Sl. No Description Unit Quantity. Rate Amount


1 SUB HEAD: 'A': CIVIL WORK sqm 7665.85
SUB HEAD-I :- EARTH WORK
Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.50 m in width as
well as 10 Sq.m. on plan including disposal of excavated earth lead upto 50 m and lift upto 1.50
m. Disposed soil to be levelled and neatly dressed.
a. Ordinary Soil
2 b. Hard Soil sqm 5110.56

3 Earth work in excavation in foundation and trenches etc. in all kinds of soil (excluding soil cum 35612.86
containing 50% or more of shingle or small size boulders upto 30 cm size, saturated soil and
rock), lift upto 1.50 m and stacking the excavated soil not more than 3 m clear from the edge of
the excavation and returning the stacked soil in 15 cm layers, when required, into plinth sides of
foundation etc on solidating each deposited layer by ramming and watering and then disposing
of all surplus soil as directed within a lead of 50m.
4 Re-filling excavated earth in foundations and plinth etc. in 15 cm layer including ramming and cum 28469.87
watering etc. complete.

5 Extra for every additional lift of 1.50 m or part thereof for earth work in all soils including shingles, cum 9688.14
small size boulders upto 30 cm size but excluding saturated soil and rock.
(From 1.5 to 3.0 m)
6 (From 4.5 to 6.0 m) cum 9688.14
7 (From 4.5 to 6.0 m) cum 16268.88
8 Extra for every additional lift or 1.50 m or part thereof for decomposed soft or hard rock. cum 9688.14
(From 1.5 to 3.0 m)

9 (From 4.5 to 6.0 m) cum 9688.14


10 (From 4.5 to 6.0 m) cum 16268.88
11 Filling in plinth with sand under floors including watering, ramming, consolidating and dressing cum 1937.63
complete.

12 SUB HEAD-II :- CONCRETE WORKS cum 1369.04


Providing and laying in foundations and plinth cement concrete 1 : 4 : 8 (1 cement : 4 coarse
sand : 8 graded stone aggregate 40 mm nominal size) excluding the cost of centring and
shuttering.
13 Providing and laying cement concrete 1 : 2 : 4 (1 cement : 2 coarse sand : 4 stone aggregate 20 cum 57.97
mm nominal size) excluding the cost of centring and shuttering in :
Foundations and plinth
14 Extra (over rates up to first floor level) for all concrete above first floor level. cum 1369.04
Note: 1% of the rate of concrete work from plinth to first floor level.

15 Making plinth protection 50 mm thick of cement concrete 1 : 3 : 6 (1 cement : 3 coarse sand : 6 sqm 314.48
stone aggregate using 20 mm nominal size) over 75 mm bed of stone ballast 40 mm nominal
size well rammed and consolidated and grouted with fine sand including finishing the top smooth.

16 SUB HEAD-III :- REINFORCED CEMENT CONCRETE WORK sqm 374.57


FORM WORK
Centring and shuttering including strutting, propping etc and removal of form work for :
Foundation, footings, bases of columns etc. and mass concrete.
17 Walls (any thickness) including attached pilasters, buttresses, plinth and string courses etc. sqm 4487.32
18 Suspended floors, roofs, landings shelves and their supports, balconies and chajjas (3.5 m sqm 12041.95
height).
Note: Timber used 8 times
19 Lintels, beams, girders, bressumers and cantilevers etc. sqm 9695.29
20 Column, pillars, posts and struts etc. sqm 14917.82
21 Stairs (excluding landings) except spiral stair cases. sqm 1156.43
Note: Timber used 8 times
22 Extra for shuttering in circular work. sqm 417.45
Note: 20% of the rate of respective item of centring and shuttering.
23 metre 1540.27
Edges of slabs and breaks in floors and walls. Under 20cms wide
24 Cornices and mouldings sqm 100.00

25 Weather shade, chajjas, corbels etc. Including edges. sqm 904.37

26 STEEL REINFORCEMENT kg 2000105.85


Reinforcement of RCC work including bending, binding and placing in position complete.
Tar/ TMT steel
27 Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. metre 1540.27

[1/80]
Page - 2
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


28 Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete cum 6572.09
work, using fly ash and cement content as per approved design mix, and manufactured in fully
automatic batching plant and transported to site of work in transit mixer for all leads, having
continuous agitated mixer, manufactured as per mix design of specified grade for reinforced
cement concrete work, including pumping of R.M.C. from transit mixer to site of laying, excluding
the cost of centering, shuttering, finishing and reinforcement, including cost of admixtures in
recommended proportions as per IS : 9103 to accelerate / retard setting of concrete, improve
workability without impairing strength and durability as per direction of the Engineer - in - charge.
NOTE- (1) Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used
as per design mix is payable/ recoverable separately.“ (2) Fly ash conforming to grade I of IS
3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with
cement to be ensured in accordance with clauses 5.2 and 5.2.1 of IS:456 -2000 in the items of
BMC and RMC.
All works upto plinth level

29 All works above plinth level upto floor V level cum 6189.25

30 Providing and fixing of expansion joint system related with floor location as per drawings and metre 328.60
direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members,
self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The
system shall be such that it provides floor to floor /floor to wall expansion control system for
various vertical locations in load application areas that accommodates multi directional seismic
movement without stress to it's components. System shall consist of metal profiles with a
universal aluminum base member designed to accommodate various project conditions and
finish floor treatments. The cover plate shall be designed of width and thickness required to
satisfy projects movement and loading requirements and secured to base members by utilizing
manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all
directions.
The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the
corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all
directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint
System to have watertight joint is mandatory requirement all as per the manufactures design and
as approved by Engineer -in-Charge. (Material shall conform to ASTM 6063).
Floor Joint of 100 mm gap
31 Providing and fixing of expansion joint system related with wall joint (internal/external) location as metre 83.60
per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum
base members, self aligning / centering arrangement and support plates as per ASTM B221- 02.
The material shall be such that it provides an Expansion Joints System suitable for vertical wall
to wall/ wall to corner application, both new and existing construction in office Buildings &
complexes with no slipping down tendency amongst the components of the Joint System. The
Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum
surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall
conform to ASTM 6063.)
Wall Joint of 100 mm gap
32 Providing and fixing of expansion joint system of approved make and manufacture for various metre 82.15
roof locations as per approved drawings and direction of Engineer-In-Charge. The joints shall be
of extruded aluminum base members with, self aligning and self centering arrangement support
plates as per ASTM B221-02. The system shall be such that it provides water tight roof to roof
/roof to corner joint cover expansion control system that is capable of accommodating
multidirectional seismic movement without stress to its components. System shall consist of
metal profile that incorporates a universal aluminum base member designed to accommodate
various project conditions and roof treatments. The cover plate shall be designed of width and
thickness required to satisfy movement and loading requirements and secured to base members
by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves
in all directions.
The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the
corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all
directions including vertical displacement. The Joint System shall resists damage or deterioration
from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic
from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to
have water tight joint is mandatory requirement. (Material shall confirm to ASTM 6063.)
Roof Joint of 100 mm gap

33 Providing & Fixing of GRC Panels Casted with Power Spray Concrete Mix Design all complete Sqm 532.62
as per architectural drawings under the direction of engineer in charge
34 Providing & Fixing of GRC Panels Casted Mouildings with Power Spray Concrete Mix Design all Meter 641.89
complete as per architectural drawings under the direction of engineer in charge
35 SUB HEAD-3A :- STONE WORK cum 141.40
Coursed rubble masonry (second sort) with hard stone in foundation & plinth with :
Cement mortar 1:6 (1 cement : 6 coarse sand)
36 Coursed rubble masonry with hard stone (first or second sort) in superstructure above plinth level cum 232.19
and upto floor five level.
Masonry work (second sort), in cement mortar 1:6 (1 cement: 6 coarse sand)
37 Pointing on brick work or brick flooring with cement mortar 1:3 (1 cement : 3 fine sand): sqm 2321.88
Flush / Ruled/ Struck or weathered pointing

[2/80]
Page - 3
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


38 SUB HEAD-IV :- BRICK WORK cum 161.51
Brick work with best available local bricks in foundations and plinth in cement mortar 1:6 (1
cement : 6 fine sand).
39 Providing and laying autoclaved aerated cement blocks masonry with 150mm/230mm/300 mm cum 4433.98
thick AAC blocks in super structure above plinth level up to floor V level with RCC band at sill
level and lintel level with approved block laying polymer modified adhesive mortar all complete
as per direction of Engineer in-Charge. (The payment of RCC band and reinforcement shall be
made for separately).
40 Providing hoop iron 25 mm x 1.60 mm or equivalent reinforcement in brick masonry at every Per floor 256.47
fourth course, embedded in cement mortar. per Cum

41 SUB HEAD-V :- MARBLE & GRANITE WORK sqm 10.00


Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished,
machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of
required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4
(1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment,
epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss
finish etc. complete at all levels.
Granite of any colour and shade
Area of slab upto 0.50 sqm
42 Area of Slab over 0.50sqm sqm 507.12

43 Extra for fixing marble /granite stone, over and above corresponding basic item, in facia and metre 141.62
drops of width upto 150 mm with epoxy resin based adhesive, including cleaning etc. complete.

44 Extra for providing opening of required size & shape for wash basin/kitchen sink in kitchen each 100
platform, vanity counter and similar location in marble/ Granite/ stone work, including necessary
holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.

45 SUB HEAD-VI :- WOOD AND PVC WORK cum 20.24


Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought
framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (
hold fast lugs or dash fastener shall be paid for separately).
Second class teak wood
46 Mealamine polishing on door windows by preparing the surface applying putty base course. sqm 778.37
prepare the surface smooth by sand papering and then applying mealamine polish with air
compressor. Two or more coats on new works including a coat of wood filler.
47 Providing and fixing panelled, glazed or panelled and glazed shutters for doors, windows and sqm 10.80
clerestory windows including aluminium butt hinges with necessary screws
38mm thick best available local wood class - B I
48 Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter each 1724
bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15cm 1:3:6 mix
(1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size)

49 Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non- sqm 640.02
decorative type, core of block board construction with frame of 1st class hard wood and well
matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on
both faces of shutters:
35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
50 Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges sqm 640.02
of flush door shutters (over all area of door shutter to be measured).
51 Providing and fixing wooden moulded beading to door and window frames with iron screws, metre 1341.35
plugs and priming coat on unexposed surface etc. complete :
2nd class teak wood
50 x 20 mm
52 Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ sqm 640.02
suede finish with high density protective surface layer and reverse side of adhesive bonding
quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality.
1.0 mm thick.

53 Extra for Providing and fixing flush doors with decorative veneering instead of non decorative ISI sqm 640.02
marked flush door shutters conforming to IS: 2202 (Part I)
On one side only
54 Providing and fixing Single Glazing 6mm thick toughened glass from Gujrat Guardian Limited or sqm 1595.69
equivalent complete in all respects as per direction of the Engineer-in-charge. (Required
properties Solar factor ≤ 0.45, U-Value ≤ (W/sq.m-K) 5.7W /M2K, Visible light transmittance ≥
0.30)
55 Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and sqm 21.12
manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement
and making necessary holes etc. for fixing required door fittings, all complete as per direction of
Engineer-in-charge (Door handle, lock and stopper etc.to be paid separately).

56 Providing and fixing 12 mm thick frameless toughened glass partitions of approved brand and sqm 74.59
manufacturer, including providing and fixing partitions at top & bottom with aluminum channel
etc. all complete as per direction of Engineer-in-charge

[3/80]
Page - 4
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


57 Providing and fixing fire resistant door frame of section 50 x 60mm on horizontal side & 35 x 60 Metre 478.80
mm on vertical sides having built in rebate made out of 1.6 mm thick GI sheet ( Zinc coating not
less than 120gm/m²) suitable for mounting 120 min Fire Rated Glazed Door Shutters. The frame
shall be filled with Mineral wool Insulation having density min 96Kg/m³ . The frame will have a
provision of G.I. Anchor fasteners 14 nos ( 5 each on vertical style & 4 on horizontal style of size
M10 x 80 ) suitable for fixing in the opening along with Factory made Template for SS Ball
Bearing Hinges of Size 100x89x3mm for fixing of fire rated glazed shutter. The frame shall be
finished with a approved fire resistant primer or Powder coating of not less than 30 micron in
desired shade as per the directions of Engineer - in- charge . (Cost of SS ball bearing hinges is
excluded).
58 Providing and fixing 60 mm thick glazed fire resistant door shutters of 120 min Fire Rating Sqm 342.72
confirming to IS:3614 (Part II) or EN1634-1:1999, tested and certified as per laboratory approved
by Engineer-in-charge, with suitable mounting on door frame, consisting of vertical styles, top rail
& side rail 60 mm x 60 mm wide and bottom rail of 110 mm x 60 mm made out of 1.6mm thick
G.I. sheet (zinc coating not less than 120gm/m²) duly filled mineral wool insulation having density
min 96 kg/m³ and fixing with necessary stainless steel ball bearing hinges of size 100x89x3mm
of approved make, including applying a coat of approved fire resistant primer or powder coating
not less than 30 micron etc all complete as per direction of Engineer-in-charge (panelling to be
paid for separately).
59 Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. Sqm 342.72
beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x
33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c
, including applying a coat of approved fire resistant primer/powder coating of not less than 30
micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as
per direction of Engineer-in-charge. The glass shall be clear, toughened, interlayered, non-wired
fire resistant having 11 mm thickness of approved brand with 120
minutes of fire resistance both integrity & radiation control (EW120) and minimum 15 min of
insulation (EI15) and having a sound reduction of 37dB and LT of 86%. Glass shall be compliant
to class 2(B)2 category of Impact Resistance as per EN 12600. The glass should be
manufactured in UL & TUV audited Facility and including UL-EU Certification. The maximum
glazing size cannot be more than 1100 mm x 2200 mm (w x h) or 2.42 sq mts in total area. The
test report for the complete system (Glazed Door or Partition) will be considered valid only if it
contains the stamp and signature of the authorized signatory from the glass manufacturer.
(Actual glass size is to be measured at site for payments).

60 Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock Nos 70
on back side of the Panic Latch of reputed brand and manufacture to be approved by the
Engineer- in- charge, all complete.
61 Providing and fixing approved brand and manufacturer SS 304 grade hardware's for Doors etc. each 530
Providing and fixing approved brand and manufacture SS 304 Lever Handle D-type fixed with SS
screws etc. complete in all respects as per manufacturers' specifications & as directed by
Engineer-in-charge.

62 Providing and fixing approved brand and manufacture SS 304 grade SS 304 grade Mortice lock each 232
with key cylinder fixed with SS screws etc. complete in all respects as per manufacturers'
specifications & as directed by Engineer-in-charge.
63 Providing and fixing approved brand and manufacture SS 304 grade Tower bolt 250mm long each 40
with 10mm dia fixed with SS screws etc. complete in all respects as per manufacturers'
specifications & as directed by Engineer-in-charge.
64 Providing and fixing approved brand and manufacture SS 304 grade Tower bolt 150mm long each 200
with 10mm dia fixed with SS screws etc. complete in all respects as per manufacturers'
specifications & as directed by Engineer-in-charge.
65 Providing and fixing approved brand and manufacture SS 304 grade wall mounted door buffer each 265
fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as
directed by Engineer-in-charge.
66 Providing and fixing approved brand and manufacture SS 304 grade Door Stopper - door each 265
mounted hanging type fixed with SS screws etc. complete in all respects as per manufacturers'
specifications & as directed by Engineer-in-charge.
67 Providing and fixing approved brand and manufacture SS 304 grade Top & Bottom Patch fixed each 24
with SS screws etc. complete in all respects as per manufacturers' specifications & as directed
by Engineer-in-charge.
68 Providing and fixing approved brand and manufacture SS 304 grade D type 1200mm Pull Handle pair 4
with 32mm dia fixed with SS screws etc. complete in all respects as per manufacturers'
specifications & as directed by Engineer-in-charge.
69 Providing and fixing approved brand and manufacture SS 304 grade D type 300mm Pull Handle pair 8
with 32mm dia fixed with SS screws etc. complete in all respects as per manufacturers'
specifications & as directed by Engineer-in-charge.
70 Providing and fixing approved brand and manufacture SS 304 grade Glass to Glass Lock Round each 6
type with SS screws etc. complete in all respects as per manufacturers' specifications & as
directed by Engineer-in-charge.
71 SUB HEAD-VII:- STEEL WORK Kg 51699.12
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position
and applying a priming coat of approved steel primer using structural steel etc. as required.
In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works

[4/80]
Page - 5
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


72 Steel work riveted or bolted in built up sections, trusses and framed work including cutting, Quintal 20.00
hoisting, fixing in position and applying a priming coat of red lead paint.
In RS Joists

73 In Tees, Angles and Channels Quintal 5292.13


74 Supplying and fixing rolling shutters of approved make, made of 80 x 1.25 mm MS laths sqm 20.00
interlocked together through their entire length and jointed together at the end by end locks
mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside
and outside locking with push and pull operation complete but excluding the cost of the top cover
and spring.
75 Providing and fixing 27.5 cm long wire spring grade No. 2 for rolling shutters. each 5

76 Providing and fixing top cover for rolling shutters. metre 5.00

77 Providing and fixing ball bearing for rolling shutters. metre 15.00

78 Providing and fixing 12 mm thick and 100 mm wide pelmet with 25 mm dia wooden curtain rod Mtr 759.43
and brackets including fixing with 25 x 3 mm MS flat 10 cm long and plugs etc complete.
Timber class - A IV

79 Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates kg 8268.51
etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and
fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with
necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required
size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of
Engineer-incharge, (for payment purpose only weight of stainless steel members shall be
considered excluding fixing accessories such as nuts, bolts, fasteners etc.).

80 Supply and fixing of STRAIGHT PROFILED KALZIP or equivalent “SELF SUPPORTED” Sqm 6041.49
SECRET FIX STANDING ROOFING SYSTEM IN 0.9mm THICK AA 3004 ALUMINIUM ALLOY.
The general roof-construction shall comprise of:
Top layer – Kalzip 65-50/400-429 profiled sheet manufactured or equivalent from aluminium self
supported standing seam roof system manufactured from aluminium alloy AA 3004 (AlMn1Mg1)
as specified in BS EN 1396: 2007 minimum material thickness of 0.9 mm and Fluorocarbon
PVDF/Stucco finish on the exposed surface.
The material properties shall be as follows:
Ultimate tensile strength: minimum 200 N/mm2, 0.2% Proof Stress: min 185 N/mm2,
Modulus of elasticity: 70,000 N/mm2.
Including Accessories, aluminium ST clips and Fasteners.
Sheets are to be laid to meet the requirements of the building geometry and fixed on Aluminum
clips. Clip to be fixed to the top hat/purlins with SS 304 screws only.
Under Deck Insulation
Liner – Kalzip 35/200 Bare or equivalent Galvalume steel liner, 0.5 mm tct, 35 mm deep ribs
spanning up to 1500mm centres (multiple spans)
Vapour Control layer - A single layer of double sided aluminium foil vapour barrier.
Insulation - Rockwool insulation of 100mm thickness minimum 48kg/m3 density with thermal
conductivity of min K=0.04 W/mk at 25 degree Celsius. Fire classification with test procedures to
BS 476: Parts 6 & 7.
Flashings manufactured from aluminium alloy AA 3004 (AlMn1Mg1) as specified in BS EN
1396: 2007 minimum material thickness of 0.9 mm and Fluorocarbon PVDF/Stucco finish on the
exposed surface. The roofing system shall be certified with a British Board of Agreement
Certificate No 98/3481 plus the Institute of Bautechnic Zulassung beschield N R -14.1 .181
All installation is to be carried out by approved trained roofing installer. The installation team shall
be fully trained and approved by the manufacturer.
The roof system manufacturer/supplier must have a registered office in India The approved
roofing system manufacturer should have at least completed 150 projects of aluminium standing
seam roofing system in India with one project having area more than 150,000 m2.
Aluminium gutter of 2mm thickness with aluminium gutter expansion joints @ 12m.
all complete as per direction of Engineer-in-charge.
81 Designing, providing, installing/fixing skylight consisting of 16mm thick multiwall polycarbonate Sqm 494.62
sheet in approved color (minimum 900mm wide) with standing seam on both sides & double
tooth snap on locking system to ensure maximum uplift capability. The panel shall be co-
extruded UV protected and antiglare/soft light to prevent glare/sun streak . The cross section of
one cell should not be more than 4mmX4mm & weight of single panel shall not be less than 3250
per square metre. The system shall be fitted on purlins with spacing as specified by manufacturer
with stainless steel fastener & screws and supported on MS tube framework, complete as per
specification, drawing and direction of Engineer in Charge. The rate includes cost of all the
operations, labour materials and tests (as applicable) for proper completion of the work except
the M.S tubular framework which shall be measured and paid separately (For payment purpose
the area of finished polycarbonate sheet fixed in position shall only be measured).

