222,08803278230, E-mail.dr.srsbms@yahoo.in,smvdsr@gmail.com, Web.Site.www.smvdsr.devhub.com
Cooperate office:- smvdsr Udhampur,Sikkim,Rajastan, Punjab,Himichal, Maharastra,Goa Nepal,Bhutan,Srilanka,China,
AN ISO 9001-2015.ISO 17025 CERTIFIED COMPANY

Member of:-1-Canada’s Society of Petroleum and hydro Energy Geoscientist,


2- American Society for Testing and Material.
3- IPMS INDIA
4- American Society of Geology.
5- DRDO(SASE) defense Research and Development Origination Govt. Of India.

INTERIM SUBMISSION TEMPLATE


Geotechnical/Geophysical Investigation Results

Name of Laboratory : SMVDSR GEOTECH RESEARCH & QUALITY CONTROL LAB


NABL Accreditation No : NA
Date of Survey : 14/09/2020
Facility Name : CHC KHALTSE, LEH
Facility Code : Block-A
Building Block Name : HOSPITAL BUILDING
Building Block Code : LA-LE-16-A
Block : LEH
District : LEH
State : LADAKH (UT)

S.NO Parameter Result


1 Soil Investigation
a Foundation
i Ultimate Bearing capacity (KN/m²) 289.29
[at base of existing footing]
ii Depth of foundation (As Built) (mm) 1000
iii Width of Foundation (As Built) (mm) 1600*1600
iv Coefficient of Subgrade Reaction (KN/m3). 11571.60
v Net safe Bearing Capacity (KN/m2) 192.86 (Factor of Safety = 1.5)

b Soil Characteristics
i 'N' value from SPT. N Value = Refusal
ii Sub Soil Strata. Boulders mixed with Gravels, pebbles and silty sand
iii Natural Moisture Content. 7.3%
iv Density (KN/m³). 21.00
v C. 2.06
vi Φ. 26 Degree
vii Liquid Limit. NP
viii Plastic Limit. NP
ix Liquefaction Potential. Non – Liquefiable
c Ground Water table Not Encountered Up to the Depth Of 2.0m during the month of
September

Smvdsr
Page 4
Head office Dr.S R Singh complex.village Bhajmasta Distt. And Tehsil Ramban Jammu and Kashmir (INDIA)
Pin Code 182144 Tele,cell No:-9419900222,08803278230, E-mail.dr.srsbms@yahoo.in,smvdsr@gmail.com, Web.Site.www.smvdsr.devhub.com
Cooperate office:- smvdsr Udhampur,Sikkim,Rajastan, Punjab,Himichal, Maharastra,Goa Nepal,Bhutan,Srilanka,China,
N.G.L C/C STIRRUPS
25MM COVER

8 NOS.

400
1000

450
250

450
300

P.C.C SECTION C
1600

SECTION A

C/C STIRRUPS
25MM COVER

4 NOS.
300

300

SECTION B
Geotechnical Investigation at CHC Khaltse

Pit Excavation at CHC Khaltse A Block (Hospital)


Rebound Hammer test at CHC Khaltse A Block

Ultrasonic Pluse Velocity Test at CHC Khaltse A Block


Core Cutting At CHC Khaltse A Block

Laboratory Testing of CHC Khaltse A Block


v ' .il.

i!flii ii
i'E::r

ta i 'i
!?
iq
p

1
j;

!E
It
:r
lt
i'
ari I
!
!; I
itL IE

rt :l
(')
rlfflifififfJtff ]l l|1 :
r: i*

^iai i;,
,],

Eii
li:t
!.
t
EI
E
,;
i;i:iii !i
u
;:iii;"

!;' l

:i:
tl, ii
22
l q$
;-l 4
!1
i i!

EI
:f
I
i' I
;iEa I
ieAl l l
3:
iiHi
!i
a
tl
tl -' -q
s i i:!

i !
I
B
I
I
:E; E
e i
: Ed;

I ilt

You might also like