Professional Documents
Culture Documents
Ammeter-Voltmeter Method
Wheatstone Bridge
Kelvin Double Bridge
Ammeter is replaced by
D‟Arsonval
galvanometer
Galvanometer can detect currents from (0.1
to 1) nA
Therefore for an applied voltage of 1KV,
resistance as high as 10^12 to 10 X 10^12 Ω.
Galvanometer measures IR, whereas IL is
bypassed through Guard Circuits.
Measurement of resistance of cable without conducting
sheath is same as Measurement of resistance of cable
with conducting sheath except that cable is immersed
in water in a tank.
Insulation resistance R is in parallel to C and
V (electrostatic voltmeter).
Capacitor is charged by means of a Battery
having „V‟ volts.
And is then allowed to discharge through
„R‟.
Voltage drop across capacitor at any instant
„t‟ is
If R is very large, the time for fall in voltage
is very large => Time Consuming
Leakage resistance of cable is as high as
resistance under measurement.
Following components are present
High voltage supply: 500V or 1000V
High gain amplifier
Electronic voltmeter or CRO are used
Dial on R2 is calibrated 1- 10- 100- 1000
MΩ.
R4 gives five multipliers 0.1, 1, 10, 100 and
1000.
Unknown resistance:
Itis an insulation testing instrument.
Current Coil is same as Permanent Magnet
Moving Coil Instrument.
Two voltage (potential) coils V1 and V2.
Torque is exerted by voltage coils when it
moves into a stronger field.
Torque is maximum when it is under pole face
=> pointer is at the zero end of resistance
scale.
Torque is minimum when voltage coil is in weak
magnetic field => pointer is at “infinite”
position.
At zero end, current in the current coil is very
large
At infinite end, current in the current coil is
very small.
Megger is called as Insulation tester and also
insulation resistances are large.
Voltage range controlled by Voltage selector
switch.
Test voltages 500, 1000 (or) 2500V are
generated by hand cranked generator G.
Breakdown at faults can be indicated by
sudden motion of the pointer to zero end.
Earth electrode is necessary because:
1. Protects various parts of insulation, persons
working against damage incase insulation
fails. Also provides low resistance path to
leakage currents to flow to earth.
2. Over voltage due to lightning discharge or
system faults does not attain high potential
because of earth electrode.
3. Neutral is connected to earth in 3-phase
circuits to stabilize the potential.
1) Fall of Potential Method
2) Earth Tester