[5/80]
Page - 6
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


82 Providing and fixing concertina coil fencing with punched tape concertina coil 600 mm dia 10 Metre 20.00
metre openable length ( total length 90 m), having 50 nos rounds per 6 metre length, upto 3 m
height of wall with existing angle iron 'Y' shaped placed 2.4 m or 3.00 m apart and with 9
horizontal R.B.T. reinforced barbed wire, stud tied with G.I. staples and G.I. clips to retain
horizontal, including necessary bolts or G.I. barbed wire tied to angle iron, all complete as per
direction of Engineer-in-charge, with reinforced barbed tape(R.B.T.) / Spring core (2.5mm thick)
wire of high tensile strength of 165 kg/ sq.mm with tape (0.52 mm thick) and weight 43.478 gm/
metre (cost of M.S. angle, C.C. blocks shall be paid separately)
83 SUB HEAD VIII :- FLOORING sqm 579.69
Providing and laying anti skid 800x800mm Full body vitrified floor tiles (thickness to be specified
by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of
approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4
coarse sand), including grouting the joints with white cement and matching pigments etc.,
complete.
84 Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished sqm 1381.83
with a floating coat of neat cement including cement slurry, but excluding the cost of nosing of
steps etc. complete.
40mm thick with 20mm nominal size stone aggregate.
85 Cement plaster skirting (up to 30 cm height) with cement mortar 1:3 (1 cement : 3 coarse sand) sqm 138.18
finished with a floating coat of neat cement.
18 mm thick.
86 Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the sqm 5344.60
manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved
make, in all colours and shades, laid on 20 mm thick cement mortar 1:4 (1 cement : 4 coarse
sand), including grouting the joints with white cement and matching pigments etc., complete
Size of Tile 800x800 mm

87 Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), sqm 2349.13
with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all
colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement:
3 coarse sand), including grouting the joint with white cement & matching pigments etc.
complete.
Size of Tile 800x800 mm
88 Providing and laying Laminate wooden flooring (Grade AC4, 8 mm thick Ambience Premium- sqm 453.51
AC4 ), having a good backing layer made up of plastic laminate or melamine as specified by the
manufacturer and approved by Engineer-in-charge.
Flooring
89 Skirting sqm 45.35
90 Floor strip on edges Meter 22.68
91 Providing and laying Polished Granite stone flooring in required design and patterns, in linear as sqm 5575.86
well as curvilinear portions of the building, all complete as per the architectural drawings, with 18
mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse
sand), laid and jointed with cement slurry and pointing with white cement slurry admixed with
pigment of matching shade, including rubbing, curing and polishing etc. all complete as specified
and as directed by the Engineer-in-Charge.
Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
92 Extra for Shot blasted finish sqm 2230.34
93 38 mm thick wood block flooring of first class teak wood laid over 25 mm thick leveling layer of sqm 253.12
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 10 mm nominal
size) to be paid separately, coated with a thin layer of hot bitumen penetration 80/25(blown type)
@ 2.45 kg per sqm, including fixing blocks in position after dipping in hot bitumen (blown type) up
to half depth, planed, levelled smooth and finished complete.
94 Providing and fixing Vinyl flooring of 2mm thick PVC flexible, homogeneous antistatic calendared sqm 13.90
compacted floor covering, minimum weight 3120 g/m2 in minimum sheet of size 2mtrs. x 20
mtrs. approved pattern & colour combination with PUR Protect or equivalent surface treatment
having wear minimum resistance of ≤ 4.0mm3 as per EN 660.2 and wear group P as per EN-
649 and should have a minimum residual indentation of <0.03mm confirming to EN-433. The laid
flooring should have non- directional design, colour dyed as a raw mixture to ensure even colour
throughout the thickness and its surface should be densely compacted for improving wear and
ease of maintenance with Anti-bacterial and Fungicidal properties. The laid flooring shall
confirms the fire rating B1 class as per EN 13501-1. The floor finish should terminate at the room
perimeter passing over a concealed cove former and continuing up the wall for 100mm. The
joints in the flooring should be sealed by using a PVC welding bar of matching colour to be
supplied by the manufacturer, using a hot air gun for fusion of welding bar with flooring and self
levelling required underneath with all accessories cove etc.

95 Extra for pre finished nosing to treads of steps of Granite stone. metre 1429.68
96 Extra for Granite stone flooring in treads of steps and risers using single length up to 2.00 metre . sqm 221.61

97 Providing and fixing Ist quality ceramic glazed wall tiles of size 300x450 mm conforming to IS: sqm 1401.92
15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades
as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed
of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg
per sqm, including pointing in white cement mixed with pigment of matching shade complete.

[6/80]
Page - 7
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


98 Providing and fixing 18mm thick Granite stone work for wall lining at all height in cement mortar sqm 2306.91
1:3 (1cement : 3 coarse sand) including pointing with white cement mortar with an admixture of
pigment to match the granite shade complete as per direction of Engineer-in-charge.

99 Providing and fixing copper pins 7.5 cm long 6 mm diameter for securing adjacent stones in Each 13841
stone wall lining in cement mortar 1:2 (1 cement : 2 coarse sand), including making the
necessary chases.
100 Toilet Cubical sqm 325.34
Providing and fixing Toilet Cubicle (of following standard dimension which includes 600 mm door
size width) made of heat, bacteria, water, chemical, scratch, impact and anti bacterial resistant
12 mm thick solid compact laminate panels Finish of the compact laminate should be raw silk
which include doors, pilasters and intermediate panels finished with approved texture/shade as
per the detail drawing and as per IS 2046 (Indian Standard) and as per fire retardant BS-476/97
standard.
This also includes providing and fixing in position necessary hardware made out of Stainless
Steel (Grade 316) as per manufacturer's specifications and EIC instructions like (1) Door Knob,
(2) Gravity Hinges, (3) Thumb turn lockset indicators, (4) Coat hooks, (5) U- Channels, (6) SS-
Shoe Box Plate, (7) MS-Base Plate, (8) Rubber noise deafening tape, (9) Screws and wall Plugs.

101 Providing and fixing 40mm thick cladding comprising of Wooden framework using 25mx50mm sqm 1401.51
sections at a maximum spacing of 600mm in any one direction (including adding members as
required) covered with12mm thick BWP ply layered with 4mm thk. veneer (Basic Rate Rs.60/-
sqft)on one side pasted and pressed with adhesive to give a uniform and smooth finish,
including 4mm thk. S.S. strip framework on all sides of veneer panels with wooden member
surround, top moldings / margins, melamine polish etc. to finish the thickness, as shown
complete in drawing. All members / ply etc. shall be treated with anti-termite solution as per
norms. No extra shall be paid for making of openings, door / window frames and for making
provisions for electric conduits.
102 Providing and fixing of 6mm thick lacquer glass SGG Planilaque glass of approved color by sqm 53.99
architect/ Client with SGG Planifix silicon on perfectly leveled water proof non-conventional
plywood (preferably marine plywood) of minimum 12mm thickness mounted on the RCC wall/any
other structure. The SGG Planilaque lacquered glass to be of 6mm thick highly durable, humid
resistance, poly urethane lacquer glass. The Planilaque glass should be manufactured by
industrial curtain coating process. It should meet quality standards as per BS EN 1036 1999 &
confirms to PERSOZ hardness test of at least 220 oscillations. The substrate of the glass should
conform to Standard BS EN 572 1995 parts 1 and 2: Glass in Building – Basic soda lime silicate
glass products. Planilaque lacquered glass to be manufactured to right specifications, relating to
consistency of color, opacity and homogeneity throughout production campaigns and also to the
ageing properties, mechanical resistance, and resistance to humidity and to chemical agents of
the lacquer. The color of the lacquer should remain stable when exposed to normal levels of ultra-
violet light in interior applications.

103 Providing and fixing partition up to ceiling height consisting of GI frame work made of special sqm 1613.94
section power pressed/ roll form G.I. sheet with zinc coating of 120 gms/ sqm(both side
inclusive), consisting of floor and ceiling channel of 0.5 to 0.55 mm Metal Thickness ,72mm wide
& having two flanges of 30mm each to the RCC Floor and Slab with Approved Fastener @600
mm C/C respectively. The wall studs 0.5 to 0.55 mm Metal Thickness, 70mm wide having one
flange of 34mm another of 36 mm). These Wall studs are placed maximum distance of 610mm
C/C in Floor and Ceiling channel. 50mm thick @ 48kg/cum density mineral wool Insulation to be
suspended on Insulation Holder Strip positioned at 1200mm vertical centers within the stud
cavity. One layer of 15 mm thick Firebloc Plasterboard on Both side is screw fixed to metal
system using Self tapping 3.5 x 25 mm corrosion resistant drywall screws spaced at 150mm
centers on all joints and 300 mm centers in the field of plasterboards. Screw fixing is done
mechanically. Install Fixing Channel of 99mm x 0.90mm behind horizontal board joints and also
shall be fixed 1.2m above the FFL. Finally, plasterboards and screw heads are to be jointed and
finished to have a flush look which includes filling of tapered edge and square edges of board
with Redi mix all purpose jointing compound, Paper Tape. (As per recommended practice of
manufacturer). All perimeters and penetrations to be sealed with fire and acoustic sealant along
with baker rod as per manufacturer’s specifications.

[7/80]
Page - 8
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


104 Providing and fixing of Noise Reduction doors (make ENVIROTECH or Equivalent ) consisting of sqm 24.36
Door frame made out of good quality hard wood , section size – 100 mm x 110 mm fitted with ‘D’
type rubber gasket to block noise leakage from gap and acoustic door shutter with minimum 60
mm thickness along with fire rating and smoke Intumescent seal strip of size 10mm x 4mm for
120 minutes fire rated and STC 37dB Tested by reputedl Laboratory and having infill of 50mm
thick resin bonded glasswool of 48 kg/cum density sandwiched by two 10mm thick approved
quality marine grade ply and finished with 1 mm thick laminate of approved make, shade and
colour and design on both sides. Further edges of shutter shall be provided with 6mm thick teak
wood beading using exterior quality synthetic adhesive, headless GI nails, screws, beading
finished with approved melamine polish etc. The ply shall be resistant to vermin, mould growth,
minor impact, abrasion and short term water attack and with a smooth surface suitable to receive
most forms of decoration. The door shall have acoustic seal in door rebates and drop dead seal
at the bottom of the door including ironmongeries. HARDWARE :-The door assembly shall be
fixed to the door frame with heavy duty hardware i.e. Geze/ Assa abloy/Dorma Make or
equivalent make SS Hinge Size: 4”x 3”x 3mm , 600 mm SS door handle , SS Tower bolt ,Door
closer , Panic Bar ,Panic trim etc. ACOUSTIC INSULATION: The Panels filled with Acoustic
material Rock wool confirming to IS-8183 of 96 kg/m3 density, very good noise absorber for high,
mid & low frequencies along with, 6 MM thick anti donning layer having Thermal Conductivity
0.037 @ 20 C as per EN ISO 8497 (DIN 52613) and 2 mm thick Sound Damping layer MTS 05-
303 to achieve higher Sound STC as per site condition.

105 Providing & Fixing of Ceiling tiles shall be of high acoustic performance of Decosonic CNBM sqm 557.42
make and micro edge glass fiber in size 600x600x15 mm of color white/Black. It comprises a
high-density glass wool panel covered with painted glass wool tissue for decorative ceiling effect
and glass wool tissue on the backside and having sealed edges. It shall have a noise reduction
co-efficient of greater than 0.90, light reflection of over 85%, density of 100kg/m3, humidity
resistance. To lay the field panel of size 600x1200mm, flush fitting 1200mm long cross tees to be
interlocked between main runners at 600mm centre. Thus a grid system of 600mm X 1200mm
is formed. Installation shall not begin until all wet work is completed and dry. Building shall be
properly enclosed and under standard occupancy conditions (temperature of 20‐40°C and not
more than 70% relative humidity) before installation begins.
106 P/F STRETCHED FABRIC ACOUSTIC PANELS using: sqm 629.11
• GI frame work of 48mm GI Studs, 50 mm foor using 0.55mm thick and stud channels at
610mm x 610mm, 0.5mm thick, fixed with MS angle cleats 1220x610mm centers to wall by using
metal fasteners, backed with 22 SWG x 12.5mm GI Chicken Wire Mesh with air gap a minimum
of 50mm on back side, as per detailed drawing.
• The frame work to be filled with glass wool of 50mm thick of 48 kg/cum Cu. (Owens Corning)
laminated with Black FRP Tissue on the outer side, and chicken wire mesh support on the rear
side abuting the wall face.
The entire glass wool surface to be covered with 12mm thick FR ply, with 8mm diameter drilled
perforations at 25mm c/c in both directions.
Finished in stretched fabric finish, using UPVC grippers (Waltract/ Cineview ) fixed to 50mm x
12.5mm commercial plywood runners. The fabric should be inherintly fire-retardancy.
107 STAGE FLOORING: Providing and fixing 75x25 mm teakwood plank (1500mm long) flooring Sqm 270.00
with tongue and groove joints (concealed screwing and minimum length 1.5m) on two layers of
12mm thick water proof marine ply, plywood bonded with phenolic resin with half headless GI
nails/steel screws wherever necessary, with joints staggered with 2nd layer glued and screwed
to the first, fixed with wooden screws to teakwood joists framework comprising 75x50mm
teakwood joist 900mm centre to centre in one direction and 50x50mm teak wood battens 400mm
centre to centre on other direction, teakwood joists resiliently supported on 150 x 150mm pads of
7.5mm nominal thickness of waffle, neoprene pad ribbed (50 p.s.i. grade) and 50x50x6mm thick
MS angle cleat fixed with 150mm long with 10mm dia. GI bolts and expansion fasteners, over
floor slab 900x900 centre to centre, support locations including providing and applying a coat of
ready mixed aluminum primer and a coat of synthetic enamel paint both of approved brand and
manufacturer over exposed surfaces and edges of marine ply. Entire work to be done complete
as per drawings, specifications and direction of Engineer-in-Charge including wax polishing of
teak wood planks after filling wood filler and sand papering up to smooth finish in natural color.
Stage Floor - Moulding : Providing and fixing 145x50mm teakwood moulding as per architect on
the edges of stage wooden flooring including wax polishing of teak wood planks after filling wood
filler and sand papering up to smooth finish in natural color.

108 HALL FLOORING:- Providing & fixing of the cut pile designed carpet with 8mm profile underlay Sqm 1106.60
in the aisles and gangway. Complete with adhesive after rectification of the floor.
Specification of Carpet:
Construction - cut pile wilton weave
Fiber - 2 ply twisted yarn pp
Pile wt - 1100 grams / meter
Pile ht - 5 to 6mm
Color fastness - As per international standards

[8/80]
Page - 9
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


109 Providing and fixing Anutone Slats Wood based panels with lineal perforations to be fixed on Sqm 340.00
walls/ ceiling. The panels shall be fire resistant grade with melamine laminate panels 2430mm x
128mm x16mm wirh 2mm slats at 32 mm pitch, Toungue and Groove edges for seamless
mounting having density of 800kg/m3 (base panel confirming to IS 12406 and laminated panel
confirming to IS 14587) . The back of the panels are perforated with 10mm diameter circular
holes with a nonwoven fabric covering of 0.2mm for providing Sound absorption via the acoustic
impedance method. Panel is to be fixed on Anutone Strut CC18 framework with screw fixed
horizontal / vertical to wall at every 600mm c/c with centre & edge bracket in tongue & groove
system on CC18 framework. The cavity of framework should be inserted with polyster fibre
AnutoneSynth AW 10x25 with surface density of 1000 gsm and along with all accessories and
direction of Engineer in charge.

110 Providing and supplying Armstrong ‘Optra Acoustical Wall Panelling’ with square edges made of Sqm 475.00
fibre glass substrate 25mm thick and wrapped on the front side with an acoustically transparent
and fire-resistant fabric with an option of colours as per the choice of the Architect/ Person in-
charge of size 2100x600 or 1200x600 or 600x600 mm providing a minimum sound absorption
level of 0.90 NRC to be affixed to wall using Wall panel impalers supplied by M/s Armstrong
Industries India Pvt. Ltd and construction adhesives as per the instructions laid down by the
manufacturer. Installation: Armstrong wall panel impalers of adequate quantity as specified by
the manufacturer shall be fixed to the wall surface using self tapping screws. Silica based
construction adhesive shall be dabbed on to the projecting elements (spikes) of the impalers.

111 Acoustic Treatment for Stage both Sides & Back wall: Providing and fixing of magnesite Sqm 350.00
bonded woodwool panels made with superfine wood fibres & gypsum, were patented with
magnesite cement, edge profiles consist of Radius, Chamfer, Tongue-Groove & H-Spline
groove, having density 400kg/m3, Acoustic NRC upto 0.90, eco-friendly, Fire Ratings - Non-
combustibility At 750 oC, Thermal Resistance, Water Vapour Diffusion Resistant, size
600x600/1200/2400x25mm installed on Strut C-system requires unfastening and refastening of
fasteners . The Strut C-System framework consisting of CC10 Channels fixed at 600mm centres,
Long edges chamfer and kerfed for H-Spline; Thickness 38 mm installed on Strut C-system with
H-Spline.
112 Providing and fixing of 8 mm MDF board laser cut jali with design as per drawing to be fixed over Sqm 110.00
the frame work of 48mm GI Stud/ 50mm wooden battens. The framework to be supported on the
wall at a distance of 1800 mm centre to centre of size as reqd long 35x35x3mm angle cleats of
required length and MS anchor fasteners of size 65mm x10mm dia. The cleats to be given two
or more coats of red oxide primer. The entire work to be executed as per the drawings /
instructions of the Engineer-in-charge. The rate includes for all Geometry of wall, openings etc.
and for complete item including all the required approved material, labour and fixing as per
drawings enclosed. The work shall be executed as per specification , & instructions of engineer
in charge including cost duco paint of desired shade on the jali.

113 Providing and fixing 150 mm border out of 19 mm thick commercial block board of reputed make Rmt 200.00
like Century, Duro, Green with 1 mm laminate of reputed make like century, Greenlam as per
approved shade. of approved shade. To be fixed as per the drawings over a framework of 48mm
GI Stud of .55mm thk gypsteel @ 600c/c.. by means of 35x35x3MM MS angle hold fasts fixed
with anchor fasteners as per drgs...
114 Providing and fixing of Anutone Subtex Nubby Soft Fibre Square edge 15mm for Ceiling of size Sqm 400.00
595x595x15 mm is to be installed on framework of Anutone Skelet. Which will comprise of NRC
0.94 base panel with humidity resistance of 90% RH and light reflectance upto 85% with Leed
points Green Performance certified. Subtex Nubby Soft Fibre 15mm for Ceiling tile meet the
stringent fire test required having Class ‘A’ rating for Flame Ignitability test as per ASTM-E-84,
with complete framework of Anutone Skelet as per Installation details given
115 Installation Details:- Anutone Subtex Nubby Soft Fibre Square edge 15mm for Ceiling Tile is to Sqm 100.00
be layed on frame work of Anutone Skelet accessories pre-coated GI angle size 24x24x0.4 mm
thick fixed to the brick wall / partition at the perimeter of ceiling with Nylon Sleeves and APS
wafer head drywall screws, Then suspended main GI ‘T’ section (bottom precoated-White) with
polyester coating of 25 microns dry film thickness. Main T-section size 24x38x0.3 mm thick and
3600 mm long from soffit in one direction with the help of metal rawl plug, cleat, leveler,
perimeter & wall spring clip & G I Rod 4 mm diameter with galvanized spring steel level clip 1200
mm centres from soffit. G I cross T section (bottom precoated-White) size 24x25x0.3 mm and
1200mm & 600mm long is insert fixed into the slots provided as interlock in main ‘T’ at 600 mm
centres to form 600x600mm grid size for a tile size of 595x595 mm. All accessories such as
Anutone Skelet accessories cleat, suspenders, levelers, clips etc, shall be supplied and installed
in accordance with manufacturer recommendation.
Providing & fixing Ecco board acoustical panels of NRC 0.90 to be fixed over frame work of
48mm GI studs fixed on the wall. The framework to be filled with 50mm thick thermal bonded
non woven polyster wadding micron fiber of 1000 gm / sqm . The mikron fiber to be held in
position with chicken mesh of 18mm & 24SWG. The mikron fiber shall be of Mikasha
International/ Sandler.

116 Providing and fixing of False Ceiling with 1mm thick laminate to be fixed on 12mm ply over 2"x2" Sqm 300.00
softwood/40mm stud framework at 2'-0" c/c both ways. There will be other layer of 4mm thick ply
over 12mm ply to give necessary grooves as per drawing. The framework to be filled with 50mm
thick thermal bonded non woven polyster wadding micron fiber of 1000 gm / sqm . The mikron
fiber to be held in position with chicken mesh of 18mm & 24SWG. The mikron fiber shall be of
Mikasha International/ Sandler.

[9/80]
Page - 10
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


117 Providing and fixing of Anutone Subtex Ebony Soft Fibre Square edge 15mm for Ceiling of size Sqm 200.00
595x595x15 mm is to be installed on framework of Anutone Skelet. Which will comprise of NRC
0.94 base panel with humidity resistance of 90% RH and light reflectance upto 85% with Leed
points Green Performance certified. Subtex Ebony Soft Fibre 15mm for Ceiling tile meet the
stringent fire test required having Class ‘A’ rating for Flame Ignitability test as per ASTM-E-84,
with complete framework of Anutone Skelet as per Installation details given. ( black colour)

118 Providing and fixing insulation above false ceiling with thermal bonded Polyester fibre 1000 gsm, Sqmt 1200.00
50mm thick confirming to 1S:8225 fixed in the spaces of frame and held in place with wire mesh
of 28Gx10 in front complete as per drawing & direction of Engineer-in-charge.
119 SUB HEAD-IX :- ROOFING meter 94.18
Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone
aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement : 3 fine
sand) as per standard design :
In 75 x75 mm deep chase
120 Providing and fixing at all height false ceiling including providing and fixing of frame work made sqm 1550.30
of special sections power pressed from M.S. sheet and galvanised in accordance with zinc
coating of grade 350 as per IS : 277 and consisting of angle cleats of size 25mm wide x 1.6mm
thick with flanges of 22mm and 37mm at 1200mm centre to centre one flange fixed to the ceiling
with dash fastener 12.5mm diax40mm long with 6mm dia bolts to the angle hangers of
25x25x0.55mm of required length, and other end of angle hanger being fixed with nut and bolts
to G.I. channels 45x15x0.9mm running at the rate of 1200mm centre to centre to which the
ceiling section 0.5mm thick button wedge of 80mm with tapered flanges of 26mm each having
clips of 10.5mm at 450mm centre to centre shall be fixed in a direction perpendicular to G.I.
channel with connecting clips made out of 2.64mm diax230mm long G.I. wire at every junction
including fixing the gypsum board with ceiling section and perimeter channels 0.5mm thick
27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to
wall/partition with the help of rawl plugs at 450mm centre to centre with 25mm long drive-all
screws @ 230mm interval including jointing and fixing to a flush finish of tapered and square
edges of the board with recommended filler, jointing tapes, finisher and two coats of primer
suitable for board as per manufactures specification and also including the cost of making
openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels
suitably fixed all complete as per drawing and specification and direction of the Engineer in
Charge but excluding the cost of painting with :
112.5 mm thick tapered edge gypsum moisture resistant board

121 Providing and fixing tiled false ceiling of approved materials of size 595x595 mm in true sqm 2325.45
horizontal level suspended on inter locking metal grid of hot dipped galvanized steel sections (
galvanized @ 120 gsm/sqm, both side inclusive) consisting of main "T" runner with suitably
spaced joints to get required length and of size 24x38mm made from 0.30mm thick (minimum)
sheet, spaced at 1200mm center to center and cross "T" of size 24x25mm made of 0.30mm
thick (minimum) sheet, 1200mm long spaced between main "T" at 600mm center to center to
form a grid of 1200x600 mm and secondary cross "T" of length 600mm and size 24x25mm made
of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600mm panel to form
grids of 600x600mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of
approved texture in the grid including, wherever, required, cutting/making, opening for services
like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended
from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 x mm fixed to ceiling with 12.5 mm
dia and 50 mm long dash fasteners, 4mm GI adjustable rods with galvanised butterfly level clips
of size 85 x 30 x 0.8 mm spaced at 1200mm center to center along main T, bottom exposed
width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete at all
heights as per specifications drawings and as directed by Engineer-in-charge.
GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595 mm, and
0.5mm thick with 8mm drop; made of G I sheet having galvanizing of 100 gms/sqm (both sides
inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum),
including factory painted after bending.

