Professional Documents
Culture Documents
∆Vmax within a range of ±3σ . This value is compared with a First Section
21.712 0.425 11.736 17.081 3.260 6.767 1.734
Boredown
real survey value of ∆Vmax from formula (1). The ∆V10 max Second Section
21.711 0.348 9.628 13.185 2.675 6.723 1.432
A1 Boredown
value is obtained based on the maximum ∆V10 found in the Refining
21.815 0.186 5.125 6.791 1.424 3.440 1.490
survey. However, the process of calculating is based on Period
formula (2) and a reasonable scaling factor of ∆V to ∆V10 is TABLE II
sought. The statistical results of ∆V / ∆V10 of factories D1 and A1
(1) σ
ΔV = ∑
(ΔV n ) 2
n
∆V / ∆V10 μ μmax μmin
Factory / Period
4
First Section Boredown 1.837 0.449 3.998 1.355 Fig. 13. Fields V, P and Q measured results based on a rate of 1sample/cycle
on the primary side of FT of factory A1
D1 Second Section Boredown 1.723 0.286 3.262 1.354
Boredown Last Section 1.720 0.130 2.057 1.454
Figure 12 presents the survey results concerning factory D1,
First Section Boredown 1.754 0.324 3.576 1.105
and reveals that the active power is between 4MW and 57MW
A1 Second Section Boredown 1.703 0.308 2.900 1.089
while the reactive power is between 19MVAR and 72MVAR.
Refining Period 1.998 0.247 2.903 1.641
The survey results also show that load control of dc EAF is
achieved using a constant current. Apparent power is
IV. ANALYSIS OF EAF LOAD maintained almost constant, while active and reactive power
The sampling rate is adjusted to one sample/cycle and a remains complementary. The ranges of variation of P and Q
total of 3600 samples per minute to help clarify the load are almost consistent, so ∆P can increase ∆V quite
changing conditions and operating characteristics of an EAF substantially from that used in formula (3). Thus, the estimate
load. Factories D1 and A1 were selected as examples. Figures of ∆V10 for dc EAF must consider not only ∆Q but also ∆P .
8 and 9 show the survey results concerning the primary side of
furnace transformer (FT). ∆V = X S × ∆P 2 + ∆Q 2 = X S × ∆S (3)
Curves of line voltage, active power and reactive power are
Figure 13 shows the survey results of factory A1, revealing
plotted and data are sampled during the initial stage of
that the active power is between 0 and 28MW while the
meltdown, during which voltage flicker is particularly evident.
reactive power is between 0 and 35MVAR. Clearly, the
Figures 12 and 13 clearly show extreme variations in EAF
estimate of ∆V10 for ac EAF must not ignore the effect of
load.
active power variation. In particular, ∆P is major cause of
voltage flicker when the reactive power has been compensated.
Therefore, this study proposes the MCAPFM of obtaining
the ∆V10 value of EAF to overcome the disadvantages of the
traditional method. The method not only considers the reactive
power variation but also the active power variation in
calculating the estimated ∆V10 value of dc and ac EAFs. Fig.
14 and 15 show the load curve of dc and ac EAF.
significantly, the relationship between voltage fluctuation and X S = 0.00437 pu ; S FT = 82 MVA ; S B = 10 MVA
active power is quite close when EAF factories typically
install reactive power compensation equipment to suppress the ∆Q max = 82 × (1 × 1.0 − Sin 36.87° ) = 3.28 pu
high voltage flicker. Besides, the authors’ investigation found
that the electrical characteristic of the EAF load does not ∆Pmax = 82 × (Cos 36.87° − 1 × Cos( Sin −1 1.0) ) = 6.56 pu
wholly match the Gaussian Distribution Probability Mode.
