Genting Sanyen Power Sdn Bhd

Doc Number: Created by Dept: Action by Dept: REV : 0


1-GSP-82-3-E-012_0 Maintenance Maintenance Derived from:
Dept Dept
Valid for: O&M GSP
Prepared by : Checked by: Approved by:
Wong Kok Loon Chok Yin Thong Sailesh Chander
ECI Engineer Maintenance Manager Senior Manager

Title :

Motor Starter General Health Check

Contents

1. Objective

2. Area of Application

3. Reference Document

4. Terminology, Definitions, Abbreviations

5. Responsibilities

6. Tools & Equipments

7. Procedure

8. Enclosures

Title : Motor Starter General Health Check Rev 00 Page 1 of 3


File: 505403401.doc
Genting Sanyen Power Sdn Bhd

Responsible Rev
Function
1. Objective

1. To establish standard engineering preventive maintenance Engineer


procedure to determine the health and functionality of the motor
starter system and circuitry

2. To ensure that the motor starters are clean and in good condition so
that motors can be started reliably as well as protecting the motors
from faults.
3rd party
auditor
2. Area of Application

Maintenance Department

3 Reference Document

None

4 Terminology, Definition, Abbreviations

TOR – Thermal Overload Relay

5 Responsibilities

ECI technician is responsible to carry out the job.

ECI Supervisor is responsible to verify the data collected after the


job and highlight to the ECI Engineer if there is discrepancies

ECI Engineer is responsible to validate the collected data and


initiate action if required.

Title : Motor Starter General Health Check Rev 00 Page 2 of 3


File: 505403401.doc
Genting Sanyen Power Sdn Bhd

Responsible Rev
Function

6 Tools & Equipments

Checklist GSP ref: GSP-ECI-PM-012_0

7 Procedure
Technician
1. Apply PTW from F5 control center and inform the affected
party.
2. Follow the listed items as highlighted in the checklist and
perform several checks as below:
i. Ensure the motor is isolated from operation and inform
the operator. Turn “OFF” the MCCB.
ii. Check the general health of the starter, clean up dust,
tidy up the cables, retighten all of the terminals, etc.
iii. Disconnect the main supply cable to the motor to
perform a test on the starter.
iv. During the starter sequence, observe for any abnormality
such as humming, excessive sparking, contactor not
energizing, and contactor discontinuity.
v. After finish testing the starter, megger the insulation of
the motor from the cable end. Record down the
measured values onto the checklist.
vi. Connect back all the power cables and perform a test run
again and observe for any abnormality. Measure the
running current of the motor.
vii. Check that the TOR setting is appropriate according to
the motor rated current.

8 Enclosures

Checklist ref: GSP-ECI-PM-012_0

Title : Motor Starter General Health Check Rev 00 Page 3 of 3


File: 505403401.doc