122 Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved sqm 1550.30
texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light
Reflectance > 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS
476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round
galvanized iron section of 0.33 mm thick (galvanized @120 gsm ) comprising of main T runners
of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary
intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600
mm suspended from ceiling using galvanized mild steel item (galvanised @80gsm) 50 mm long
8mm outer diameter M-6dash fasteners, 6 mm diameter fully threaded hanger rod upto 1000 mm
length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre
along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter
wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help
of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed
bottom portion of all T-sections used in false ceiling support system shall be prepainted with
polyester baked paint, for all heights. The work shall be carried out as per specifications,
drawings and as per directions of the engineer-in-charge.
With 16 mm thick beveled tegular mineral fibre false ceiling tile (NRC 0.55 to 0.6)

[10/80]
Page - 11
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


123 Providing & fixing access panel is made out of Moist Bloc (Moisture Resistant) board for opening sqm 155.03
600 x 600mm of thickness 12.5mm. All edges of the panel are reinforced with aluminium profiles
and corners are guarded with stainless steel 304 grade clips to increase strength and prevent
damages. complete in all respect as directed by Engineer-in-charge.
124 Providing and making 75mm deep suspended feature panel ceiling comprising of 19mm Thk. sqm 1550.30
Commercial Board layered with 4mm Thk. Italian Veneer ply including all edge mouldings,
melamine polish, suspension system etc. complete as per drawing & as directed by Engineer-in-
charge.
125 Providing and fixing U Baffle Aluminium panel ceiling (M/s Hunter Douglas or Equivalent) sqm 1550.30
consisting of Wood finish panel size 30 mm width X 100mm deep using 0.6mm thick, panel
length upto 4 mtr, Coil Coated on a Continuous Paint Line, Double baked and roll formed from
enamelled corrosion resistance Aluminium alloy AA 3005 (Al. Mg) for higher strength and good
roll forming characteristics. Panels shall be clipped to a baked enamelled Aluminium carrier of 30
mm wide x 47 mm high x 0.5 mm thick, Black Colour coated, one leg of the carriers with cut outs
to hold the panels in a module of 150 mm. Panel carrier shall be suspended by means of
threaded rod at a distance of 1.8 mtr c/c. Aluminium panels shall be chromatised for maximum
bond between metal and paint enamelled twice under high temperature, Exposed side with a full
primer and finish coat on a Continuous Paint Line. Ceiling area above U Baffle to be painted in
black colour before fixing this system (Cost of black paint shall be paid separately).

126 Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar sqm 6041.49
refractive index) > 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and
sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement :
4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1,
including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting
upto 150 mm height along the parapet walls in the same manner.
127 Providing and laying roof insulation with 40 mm thick impervious sprayed, closed cell free Rigid sqm 6041.49
Polyurethane foam over deck insulation conforming to IS - 12432 Pt. III (density of foam being 40-
45 kg/cum), over a coat of polyurethane primer applied @ 6-8 sqm per litre, laying 400 G
polythene sheet over PUF spray and providing a wearing course of 40 mm thick cement screed
1:2:4 (1 cement : 2coarse sand : 4 stone aggregate 20 mm nominal size) in chequered rough
finish, in panels of 2.5 m x 2.5 m and embedding with 24 G wire netting and sealing the joints
with polymerized mastic, all complete as per direction of Engineer-in-Charge.

128 SUB HEAD-X :- FINISHING WORK sqm 10992.79


12 mm cement plaster 1 : 6 (1 cement : 6 fine sand).
129 15 mm cement plaster 1 : 6 (1 cement : 6 fine sand) on the rough side of single or half brick wall. sqm 7328.53

130 6 mm cement plaster to ceiling 1 : 3 (1 cement : 3 fine sand). sqm 3636.12

131 20 mm cement plaster 1 : 6 (1 cement : 6 fine sand). sqm 5776.69

132 Providing and applying white cement based putty of average thickness 1 mm, of approved brand sqm 21957.44
and manufacturer, over the plastered wall surface to prepare the surface even and smooth
complete.
133 Finishing walls with textured exterior paint of required shade : sqm 5776.69
New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of
exterior primer applied @ 2.20kg/10 sqm.
134 Painting one or more coats with black Japan paint of approved brand and manufacture to give an sqm 221.32
even shade.
135 Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less sqm 24618.93
than 50 grams/ litre, of approved brand and manufacture, including applying additional coats
wherever required, to achieve even shade and colour.
Two coats
136 Providing & fixing 150mm wide Chicken wire mesh on joints of RCC & Brick work before sqm 2195.74
plastering complete in the direction of Engineer-in-charge.
137 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per sqm 58311.24
manufacturer's specifications including appropriate priming coat, preparation of surface, etc.
complete.
On steel work
138 SUB HEAD-XI :- ALUMINIUM WORK kg 24098.85
Providing and fixing aluminum work for doors, windows, ventilators and partitions with extruded
built up standard tubular sections/ appropriate Z sections and other sections of approved
make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or
with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom
and sides with required PVC/neoprene felt etc. Aluminum sections shall be smooth, rust free,
straight, mitred and jointed mechanically wherever required including cleat angle, Aluminum
snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per
architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be
paid for separately) :
For fixed portion
Powder coated aluminum (minimum thickness of powder coating 50 micron)
139 For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and kg 22819.44
making provision for fixing of fittings wherever required including the cost of PVC / neoprene
gasket required (Fittings shall be paid for separately).
Powder coated aluminum (minimum thickness of powder coating 50 micron)

[11/80]
Page - 12
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


140 Providing and fixing over glass 1.5mm thick Etching strips (film) of approved make fixed as per sqm 9.57
manufacturer's specifications all complete as per direction of the Engineer-in-charge.
141 Filling the gap in between aluminum frame & adjacent RCC/ Brick/ Stone work by providing metre 3012.36
weather silicon sealant over backer rod of approved quality as per architectural drawings and
direction of Engineer-in-charge complete.
Upto 5mm depth and 5 mm width
142 SUB HEAD - XII - WATER PROOFING WORK kg 6255.92
Providing and mixing integral crystalline admixture for waterproofing treatment to RCC structures
like basement raft, retaining walls, reservior, sewage & water treatment plant, tunnels / subway
and bridge deck etc. at the time of transporting of concrete into the drum of the ready-mix truck,
using integral crystalline admixture @0.80% (minimum) to the weight of cement content per
cubic meter of concrete) or higher as recommended by the manufacturer's specification in
reinforced cement concrete at site of work. The material shall meet the requirements as specified
in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90%, compared with
control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure. The crystalline
admixture shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be
carried out all complete as per specification and the direction of the Engineer-in-charge. The
product performance shall carry guarantee for 10 years against any leakage.

143 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing sqm 2769.32
treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs,
podiums, reservior, sewage & water treatment plant, tunnels/subway and bridge deck etc.,
prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for
vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces
and applying the same from negative (internal) side with the help of synthetic fiber brush. The
material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing
permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and
resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable
of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as
per specification and the direction of the engineer-in-charge. The product performance shall carry
guaranteed for 10 years against any leakage.
For vertical surface two coats @0.70 kg per sqm per coat
144 For horizontal surface one coat @1.10 kg per sqm. sqm 6673.03
145 Providing and applying crystalline mortar by mixing in the ratio of 4.5 : 1 (4.5 parts crystalline metre 1230.81
mortar : 1 part water) for the treatment of faulty construction joints, cracks, tie rod holes and
spalled & honeycombed surface of RCC underground structures like basement, water tanks,
bridge deck etc. to ensure water tightness. The crystallie mortar shall conform to the EN 1504-3
having compressive strength Class R4 > 45 MPa and adhesive bond strength Class R3 > 1.5
MPa. The work shall be carried out all complete as per specification and the direction of the
Engineer-in-charge. The product performance shall carry guarantee for 10 years against any
leakage.
For sealing cracks and faulty construction joints, by preparing the surface, making U-shape
groove size of 25x25mm and then priming the surface with integral crystalline slurry @0.05kg per
running meter and while the surface is tacky then filling the groove upto top edge with crystalline
mortar @1.50kg per running meter. Once crystalline mortar is touch dry then finally applying two
coats of integral crystalline slurry @0.05kg per running meter per coat on treated surface.

146 For patching of tie rod holes, preparing tie rod hole surface and then priming the area with each hole 923
integral crystalline slurry @0.070kg per sqm and while the surface is tacky, repairing and then
filling the tie rod holes with crystalline mortar @0.040kg per hole. The crystalline mortar shall be
tightly rodded into tie rod holes or packed tightly (For 25x25x25 mm tie rod hole, use 0.040 kg to
fill the hole)
147 Providing and applying of swellable type water stop tape, 19mm x 25mm thick in linear meter metre 1230.81
(expansive nature) for construction joints treatment of RCC structure, such as raft slab, retaining
walls, water storage tank and at the junctions of raft slab with the retaining walls etc.. After
cleaning the surface, one coat of required primer for swellable water stop tape shall be applied
throughout the length of the joint @3.78 litre per 240 running meter. Over the primed surface
swellable type water stop tape shall be placed. The work shall be carried out all complete as per
specification and the direction of the engineer-in-charge. The product performance shall carry
guaranteed for 10 years against any leakage.
148 Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by sqm 753.60
applying cement slurry mixed with water proofing cement compound consisting of applying :
(a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound
@ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours.
(b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement
compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water
curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints,
corners, junctions of pipes and masonry with polymer mixed slurry.
149 Providing and laying broken AAC block in sunken portion of W.C. & kitchen. These broken Block cum 278.25
mixed with cement mortar 1:8 ( 1 cement : 8 coarse sand) laid and compacted properly including
supply of labour, material, and tools and plant etc. as per instruction of Engineer-in-charge.

[12/80]
Page - 13
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


150 Waterproofing Treatment for Landscaping Decks sqm 1704.00
Polyurethane based waterproofing system for podium and landscape decks.
Base preparation
1. Compressed air cleaning has to be done so as to make the surface free of dust, debris,
laitance etc. Repairing cracks by cutting and making V-groove in 25x25 mm, with SBR polymer
modified mortar , filling the groove with CM(1:3) mixed with SBR latex 10% by weight of cement
2. Providing and making fillets at the junction of the walls and the slabs using cement mortar of
1:4 mix admixed with 5 % of SBR latex by weight of cement.
3. Provide and applying liquid applied, highly permanent elastic, cold applied & cold curing single
component PU based waterproofing coating based on pure elastomeric hydrophobic
polyurethane resins having resistance to root penetration, Apply 2 coats@1.8kg/sq.mtr to
achieve an avergae thickness of 1.2 .The product must have the following technical properties:
Elongation at break 400 % as per ASTM D-412, Tensile strength 4 N/mm2 as per ASTM D412,
Shore hardness-65 as per ASTM 2240.The coating must be applied over the prepared substrate
primed with PU Primer@180-190 gms/sq.mtr.
4. Providing & laying of minimum 150 gsm geotextile layer.
5. Laying of Protection screed of average 75 mm thick in slope using 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 20 mm nominal size) grade concrete over geotextile as per
recommendations (supply of oncrete in scope of civil contractor)
FOR LANDSCAPE AREAS
Supply and installation of approved make Rolled Matrix Soil Filter cum surface drainage System
as per approved manufacturers specifications. consist of dimple raised, moulded polypropylene
sheet bonded to a high strength polypropylene geotextile fabric This geotextile fabric composite
allows passage of moisture through fabric while preventing fine soil from entering to drainage
channel. all complete as specified and as directed by the Engineer-in-Charge :

151 SUB HEAD-XII:- STRUCTURAL GLAZING, CURTAIN GLAZING, ALUMINIUM COMPOSITE Kg 23935.42
PANEL WORK
Providing and supplying aluminium extruded tubular and other aluminium sections as per the
rchitectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5
or T6 as per BS74,including super durable powder coating of 60-80 microns conforming to
AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. (The item
includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of
extruded aluminium frame work. Nothing extra shall be paid on this account).
152 Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized sqm 1595.69
system of structural glazing (with open joints) for linear as well as curvilinear portions of the
building for all heights and all levels, including:
a) Structural analysis & design and preparation of shop drawings for the specified design loads
conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind
pressure without any failure), including functional design of the aluminum sections for fixing
glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets,
screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire
stop (barrier)-cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure
equalisation & drainage and protection against fire hazard including:
b) Fabricating and supplying serrated M.S. hot dip galvanised /Aluminium alloy of 6005 T5
brackets of required sizes, sections and profiles etc. to accommodate 3 Dimensional movement
for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/
masonry/structural steel framework of building structure using stainless steel anchor fasteners/
bolts,
nylon separator to prevent bimetallic contacts with nuts and
washers etc. of stainless steel grade 316, of the required
capacity and in required numbers.
c) Providing and filling, two part pump filled, structural silicone sealant and one part weather
silicone sealant compatible with the structural silicone sealant of required bite size in a clean and
controlled factory / work shop environment , including double sided spacer tape, setting blocks
and backer rod, all of approved grade, brand and manufacture, as per the approved sealant
design, within and all around the perimeter for holding glass.
d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes,
shapes and profiles, as required as per the site conditions, to seal the gap between the building
structure and all its interfaces with curtain glazing to make it watertight.
e) Making provision for drainage of moisture/ water that enters the curtain glazing system to
make it watertight, by incorporating principles of pressure equalization, providing suitable gutter
profiles at bottom (if required), making necessary holes of required sizes and of required
numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating
and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other

[13/80]
Page - 14
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


153 Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically- sqm 1595.69
sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as
required and specified, comprising of an outer heat strengthened float glass 6mm thick, of
approved colour and shade with reflective soft coating on surface # 2 of approved colour and
shade, an inner Heat strengthened clear float glass 6mm thick, spacer tube 12mm wide,
dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all
complete for the required performances, as per the Architectural drawings, as per the approved
shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be
assembled in the factory/ workshop of the glass processor.“(Payment for fixing of IGU Panels in
the curtain glazing is included in cost of item No.26.2)“For payment, only the actual area of glass
on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant)
provided and fixed in position, shall be measured in sqm.“
(i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, +
12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as
visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection
external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K
etc. The properties of performance glass shall be decided by technical sanctioning authority as
per the site requirement.
154 Extra for openable side / top hung vision glass panels (IGUs) including providing and supplying sqm 478.71
at site all accessories and hardwares for the openable panels as specified and of the approved
make such as heavy duty stainless steel friction hinges, min 4 -point cremone locking sets with
stainless steel plates, handles, buffers etc. including necessary stainless steel screws/ fasteners,
nuts, bolts, washers etc. all complete as per the Architectural drawings, as per the approved
shop drawings, as specified and as directed by the Engineer in- Charge.

155 SUB HEAD-XIII :- ROAD WORKS : sqm 3914.00


Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after
excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road
roller including making good the undulations etc. and re-rolling the sub grade and disposal of
surplus earth with lead upto 50 metres.
156 Extra for compaction of earth work in embankment under optimum moisture conditions to give at cum 3718.30
least 95% of the maximum dry density (proctor density).
157 Supplying and stacking at site cum 587.00
90 mm to 45 mm size stone aggregate
158 63 mm to 45 mm size stone aggregate cum 587.00

159 Stone screening 13.2 mm nominal size (type A) cum 293.50

160 Stone screening 11.2 mm nominal size (type A) cum 293.50

161 Moorum cum 196.00

162 Laying spreading and compacting stone aggregate of specified sizes to WBM specifications cum 784.10
including spreading in uniform thickness, hand picking, rolling with 3 wheeled road/vibratory roller
8-10 tonne in stages to proper grade and camber, applying and brooming requisite type of
screening/binding material to fill up interstics of coarse aggregate watering and compacting to
the required density.
163 Providing and laying 400 micron thick PVC Sheet on WBM Surface complete as per direction of sqm 2614.10
engineer-in-charge.
164 Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. cum 1265.83
The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum
dewatering process and finally finished by floating, brooming with wire brush etc. complete as per
specifications and directions of Engineer-in-charge. (The panel shuttering work shall be paid for
separately).
(Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as
per design mix is payable/ recoverable separately).
165 Providing & Fixing in position premoulded joint filler in expansion joint per cm 7469.82
depth per
cm width
per m
length
166 Providing and laying in position bitumen hot sealing compound for expansion joints etc. per cm 7469.82
16.46.1 Using grade 'A' sealing compound. depth per
cm width
per m
length
167 PAINTING ROAD / RUNWAY MARKING sqm 41.60
Painting runway/taxi track/apron marking with adequate no. of coats to give uniform finish with
road marking paint of superior make as approved by the Engineer-in-charge i/c cleaning the
surface of all dirt, scales, oil, grease and other foreign material etc. and lining out complete
New work (Two or more coats)

168 Providing and laying 60mm thick factory made cement concrete interlocking paver block of M-30 sqm 1299.63
grade made by block making machine with strong vibratory compaction and of approved size and
design/shape laid in required colour and pattern over and including 50 mm thick compacted of
coarse sand, filling the joints with coarse sand etc. all complete as per direction of engineer-in-
charge.

[14/80]
Page - 15
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


169 Providing and laying at or near ground level factory made kerb stone of M-25 grade cement Cum 37.35
concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1
cement: 3 coarse sand), including making joints with or without grooves (thickness of joints
except at sharp curve shall not to more than 5mm), including making drainage opening wherever
required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall
be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).

170 Providing and fixing factory made precast RCC perforated drain covers, having concrete of each 415
strength not less than M-25, of size 1000 x 450x50 mm, reinforced with 8 mm dia four nos
longitudinal & 9 nos cross sectional T.M.T. hoop bars, including providing 50 mm dia perforations
@ 100 to 125 mm c/c, including providing edge binding with M.S. flats of size 50 mm x 1.6 mm
complete, all as per direction of Engineer in-charge.
171 Providing and fixing 10x10 x7.50 cm stone block hand cut and chisel dressed on top, for paving Sqm 293.17
in floors, drains etc. laid over 20mm thick base mortar 1:4 (1 cement : 4 coarse sand) with joints
10mm wide filled with same mortar including ruled pointing etc. complete as per direction of
engineer-in-charge.
172 SUB HEAD-XIIII :- HORTICULTURE & LANDSCAPING cum 3952.35
Trenching in ordinary soil up to a depth of 60 cm including removal and stacking of serviceable
materials and then disposing of surplus soil, by spreading and neatly leveling within a lead of 50
m and making up the trenched area to proper levels by filling with earth or earth mixed with
sludge or/and manure before and after flooding trench with water (excluding cost of imported
earth, sludge or manure).
173 Supplying and stacking of good earth at site including royalty and carriage up to 1 km (earth cum 3293.63
measured in stacks will be reduced by 20% for payment).
174 Supplying and stacking at site dump manure from approved source, including carriage up to 1 cum 548.94
km (manure measured in stacks will be reduced by 8% for payment) :
Screened through sieve of I.S. designation 20 mm
175 Screened through sieve of I.S. designation 16 mm cum 548.94

176 Screened through sieve of I.S. designation 4.75 mm cum 548.94

177 Fine dressing of the ground sqm 10978.75

178 Spreading of Sludge Farm Yard Manure or/and good Earth (Spreading of sludge farm yard cum 548.94
manure or/ and good earth in required thickness (cost of sludge, farm- yard manure or/and good
earth to be paid for separately))
179 Mixing earth and sludge or manure in the required proportion specified or directed by the Officer- cum 548.94
in-charge..
180 Grassing with ' Doobs' Grass (Grassing with 'Doobs' grass including watering and maintenance sqm 4391.50
of the lawn for 30 days or more till the grass forms a thick lawn free from weeds and fit for
moving including supplying good earth if needed)
i) In rows 15 cm apart in either direction
181 In rows 7.5 cm apart in either direction sqm 4391.50
182 Digging holes in ordinary soil and refilling the same with the excavated earth mixed with manure each 50
or sludge in the ratio of 2:1 by volume (2 parts of stacked volume of earth after reduction by 20%
: 1 part of stacked volume of manure after reduction by 8%) flooding with water, dressing
including removal of rubbish and surplus earth, if any, with all leads and lifts (cost of manure,
sludge or extra good earth if needed to be paid for separately) :
Holes 60 cm dia, and 60 cm deep.
183 Holes 45 cm dia, and 45 cm deep. each 50

184 Tree Guard with MS Iron (Providing and fixing MS iron tree guard 60 cm dia and 2 metre high each tree 50
above ground level formed of 4 Nos (25 x 6 mm) and 8 Nos (25 x 3 mm) vertical MS riveted to 3 guard
Nos (25 x 6 mm) iron rings in two halves, bolted together with 8 mm dia and 30 mm long bolts
including painting two coats with paint of approved brand over a coat of priming, complete in all
respects.)
185 Tree Guard with MS Angle Iron and Steel Wire (Providing and fixing tree guard 0.60 metre each tree 50
square, 2.00 metre high fabricated with MS angle iron 30 x 30 x 3 mm, MS iron 25 x 3 mm and guard
steel wire3 mm dia welded and fabricated as per design in two halves bolted together)
186 GROUND COVERS PLANTS each 50
Providing and Displaying of Wadelia trilobata plant, full of leaves in 15 cm size of Poly bags & as
per direction of the officer-in-charge.
187 Providing and Displaying of Duranta Golden plant, having ht.15 to 20 cm bushty shape plant with each 25
fresh and healthy leaves in 20 cm size of Earthen Pot / Plastic Pot & as per direction of the
officer-in-charge..
188 Providing and Displaying of Iresine herbstii plant, of height 20-30 cm. full of branches well each 25
developed in 15 cm size of Earthen Pot / Plastic Pot & as per direction of the officer-in-charge.

