You are on page 1of 1

Plant visit: Mist Cooling Tower

05.10.2013
Particulars Unit Design Value Actual Value

Cooling water flow rate M3/hr 5500 NA

CW supply temperature 30.5/31 28

CW return temperature 43 32

CW pump discharge pressure Kg/cm2G 3.2 2.68

Wet bulb temperature 29 24

Approach

a) At discharge head of return Deg C 2 4


header of 18 M
b) At discharge head of return Deg C 1.5
header of 20 M

Observations Action Taken


Actual approach is 4 deg C against design
of 2 deg C as Mist CT is running at part
load.