Therefore, the ∆V10 value can be evaluated using the ∆S max = 6.56 2 + 3.28 2 = 7.334 pu
∆ V max /1.8 [12]. Meanwhile, surveyed results reveal that this ∆V max = 0.00437 × 7.334 = 3.205 %
way can more accurately estimate ∆V10 . Finally, ∆ V max can be
∆V10 max = 3.205 1.8 = 1.781 %
analyzed and studied as follows.
A. The ac EAF Similarly, the ∆V10max values for factories A2, A3, D2 and
D3 are also calculated. Table III compares the original design,
Qmax = 1 X 0 modification and cumulative probability value of the actual
∆Q max
'
≅ Q max × Cos 2θ r (Uncompensated) (4) field surveys of ∆V10 for the ac and dc EAF factories.
TABLE IV
∆Qmax ≅ Qmax
'
× (1 − α %) (Compensated) (5) ORIGINAL DESIGN, MODIFICATION AND CUMULATIVE PROBABILITY VALUE
OF THE ACTUAL FIELD SURVEY OF ∆V10 FOR THE EAF FACTORIES
∆Pmax ≅ Q max × Sinθ r Cosθ r (6) Original Modified Actual Field Survey
Calculation Calculation (Cumulative Probability)
∆S max = ∆Pmax + ∆Qmax
2 2
(7)
∆Q max ∆V ∆S max ∆V10max ∆V10 − 95% ∆V10 − 97.5% ∆V10 − 99.9%
Factory 10max
(MVAR
∆Vmax = X s × ∆Smax = ∆Smax MVAsc (8) )
(%) (MVA) (%) (%) (%) (%)
∆V10 max = ∆Vmax / 1.8 (9) A1 8.58 0.351 18.97 1.552 1.125 1.222 1.546
ac A2 7.41 0.162 19.18 0.837 0.665 0.725 0.929
B. The dc EAF EAF
A3 22.05 0.150 35.90 0.488 0.438 0.476 0.590
∆Qmax
'
≅ S FT ( β × Sinθ s − Sinθ α min ) (10)
D1 32.77 0.398 73.34 1.781 0.820 0.944 1.321
∆Qmax ≅ Q '
max × (1 − α %) (Compensated) (11) dc D2 41.86 0.302 69.98 1.003 0.529 0.616 1.006
EAF
∆Pmax ≅ S FT (Cosθ α min − β × Cosθ s ) (12) D3 38.71 0.350 87.89 1.592 0.948 1.077 1.505
and the actual measurement of ∆V10 . The important point is engineering from the National Taiwan University of Science and Technology
(NTUST), Taipei, Taiwan, R.O.C., in 1995 and 2003, respectively. Currently,
that the conventional means of estimating ∆V10 is inaccurate. he is an Associate Professor at Hwa Hsia Institute of Technology, Taipei,
Taiwan, R.O.C. His current research intersets lie in electric power quality and
The estimated ∆V10 max would be significantly lower than the power system.
actual value if the ∆V10 max is evaluated by the ∆Vmax /3.6
Jyh-Cherng Gu (M’92) was born in 1958. He
equation. However, we suggest that the scaling factor-1.8, received the B.S.E.E. degree from the NTUST in
arrived at herein, is adopted to replace a traditional scaling 1984. He received the M.S. and Ph.D. degree in
factor-3.6 when utilizing the MCAPFM to do the electrical engineering from the University of Texas
at Arlington in 1987 and 1992, respectively. Since
transformation between ∆Vmax and ∆V10 max . Besides, the then, he joined the NTUST as an Associate
authors’ investigations found that an estimate of ∆V10 for EAF Professor. He has been involved in research on
microcomputer-based relay, protection coordination,
must simultaneously consider the variation in active power electric power quality, and distribution automation
and reactive power. Furthermore, this study proposes for power systems.