189 TREE PLANTS each 10


Supply and stacking of Alstonia scholaris plant of height 150-165 cm. in bag of size 25 cm as per
direction of the officer-in-charge.
190 Supply and stacking of Bauhinia blakeana (Kachnar) plant of height 120-150 cm. in big poly bags each 10
of size 25 cm as per direction of the officer-in-charge.
191 Supply and stacking of Bombax ceiba plant of height 150-165 cm. in big poly bags of size 25 cm each 5
as per direction of the officer-in-charge.
192 Supply and stacking of Grevillea robusta (Silver Oak) plant of height 150-165 cm. in big poly each 18
bags of size 25 cm as per direction of the officer-in-charge.

[15/80]
Page - 16
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


193 Supply and stacking of Kigelia pinnata plant of height 150-165 cm. in big poly bags of size 25 cm each 10
as per direction of the officer-in-charge.
194 Supply and stacking of Melia azedarach plant of height 120-135 cm. in big poly bag of size 25cm each 17
as per direction of the officer-in-charge.
195 Supply and stacking of Michelia champa (Golden Champa)plant of height 90-105 cm. in earthen each 10
pots of size 25 cm as per direction of the officer-in-charge.
196 Supply and stacking of Putranjiva roxburghii plant of height 90-105 cm. in big polybag of size 25 each 20
cm as per direction of the officer-in-charge.
197 SHRUBS each 20
Supply and stacking of plant Jatropha multifida (red colour) of height 60-75 cm. multibranched in
p.bag of size 25 cm as per direction of the officer-in-charge.
198 Supply and stacking of plant Calliandra hybrida of height 105-120 cm., well branched, bushy in each 40
big size HDPE bag as per direction of the officer-in-charge.
199 Supply and stacking of plant Gardenia jasminoides of height 45-60 cm. with 3-4 branches in each 20
earthen pots of size 20 cm as per direction of the officer-in-charge.
200 Supply and stacking of plant Nerium oleander (kaner) of height 45-60 cm. with 3-4 branches in each 20
poly bags of size 20 cm as per direction of the officer-in-charge.
201 CREEPER PLANTS each 50
Supply and stacking of Clerodendrum splendens plant of height 30 cm to 45 cm. in 20 cm size of
Earthen pots / Plastic pots & as per direction of the officer-in-charge.
202 Supply and stacking of Jasminum grandiflorum (chameli) plant of height 30 cm to 45 cm. in 20 each 50
cm size of Earthen pots / Plastic pots & as per direction of the officer-in-charge. .
203 SUB HEAD-XV :- MISCELLANEOUS WORK Meter 2000.00
Providing & Fixing PVC Stretcher Guard minimum 150 mm wide with extruded aluminium base
including all accessories per approved design all complete as per direction of Engineer-In-
Charge.
204 Providing and Fixing Precast Cement Concrete Wheel stop all complete as per drawing (make- cum 35.00
K.K.Manhole or equivalent ).
205 Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : Each 240
10910 on 12mm dia steel bar conforming to IS :1786 having minimum cross section as 23
mmx25mm and over all minimum length 263 mm and width as 165mm with minimum 112 mm
space between protruded legs having 2 mm tread on top surface by ribbing or chequering
besides necessary and adequate anchoring projections on tail length on 138 mm as per standard
drawing and suitable to with stand the bend test and chemical resistance test as per
specifications and having manufacture's permanent identification mark to be visible even after
fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3
coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design.

206 Providing and fixing M.S. angle 50x50x5 mm to act as nosing with lugs of M.S. flat 10x5 mm, 10 Kg 2827.20
cm long, forked at end 60cm apart (minimum three lugs to be provided), including necessary
welding and applying a priming coat of approved primer on exposed surface etc. complete.

207 SUB HEAD: 'B1': PLUMBING WORKS & F/F Each 115
SUB HEAD I - SANITARY FIXTURE & FITTINGS
Supply and install white vitreous china extended wall mounted water closet of approved shape
(size: 540mmx360mmx335mm depth) including providing and fixing vitreous china concealed
cistern with duel flush fitting, of flushing capacity 3 litre/6litre and adjustable 2litre/4 Litre including
seat cover, and cistern fitting, nuts, boltsand gasket etc complete.
208 Supply and install white vitreous china powered by 220 volt AC Model based infrared sensor Each 103
operated urinal of 558x325mm approx. having Flow rate at 45 psi ≤ 2.5 lpm with concealed
urinal sensor, having water inlet from back side, including fixing to wall with suitable brackets all
as per manufacturers specification and direction of Engineer.
209 Supply and install Wash basin vanity in white color for over counter mounting (Size:450mm x Each 92
450mm), specially fabricated brackets, painted white, 32mm dia CP waste and connections
pipe 450mm / 600mm long braided hose with nipple, nut, oring and rubber washer etc complete.
with C.P. wall flange and rubber adopter for waste connection, complete including cutting and
making good the walls, wherever required.
210 Supply and install CP brass single lever low flow wash basin mixer Flow rate at 45 psi ≤ 6 lpm Each 34
with 15 mm CP single lever pillar cock with pop up and waste complete including cutting and
making good the walls where required.
211 Supply and install CP brass push type pillar tap for wash basin Flow rate at 45 psi ≤ 6 lpm with Each 58
waste coupling complete including cutting and making goood deck mounted basin Faucet.

212 Supply and install Salem Stainless Steel kitchen sink (Size: 610mm x 460mm x 205 mm) without Each 3
drain board as per manufacturers specification and direction of Engineer with CI brackets and
stainless steel waste with plug 40mm including painting of fittings and brackets, cutting and
making good the walls wherever required.
213 Supply and install CP brass single lever low flow Sink mixer Flow rate at 45 psi ≤ 6 lpm with 15 Each 3
mm CP single lever pillar cock with pop up and waste complete including cutting and making
good the walls where required.
214 Supply and install of 15mm C.P shower arm 190mm long with divertor with provision for over Each 2
head shower with spout and with wall flange including cutting and making good the walls,
wherever required.
215 Supply and install towel ring (Size:210mmx160mm) including cutting and making good the Each 66
walls/doors wherever required complete as directed by Engineer In charge.
216 Supply and install CP angular stop cock with wall flange 15mm dia for basin mixer, health faucet Each 115
and geyser points

[16/80]
Page - 17
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


217 Supply and install wall mounted CP shop dispenser with metallic bottle etc complete in all Each 66
respects.
218 Supply and install straight type Macfit single body push fit type WC pan connector with factory Each 115
supplied spring loaded seal guard with integral single mould sealing fins made of flexible EVA
body, including bush/adaptor for use with C.I. Pipe as supplied with the pan connector.

219 Supply and install hand shower (Health faucet) Flow rate at 45 psi ≤ 6 lpm with 1mtr long Easy Each 115
Flex Tube in chrome finish and wall hook.
220 Providing & fixing glass urinal partition of Height: 900mm,Width: 450mm &Frosted Safety Glass: Each 99
8 mm with fixed with expandable anchor fasteners with C.P. brass bolts and washers, embedded
in wall with anchor and set in cement concrete complete including cutting and making good the
walls wherever required.
221 Supply and install towel rail single towel rail 600mm long including fixing of brackets with CP Each 2
screws with concealed fitting arrangement of approved quality and colour.
222 Supply and install C.P brass short body bib cock of approved quality as per manufacturers Each 17
specification and direction of Engineer.
15 mm nominal bore
223 Supply and install Toilet Paper Holder with flap complete including cutting holes in wall and Each 115
making good the wall wherever required.
224 Supply and install first quality bottle trap (with internal partition) 32mm size with 190mm long Each 92
wall connection pipes and wall flange.and waste coupling 32mm size full thread with 130mm
height etc complete in all respect as per site.
225 Supply and install wall mounted Stainless steel grab bars of 600mm long grab bar including Each 9
cutting & making good the walls .
226 Supply and install satin finish stainless steel 316 grade wall mounted coat hooks/peg rag on door Each 115
complete.
227 Supply and install of cp brass soap dish of approved design Each 2
228 Supply and install solid state no touch operating fully highgenic SS hand drier of best quality, to Each 22
be operated with 230 volts, single phase, with fully hygienic condition, with all accessories
including cutting and making good the walls, wherever required.
229 Providing and fixing CP brass waste for wash basins and sinks. Each 3
32 mm dia
230 Providing and fixing 600x450 mm bevelled edge mirror or superior glass (of approved quality) Each 60
complete with 6 mm thick asbestos sheet ground fixed to wooden cleats with CP brass screws
and washers.
231 Providing and fixing PVC connection pipe with brass union. Each 133
45 cm length
15 mm nominal bore
232 Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS Each 12
standards and weighing not less than 690 gms.
15mm nominal bore
233 Providing and fixing CP brass angle valve for basin mixture and geyser points of approved Each 133
quality confirming to IS: 8931.
234 Supply and install 6mm thick beveled edge glass mirror with side polished complete including Sqm 72.00
fixing over marine plywood frame work at all levels & height including fixing of molded ,screw and
silicon etc. incl labors, tools, scaffolding at all heights as per Direction of EIC
.
235 Supply and install S&S grating of approved quality and colour. Each 26
Circular type
100 mm nominal dia
236 125 mm nominal dia with 25 mm waste hole. Each 145
237 Providing, Installing & fixing storage type water heater of approved shade with copper container, Each 7
glasswool insulation, stove enamelled M.S jacket, thermostatically controlled inner heater with
pilot neon lamps, 15mm inlet stop cock valve, on inlet connection, 15mm dia C.P flexible
connection pipe in inlet & outlet suitable for working pressure of 8 kg/sqcm complete as required.
Capacity 25 litres

238 SUB HEAD II - SOIL, WASTE , VENT WATER PIPES Metre 1882.00
Providing and fixing sand cast iron/ cast iron (spun) soil, waste and vent pipes
100 mm dia
239 75mm dia Metre 284.00
240 Providing and fixing sand cast iron heel rest sanitary bend. Metre 33.00
100 mm dia
241 Providing and fixing sand cast iron single equal plain junction of required degree with access Each 77
door, insertion rubber washer 3 mm thick, bolts and nuts complete.
100 x 100 x 100mm
242 80x80x80 mm Each 12
243 Providing and fixing single equal plain junction of required degree . Each 370
100 x 100 x 100mm
244 80x80x80 mm Each 72
245 Providing and fixing sand cast iron trap of self cleaning design with sand cast iron screwed down Each 166
or hinged grating with or without vent arm complete including cost of cutting and making good
the walls and floors.
100mm inlet and 100mm outlet

[17/80]
Page - 18
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


246 Providing and fixing M.S. holder bat clamps of approved design to sand cast iron/cast iron (spun) Each 942
pipe embedded in and including cement concrete blocks 10 x 10 x 10 cm of 1:2:4 mix ( 1 cement
: 2 coarse sand : 4 graded stone aggregate 20mm nominal size ) including cost of cutting holes
and making good the walls etc.
100mm dia
247 75mm dia Each 142
248 Providing and fixing plain bend of required degree. Each 137
100mm dia
sand cast iron S & S as per IS: 3989
249 75mm dia Each 22
sand cast iron S & S as per IS: 3989
250 Providing and fixing terminal guard. Each 33
100mm dia
sand cast iron S & S as per IS: 3989
251 75mm dia Each 17
sand cast iron S & S as per IS: 3989
252 Providing lead caulked joints to sand cast iron / centrifugally cast (spun) iron pipes and fittings of Each 941
diametre:
100mm dia
253 75mm dia Each 142
254 Providing & fixing GI pipes complete with GI fittings and clamps, including cutting & making good Metre 207.00
the walls etc.
Internal work- Exposed on wall
32mm nominal bore
255 40mm nominal bore Metre 200.00
256 50mm nominal bore Metre 79.00
257 Painting GI pipes and fittings with two coats of anti corrosive bitumestic paint of approved quality. Metre 207.00
32mm nominal bore

258 40mm nominal bore Metre 200.00


259 50mm nominal bore Metre 79.00
260 Painting sand cast iron/ centrifugally cast (spun) iron soil, waste vent pipes and fittings with two Metre 1882.00
coats of synthetic enamel paint of any colour such as chocolate grey, or buff etc. over a coat of
primer (of approved quality) for new work
100mm diameter pipe
261 75mm diameter pipe Metre 284.00
262 Providing and fixing single unequal plain invert branch of required degree : Each 72
100 x 100 x 75mm
sand cast iron S & S as per IS: 3989
263 Providing and fixing on wall face unplaqsticised- PVC rain water pipes confirming to IS: 13592 Metre 30.00
TYPE A, including jointing with seal ring confirming to IS: 5382 leaving 10 mm gap for thermal
expansion, (i) Single socketed pipes.
75mm diameter.
264 110mm diameter. Metre 80.00
265 160mm diameter. Metre 516.00
266 Providing and fixing on wall face unplaqsticised- PVC moulded fitting/ accessories for Each 23
unplaqsticised- PVC rain water pipes confirming to IS: 13592 TYPE A, including jointing with
seal ring confirming to IS: 5382 leaving 10 mm gap for thermal expansion, (i) Single socketed
pipes.
Single Tee with door
160x160x160 ,mm
267 Bend 87.5 degree Each 23
160 mm bend
268 75mm diameter. Each 2
269 110mm diameter. Each 8
270 Making khurras 45x45 cm. with average minimum thickness of 5 cm cement concrete 1:2:4 (1 Each 26
cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) over PVC
sheet1mx1mx400 micron, finished with12 mm cement plaster1:3 (1 cement : 3 coarse sand) and
a coat of neat cement, rounding the edges and making and finishing the outlet complete
271 Providing and laying cement concrete 1 : 5 : 10 (1 cement : 5 lime sand : 10 graded stone Metre 85.00
aggregate 40 mm nominal size) all around CI/SW Pipe including bed concrete 15 cm thick as
per standard design.
100 mm diameter
272 Providing and fixing 100mm dia G.I. inlet fitting consisting of 100mm dia main G.I pipe with Each 166
multiple G.I. sockets (Inlets) of required diameter welded to it (as per site requirement) and fixing
the same to C.I trap and setting in cement concrete, complete as per instructions of the
Engineer in charge.
273 Providing and fixing G.I reducer/hopper/elbow (Floor Drain) of 100 x 75mm, complete as per Each 55
instructions of the Engineer in charge.(grating and G.I pipe to be paid separately)
274 Providing and fixing cast brass Floor Clean Out plug with suitable insert keys for opening, male Each 144
threaded joint with G.I. socket lead caulked to soil pipe / waste pipe of C.I. and C.I.(LA) pipe as
required complete as per instruction of the Engineer in charge.
275 Providing and fixing soil waste and vent pipes Meter 90.00
150 mm dia centrifugally cast (spun) iron Socket & Spigot (S&S) pipe as per IS:3989.
276 Providing and fixing plain bend of required degree: Each 15
150mm Sand cast iron S&S as per IS:3989.

[18/80]
Page - 19
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


277 Providing and fixing single equal plain junction of required degree. Each 15
150 x 150 x 150mm Sand cast iron S&S as per IS:3989
278 Providing and fixing single unequal plain junction of required degree. Each 15
150 x 150 x 100mm Sand cast iron S&S As per IS: 3989
279 Providing and fixing terminal guard Each 2
150mm Sand cast iron S&S as per IS: 3989.
280 Providing and fixing M.S. stays and clamps for sand cast iron/centrifugally cast (spun) iron pipe Each 4
of diameter:
150mm
281 Painting sand cast iron/centrifugally cast (spun) iron soil, waste vent pipes and fittings with paint Metre 90.00
of any colour such as chocolate, grey or buff, etc., over a coat of primer (of approved quality) for
new work.
150mm diameter pipe
282 SUB HEAD III - INTERNAL WATER SUPPLY Metre 68.00
Providing & fixing GI pipes complete with GI fittings and clamps, including cutting & making good
the walls etc.
Internal work- Exposed on wall
15mm nominal bore
283 20mm nominal bore Metre 122.00
284 25mm nominal bore Metre 147.00
285 32mm nominal bore Metre 391.00
286 40mm nominal bore Metre 326.00
287 50mm nominal bore Metre 85.00
288 65mm nominal bore Metre 334.00
289 80mm nominal bore Metre 339.00
290 100mm nominal bore Metre 50.00
291 Providing and fixing chlorinated poly vinyl chloride (CPVC) pipes having thermal stability for hot Metre 675.00
&coldwater supply, including all CPVC plain & brass threaded fitting, including fixing the pipe with
clamps at 1 m spacing. This includes jointing of pipes &fitting with one step CPVC solvent
cement and cost of cutting chases and making good the same including testing of joints
complete as per direction of Engineer in Charge.
Concealed work including cutting chases and making good the walls etc.
15mm nominal outer dia. Pipes.
292 20mm nominal outer dia. Pipes. Metre 357.00
293 25mm nominal outer dia. Pipes. Metre 174.00
294 32mm nominal outer dia. Pipes. Metre 306.00
295 Providing and fixing GI pipes complete with GI fittings including trenching and refilling etc Metre 15.00
(external work).
25mm nominal bore
296 32mm nominal bore Metre 15.00
297 40mm nominal bore Metre 20.00
298 50mm nominal bore Metre 20.00
299 65mm dia nominal bore Metre 15.00
300 80 mm dia nominal bore Metre 20.00
301 Providing & fixing brass stop cock of approved quality . Each 12
15 mm nominal bore
302 20 mm nominal bore Each 24
303 Providing and fixing gunmetal gate valve with CI wheel of approved quality (Screwed end) Each 22
25mm nominal bore
304 32mm nominal bore Each 17
305 40mm nominal bore Each 12
306 50mm nominal bore Each 6
307 65mm nominal bore Each 6
308 80mm nominal bore Each 5
309 100mm nominal bore Each 5
310 Constructing masonry chamber 30x30x50cm, inside with 7.5 class designation brick work in Each 7
cement mortar 1:4 (1 cement : 4 coarse sand) for stop cock with C.I. Surface box 100x100x75
mm ( inside) with hinged cover fixed in cement concrete slab 1:2:4 (1 cement:2 coarse sand:4
graded stone aggregate 20mm nominal size) necessary excavation foundation concrete 1:5:10
(1 cement:5 fine sand: 10 graded stone aggregate 40mm nominal size) and inside plastering with
cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick finished with a floating coat of neat
cement complete as per standard design with F.P.S. bricks.
311 Painting G.I. pipes and fittings with white paint over a coat of ready mixed priming coat both of Metre 68.00
approved quality for new work.
15 mm dia pipe
312 20 mm dia pipe Metre 122.00
313 25 mm dia pipe Metre 147.00
314 32 mm dia pipe Metre 391.00
315 40 mm dia pipe Metre 326.00
316 50 mm dia pipe Metre 85.00
317 65 mm dia pipe Metre 334.00
318 80 mm dia pipe Metre 339.00
319 100 mm dia pipe Metre 50.00
320 Painting GI pipes and fittings with two coats of anti corrosive bitumestic paint of approved quality. Metre 15.00
25 mm dia pipe

321 32 mm dia pipe Metre 15.00

[19/80]
Page - 20
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


322 40 mm dia pipe Metre 20.00
323 50 mm dia pipe Metre 20.00
324 65 mm dia pipe Metre 15.00
325 80 mm dia pipe Metre 20.00
326 Providing and filling sand all round GI pipes in external work. Metre 5.00
25 mm dia pipe
327 32 mm dia pipe Metre 5.00
328 40 mm dia pipe Metre 5.00
329 50 mm dia pipe Metre 5.00
330 65 mm dia pipe Metre 5.00
331 80 mm dia pipe Metre 5.00
332 Providing & fixing C.I double air valve of approved quality with bolts , nuts , rubber insertion etc Each 8
complete (The tail pieces , tapers etc if required will be paid separately )
50 mm dia
333 Installing & fixing cast-iron manhole cover and frame suitable for 600mm dia manhole with Each 12
lockable and lifting arrangement. The entire item shall be epoxy coated and approved by
insecticide department
Medium duty double seal of size 560 mm dia and total weight of cover & frame to be not less
than 116 KG. (Location : U/G Water Tanks Top)
334 Light duty double seal of size 560 mm dia and total weight of cover & frame to be not less than Each 12
116 KG. (Location : O/H Water Tanks Top)
335 Providing and fixing M.S fabricated hot dipped galvinised coating puddle flange comprising of Each 9
600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm
dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate,
inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded
joint in position with reinforcement bars of RCC tank wall/slab including making cutout in
shuttering during concrete casting of tank of following diameter. (Location: underground/
overhead tanks.)
25 mm dia
336 32 mm dia Each 6
337 40 mm dia Each 8
338 50 mm dia Each 25
339 80 mm dia Each 12
340 100 mm dia Each 19
341 150 mm dia Each 22
342 250mm dia Each 2
343 Providing orange colour safety foot rest of minimum 6mm thick plastic encapsulated as per IS : Each 115
10910 on12mm dia steel bar conforming to IS :1786 having minimum cross section as 23mm x
25mm and over all minimum length 263mm and width as 165mm with minimum 112mm space
between protrude legs having 2mm tread on top surface by ribbing or chequering besides
necessary and adequate anchoring projections on tail length on 138mm as per standard
drawing and suitable to with dtand the bend test and chemical resistance test as per
specifications and having manufacture's permanent identification make to be visible even after
fixing, including fixing in manholes with 30x20x15cm cement concrete block 1:3:6 (1 cement : 3
coarse sand : 6 graded stone aggregate 20mm nominal size) complete as per design.

