Professional Documents
Culture Documents
Revision 02
Date 30-Dec-20
GL 0.25
w2 W1
WL
6.75
W5 W4
1.1 1.1
a 4 0.7 4 c
P= 1157.18 RM = 4521.20
Stability against Overturning and Tension
Over Turning Moment acting at the base = 378.11 kN-m
Factor of safety against overturning = (RM)/(OTM) = 11.96 Overturning Check satisfied (>1.5)
Gross safe bearing capacity of soil at 6.75m below FGL= 421.5 kN/m2
GL 0.25
w2 W1
WL
6.75
W4
1.1 1.1
a 4 0.7 4 c
P= 596.65 RM = 3307.51
Stability against Overturning & Tension
Over Turning Moment acting at the base = 208.33 kN-m
b\6 = 1.450 m
Factor of safety against oerturning = (RM)/(OTM) = 15.88 Overturning Check satisfied (>1.5)
Case 3: Inside Tank Empty with Soil outside (lateral earth pressure with surcharge):
Width of wall at the base tb = 0.70 m
Width of wall at the top tt= 0.25 m
Width of footing near water face L1 = 4 m
Width of footing near soil face L2 = 4 m
Total Height of wall (H1) = 6.75 m
Height of straight portion of wall (H2) = 0 m
Height of taper portion of wall (H4) = 6.75 m
Depth of footing below the GL (H3) = 7.85 m
Thickness of footing at the water edge (t1) = 1.1 m
Thickness of footing at soil edge (t2) = 1.1 m
Thickness of footing at face of wall (t3) = 1.1 m
Gross safe bearing capacity of soil at 6.75m below FGL= 421.5 kN/m2
GL 0.25
w2 W1
WL
6.75
W5 W4
1.1 1.1
a 4 0.7 4 c
Dist. from
point C
S.No Length(m) Breadth(m) Depth(m) Dens. Tri/Rec Load(kN) (m) Moment(kN-m)
x = (RM-OTM)/P 5.28 m
b\6 = 1.450 m
Factor of safety against oerturning = (RM)/(OTM) = 9.55 Overturning Check satisfied (>1.5)