CHARGING PROCEDURE OF 3.

3KV BUS COUPLER

CHARGE UAA-1 THROUGH BUS COUPLER :

 PUT BUS COUPLER IN ‘TIE-1 ‘POSITION.


 ENSURE THAT THE DUMMY TIE BREAKER ON UAA-1 IS CLOSED AND THE WORKING TIE
BREAKER ON UAA-2 IS RACKED IN CONDITION.
 CLOSE BUS COULER, INCOMER TO UAA-1 FROM UAT WILL OPEN AUTOMATICALLY.
 SIMILARLY REPEAT THE PROCEDURE FOR UAA-2, IN THIS CASE PUT BUS COUPLER IN TIE-
2 POSITION.

CHARGING PROCEDURE OF 3.3KV THROUGH NORMAL


INCOMER
 BEFORE CLOSING THE BREAKER (UAA-1/2 INCOMER) , ENSURE THAT THE BREAKER
MUST BE IN RACKED IN AND SUPPLY NORMAL CONDITION.
 CLOSE INCOMER BREAKER (UAA-1/2), WORKING BUS COUPLER WILL OPEN
AUTOMATICALLY.