344 Providing, Fixing, Testing & Commissioning of nitrle rubber insulation on hot water supply pipes. Metre 142.00
K-Flex, A-Flex, Armacell
15mm (9 mm thickness)
345 20mm (9 mm thickness) Metre 142.00
346 25mm dia (9 mm thickness) Metre 85.00
347 32mm dia (9 mm thickness) Metre 55.00
348 40mm dia (13 mm thickness) Metre 35.00
349 50mm dia (13 mm thickness) Metre 150.00
350 65mm dia (13 mm thickness) Metre 75.00
351 80mm dia (13 mm thickness) Metre 75.00
352 SUB HEAD IV - SEWERAGE & DRAINGE SYESTEM Metre 259.00
Providing laying and jointing glazed stone ware pipe grade 'A' with stiff mixture of cement mortar
in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete.
150 mm dia SW pipes

353 200 mm dia SW pipes Metre 213.00


354 Providing and laying cement concrete 1:5:10 ( 1 cement: 5 coarse sand: 10 graded stone Metre 259.00
aggregate 40 mm nominal size) alround stoneware pipes including in bed for pipes to be laid
in trenches as per standard details.
150 mm diameter
355 200 mm diameter Metre 213.00
356 Providing and Layng light duty non-pressure NP2 Class RCC pipes with Metre 474.00
collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 Cement : 2 fine sand)
including testing joints etc complete.
150 mm dia RCC Pipes (NP2)
357 250 mm dia RCC Pipes (NP2) Metre 346.00
358 300 mm dia RCC Pipes (NP2) Metre 58.00
359 450 mm dia RCC Pipes (NP2) Metre 50.00

[20/80]
Page - 21
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


360 Constructing brick masonry manhole with 7.5 class designation bricks in cement mortar 1:4 Each 5
(1 cement: 4 coarse sand) R.C.C. top slab 1:2:4 mix (1 cement: 2 coarse sand: 4 graded
stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement: 4 coarse sand:
8 graded stone aggregate 40 mm nominal size) inside plastering 12 mm thick with cement
mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making
channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size) finished with a floating coat of neat cement complete as per standard design.
Inside size:90 cmx80cm and 45 cm deep including CI cover with frame (Light Duty) 455x610mm
internal dimensions total weight of cover and frame to be not less than 38 kg and weight of
frame 15 kg.
With common burnt clay FPS (Non Modular Bricks) of class designation 7.5

361 Constructing brick masonry manhole with 2nd class bricks in cement mortar 1 : 5 (1 cement :5 Each 15
fine sand) RCC top slab with 1 : 2 : 4 mix (1 cement : 2 coarse sand : 4 stone single 20 mm
nominal size), foundation concrete 1 : 4 : 8 mix (1 cement : 4 coarse sand : 8 stone aggregate 40
mm nominal size) inside plastering 12 mm thick with cement mortar 1 : 3 (1 cement : 3 coarse
sand) finished with a floating coat of neat cement and making channels in cement concrete 1 : 2 :
4 mix (1 cement : 2 coarse sand : 4 stone aggregate 20 mm nominal size) neatly finished
complete as per standard design.
Inside size 90 x 80 cm and 45 cm deep including CI cover with frame (light duty) 455 x 610 mm
internal dimensions total weight of cover and frame to be not less than 38 Kg (weight of cover
and frame to be not less than 38 kg, (weight of cover 23 Kg and weight of frame 15 Kg).

362 Extra for depth for manholes Metre 6.00


Size 90 x 80 cm
With F.P.S. bricks class designation 7.5
363 Inside size 120x90 cm and 90 cm deep including CI Cover with frame (medium duty) 500 mm Each 6
internal diameter, total weight of cover and frame to be not less than 116 kg ( weight of cover 58
kg and weight of frame 58 kg)
with common burnt clay F.P.S.(non module) brick of class designation 7.5
364 Extra for depth for manholes Metre 3.00
Size 120 x 90 cm
With F.P.S. bricks class designation 7.5
365 Constructing brick masonry road gully chamber 50x45x60 cm with bricks of class designation 7.5 Each 25
in cement mortar 1:4 (1 cement :4 coarse sand ) including 500x450 mm precast RCC horizontal
grating with frame complete as per standard design .
With F.P.S bricks
366 Providing orange colour safety foot rest of minimum 6mm thick plastic encapsulated as per IS : Each 150
10910 on12mm dia steel bar conforming to IS :1786 having minimum cross section as 23mm x
25mm and over all minimum length 263mm and width as 165mm with minimum 112mm space
between protrude legs having 2mm tread on top surface by ribbing or chequering besides
necessary and adequate anchoring projections on tail length on 138mm as per standard
drawing and suitable to with dtand the bend test and chemical resistance test as per
specifications and having manufacture's permanent identification make to be visible even after
fixing, including fixing in manholes with 30x20x15cm cement concrete block 1:3:6 (1 cement : 3
coarse sand : 6 graded stone aggregate 20mm nominal size) complete as per design.

367 Constructing brick masonry circular manhole 0.91m internal dia at bottom and 0.56m dia at top in Each 5
cement mortar 1:4 (1 cement : 4 coarse sand) inside cement plaster 12mm thick with cement
mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation
concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) and
making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20mm nominal size) finished with a floating coat of neat cement all complete as per
standard design.
0.91m deep with SFRC cover and frame (heavy duty HD-20 grade designation) 560mm internal
diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg.
fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm
nominal size) including centering shuttering all complete. Excavation, foot rests and 12mm thick
cement plaster at the external surface shall be paid for separately).
With common burnt clay F.P.S.( Non modular) bricks of class designation 7.5
368 Extra depth for circular type manhole 0.91m internal dia. ( at bottom) beyond 0.91m to 1.67m. Metre 2.00
With common burnt clay F.P.S.( Non modular) bricks of class designation 7.5

369 Constructing brick masonry circular manhole 1.22m internal dia at bottom and 0.56m dia at top in Each 5
cement mortar 1:4 (1 cement : 4 coarse sand) inside cement plaster 12mm thick with cement
mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation
concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) and
making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20mm nominal size) finished with a floating coat of neat cement all complete as per
standard design.
1.68m deep with SFRC cover and frame (heavy duty HD-20 grade designation) 560mm internal
diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg.
fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm
nominal size) including centering shuttering all complete. Excavation, foot rests and 12mm thick
cement plaster at the external surface shall be paid for separately).
With common burnt clay F.P.S.( Non modular) bricks of class designation 7.5

[21/80]
Page - 22
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


370 Extra depth for circular type manholes 1.22m internal dia (at bottom) with beyond 1.68m to Meter 2.00
2.29m.
With common burnt clay F.P.S(Non Modular) bricks of class designation 7.5
371 Providing and fixing square mouth SW gully trap grade ‘A’ complete CI grating brick masonry Each 15
chamber with bricks of class designation 75 and water tight CI cover with frame of 300 x 300 mm
size (inside) the weight of cover to be not less than 13.00 kg and frame to be not less than 5 kg.
as per standard design. (COVER MIN. 4.5 KG & FRAME MIN.2.7 KG )
180x150mm size P type With FPS bricks
372 Making connection of drain or sewer line with existing manhole including breaking into and Each 2
manhole good the wall, floors with cement concrete 1:2:4 mix ( 1 Cement : 2 Coarse Sand : 4
Graded Stone Aggregate 20mm nominal size) cement plastered on both sides with cement
mortar 1:3 (1 cement : 3 Coarse sand), finished with a floating coat of neat ement and making
necessary channels for the drain etc, complete: .
For pipe 100 to 250 mm diameter
373 SUB HEAD V -.PUMPS, & ALIED EQUIPMENTS Set 1
Domestic Water Pump (Hydro pneumatic System With Variable Speed Pumps)
Providing, fixing and testing of packaged fixed drive type skid mounted hydro pneumatic system
comprising of :-
Vertical, inline multistage centrifugal pumping set with stainless steel SS-304 stage casing and
SS-304 impellers with stainless steel SS-316L shaft as per IEC standards and GJL250 cast iron
suction & discharge casing, connected to TEFC ventilated induction motor of 2 pole, 2900rpm,
suitable for 400/440 Volts, 3 phase, 50 Hz A.C. supply No. of Pumps: 3 (2 Working +1
Standby)=1 set
Pressure vessel of non corrosive FRP composite construction lined with NSF and/or FDA listed
material, like high density polyethylene with fully replaceable polyurethane. Air cell burst
pressure of minimum of 5 times the vessel operating pressure and cycle tested for 2,50,000
cycles.
No. and capacity of Pressure Vessel – 01 Nos. x 200 Ltrs
Control Panel with programmable logic controller (PLC) for cyclic operation of pumps. Pump
working sequence should change after every operation. Contractor overload relays and MCBs
should confirm to IEC 898 – 1995/ specifications. Blinking indications for pumps start, trip, low
level trip, health supply should be provided in the panel along with the ammeter & voltmeter.
Control panel should also consist of cooling fan.
Pressure switches bellow type fitted with micro switch and having maximum pressure and
differential scale should confirming BS-6134 standards and IP55 protection class.
Stainless steel suction and delivery header, ball valve on each pump on section delivery side,
non return valves, Y stainer complete in all respect.
Ball valves to be used should be Hot Pressed brass OT-58 with stainless steel ball and
P.T.F.E seal and O-Ring. NRVs to be used should be with Springs and O-Ring arrangement.
Complete set system to be mounted on a common base frame and shall follow following
duty.
For Domestic Water Supply
Set of Two Pumps( 1Working+ 1 Standby)
Capacity : app. 450 lpm
Head : app. 60 m
374 For Flushing Water Supply Set 1
Set of Two Pumps( 1Working+ 1 Standby)
Capacity : app. 250 lpm
Head : app. 60 m
375 Water Make up Pump to STP & Irrigation Pumps Set 1
Set of Two Pumps( 1 Working+ 1 Standby)
Capacity : app. 200 lpm
Head : app. 30 m
376 Drainage Sump Pumps Set 3
Submersible pumps for basement drainage & Pump Room drainage.
Submersible single stage single entry pumps with C.I.body and C.I. two vane enclosed type
impeller connected to TEFC submersible motor for 415 volts, 3 phase, 50 cycles including MCC
panel with level controllers, auto control, sequential change over facility with one proper working
at low level & two proper working at high level with an audible alarm including all interconnectivity
cables, with both pumps connected to common outlet header including valves, non return valves,
lifting chains etc. complete in all respect
No. of Pumps: 2 (1 Working +1 Standby)=1 set
For Basement Drainage
(Solid handling capacity 12mm)
Capacity- 300 lpm (Each)
Head - 12 m
377 For Pump Room Drainage Set 1
(Solid handling capacity 12mm)
Capacity- 200 lpm (Each)
Head - 12 m
378 For Water level indicators with following details: Each 2
Underground tanks
Minimum 4 level Multi level indicators with magnetic type sensor probes complete.
379 Overhead tanks Each 4
Minimum 4 level Multi level indicators with magnetic type sensor probes complete.

[22/80]
Page - 23
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


380 Providing, fixing and testing of factory fitted packaged type skid mounted pumping system Set 1
comprising of :-
Horizontal inline centrifugal pumping set with CI casing and SS-304 impellers with stainless steel
SS-316L shaft as per IEC standards and GJL250 cast iron suction & discharge casing,
connected to TEFC ventilated induction motor of 2 pole, 2900rpm, suitable for 400/440 Volts, 3
phase, 50 Hz A.C. supply.
Motor Control Panel with DOL starter MCB and controller for cyclic operation of pumps. Pump
working sequence should change after every operation. Contractor overload relays and MCBs
should confirm to IEC 898 – 1995/ specifications. Blinking indications for pumps start, trip, low
level trip, health supply should be provided in the panel along with the ammeter & voltmeter.
Control panel should also consist of cooling fan and liquid level controller with control wiring from
UG tank to UG tank with float switch for controlling cut-off and cut-in of pumps and dry run
protection complete in all respects.
Suction and delivery header with Ball valves Hot Pressed brass OT-58 with stainless steel ball
and P.T.F.E seal and O-Ring. NRVs to be used should be with Springs and O-Ring
arrangement.
Complete set system to be mounted on a common base frame and shall follow following
duty.
Filter Feed Pump
No. of Pumps: 2(1Working + 1 Stand by )
Capacity : 450 lpm
Head : 35m
381 Providing and fixing vertical pressure filter with dual media filter (comprising of 600mm bed depth Each 1
of graded sand gravel and 600mm bed depth of Anthracite) fabricated from high performance
M.S plate of minimum 8mm thick for shell & 10mm thick for dished ends with top and bottom
flanged openings including top and bottom hub and lateral distribution and collection system
complete with initial charge of filter media, face piping, valves, accessories, painting, testing and
commissioning complete.(Tested to 6 Kg/m2)
Discharge : 450 lpm
Filtration Rate : 15000 lit./m2/h
Suggested dia app. : 1.60 m
382 Activated carbon Filter (Domestic Water) Each 1
Providing and fixing vertical activated carbon filter comprising of activated carbon filter media
fabricated from high performance M.S plate of minimum 8mm thick for shell & 10mm thick for
dished ends with top and bottom flanged openings including top and bottom hub and lateral
distribution and collection system complete with initial charge of filter media, face piping, valves,
accessories, Epoxy painting, testing and commissioning complete.(Tested to 6 Kg/m2)
Discharge : 450 lpm
Filtration Rate : 15000 lit./m2/h
Suggested dia app. : 1.60 m

383 Providing, fixing, testing & commissioning of MSEP water softening plant (suitable for 3 Kg/Sqcm Set 1
working pressure) complete with initial charge with T-40 NA Resin, multiport valve with built in
ejector for controlling all operations), regeneration system and HDPE tank, pressure gauge at
inlet, outlet and back wash (each with isolation cock), valves, fittings and water hardness testing
kit & associated works. Softener shall be suitable for the following duty:
Note: The successful contractor will have to carry out a test of raw water from all the sources of
water for the Commercial, Residential & apartment at their own cost from a reputed lab as
approved by the Engineer-in-Charge / Consultant. On the basis of these results the contractor
has to submit his shop drawings, design calculations and specifications accordingly.
Please note that it is ultimately the responsibility of the contractor to provide treated water for
different use as per International Standard as given in the attached guidelines.
Raw water hardness 500 Mg/L
Treated water hardness 100 Mg/L
Regeneration Period 12 Hrs.
Capacity : 700 lpm

384 Supplying, installing, testing and commissioning of dosing system (for domestic water treatment Set 1
plant) consisting of one HDPE tank of 100 litres capacity with a positive displacement diphragm
dosing pump having variable flow rate of 0-6 lph. The motor shall be suitable for operation at 240
V / single phase/50 Hz. Supply. The pump shall be supplied complete with necessary
polypropylene piping, valves, strainers, low level switch and injection fittings. The pump shall be
speed & stroke control Asia LMI / equivalent make.
The cost shall be inclusive of providing salt for the testing and operation of system before
handover to the owner.
385 Supplying, installing, testing and commissioning of annunciation and indication panel with Each 1
interlocking arrangement complete in accordance to specification for level controller etc with
control cabling from field to MCC as required.
The system shall be complete to ensure automatic operation of pump in accordance to water
level in respective tanks.
386 Providing & fixing level controllers for water pumps to start/stop the pump at set level. Including Each 1
wiring, cabling from pump to panel & all other accessories as required to operate the system
automatically.
387 Providing & fixing pressure switch for water pumps to start/stop the filter feed pump at set Each 5
pressure. Including wiring, cabling from pump to panel & all other accessories as required to
operate the system automatically.

[23/80]
Page - 24
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


388 Supply, installation, testing and commissioning of tanker inlet connection complete with 200 mm Each 1
dia GI (heavy) inlet piping, hose inlet connection, MS cabinet enclosure (epoxy painted after
fabrication), pad locking arrangement, inlet flexible hose complete with all necessary
arrangement.
389 Providing & fixing butterfly valve Rated for PN16 pressure rating. Including rubber gasket, No. 5
flanges, nuts, bolts, washers & painting complete as required.
50 mm dia
390 65 mm dia No. 16
391 80 mm dia No. 8
392 100 mm dia No. 12
393 150 mm dia No. 18
394 Providing & fixing CI `Y' Strainer (screwed/ flanged) with stainless steel fine wire mesh perforated No. 2
sheet basket with necessary flange/ unions nuts, bolts and washers complete as required (on
pump suction).
150 mm dia
395 Providing & fixing dual plate CI wafer type check valve tested to a pressure of 15 Kg/sqcm. No. 2
Including rubber gasket, flanges, union, nuts, bolts, washers & painting complete as required
50 mm dia
396 80 mm dia No. 7
397 100 mm dia No. 5
398 150 mm dia No. 2
399 Providing and fixing Heavy class GI pipe (IS 1239 up to 150 mm dia. and IS3589 6.35 mm RM 30.00
thickness above 150 mm dia.)header complete for pump suction / discharge manifold comprising
of flanges, unions, check nuts, tee elbow etc. including all flanged connections as per drawing /
site requirement. Supports from wall, floor and ceiling etc. Including dead end flanged connection
complete as required. The header size shall also include tee connections with blank flanges for
the future connections. two coats of synthetic enamel paint of approved shade as per IS : 2379
pipe colour code
50 mm dia
400 65 mm dia RM 35.00
401 80 mm dia RM 25.00
402 100 mm dia RM 30.00
403 150 mm dia RM 40.00
404 200 mm dia RM 20.00
405 Providing & fixing neoprene rubber double flanged rubber expansion joint (anti vibration bellow) No. 6
of standard length as per manufacturers specifications. suitable for hydrostatic test pressure of
15 kg/sqcm including all necessary fittings i.e. rubber gasket, nuts, bolts, washers etc complete
as required.
80 mm dia
406 Providing & fixing brass ball valve with CW617N grade brass with hard chrome plated ball inside No. 9
PTFE (Teflon) seat & ring with chrome plated centre handle with female BSP threads tested to a
pressure not less than 15 Kg / sqcm complete: in all respects.
25 mm dia.
407 32 mm dia. No. 1
408 40 mm dia. No. 1
409 50 mm dia. No. 5
410 SUB HEAD VI -SEWAGE TREATMENT PLANT (STP) Nos 2
Design, Supplying, of Sewage Treatment Plant capacity 120 KLD .(excluding excavation, back
filling & disposal of surplus earth /Civil construction work) for the following duty:
Nature of effluent - Residential Buildings Sewage from Toilet use , kitchen waste and other
areas of office buildings.
Incoming parameters:
pH - 6 - 8.5
BOD5 - upto 250-350 Mg/L
S. Solids - 250 - 400 Mg/L
COD - upto 450-600 Mg/L
Oil & Grease - 50-100 Mg / LFinal effluent discharge standard after treatment
pH - 6.0 - 8 After UF 6-8
BOD5 - Less than 10 Mg/L After UF <4
S. Solids - Less than 30 Mg/L After UF <2
COD - Less than 60 Mg/L After UF <30
Oil & Grease - Less than 5 Mg/L After UF <Nil
Supply of 2 Nos Manual Stainless Steel Bar Screen with suitable lifting arrangement for required
sizes (size 1000 mm wide x 1000 mm high) approx.
411 Supply, installation, testing & commissioning of Mechanical roto brush Fine Screen having 3 mm Set 1
opening. Make - Jash/Eqvt
412 Supply, installation, testing & commissioning of electronic type level indicator and controller for Each 1
automatic operation of the system with high/low level alarm complete with auxiliary NO/NC
contacts.

[24/80]
Page - 25
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


413 Supply, installation, testing & commissioning of non clog open impeller type pumps, having CI Set 1
casing & CI impeller complete with all accessories, motor of required capacity. Delivery header
with isolation valve and NRV, lifting arrangement, pressure gauge on delivery line with isolation
cock level controller with wiring to control the level of sump automatically. Pump shall have
following duty for reference and vendor to confirm on design base.
Submersible Sewage Transfer Pumps 2 Nos. (1 Working + 1 Standby )
(Solid Handling Cap. 35 mm)
Flow rate (each) = 6 M3 / Hr
Head = 10 Mtr
Make: Grundfoss/Wilo/KSB/CNP
414 Supply, installation, testing & commissioning of non clogging submersible type Return Activated Set 1
Sludge Pumps and Secondary Activated pumps(RAS and SAS Pumps) having CI casing & CI
impeller complete with and foundation bolt and lifting arrangement with all accessories, motor of
required capacity. pressure gauge on delivery line with isolation cock, level controller to control
the level of sump automatically. Pumps shall have following duty: Pumps 2 Nos. (1 Working + 1
Standby)
(Solid handling cap. 8.5 mm)
Flow rate (each) = 4m3 / hr
Head = 12 Mtr
Make: Grundfos/Wilo/KSB/CNP
Cost shall be inclusive of PVC flexible Hose pipe ( for piping submerged in effluent) with M S
epoxy piping (for piping non-submerged in effluent)
415 Provision of guide ropes to guide submersible pump from upper level to operational level in Lot 1
sump basin with channels / angle section of MSEP shall be made by the STP contractor.
416 Air diffusion system shall include the following: Each 2
Twin type rotary air blowers 2 Nos. (1 W + 1 S) Capable of delivering 120 cum/hr (each) of free
air at 0.6 kg/cm2 driven through “V” belt or directly coupled through flexible coupling to a
TEFCmotor of suitable HP Suitable for 415 ± 10% volts, 3 phase, 50 cycles a/c supply
417 Air piping shall comprise of pipes droppers/ laterals with M S (epoxy coated) Header complete Lot 1
with all fittings such as tees, crosses, plugs, sockets, elbows, reducers, supports & clamps,
puddle flanges etc cutting chases & making good in Plant Room. All submerged piping will be
SS-304
418 Non clog type air dispersion system capable of handling 3-5 cfm of air with oxygen transfer Lot 1
efficiency of 3-4% per/meter water depth. Air dispersion grid shall be assembled in modular
form so that they can be replaced / repaired Fine /coarse aeration bubble diffusers as required.
For equalization tank -1 Nos.