MCAPFM to calculate the ∆V10 value for ac and dc EAFs. Ming-Ta Yang (S’04) was born in 1968. He received his B.S.E.E. degree
Meanwhile, the revised method developed here should replace from the National Taiwan University of Science and Technology in 1993,
M.S.E.E. degree from the National Yunlin University Science and Technology
the traditional method. However, survey results clearly reveal in 1998. He is currently enrolled in the Ph.D.
that the revised method can more accurately estimate ∆V10 . program in electrical engineering at National
Then, the appropriate equipment for compensating for voltage Taiwan University of Science and Technology. He
has also joined the St. John’s & St. Mary’s Institute
flicker can be installed in advance, effectively improving of Technology as a instructor since 1999. His
problems of voltage flicker. research interests include protection coordination
and power quality.
Hsin-Hung Chang was born in 1962. He received
VII. REFERENCES the B.S and M.S. degrees in electronic engineering
from the National Taiwan University of Science and
[1] Robert A. and M. Couvreur, "Arc Furnace Flicker Assessment and
Technology, Taipei, Taiwan, R.O.C., in 1985 and 1987. His research
Prediction," CIRED 12th International Conference on Electricity
interests are in the field of automatic measurement
Distribution, no. 373, vol.2, pp2.2.1-6,1993.
on power systems and the microcomputer-based
[2] IEC Publication 868: Flicker-Meter, functional and design specification,
instrument design. Currently, he is an instructor at
1986.
Hwa Hsia Institute of Technology, Taipei, Taiwan,
[3] New trend in supply problems of arc furnace for steel plants, Japanese:
R.O.C.
Elect. Eng. Soc., 1978, vol.2, no.72, pp.3-26.
[4] G. Manchur and C. C. Erven, "Development of A Model for Predicting
Flicker from Electric Arc Furnaces," IEEE Trans. Power Delivery, vol.
7, no. 1, pp. 416-426, Jan.1992.
[5] G. C. Montanari, M. Loggini, A. Cavallini, L. Pitti, and D. Zaninelli,
"Arc Furnace Model for The Study of Flicker Compensation in
Electrical Networks," IEEE Trans. on Power Delivery, vol.9, no.4,
pp.2026-2036, 1994.
[6] J. C. Gu, C. J. Wu, and J. C. chiang, "Effects of High Voltage Side
Voltage Flicker Sources on Low Voltage Side Customers," Power
Research Institute, Taiwan Power Company, 1994.
[7] C. J. Wu and L. H. Lee, "Electric Power Quality Evaluation of 161kV
Large Size Steel Plants," Power Research Institute, Taiwan Power
Company, 1995.
[8] C. J. Wu and J. C. Gu, "Measurement and Analysis of Voltage Flicker,"
Power Research Institute, Energy Commission, Ministry of Economic
Affairs, Technical Report, 2000.
[9] G. Manchur and C. C. Erven, "Development of A Model for Predicting
Flicker from Electric Arc Furnaces," IEEE Trans. Power Delivery, vol.
7, no. 1, pp. 416-426, Jan.1992.
[10] M. D. Cox, A. Mirbod, "A New Static Var Compensator for an Arc
Furnace," IEEE Trans. on Power System, vol. PWRS-1, no.3, Aug. 1986.
[11] The Survey of DC Arc Furnace, Japanese: Nihon Kou-Kan Co., NKK,
Technical Report, 1989.
[12] J. L. Guan, J. C. Gu, and C. J. Wu, " Real-time Measurement Approach
for Tracking the Actual Coefficient of ∆V / ∆V10 of Electric Arc
Furnaces," IEEE Trans. on Power Delivery, vol. 19, no. 1, pp. 309-315,
Jan. 2004.
[13] J. L. Guan, J. C. Gu, and C. J. Wu, “A Novel Method for Estimating
Voltage Flicker," IEEE Trans. on Power Delivery, vol. 20, no. 1, pp. 242-
247, Jan. 2005.
VIII. BIOGRAPHIES
Jin-Lung Guan was born in 1967. He received the
B.S.E.E. degree from the National Sun Yat-Sen
University, Kaohsing , Taiwan, R.O.C., in 1990. He
received the M.S. and Ph.D. degrees in electrical