PD Sandvik CH&CS CRUSHER Vegapuls 67 and Vegamet 624
1. Introduction
1.1 Equipment information.......................................................... 4
3. Software adjustments
3.1 General ............................................................................... 14
3.1.1 Change of language............................................... 15
3.2 Setup procedure ................................................................. 16
3.2.1 Find the sensor ...................................................... 16
3.2.2 Adjustment of minimum and maximum values ...... 17
3.2.3 Outputs .................................................................. 19
3.2.4 Damping and linearization ..................................... 20
4. Spare parts
4.1 Level sensor ....................................................................... 22
4.2 Vegamet 624....................................................................... 23
1 Sensor
2 Plug-in connector
1
Vegamet 624
1 Signal conditioning
instrument 2
2 Plug-in socket
1 2 3
1 Sensor position
2 Angle adjustment
points
3 Mounting to
crusher
3
The Vegapuls 67 sensor is to be placed on the flange of the open feed hopper
or on a suitable place of the crusher structure.
a) Drill two holes on the location spot according to the measurements of the
Vegapuls 67 sensor holder assembly.
b) Mount the holder on the flange with two screws, washers and nuts.
c) To adjust the angle of the Vegapuls 67 sensor: loosen the nuts of the
holder assembly’s parts and direct the Vegapuls 67 sensor according to
previous guiding principles.
d) When finished tighten the nuts to secure the adjusted position.
1
1 Sensor position
2 White mounting
flange 2
3 Black mounting 3
flange
4 Metal plate
construction 4
The Vegapuls 67 sensor is to be placed on the dust encapsulating top of the
closed feed hopper.
a) Decide the location of the Vegapuls 67 sensor according to previous
guiding principles.
b) When the location is set, cut out a hole in the sheet metal of the dust
encapsulating top. The size should be less than 200 x 200 mm.
c) Take away all removable parts from the metal plate construction. This
includes nuts, washers, black and white mounting flanges and the
Vegapuls 67 sensor.
d) Weld together the metal plate construction with the dust encapsulating
top so that the plate covers the hole completely.
e) Reassemble the plate with the black and white flanges and the Vegapuls
67 sensor, but do not tighten the nuts.
f) Adjust the angle of the Vegapuls 67 sensor, according to previous
guiding principles. Do this by turning the two parts of the black
mounting flange.
g) When finished, tighten the nuts to secure the adjusted position.
1 Gland
2 Vegamet
624
3 Earth bar
1 3
3.1 General
The Vegamet 624 is operated via an interface consisting of a display and four
buttons. This interface is also where the operator adjusts the setting of the
software.
1 2 3 4
1 Escape button
2 Plus button
3 Arrow button
4 OK button
A B
A Distance A
B Distance B
Procedure
To carry through the software adjustment follow procedure below:
a) Push OK-button (4) to reach the menu overview.
b) Move the indicator by pushing the arrow button (3). Do this until the
menu item “Adjustment” is marked.
c) Confirm your choice by pushing the OK button (4).
d) The following frame “Units of measurement” displays the current active
unit. To edit the displayed unit push the OK button (4). Otherwise go
directly to step g) in the instruction.
e) Move the indicator through the list of available units by pushing the
arrow button (3).
(Continued)
f) When the indicator is marking the desired unit, push the OK button (4) to
confirm the choice.
g) Browse to the next frame, “Min. adjustment”, by pushing the arrow
button (3).
h) To be able to edit the given values push the OK button (4).
i) Move the indicator by pushing the arrow button (3) and change the
active figure by pushing the plus button (2).
NOTE! It is recommended to keep the percentage value to 0% when representing the
lowest acceptable level and 100% when representing the highest acceptable
level.
3.2.3 Outputs
Output data from the Vegamet 624 can be used to simplify the operating
process of the crusher. It is possible to use both relay and/or current output.
For further output information refer to section 2.2 How to connect the
equipment. For adjustment of output data see respective instruction:
Relay output
a) If not already in the menu overview, push the OK button (4) to reach it.
b) Move the indicator by pushing the arrow button (3). Do this until it
marks the menu item “Measurement loop”.
c) Push the OK button (4) to confirm the selection.
d) Move the indicator in the listed “Measurement loop” menu by pushing
the arrow button (3).
e) Choose the menu item “Outputs” by pushing the OK button (4).
f) Move the indicator between the menu items “Relay output” and “Current
output” by pushing the arrow button (3).
g) Choose which relay output to adjust by pushing the arrow button (3).
h) When the indicator is marking the desired relay output, push the OK
button (4) to confirm the choice.
i) The following frame “Relay operating mode” displays the active
operating mode of the chosen relay output. To edit the displayed
operating mode push the OK button (4). Otherwise go directly to step l)
in the instruction. It is later also possible to program several relay
outputs that are adjusted to control different functions and operating
modes.
j) Move the indicator between the two types of protection: “Overfill
protection” and “Dry running protection” by pushing the arrow button
(3).
k) When the indicator is marking the desired type of protection, push the
OK button (4) to confirm the choice.
l) Browse to the following frame, “Basic measurement value”, by pushing
the arrow button (3).
m) To edit the current basic measurement value push the OK button (4).
Otherwise go directly to step o) in the instruction.
n) Move the indicator between the different types of basic measurement
values by pushing the arrow button (3).
o) When the indicator is marking the desired basic measurement value,
push the OK button (4) to confirm the choice.
(Continued)
3 1