419 For sludge holding tank - 1 No. Lot 1


420 SBR reactor tank- 1 No. Lot 1
Note : Air dispersion system shall be provided for Equalisation Tank, Sludge holding Tank and
SBR reactor Tanks.
421 Supply of all piping (as described below) and isolation control valves for making the system Job 1
complete. SS 304 : Submerged air piping
MS Epoxy : Air piping, Filters & other Eqp.
PVC piping ASTM SCH 40 :Pumped effluent & tank overflow pipe line
422 Supplying of Submersible Mixer in Equalization Tank 1 Nos . Each 3
Capacity :suitable for 80 M3/day plant
MOC :CI
Make:Stormix/CNP
423 Supply of motorized Moving Decanter to suit SBR tank with MOC SS-304 with scum guard and Each 2
connected with ultrasonic level transmitter & ultrasonic level element for automatic control etc.
complete as required. Make of Decanter : Premier Tech/C-Tech/BS Enviro
424 Supply of multitube type disinfection system comprising of U.V and U.F Reactor in a close circuit Set 1
chamber with required no of lamps as per detail design on flow conditions with auto dosing
controller, display monitor as per manufacturers requirement complete in all respects
Flow Rate = 6 M3 / Hr
Make: Alfa & Qua
425 Supply of vertical inline multistage pumping set (Imported) with Stainless steel-304 body, Set 1
Stainless steel-304 impeller, Stainless steel-304 casing, shaft of Stainless steel-316 and C.I.
base & head with mechanical seal, connected to a TEFC induction motor suitable for 415+/-
10% volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal
isolation cock, vibration eliminating pads under foundations, 80x40 mm I section base plate
bolted to cement concrete foundations complete. Vendor to submit performance curves and
technical catalogue of the proposed model for review and information.
Capacity : 6 M3 / Hr
Head : 25-30 M
No. of Pumps (1 working + 1 standby)
Note: Operation of pump shall be based on level controller proposed to be installed in tank as
per site location. The contractor to ascertain the Head required for pumps as per site conditions
and provide accordingly.

[25/80]
Page - 26
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


426 Supply of MSEP vessel filter with all necessary accessories. Filter shall be suitable for minimum Each 1
working pressure of 5 kg / cm2 and shall include media, standard fittings like pressure gauges,
sampling cock, rinse drain, vacuum breaker etc. The MS sheet thickness for shell shall be min. 8
mm and for dishes shall 10 mm. The internal surfaces of tank shall be treated with epoxy coaing
and external surface with primer and anticorrosive enamel paint (Min. 2 coats). with frontal
piping shall be 100 mm dia MSEP along with valves PN 1.0, test cock, air inlet for back washing
and pressure gauges at inlet and outlet.
Multigrade Pressure Sand Filter
Flow Rate = 6 M3 / Hr
Filtration velocity : 15 Cum/Hr/Sqm
Filter HOS : 1200 MM
Filter Diameter : 900 MM.
427 Activated Carbon Filter Each 1
Flow Rate = 6 M3 / Hr
Filtration velocity : 15 Cum/Hr/Sqm
Filter HOS : 1200 MM
Filter Diameter : 900 MM.
428 Supply of Filter Press of plate as required (size18"x 18" x 18 nos plate for reference) with Set 1
screw feed pumps of 6 m3/hr with adequate head (1Working+1Standby) with interconnecting
piping and poly dosing system all complete.
429 Supply of Magnetic flow meter suitable for 120 KLD Plant with preamplifier and microprocessor Each 1
including necessary cabling, conduit, etc complete suitable for raw sewage application.

430 Electrical panel With PLC Control Each 1


Supply of the PLC based control panel with interlocking arrangement with supply pumps, suction
pumps, modulating or shut-off valves including necessary wiring, magnetic switches & sensors
complete to make the system functional with following interlocking
Construction: Compartmentalized Type Skid Mounted, MCC Cum PLC Control panel will be free
standing; vertical, fabricated from CRCA steel sheet 14/16 G conforming to degree of protection
IP-52 or better. Cable entry will be from bottom. Colour shade - RAL 7032
System Voltage: 380 to 410 Volts & 50HZ ( 415 V ±10% , AC, 50 HZ ±5% for India ). Surge
protection to be provided at every applicable point.
PLC: The Programmable Logic Controller [PLC] shall consist of a PLC hardware, with 16k (min)
program memory shall be protected by a backup battery with further memory protection from an
EEPROM.
HMI: 5.5 Inch Colour Touch screen HMI, will be mounted on A Man-Machine Interface Terminal
(MMI) shall be mounted on the front of the main control panel for control of the activated sludge
plant. It will provide a display of the process parameters and equipment status. The display will
have an associated keypad. The system will allow operator changes to set points and control of
equipment. The terminal shall include an alarm annunciation with a dedicated alarm page and
allow acknowledgment of alarms.
431 Motor Control Centre Each 1
Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of motor
control centre shall be fabricated with reinforcement of suitable size angle iron, channel ‘T’
sections irons and/or flats wherever necessary. Cable gland plates shall be provided on top as
well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before
painting as per specifications with 2 coats of red oxide primer and final approved shade of
powder coated paint. 2 Nos. earthing terminals shall be provided for 3 phase, 4 wire, 50 Hz
supply system. Lifting hooks shall also be provided in case of large panels.
Incoming
400 amps TPN MCCB with the following accessories:
a. 0-500 volts 96 x 96 mm square electronic voltmeter with selector switch shall be protected by
2 amps TP MCB. 1 Set
b. 0-100 amps 96 x 96 mm square electronic ammeter with selector switch and 100./5 amps 10
VA CL:1 CTs. 1 Set
c. Phase indicating lamps shall be protected by 2 amp SP MCB 3 Sets Bus Bar
300 amps TPN (15 KA) copper bus bar with heat shrinkable insulation sleeves.
Required Nos of required capacity TPN MCB for direct on line starter/star delta starters and out
going feeders to all the pumps/blowers etc. (including standbys). Each compartment shall
contain auto / manual selector switch and indicating lamp with MCB’s for ‘ON/OFF/TRIP’ status
of motor
Spare MCB’s of following capacities: 32 amps TPN MCB’s 3 Nos.
Notes: All MCCBs / MCBs shall be of 15 KA breaking capacity and suitable for motor duty
application.
All motor starters shall be provided with Automatic level controller
DOL starters shall be used for mototrs below 10HP and Star-Delta Starters for other motors
Provision shall be made for providing potential free contacts to all pumps starters

432 Supply of Cables , Connector, Cable Trays, to make Electrical Installation Complete. Necessary Lot 1
cable alleys, internal / cabling, wiring, cabling from MCC to various pumps / equipment and
interlocking, earthing and earthing pits for all equipment .
433 Installing & fixing cast-iron manhole cover and frame suitable for 600mm dia manhole with Each 8
lockable and lifting arrangement. The entire item shall be epoxy coated and approved by
insecticide department
Medium duty double seal of size 560 mm dia and total weight of cover & frame to be not less
than 116 KG. (Location : U/G Water Tanks Top)

[26/80]
Page - 27
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


434 Providing and fixing M.S fabricated hot dipped galvinised coating puddle flange comprising of Each 6
600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm
dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate,
inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded
joint in position with reinforcement bars of RCC tank wall/slab including making cutout in
shuttering during concrete casting of tank of following diameter. (Location: underground/
overhead tanks.)
25 mm dia
435 50 mm dia Each 6
436 80 mm dia Each 2
437 150 mm dia Each 1
438 Providing orange colour safety foot rest of minimum 6mm thick plastic encapsulated as per IS : Each 144
10910 on12mm dia steel bar conforming to IS :1786 having minimum cross section as 23mm x
25mm and over all minimum length 263mm and width as 165mm with minimum 112mm space
between protrude legs having 2mm tread on top surface by ribbing or chequering besides
necessary and adequate anchoring projections on tail length on 138mm as per standard
drawing and suitable to with dtand the bend test and chemical resistance test as per
specifications and having manufacture's permanent identification make to be visible even after
fixing, including fixing in manholes with 30x20x15cm cement concrete block 1:3:6 (1 cement : 3
coarse sand : 6 graded stone aggregate 20mm nominal size) complete as per design.

439 SUB HEAD VII -ELECTRICAL PANEL BOARDS FOR PHE WORKS. Item 1
ii) For 2 x 2 HP sump Pump (1 Duty + 1 Stand by)
CUBICAL PANEL BOARD - PLUMBING
i) For 2 x 5.0 HP Domestic Water fixed speed hydroneumatic Pumps (1 duty + 1 stand by)
Supply, installation, testing and commissioning of Cubical type sectionalised floor standing
switch board of 31 MVA fault capacity at 415 V complete with 3.5 strip, 160 A capacity Aluminium
Bus - Bar Electrolytic grade, cable alley, switchgears of following capacity & as per specifications.
A) INCOMER
100 A TP MCCB with heavy duty solid neutral link with (0-100A) ammeter with 3 CT and selector
switch, (0 - 500 V) voltmeter with selector switch, phase indication light with protection fuse. - 01
S
B) OUTGOINGS
i) For 2 x 3.0 HP Domestic Water fixed speed hydroneumatic Pumps (1 duty + 1 stand by)
II) For 2 x 2 HP sump Pump (1 Duty + 1 Stand by)
40 A TP MCB with 40 A DOL starter, overload relay, 96 mm (0-40A) ammeter with single CT,
start / stop push buttons, on / off / trip indication lights with protection fuse, single phase
preventer. - 01 set.
25 A TP MCB with 25 A DOL starter, overload relay, 96 mm (0-25A) ammeter with single CT,
start / stop push buttons, on / off / trip indication lights with protection fuse, single phase
preventer. - 01 set.

440 SUBHEAD-VIII: ROOF TOP SOLAR SYSTEM Set 6


For Solar Water Heating System-1000 LPD
Providing and fixing Solar Hot Water indirect Heating System using heating liquid medium
comprising of flat plate solar panels, including all interconnecting insulated G.I. piping, primary
and secondary recirculation pumps, pressure type insulated hot water tank, , outlet, Y stainer and
a water meter on the inlet, air release valve all mounted on galvanized MS sections complete
with connection with the existing piping. Comprising of following:-
Ten Nos of. flat plate solar collector panels of 10 Sqm size approx. the panels enclosed in
insulated collector boxes with single piece toughned glass 4 mm thick and fixed with heat
resistant gasket.
One Lot of Inter-connected insulated G.I. piping insulated with 9 mm thick nitrile rubber heat
resistant insulation sections ( Vidoflex or equiv.) and valves with outer mechanical protection of
aluminium sheet cladding.
Solar Water Heating System as Describe Above
441 SUBHEAD-IX: HARVESTING PITS & TUBEWELL Cum 200.00
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas
(exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including disposal of
excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly
dressed.
All kinds of soil
442 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in Cum 350.00
layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and
watering, lead up to 50 m and lift upto 1.5 m.
443 Extra for every additional lift of 1.5 m or part thereof in. Cum 350.00
All kinds of soil.
444 Providing and laying in position cement concrete of specified grade excluding the cost of Cum 40.00
centering and shuttering - All work up to plinth level :
1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size).
445 Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° Cum 40.00
landings, balconies, shelves,chajjas, lintels, bands, plain window sills, staircases and spiral stair
cases up to floor five level excluding the cost of centering, shuttering, finishing & reinforcement
with1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size)

446 Centring and shuttering including stutting, propping etc. and removal of form for: Sqm 40.00
Suspended floors, roofs, landings, balconies and acees platform

[27/80]
Page - 28
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


447 Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and Kg. 250.00
binding all complete.
Thermo-Mechanically Treated bars.
448 Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in: Cum 60.00
Cement mortar 1:6 (1 cement : 6 coarse sand)
449 Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS: Each 35
10910 on 12mm dia steel bar conforming to IS :1786 having minimum cross section as 23 mm x
25 mm and over all minimum length 263mm and width as 165mm with minimum 112mm space
between protruded legs having 2mm tread on top surface by ribbing or chequering besides
necessary and adequate anchoring projections on tail length on 138mm as per standard
drawing and suitable to with stand the bend test and chemical resistance test as per
specifications and heaving manufactures permanent identification mark to be visible even after
fixing " including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6: (1 cement :3
coarse sand :6 graded stone aggregate 20mm nominal size )complete as per design.

450 Providing and fixing in position precast RCC manhole cover and frame of required shape and Each 25
approved quality.
HD-20 circular shape 560 mm internal diameter.
451 Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in Metre 250.00
IS: 2800 (part I), including collecting samples from different strata, preparing and submitting
strata chart/bore log, including hire & running charges of all equipments, tools, plants &
machineries required for the job, all complete as per direction of Engineer –in-charge, upto 90
metre depth below ground level.
All types of soil
400 mm dia.
452 Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC Metre 150.00
medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire
and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of
Engineer –in-charge.
200 mm nominal size dia.
453 Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC Metre 150.00
medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour
charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-
charge.
200 mm nominal size dia.
454 Supplying, filling, spreading & levelling stone boulders of size range 5 cm to 20 cm, in recharge Cum 25.00
pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-
charge.
455 Supplying, filling, spreading & levelling gravels of size range 5 mm to 10 mm, in the recharge pit, Cum 10.00
over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per
direction of Engineer-in-charge.
456 Supplying, filling, spreading & levelling coarse sand of size range 1.5 mm to 2 mm in recharge Cum 15.00
pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of
Engineer –in-charge.
457 Gravel packing in tube well construction in accordance with IS: 4097, including providing gravel Cum 10.00
fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per
direction of Engineer-in-charge.
458 Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore Each 10
well housing/ casing pipe, removable as per requirement, all complete for bore well of:
200 mm dia
459 Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tube well as Each 2
per IS: 2800 (part I), including necessary bolts & nuts of required size complete.
200 mm clamp.
460 TUBEWELL Each 6
Providing and laying in position cement concrete of specified grade excluding the cost of
centering and shuttering - All work up to plinth level :
1:2:4 ( 1cement : 2 Coarse sand : 4 graded stone aggregate 20 mm nominal size )
461 Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in Metre 150.00
IS: 2800 (part I), including collecting samples from different strata, preparing and submitting
strata chart/bore log, including hire & running charges of all equipments, tools, plants &
machineries required for the job, all complete as per direction of Engineer –in-charge, upto 90
metre and upto 150 metre depth below groung level.
All types of soil
400 mm dia
462 Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC Metre 150.00
medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire
and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of
Engineer –in-charge.
200 mm nominal size dia.
463 Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC Metre 150.00
medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour
charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-
charge.
200 mm nominal size dia.
464 Gravel packing in tube well construction in accordance with IS: 4097, including providing gravel Cum 120.00
fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per
direction of Engineer-in-charge.

[28/80]
Page - 29
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


465 Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish Hour 150
maximum rate of usable water yield without sand content (beyond permissible limit), with
required capacity air compressor, running the compressor for required time till well is fully
developed, measuring yield of well by "V" notch method or any other approved method,
measuring static level & draw down etc. by step draw down method, collecting water samples &
getting tested in approved laboratory, i/c disinfection of tube well, all complete, including hire &
labour charges of air compressor, tools & accessories etc., all as per requirement and direction
of Engineer-in-charge.
466 Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore Each 2
well housing/ casing pipe, removable as per requirement, all complete for bore well of:
200 mm dia
467 Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tube well as Each 2
per IS: 2800 (part I), including necessary bolts & nuts of required size complete.
200 mm clamp.
468 Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tube Each 2
well as per IS:2800 (part I).
200 mm dia
469 Providing and fixing 80mm dia GI pipes to IS:1239 heavy class with fittings. Metre 125.00
470 Supply, Lowering, installation & testing of KSB make submersible pumping set with 7.5 HP motor Each 2
4 stage pump suitable for 20/26/30/38/40/45/50 m3 hr. at 90/50/32/29/25/20 mtr. Head
respectively. With Three Phase. (Model: 273/4)
471 Providing & fixing cable 6 sq.mm. From submersible pump to panel board. Metre 195.00
472 Providing & fixing Panel Board for submersible pump fitted with DOL starter ammeter, voltmeter Metre 2.00
single phase preventer standard/indo/cop make MCB of off switch push bottom duly wired and
made out of 16/18 SWG sheet.
473 Providing and fixing lever operated butterfly valve conforming to IS:13095-91 PIN 1.6 including Each 2
necessary companion flanges, bolts and nuts complete.
80mm dia
474 Providing and fixing C.I. Wafer type flanged non-return valves with bolts, nuts, washers & Each 2
companion flanges complete.
80mm dia M
475 SUBHEAD-X: LANDSCAPE IRRIGATION SYSTE Rm 18.00
Manual Irrigation Works
Supply, laying & commissioning in position HDPE pipe conforming to IS:4984 (1995) and
suitable for the respective working pressures with all accessories e.g. couplings, tees, bends,
reducers, screwed adapters, flanged tail pieces etc. jointing as per manufacturers' instruction,
Design working temperature at 30°C and raw material grade. The quoted rate shall also include
pipe to be laid below podium slab / fixed on walls / in plumbing shafts, with necessary 10mm
anchoring supports, brackets, threaded rods, threaded U-clamps, universal clamps, etc. spaced
@ 2 mtr intervals, (all supports in Shafts shall necessarily be with Wall Brackets & Anchoring
Bolts). The quoted rate shall include lead and lifting charges to all levels, necessary scaffolding
etc., complete, as per the instructions of Architect/Landscape Architect/Engineer In Charge. (
Pipes crossing at expansion joints will be connected with necessary expansion connectors).
140mm dia HDPE pipe PN10 PE80

476 110mm dia HDPE pipe PN10 PE80 Rm 350.00


477 90mm dia HDPE pipe PN10 PE80 Rm 200.00
478 75mm dia HDPE pipe PN10 PE80 Rm 150.00
479 Pipes Work: Supply, laying & commissioning in position PVC pipe conforming to IS:4985:2000 Rm 400.00
and suitable for the respective working pressures without all fittings and accessories e.g.
couplings, tees, bends, reducers, screwed adapters, flanged tail pieces etc. jointing as per
manufacturer's instruction
PVC pipe 63mm-6 kg/cm²
480 PVC pipe 50mm-6 kg/cm² Rm 200.00
481 PVC pipe 40mm-6 kg/cm² Rm 750.00
482 PVC pipe 20mm-10 kg/cm² Rm 258.00
483 PVC fittings LS 1
484 Earth work excavation and refilling 300x450mm Rm 2500.00
485 DRIP & ACCESSORIES Rm 200.00
Supply, Fixing & commissioning of flexible, kink resistant 16mm subsurface inline tubing and
copper shield technology protects the root intrusion and self flushing emitter, brown in colour,
UV damage and algae growth with flow rate of 3.4 lph pressure rating 0.58 to 4.14 bar - WITH
EARTH WORK - XFSDI
486 Supply, Fixing & commissioning of Sub surface drip system operation Indicator, Includes 16” of Nos 1
¼” distribution tubing with connection fitting pre-installed

487 Supply, Fixing & commissioning of 2" Large Capacity Y Filters for sub main filtration ,Maximum Nos 1
Flow Up to 110 gpm (25m³/hr), Maximum Pressure 116 psi (8 bar),Maximum Temperature Up to
140ºF (60ºC). LCRBY200D
488 Supply, Fixing & commissioning of 63mm/50mm/40mm dia self-closing flushing valves. Nos 1
489 Supply, Fixing & commissioning of High Quality Barbs Grab Tubing for a Secure Fit. Non - Nos 25
Obtrusive Brown Colored Fittings of 17mm BARBX BARB TEE
490 Supply, Fixing & commissioning of High Quality Barbs Grab Tubing for a Secure Fit.Non - Nos 25
Obtrusive Brown Colored Fittings of 17mm BARBX BARB COUPLING
491 Supply, Fixing & commissioning of High Quality Barbs Grab Tubing for a Secure Fit. Non - Nos 10
Obtrusive Brown Colored Fittings of 17mm BARBX BARB ELBOW

