Professional Documents
Culture Documents
Test Device: Excitation Curve
Test Device: Excitation Curve
Overall assessement OK
Asset
Ipn 400.0 A Object Location
Isn 1.0 A Manufacturer RITZ Company SEC
Rated burden 15.0 VA /0.80 Type ASG36-70 Country KSA
Operating burden 15.0 VA /0.80 Serial number 19/80325435 Station MOBILE SS
Standard IEC 61869-2 Core 2 Feeder M04
Application Protection Tap 1 Phase B
Class 5P Optional IEC-ID
Frequency 60.0 Hz Comment
Rct max 2.611 Ω ?
ALF 20.0
Ts
Burden
Burden cos φ: Z
V-meas I-meas
Excitation
Ls 0.001887 H Lm 32.133023 H Results at rated burden (15.00 VA) Results at operating burden (15.00 VA)
Kr 84.5 % ALF 24.90 ALFi 23.97 ALF 24.90 ALFi 23.97
Standard IEC 61869-2 εci (@ ALF=20) 0.214 % εci (@ ALF=20) 0.214 %
V-kn 320.78 V I-kn 0.0357 A Ts 2.199 s Ts 2.199 s
Ratio
Turns ratio 399.9916 Results at rated burden (15.00 VA) Results at operating burden (15.00 VA)
εt -0.0021 % Ratio 400.0 : 0.9978 Ratio 400.0 : 0.9978
Polarity OK ε -0.2246 % ∆φ 1.05 min ε -0.2246 % ∆φ 1.05 min
εc 0.2266 % εc 0.2266 %
Residual magnetism
Residual flux
Residual magnetism
Excitation curve
450.00
400.00
350.00
300.00
Voltage [V]
250.00 X1-X2
200.00
150.00
100.00
50.00
0.00
0.00 0.500 1.00 1.50 2.00 2.50 3.00 3.50
Ie [A]
1/2
Current ratio error in % at % of rated current at rated burden (15.00 VA)
VA/cos φ 1.00 % 5.00 % 10.00 % 20.00 % 50.00 % 100.00 % 120.00 % 200.00 %
15/0.8 -1.0560 -0.5159 -0.4074 -0.3287 -0.2591 -0.2246 -0.2169 -0.1990
7.5/0.8 -0.8247 -0.3491 -0.2675 -0.2136 -0.1633 -0.1379 -0.1325 -0.1203
3.75/1 -0.2682 -0.1495 -0.1229 -0.1033 -0.0834 -0.0716 -0.0690 -0.0630
1.875/1 -0.1947 -0.1140 -0.0930 -0.0766 -0.0617 -0.0524 -0.0504 -0.0454
20.0000
3.75 VA
0.0000
-20.0000 1.88 VA
-40.0000
Limits
-60.0000
-80.0000
0.00 50.00 100.00 150.00 200.00 250.00
I/Ipn [%]
2/2