Contractor: Consultant: End Client:

Page: 1 of 2
Project: CONSTRUCTION OF 306 VILLAS – AL SAAD
Date: 03.02.2020
TEST REPORT FOR 33 kV CABLE
To Station: NRMAH-GD Feeder No: A05
From Station: SAAD PY Feeder No.:H06
To Joint Loc. Joint location no.12

SITE ACCEPTANCE TEST REPORT FOR 33kV CABLE


1. CABLE PARAMETERS:

Location Reference As Per Soft Drawing: Circuit – 2


Cable Manufacturer Nokia cables
Cable Type / Size XLPE/3C x 240 mm²
Cable From SAAD PY – H06
Cable To Joint location no.12
Approximate cable length (Meters) 60 m

2. PHASE IDENTIFICATION (CONTINUITY) OF CABLE CORES:

Phases R-phase Y-phase B-phase Remarks


Results OK OK OK

3. INSULATION RESISTANCE TEST:


Ambient Temperature : 24°C

Reference Applied Voltage Duration Insulation Resistance Value (GΩ)

R – (Y+B+E) 202
Y – (B+R+E) 5000 V DC 60 sec 271
B – (R+Y+E) 256

TESTED CARRIED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER ALJABER AL SUWEIDI AADC
NAME Jayaprakash M P

SIGNATURE
03.02.2020 03.02.2020 03.02.2020
DATE
Contractor: Consultant: End Client:

Page: 2 of 2
Project: CONSTRUCTION OF 306 VILLAS – AL SAAD
Date: 03.02.2020
TEST REPORT FOR 33 kV CABLE
To Station: NRMAH-GD Feeder No: A05
From Station: SAAD PY Feeder No.:H06
To Joint Loc. Joint location no.12

4. REMARKS:

5. EQUIPMENT DETAILS:

Calibration
Sl.No Instrument Name Make / Model Serial No
Valid
1 IR Tester Megger/MIT515 101574096 10.03.2020

3 Digital Multimeter Fluke/87V 24890267 25.01.2021

TESTED CARRIED BY WITNESSED BY APPROVED BY


COMPANY ALPHA POWER ALJABER AL SUWEIDI AADC
NAME Jayaprakash M P

SIGNATURE
03.02.2020 03.02.2020 03.02.2020
DATE