[29/80]
Page - 30
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


492 Supply, Fixing & commissioning of High Quality Barbs Grab Tubing for a Secure Fit. Non - Nos 5
Obtrusive Brown Colored Fittings of 17mm BARBX 1/2" MPT ADAPT
493 Supply, Fixing & commissioning of 17mm End cap S Type for dripline closure at the end of the Nos 20
dripline
494 SPRINKLERS & ACCESSORIES Nos 150
Supply, Fixing & commissioning of Pop up spray head1804 SAM PRS Series Spray bodies, with
Rotary nozzle having multiple stream MPR spray having Co-moulded wiper seal capable of
covering 4.0-7.3m at 1.4 - 3.8 Bars pressure. Built-in Seal-A-Matic™ (SAM) check valve. Traps
water in lateral pipes in elevation changes of up to 14 feet (4.2 m). PRS Maintains constant
outlet pressure at 30 psi or 45 psi at varying inlet pressures.
495 Supply, Fixing & commissioning of 5004 PLUS SAM PRS Series Rotor pop up sprinkler full/part Nos 50
circle having radius of 6.7m - 12m @ 2.5 - 4.5 bar with discharge of 0.09 - 0.61 ltr./sec. the
sprinklers having Arc Adjust thru Top Cover w/ Std. Screwdriver.
496 Supply, Fixing & commissioning of Pop up sprinkler full/part circle having radius of 11.9 to 19.8 m Nos 10
- flow of 0.6 ltr./sec to 1.1 lps at an operative pressure of 2.5- 6 bar. The sprinkler shall have
internal Seal - A - Matic device which prevents low head drainage (upto 3.1m).
497 Supply, Fixing & commissioning of Pop up sprinkler full/part circle having radius of throw 11.9 to Nos 20
24.7 m & flow of 0.23 - 2.28 ltr./sec.at an operative pressure of 2.5 - 4.5 bar. 8005 SAM Rain
Curtain™ Nozzle Technology, Color-coded Nozzles
498 Supply, Fixing & commissioning of 1/2" Pop up Connecting Swing joint Assembly having wall Nos 150
thickness of 2.3mm ,a working pressure of 5.5 kg/cm² at 43⁰C and a surge pressure of 16.6
kg/cm². The fittings shall be made of UV resistant thermo plastic.
499 Supply, Fixing & commissioning of 3/4" Pop up Connecting Swing joint Assembly having wall Nos 50
thickness of 2.3mm ,a working pressure of 5.5 kg/cm² at 43⁰C and a surge pressure of 16.6
kg/cm². Flex pipe textured for wet conditions. The fittings shall be made of UV resistant thermo
plastic.
500 Supply, Fixing & commissioning of 1" Pop up Connecting Swing joint Assembly having a Nos 50
working pressure of 5.5 kg/cm² at 43⁰C and a surge pressure of 16.6 kg/cm².The fittings shall be
made of UV resistant thermo plastic.
501 Supply, Fixing & commissioning of Imported HDPE service saddle of varying size upto 63mm Nos 350
dia with pressure rating of PN 10
502 VALVES & ACCESSORIES Nos 20
Supply, Fixing & commissioning of PVC Ball Valve of size 63mm with pressure rating PN 10
503 Supply, Fixing & commissioning of PVC Ball Valve of size 50mm with pressure rating PN 10 Nos 6
504 Supply, Fixing & commissioning of PVC Ball Valve of size 40mm with pressure rating PN 10 Nos 1
505 Supply, Fixing & commissioning of a double acting air and vacuum release 1/2 " Air release Nos 1
valve. The working pressure shall be 5 bar.
506 Supply of a double acting air and vacuum release 2 " Air release valve .The working pressure Nos 2
shall be 10 KSC .
507 Supply, Fixing & commissioning of 6"Round box with green lid and corrugated structure with Nos 10
unique shovel access slot and bolt hole knockout & Having Dimensions @ Top Opening :6 1/8"
Dia & Bottom Opening 8 5/8" Dia. PVB/VB
508 Supply, Fixing & commissioning of 10" Round Valve Box with green lid and corrugated structure Nos 10
with unique shovel access slot and bolt hole knockout & Having Dimensions @ Top Opening
10" Dia & Bottom Opening 12 13/16" Dia. PVB/VB
509 Supply, Fixing & commissioning of 12" Rectangular Standard Valve Box with green lid and Nos 10
corrugated structure with unique shovel access slot and bolt hole knockout & having
Dimensions @ Top Opening:18 1/4" L X 13" W & bottom opening :21 1/4" L X 15 15/16"W X 12"
H PVB/VB
510 Supply, Fixing & commissioning of 18'' Jumbo Rectangular Standard Valve Box with green lid Nos. 1
and corrugated structure with unique shovel access slot and bolt hole knockout & having
Dimensions @ Top Opening:18 1/4" L X 13" W & bottom opening :21 1/4" L X 15 15/16"W X 12"
H PVB/VB
511 Supply, Fixing & commissioning of 3/4th Quick coupling valve made up of solid brass with Nos 5
locking cover corrosion resistant and stainless steel spring 3RC
512 Supply, Fixing & commissioning of 3/4th Key threads into top of QCV to provide water access Nos 3
33DK
513 Supply, Fixing & commissioning of 3/4th Hose Swivel Made up of Solid Brass Swivels up to 360 Nos 3
degrees to allows hose to be pulled in any direction & Also to prevent Hose Damage. SH-0

514 FILTRATION UNIT Nos 1


Supply, Fixing & commissioning of 3'' Fully Automatic Self Cleaning Filter.
515 PUMPING UNIT Nos 1
Supply, Fixing & commissioning of Hydro-Pneumatic Pumping System with Variable Frequency
Drive Mechanism of suitable capacity with Suction & Delivery Manifold, Wafer Seal Butterfly
Valve as Isolation Valves, Non Return Valves, Pump Control Panel, Pressure Vessel, mounted
on a Base frame with proper supports.
Duty of Pump : 16.00 LPS Each Pump
Pressure Head Range =55 Mtr
No. of Pumps : 2 Working + 1 Standby

516 Supply, Fixing & Commissioning of Direct burial14 Awg x 2 Maxi cable with PVC insulated UL Mtr 1000.00
standard 493 with impregnated polyethylene jacket and soft annealed tin coated copper
confirming to ASTM B-33 for two way communication between decoder controller and decoders
complete with suitable conduit pipe

[30/80]
Page - 31
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


517 Supply, Fixing & commissioning of ESPLXD Station Modular Controller UV resistant basic 8 No 1
station and expandable upto 48stations,wall mount case, with LCD display ,non volatile memory
for 100years,10KV surge protection with removable front panel and programmable under battery
in office, and flow watch options to shutdown system if any damage or excess flow or dry run
shutdown,cycle+soak,raindelay,station delay ,alarm light ,electronic diagnostic circuit breaker
,program summary and review, wiring test,,4programm and 8start time per program with
adjustable delay between stations, slow closing valve, removable battery, and sensor
terminals ESPseries
518 Supply , Fixing & Commissioning of ESP-LXD Control ESP LXDSM75 Module for adding the Nos 1
stations
519 Supply, Fixing & Commissioning of Field Decoder support 1 station ,fully water proof Nos 15
encapsulation, power draw 0.5mA at idle and 18mA at active ,working range 0 deg to 50 degree
centigrade as per specifications and with different station capacities as given below Field
Decoder 1 station FD101
520 Supply, Fixing & commissioning of 2" Solenoid globe Valves with fabric reinforced diaphragm Nos 10
and rugged PVC durable glass -filled nylon construction ,compatible with and slow closing to
prevent water hammer, pressure rating upto 10.4 KSC and maximum flow of 150GPM ,max
water temp. upto 42degree centigrade, with 24AC solenoid, current rating 0.41A @60Hz,coil
resistance 30ohm with provision to attach PRS-Dial PGA
521 Supply, Fixing & commissioning of 1.5" Solenoid globe Valves with fabric reinforced diaphragm Nos 6
and rugged PVC durable glass -filled nylon construction ,compatible with and slow closing to
prevent water hammer, pressure rating upto 10.4 KSC and maximum flow of 150GPM ,max
water temp. upto 42degree centigrade, with 24AC solenoid, current rating 0.41A @60Hz,coil
resistance 30ohm with provision to attach PRS-Dial PGA
522 Supply, Fixing & commissioning of 1" Solenoid globe Valves with fabric reinforced diaphragm Nos 1
and rugged PVC durable glass -filled nylon construction ,compatible with and slow closing to
prevent water hammer, pressure rating upto 10.4 KSC and maximum flow of 150GPM ,max
water temp. upto 42degree centigrade, with 24AC solenoid, current rating 0.41A @60Hz,coil
resistance 30ohm with provision to attach PRS-Dial PGA
523 Supply, Fixing & commissioning of 3" Solenoid globe Valves as central shut off valve with fabric Nos 1
reinforced diaphragm and rugged PVC construction ,compatible and slow closing to prevent
water hammer, pressure rating upto 0,7 to 10 KSC and maximum flow of 10 to 100 m3/h ,max
water temp. upto 60°C with 24 VAC - 50 Hz, coil resistance 30ohm with provision to attach
PRS-Dial
524 Supply, Fixing & commissioning of PRS-DIAL to Maintain constant outlet pressure between Nos 1
1.04 to 6.9 KSC
525 Supply, Fixing & commissioning of Line Surge Protection device as required with copper Nos 5
grounding rod, clamps, charcoal and all requisite accessories complete LSP
526 Supply, Fixing & commissioning of direct bury -on wire connector with strain relief ,UL486 D Nos 30
certified ,with waterproof silicon sealant ,fits wire from 22ga to 6 ga as per specifications
complete DBRY
527 UPVC PERFORATED DRAINAGE PIPE FOR PLANTER DRAINAGE/TERRACE RM 350.00
GARDEN/LANDSCAPED AREA :
Providing, fixing, testing and commissioning of UPVC perforated drainage pipe conforming to IS:
4985 -2000 class -III (6.0kg.cm2) including all moulding fittings conforming to IS: 7834 (Part -1 -
Part -7) 1987 such as tees, bends, reducers, coupling, adopter etc. solvent weld joint as per
manufacturer recommendating including earth work in excavation of required width and up to 1.5
m depth for all kind of soil including 150 mm thick cement concrete 1:3:6 mix (1 cement : 3 fine
sand : 6 graded stone aggregate 40 mm nominal size) up to haunches perforated of perforating
pipe including bed concrete 150 mm thick as per standard design complete cutting and making
good the wall, floors, R.C.C work etc. (Lower Ground + Terrace).
75 mm OD [ 1.5 mm slot width x 55 mm slot length ] (Lower Ground +Terrace).

528 110 mm OD [ 1.5 mm slot width x 55 mm slot length ] RM 200.00


529 160 mm OD [ 2.0 mm slot width x 70 mm slot length ] RM 100.00
Note:
Slot shall be made on half upper half portion of UPVC pipe.
Slot shall be provided at 1800 in two rows.
Spacing between two slots shall be 20 mm.

[31/80]
Page - 32
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


530 SUB HEAD: 'B2': FIRE FIGHTING WORKS Set 2
SUB HEAD-1.0 FIRE PUMP WORKS FOR HYDRANTS & SPRINKLER SYSTEM

1.NOC from fire authority shall be in the scope of Contractor . Only fee paid to the fire authority
shall be reimbursed against the submission of the receipt and nothing shall be paid extra.
2. All the Fire Fighting works shall be done in compliance of Fire Fighting authority requirement.

Pump shall be capable of furnishing not less than 150% of rated capacity at a head not less than
65 % of rated head. The shut off head shall not exceed 120% of rated head.

FIRE PUMPS - ELECTRICAL


Supplying Installation, testing and Commissioning of electric driven main fire pump suitable for
automatic operation and consisting of following Complete in all respect as required.
Horizontal type, single / multistage, centrifugal, split casing pump of cast iron body and bronze
impeller with stainless steel shaft, mechanical seal to ensure a minimum pressure of 3.5
kg/sq.cm. at highest and farthest outlet at specified flow of 2280 LPM at 80 Metres head
conforming to IS 1520.
Suitable HP SQ cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for
operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot
mounted type with Class-'F' insulation, conforming to IS-325
M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
Suitable cement concrete foundation duly plastered with anti vibration pads and suitable size
copper unarmoured cables upto 15 mtr. Length (Above 15 mtr. will be paid separately) complete
with connection interconnection as reqd.
(For Hydrant & Sprinkler System).

531 Supplying Installation, testing and Commissioning of electric driven main fire pump suitable for Set 1
automatic operation and consisting of following Complete in all respect as required.
Horizontal type, single / multistage, centrifugal, split casing pump of cast iron body and bronze
impeller with stainless steel shaft, mechanical seal to ensure a minimum pressure of 3.5
kg/sq.cm. at highest and farthest outlet at specified flow of 1620 LPM at 35 Metres head
conforming to IS 1520.
Suitable HP SQ cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for
operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot
mounted type with Class-'F' insulation, conforming to IS-325
M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
Suitable cement concrete foundation duly plastered with anti vibration pads and suitable size
copper unarmoured cables upto 15 mtr. Length (Above 15 mtr. will be paid separately) complete
with connection interconnection as reqd.
(For Water Curtain System).

532 FIRE PUMPS - DIESEL ENGINE DRIVEN Set 1


Supplying, Installation, Testing and Commissioning of diesel engine driven main fire pump
suitable for automatic operation and consisting of following : complete in all respect as required.
Horizontal type, single / multistage, centrifugal pump of cast iron body and bronze impeller with
stainless steel shaft, mechanical seal to ensure a minimum pressure of 3.5 kg/sq.cm. at highest
and farthest outlet at specified flow of 2280 LPM at 80 metres m. head conforming to IS 1520.
Suitable HP, 1500 RPM water cooled with radiator diesel engine conforming to relevant BS & IS
standard complete with auto starting mechanism 12/24 Volts electric starting equipment, Diesel
Tank, exhaust pipe extended upto 1m. outside pump house duly insulated with 50 mm. thick
glass wool with 1.0 mm. thick aluminium sheet cladding, residential silencer, instruments and
protection as per specification, stop solenoid for auto stop in the event of fault with audio
indications, painted with post office red colour etc. as reqd.
M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc.as required.
Suitable cement concrete foundation duly plastered with anti vibration pads.
(For Hydrant & Sprinkler System).

[32/80]
Page - 33
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


533 FIRE PUMPS - JOCKEY PUMP Set 2
Supplying, Installation, Testing and Commissioning of electric driven pressurisation pump
suitable for automatic operation and consisting of following: complete in all respect as required.
Horizontal type, single / multistage, centrifugal pump of cast iron body and bronze impeller with
stainless steel shaft, mechanical seal and flow of 180 LPM at 80 metre head conforming to
IS:1520.
Suitable HP SQ cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50
HZ. AC with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F
insulation, conforming to IS : 325.
M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
Suitable cement concrete foundation duly plastered with anti vibration pads and suitable size
copper unarmoured cables upto 15 mtr. Length (Above 15 mtr. will be paid separately) complete
with connection interconnection as reqd..
(For Hydrant & Sprinkler System).

534 Pressure Switch Nos. 6


Supplying, installing, testing and commissioning 0 to 16 Kg/ cm2 ON/OFF digital pressure switch
in delivery line of pump along with control wiring for auto starting and auto stopping of hydrant /
sprinkler and jockey pumps. Complete as per manufacturer's specifications & as directed by
Engineer- in-charge.
535 Pressure Vessel Nos. 3
Supplying, installing, testing and commissioning of pressure vessel for pressurization of fire
system complete with valves at outlet / drain to operate as per operating sequences including
25 mm dia drain valve, air release valve with stop cock on the top, outside with one coat of
primer & two coats of synthetic enamel paint of approved shade complete as required to operate
commonly main fire pump, sprinkler pump & jockey pump at drop of pressure, automatically at
required pressure setting. Complete as per manufacturer's specifications & as directed by
Engineer- in-charge.
working pressure:- 8 kg/sqcm
test pressure: 16 kg/sqcm
(450 mm dia & 2000 mm height)
536 Providing, Fixing, testing and commissioning of resilient rubber lined single arch vibration Nos. 8
eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8 Kg/cm2 and
test pressure 16 Kg/cm2 to provide relief from stresses at pipe flanges. Complete as per
manufacturer's specifications & as directed by Engineer- in-charge.
150 mm dia
537 80 mm dia Nos. 4
538 Supply, installation, testing, trial run and commissioning of hydrants. Complete as per Set 21
manufacturer's specifications & as directed by Engineer- in-charge.
Internal hydrants/landing valves as specified and all complete with:
i) Providing & fixing SS fire hydrant single landing valve with 80 mm N.B. flanged inlet, SS
spindle controlled 63 mm dia female instantaneous outlet type. SS coupling, blank cap, chain,
twist release type lug & all accessories Conforming to IS:5290. Including fixing with anchor
fastener and flanged tapping from wet riser and suitable for pressure gauge with gun metal ball
valve complete as required.
ii) Providing & fixing swinging type First Aid hose reel in red colour drum with 36 mts. long and 20
mm dia heavy duty rubber water hose, 20 mm dia globe valve stop cock, terminating with SS
coupling & nozzle of 5mm outlet with shut off valve confirming to IS 8090 - 1976 complete with
MS socket for tap-off, drum and brackets (including painting) for fixing on wall with anchor
fastener, bolts & nuts conforming to IS:884-1969 complete as required.
iii) Providing & fixing non-per locating, rubber reinforced lined fire hose pipe (as per IS : 636,
Type B) of 63 mm dia and length 15m . The hose shall be rated for brust pressure of 35.7
Kg/sqcm. Hose shall be complete with ISI marked brass male & female coupling (IS:903) bound
& rivetted to hose pipe with copper rivets & 1.5 mm copper wire. (Two nos. for each
hydrant-valve)
iv) Providing and placing in proper position stainless steel 63mm dia short size branch pipes with
20 mm dia nozzles with 63mm instantaneous coupling ISI marked (IS: 903).
v) Providing and fixing standard fireman's axe with heavy insulated rubber handle conforming to
IS: 926 complete.

[33/80]
Page - 34
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


539 External/Terrace hydrant valve, IS marked of SS with as specified and as required all complete Set 18
with :
i) Providing & fixing SS fire hydrant single landing valve with 80 mm N.B. flanged inlet, brass
spindle controlled 63 mm dia female instantaneous outlet type. SS coupling, blank cap, chain,
twist release type lug & all accessories Conforming to IS:5290. Including fixing with anchor
fastener and flanged tapping from wet riser and providing pressure gauge with gun metal ball
valve complete as required.
ii) Providing & fixing non-per locating, rubber reinforced lined fire hose pipe (as per IS : 636, Type
B) of 63 mm dia and length 15m . The hose shall be rated for brust pressure of 35.7 Kg/sqcm.
Hose shall be complete with ISI marked brass male & female coupling (IS:903) bound & rivetted
to hose pipe with copper rivets & 1.5 mm copper wire. (Two nos. for each hydrant-
valve)
iii) Providing and placing in proper position stainless steel 63mm dia short size branch pipes with
20 mm dia nozzles with 63mm instantaneous coupling ISI marked (IS: 903).
iv) Providing & Fixing of M.S. fire hose weather proof cabinet (750x600x250mm) made out of 16
gauge M.S. sheet capable of accommodating landing valve, hose pipes, fittings & accessories.
The box shall have a front glass door with lock and key arrangement & shall be painted with one
coat of primer & two coat of finished stove enamelled post office red colour paint & "FIRE HOSE"
written on front.

540 Supply, installation, testing and commissioning brass orifice plates made out of 8mm thick Nos. 25
stainless plate in pipelines to reduce pressure from 8 kg. to 3.5 kg/sq.cm. Complete as per
manufacturer's specifications & as directed by Engineer- in-charge.
80/100 mm dia.
541 Supplying and fixing, testing and commissioning of 1 Set of 63mm instantaneous 4 way fire Set 2
brigade inlet connection (FBC) comprising of S.S and S.S instantaneous male inlet coupling
confirming to IS:604 with 1 No. 150 mm diameter butterfly valve, 1 No. 150mm dia. Non-return
valve, plug and cap with chain as required with nut & bolts, washers, high pressure gasket as
required. Complete as per manufacturer's specifications & as directed by Engineer- in-charge.
(FOR UG TANK & EXTERNAL RING MAIN)
542 Supplying and fixing, testing and commissioning of 1 Set of 63mm instantaneous 2 way fire Set 1
brigade draw out connection (FBC) comprising of S.S and S.S instantaneous male inlet coupling
confirming to IS:604 with 1 No. 150 mm diameter butterfly valve, 1 No. 150mm dia. Non-return
valve, plug and cap with chain as required with nut & bolts, washers, high pressure gasket as
required. Complete as per manufacturer's specifications & as directed by Engineer- in-charge.
(FOR UG TANK)
543 Providing and fixing air vessel made of 250 mm dia. 8 mm thick MS sheet, 1200 mm in height Nos. 8
with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia
gunmetal wheel valve. With required accessories. Pressure gause and painting with synthetic
enamel paint of approved shade as required.
544 Supplying Installation, testing and Commissioning of electric driven Terrace fire pump suitable for Set 1
automatic operation and consisting of following Complete in all respect as required.
Horizontal type, single / multistage, centrifugal, split casing pump of cast iron body and bronze
impeller with stainless steel shaft, mechanical seal conforming to IS 1520.
Suitable HP SQ cage induction motor, TEFC, synchronous speed 2900 RPM, suitable for
operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot
mounted type with Class-'F' insulation, conforming to IS-325
M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
Suitable cement concrete foundation duly plastered with anti vibration pads.

For pump defined above & of duty as follows :


Flow : 900 LPM
Head : 35 mts

545 SUB HEAD-2.0 PIPING FOR FIRE HYDRANT, SPRINKLER & WATER CURTAIN SYSTEM Meter 610.00
Providing, fixing, testing and commissioning of the following size of flange jointed / screwed /
welded, M.S. pipes of Class C (heavy class) ISI marked and of approved make, IS : 1239/3589
including accessories such as tees / elbows / reducers / couplings / unions / bends / flanges etc.,
including excavation in all kinds of soil and all types of roads, direct in ground to a depth of 30 cm
to 1 mtr as per site condition i/c concrete supports/anchors/ thrust pads and refilling the trench
along with disposal of melba to the nearest dumping ground, and wrapping with 1 no. 4 mm thick
polymeric corrosion protection tape conforming to IS 10221 and painting with bituminous paint
after laying and testing to 13.5 Kg / Sq. cm hydraulic pressure after installation etc as per
specification complete as required. ( For Underground )
150 mm nominal bore

546 100 mm nominal bore Meter 40.00


547 80 mm nominal bore Meter 80.00
548 Supply, fixing, testing and commissioning of screwed type brass/bronze lever operated ball valve Nos. 13
of full flow with stainless steel ball (AISI 304 & spindle AISI 410) with setting & gland of superior
quality having minimum working pressure of 16 kg/sqcm.
Complete as per manufacturer's specifications & as directed by Engineer- in-charge.
25 mm Dia

[34/80]
Page - 35
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


549 Supply, installation testing & commissioning double flanged CI Y strainers with SS 304-grade Nos. 2
perforated screen, PN 16 rating. Complete as per manufacturer's specifications & as directed by
Engineer- in-charge.
200 mm dia.
550 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS : Meter 20.00
1239/3589 including cutting, threading, welding etc. i/c all fittings like bends, elbow, reducers,
tees, flanges, tapers, nut bolts, gasket etc. fixing the pipe on the wall/ceiling with suitable
hangers, clamps, supports as required and painting with two or more coats of synthetic enamel
paint of required shade complete as required.
(Plant Room piping/Vertical Riser/Down comer/Floor)
Note:
Threaded joint upto 50mm diameter pipe.
Welded joint above 50mm diameter pipe.
250 mm nominal bore (6.35 mm thick)

551 200 mm nominal bore (6.35 mm thick) Meter 30.00


552 150 mm nominal bore Meter 743.00
553 100 mm nominal bore Meter 430.00
554 80 mm nominal bore Meter 575.00
555 65 mm nominal bore Meter 425.00
556 50 mm nominal bore Meter 430.00
557 40 mm nominal bore Meter 515.00
558 32 mm nominal bore Meter 260.00
559 25 mm nominal bore Meter 2023.00
560 Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves Each 51
complete as required
561 Supply, fixing, testing and commissioning of following valves, gauges and strainers as per Nos. 2
specifications:-
Butterfly valve (manual) with C.I body SS disc nitrile sheet & O ring & PN 16 Pressure rating as
specified 100 mm nominal bore. It should be complete in all respect & as per directions of
Engineer-in-charge.
200 mm dia.
562 150 mm dia. Nos. 22
563 80 mm dia. Nos. 9
564 50 mm dia. Nos. 2
565 Non - return valve with dual plate of CI Body SS plates vulcanized NBR seal flanged end & PN Nos. 1
16 rating as specified. It should be complete in all respect & as per directions of Engineer-in-
charge.
200 mm dia.
566 150 mm dia. Nos. 9
567 100 mm dia. Nos. 1
568 80 mm dia. Nos. 2
569 SUB HEAD-3.0 SPRINKLER & WATER CURTAIN SYSTEM Set 4
Supply, installation, testing and commissioning of 150 mm dia Installation Control Valve inclusive
of 1 no. 150 mm dia Butterfly Valve, strainer, Alarm Valve with turbine type automatic alarm
Gong, Pressure Gauges, Test Lines with Ball Valves with necessary MS Class "C" piping with
threaded fittings of required sizes. All accessories cost shall be included in this item & nothing
extra will be paid in this regard. Complete as per manufacturer's specifications & as directed by
Engineer- in-charge.
570 Supply, installation, testing and commissioning of 150 mm dia Zonal Control Valve (Inspection Set 14
test assembly) inclusive of 1 nos 150 mm dia butterfly valve, 150mm diam. non return valve,
Flow Switch, & 25 mm dia. Auxiliary Drain valve with sight glass with necessary MS Class "C"
piping with threaded fittings of required sizes. All accessories cost shall be included in this item
& nothing extra will be paid in this regard. Complete as per manufacturer's specifications & as
directed by Engineer- in-charge.
571 Providing, fixing, testing and commissioning of quick response 15 mm dia. quartz bulb type Nos. 2230
having Bronze/Brass Frame and Deflector and chrome finished type sprinkler head to operate at
68 degree centigrade including two piece of adjustable C.P. Rosset complete as required.
(UL/FM approved). Complete as per manufacturer's specifications & as directed by Engineer- in-
charge.
Side wall / Pendent / Upright Type
572 Providing and fixing UL/Fm listed powder coated finish Escutcheon plate complete including Each 893
fixing in position on pipe and ceiling complete in all respects. (Size=15NB)
573 Providing & fixing in the false ceilings, high pressure metallic hose with fittings (25 NB at one end Each 536
for connection to pipe and 15 NB at the other end for the Sprinkler) for connecting the Sprinklers
to Sprinkler piping system, Hose & Fittings to be UL listed or FM approved and installed in
accordance with para 9.2.1.3.3 of NFPA-13 (2007 edition) Test Pressure 10.0 Kg/Sq.m.
Length 700 mm

574 Length 1200 mm Each 357


575 Providing & fixing cast iron 150 mm dia. Foot valve with nuts, bolts, 1.5 mm thick CAF gasket Each 2
complete with all accessories (To be provided into UG Fire Water Tanks).
576 Providing and fixing UL/Fm listed water curtain nozzle chrome plated complete including fixing in Each 16
position on pipe complete in all respects with Teflon tape. (Size=15NB)
577 Providing and fixing UL/Fm listed Deluge valve complete including fixing in position on pipe Each 1
complete in all respects with drain valve, inlet/outlet . (Size=80NB)

[35/80]
Page - 36
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


578 SUB HEAD-4.0-FIRE EXTINGUSHER Nos. 28
Providing, storing, handling, shifting, installation, testing and commissioning of halon free
portable fire Extinguishers as described below:
Concealed work, including cutting chases and making good the walls etc.
4.5 kg carbon dioxide extinguisher, IS marked, with high pressure discharge tube, horn, control
valve, CCE approved cylinder

579 6 kg Mono Ammonium Phosphate (ABC) type cartridge operated extinguishers Nos. 28
580 9 kg Mono Ammonium Phosphate (ABC) type cartridge operated extinguishers Nos. 10
581 Providing, fixing, testing and commissioning of 50 Litres (trolley mounted) Mechanical Foam type Nos. 2
Fire Extinguisher. In HP Mild Steel Cylinders ISI marked TAC approved fitted with pressure
indicating gauge, internal tube, squeeze lever type valve fully charged complete in all respects
including wall suspension bracket / trolley mounted and conforming to IS:910 .
582 Providing, fixing, testing and commissioning of CO2 type Fire Extinguisher of capacity 22.5 kg Nos. 2
filled with Co2 Gas as per IS 15222 with control discharge mechanism fitted with Hose, Horn &
TROLLEY confirms to IS 2878 bearing ISI mark. Co2 Cylinder as per IS 7285
583 Providing and fixing Fire related signages printed on photo luminescent U1000 aluminium sheet Square 8500.00
of 1.0 mm (+-10%) containing Lumigen II as base chemical, covered under UV stablized coating Inch
and of appropriate size including fixing on wall, door, ceiling etc. with proper clamps, hangers,
cleats, anchor fasteners etc. complete in all respects as directed by Engineer-in-charge.

584 SUB HEAD : 5.0- ELECTRICAL WORKS Each 1


Providing, fixing, testing & commissioning of annunciator panel for flow control switches,
providing audio /visual indication of actuation of automatic sprinkler system for each zone
complete as per specifications. The panel should have interface for connection to complete
controlled building management system. The panel should have:-
a) Fault indication for each zone
b) Indication of zone fire
c) Fire/Fault hooter
d) Alarm Panel for fire/fault
e) Battery for emergency
f) Battery Charger
g) mains supply and shall cater for minimum 14 zones working and 6 zones spare
585 FIRE FIGHTING PANEL Set 1
Fabricating, supplying, installation, testing and commissioning of electrical control panel of
cubical construction, floor mounted type , fabricated from 2 mm thick CRCA sheet
compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of
approved shade after 7 tank treatment process, cable alley, inter connection, having switchgears
and accessories mounting and internal wiring, earth terminals numbering etc complete in all
respect ,suitable for operation on 415 V ,3 phase,50 Hz AC supply with enclosure protection
class IP 42 as reqd
PANEL IN FIRE PUMP HOUSE
INCOMER
i)400A, 4 pole, 35/36 KA,MCCB with microprocessor release with Ics=100%Icu digital Voltmeter
(0-500 Volts) with selector switch. digital Ammeter (0-400Amps) with in built selector switch and
CT's etc. Set of 3 Phase LED indicating lamps, Set of Al. bus bar for 500 Amps.
OUTGOING.
a) Main fire pump.
i)200Amps. 4P MCCB,35/36 KA Ics=100%Icu with suitable HP fully automatic star/delta starter
with over load protection, (without no volt and under voltage trip) current sensing type single
phase preventer complete with all accessories and internal wiring required for automatic
operation, selector switch for local /remote, auto/manual/OFF operation.--- 2Sets
ii)Digital ammeter with selector switch along with suitable ratio CTs---2 Set
iii)Pump on LED Indication lamp --- 2 No.
b) 100Amps. 4P MCCB,35/36 KA Ics=100%Icu-- 1 Set
c) Jockey pump.
i)63Amps. 4 P MCCB 25 KA Ics=100%Icu with suitable HP fully automatic star/delta starter with
over load protection,( without no volt and under voltage trip), current sensing type single phase
preventer complete with all accessories and internal wiring required for automatic operation,
selector switch for local / remote, auto/manual OFF operation.-2 Set
ii)Digital ammeter with selector switch along with suitable ratio CTs---2 Set
iii) Pump on LED Indication lamp --- 2 No.
d) Diesel Engine Control
Control for Diesel Engine comprising:-
586 Supply, installation , testing & commissioning of XLPE insulated and PVC sheathed Aluminium Meter 100.00
/copper conductor armoured cable of 1.1 KV grade confirming to IS : 7098:1988 (with upto date
amendments) of following sizes.
3 Core ,16 sqmm. Aluminium Armoured
587 3 Core, 50 sqmm. Aluminium Armoured Meter 100.00
588 Supply and fixing in position 1 m wide Insulation mat made of elastomeric polymers Material Meter 5.00
(Class -A) of 415V grade as per IS 15642-2006 . Thickness of insulation mat shall be not less
than 2 mm to withstand 1.1 KV dielectric strength AS PER IS 15652 : 2006. It should be
complete as per specifications & directions of Engineer-in-charge. It should be complete as per
specifications & directions of Engineer-in-charge.

[36/80]
Page - 37
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


589 Supplying and making end termination with brass compression gland and aluminium lugs for Each 2
following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV
grade as required. It should be complete as per specifications & directions of Engineer-in-charge.
3 Core ,16 sqmm. Aluminium Armoured

590 3 Core, 50 sqmm. Aluminium Armoured Each 3


591 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Meter 20.00
with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended
from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as
required.
150 mm width x 50mm depth x 1.6 mm thickness.
592 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and Set 2
providing masonry enclosure with cover plate having locking arrangement and watering pipe of
2.7 metre long etc. with charcoal/ coke and salt as required.
593 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode Meter 15.00
including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.

594 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as Meter 30.00
required.
595 SUB HEAD : 6.0- LT & HT PANEL, ELECTRICAL ROOM & SERVER ROOM GAS FLOODING Nos. 8
SYSTEM
Supply, fixing, testing and commissioning of Automatic Linear pneumatic Tube Detection based
Novec 1230/ FK5-1-12 System for Electrical Panels (consisting of the following components:
5 Lb Novec 1230/ FK5-1-12, DLP Assembly with automatic valve mounted on DOT approved
cylinder, push in connector for tube, 5lb Novec 1230/ FK5-1-12 gas, mounting bracket, End of
Line adopter and low pressure switch for monitoring system activation.

596 10 Lb Novec 1230/ FK5-1-12, DLP Assembly with automatic valve mounted on DOT approved Nos. 11
cylinder, push in connector for tube, 10 lb Novec 1230/ FK5-1-12 gas, mounting bracket, End of
Line adopter and low pressure switch for monitoring system activation.
597 Linear pneumatic heat Detection Tube with all necessary fittings & supports. Meter 825.00
598 Master Control Unit with Audio Visual Alarm with wiring to make complete system operational. Nos. 19
The Control Panel should have provision for integration with Fire Alarm/SCADA/BMS System.
599 Supply, fixing, testing and commissioning of 1x80 Itr completely system with CCOE approved set 2
high pressure, seamless Cylinders having suitable 80 ltr water capacity & suitable to store Novec
1230 (FK5-1-12) gas at 34.5 bar pressure with valve assembly, low pressure supervisory switch
for monitoring cylinder pressure gauge with safety burst disc safety cap, elbow and other
accessories, mounting bracket, container straps, NRV. Electrically operated control head
capable of being electrically operated from the fire detection & control, Pressure operated control
head which shall allow for pressure actuation of gas mounted directly on top of cylinder valve,
manually operated actuator to actuate the gas flooding process with the help of a lever, flexible
rubber hose with wire bralded enforcement to route the gas from the storage cylinder to the
discharge piping, to be connected to the discharge outlet of gas cylinder valve & to be terminated
at the system piping or discharge manifold, Flexible actuation hose complete as required.
Discharge nozzle, 180/360 degree. Designated to provide proper flow rate & distribution Novec
1230 (FK5-1-12) gas to flood the hazard area as per requirement. Electrical non conductive,
Novec 1230 (FK5-1-12) required as per NFPA 2001 latest addition 4.7% Design Concentration.
Piping ASTM grade A 106 schedule 40 with fittings & supports and Gas Release Panel
compatible to Fire Alarm System. Makes : Firetrex / Trace fire/Safe Fire as approved by
architect.
600 SUB HEAD: 'C': ELECTRICAL WORKS Each 274
SH: I: POINT WIRING
Wiring for Light/Fan/Call Bell Point with 2X1.5 sq.mm. P.V.C. insulated single core unsheathed
industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed
electrolytic copper conductor for voltage grade up to 1100 volts (Finolex/RR Kabel or equivalent
make as approved by the Dept.) in surface/recessed conduit wiring system with 20mm dia rigid
ISI marked steel conduit pipe complete.
Short point upto 3.00 metre length.
601 Medium point upto 6.00 metre length. Each 685
602 Long point upto 10.00 metre length. Each 1872
603 Wiring for circuit wiring with P.V.C. insulated single core unsheathed industrial (Multistrand) Metre 15067.00
cable FR conforming to IS-694:1990 with flexible bright annealed electrolytic copper conductor
for voltage grade up to 1100 volts (finolex/RR Kabel/Nicco/Anchor or Equivalent make as
approved by the Dept.) in surface/recessed ISI marked steel conduit pipe wiring system.
with 3X1.5 sq.mm cable in 20 mm dia. Rigid Steel conduit.

604 Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial Metre 7202.00
(Multistrand) cable FR conforming to IS-694:1990 with flexible bright annealed electrolytic copper
conductor for voltage grade up to 1100 volts (Finolex/RR Kabel or equivalent make as approved
by the Dept.) in ISI marked steel conduit pipe including earth continuity in surface/recessed
conduit wiring system.
With 2X2.5 sq.mm. + earth continuity with 1X1.5 sq.mm cable in 20 mm. dia. Rigid steel conduit.

605 With 2X4 sq.mm. + earth continuity with 1X2.5 sq.mm cable in 20 mm. dia. Rigid steel conduit. Metre 9312.00

606 With 2X6 sq.mm. + earth continuity with 1X4 sq.mm cable in 25 mm. dia. Rigid steel conduit. Metre 525.00

[37/80]
Page - 38
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


607 Wiring for Drawing sub main line with P.V.C insulated single core unsheathed industrial Metre 7224.00
(multistrand) cable FR conforming to IS-694:1990 with flexible bright annealed electrolytic copper
conductor for voltage grade up to 1100 volts (Finolex/ RR Kabel or equivalent make as approved
by the Dept. ) including earth continuity in surface/ recessed ISI marked steel conduit pipe wiring
system.
With 4X2.5 sq.mm. + earth continuity with 2X1.5 sq.mm cable in 25 mm. dia. Rigid steel conduit.

608 With 4X4 sq.mm. + earth continuity with 2X2.5 sq.mm cable in 25 mm. dia. Rigid steel conduit. Metre 3612.00

609 With 4X6 sq.mm. + earth continuity with 2X4 sq.mm cable in 25 mm. dia. Rigid steel conduit. Metre 60.00
610 Wiring to 5 pin 6 Amps plug point with 1.5 sq. mm. P.V.C insulated single core unsheathed Each 135
industrial (Multistrand) cable FR conforming to IS-694:1990 with flexible bright annealed
electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR kabel or equivalent
make as approved by the Dept.) in surface/recessed ISI marked steel 20 mm. dia. conduit pipe
wiring system including earth continuity with 1.5 sq. mm. cable to third pin of the plug socket etc.
as required complete.
Short point upto 3.00 metre length.
611 Medium point upto 6.00 metre length. Each 451
612 Long point upto 10.00 metre length. Each 918
613 Wiring to 5/6 pin 16 Amps plug point with 4 sq. mm. P.V.C insulated single core unsheathed Each 32
industrial (Multistrand) cable FR conforming to IS-694:1990 with flexible bright annealed
electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR kabel or equivalent
make as approved by the Dept.) in surface/recessed conduit wiring system including earth
continuity with 2.5 sq. mm cable to the 3rd pin of the socket as required complete with 20mm.
dia. steel conduit (AK G or equivalent as approved by the Dept.)
Short point upto 3.00 metre length.
614 Medium point upto 6.00 metre length. Each 104
615 Long point upto 10.00 metre length. Each 376
616 Wiring for twin control light point with 1.5 sw. mm. P.V.C insulated single core unsheathed Each 12
industrial (Multistrand) cable FR conforming to IS-694:1990 with flexible bright annealed
electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR kabel or equivalent
make as approved by the Dept.) in surface/recessed conduit wiring system with 20mm dia rigid
ISI marked steel conduit pipe including 6 Amp flush type 2 way switch ( Anchor penta/Gold
medal /Kolor Kany.Kom/Havells or equivalent make as approved by the dept.) GI/MS switch
board (ISI marked) with phenolic laminated sheet cover, ceiling rode etc complete.
Short point upto 3.00 metre length.

617 Medium point upto 6.00 metre length. Each 24


618 Long point upto 10.00 metre length. Each 72
619 Supplying and fixing 19 mm dia ISI marked steel conduit pipe (AKG or equivalent as approved by Metre 1938.00
the Dept.) in surface/recessed including cutting the wall and making good the same ti its original
architectural finish.
620 Supplying and fixing 25 mm dia ISI marked steel conduit pipe (AKG or equivalent as approved by Metre 3230.00
the Dept.) in recessed including cutting the wall and making good the same ti its original
architectural finish.
621 Supplying and fixing 32 mm dia ISI marked steel conduit pipe (AKG or equivalent as approved by Metre 2153.00
the Dept.) in recessed including cutting the wall and making good the same ti its original
architectural finish.
622 Supplying and fixing 38 mm dia ISI marked steel conduit pipe (AKG or equivalent as approved by Metre 170.00
the Dept.) in recessed including cutting the wall and making good the same ti its original
architectural finish.
623 Supplying and fixing 50 mm dia ISI marked steel conduit pipe (AKG or equivalent as approved by Metre 150.00
the Dept.) in recessed including cutting the wall and making good the same ti its original
architectural finish.
624 Supplying and fixing of following Metal Boxes for Model Range Legrand (Arteor), Anchor (AVE), Each 851
MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) in surface / recessed system
complete as per direction of department.
1-2 Module Type Metal
625 3 Module Type Metal Each 776
626 6 Module Type Metal Each 40
627 8 Module Type Metal Each 195
628 12 Module Type Metal Each 390
629 Supplying including installation of socket outlet 6/10/13 Amps INTERNATIONAL SOCKET, Each 1504
MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER
(ZENSELO), CRABTREE (MURANO) including making necessary connections as per direction
of department.
630 Supplying with fitting and fixing of 16 amp one way modular clip in switch, MODEL RANGE Each 522
LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO),
CRABTREE (MURANO) including making necessary connections as per direction of department.

631 Supplying with fitting and fixing of 6 amp one way modular clip in bell push MODEL RANGE Each 684
LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO),
CRABTREE (MURANO) including making necessary connections as per direction of department.

[38/80]
Page - 39
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


632 Supplying with fitting and fixing of 16 amp one way modular clip in switch, MODEL RANGE Each 522
LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO),
CRABTREE (MURANO) including making necessary connections as per direction of department.

633 Supplying with fitting and fixing of 6/10 amp two way modular clip in switch, MODEL RANGE Each 108
LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO),
CRABTREE (MURANO) including making necessary connections as per direction of department.

634 Supplying fitting and fixing industrial plug & socket in surface mounted SPN sheet steel powder Each 13
painted MCB DB incorporated with MCB DIN rail, neutral link Earth bar of the following rating of
DP MCB complete with making necessary connection etc. as specified and directed by the Dept.
20A Capacity. (ABB, Schneider MG, legrand, Hager make)

635 Supplying fitting and fixing industrial plug & socket in surface mounted TPN sheet steel powder Each 2
painted MCB DB incorporated with MCB DIN rail, neutral link Earth bar of the following rating of
4P MCB complete with making necessary connection etc. as specified and directed by the Dept.
(ABB, Schneider MG, legrand, Hager make).
20A Capacity
636 Supplying with fitting and fixing sheet steel, phosphatised, powder painted dust & vermin proof Each 16
Double door(IP-43) surface mounting SPN MCB DB incorporated with bus-bar, Neutral link,
Earth Bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making
necessary connection as approved , specified & directed by the dept. (ABB, Schneider MG,
legrand, Hager, Crabtree xpro make).
8 way SPN double door
637 12 way SPN double door Each 11
638 Supplying with fitting and fixing sheet steel, phosphatised, powder painted dust & vermin proof Each 25
Double door(IP-43) surface mounting vertical per phase isolation (PP) DB incorporated with bus-
bar 125A, Neutral link, Earth Bar and din rail etc fitted on wall with grouting nuts & bolts as reqd.
complete with making necessary connection as approved , specified & directed by the dept.
(ABB, Schneider MG, legrand, Hager, Crabtree xpro make)
6 way TPN (8+6+18) double door
639 8 way TPN (8+6+24) double door Each 15
640 12 way TPN (8+6+36) double door Each 19
641 Supplying with fitting and fixing single pole 10KA 240/415V 50Hz MCB of the following capacity Each 1646
complete with making necessary connection as approved, specified and directed by the Dept. (
Schneider MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A
642 Supplying with fitting and fixing DP 10KA 240/415V 50Hz MCB of the following capacity complete Each 20
with making necessary connection as approved, specified and directed by the dept. (ABB,
Schneider MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A
643 40A Each 5
644 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 29
with making necessary connection as approved, specified and directed by the dept. (Schneider
MG, legrand, Hager, Crabtree Xpro make)
C Series
6 to 32A
645 40A Each 11
646 63A Each 21
647 Supplying with fitting and fixing 30/100/300mA sensitivity 240/415V 50Hz DP RCCB of the Each 107
following capacity complete with making necessary connection as approved, specified and
directed by the dept. ( ABB, Schneider MG, legrand, Hager, Crabtree xpro make)
30mA sensitivity DP RCCB
25A
648 40A Each 38
649 63A Each 63
650 100/300mA sensitivity DP RCCB Each 1
25A
651 40A Each 1
652 63A Each 1
653 Supplying with fitting and fixing Surge protector of max operation voltage 350V at 400 V network Each 25
for maximum discharge current 40KA with operator indicator and draw out cartridge of
(Schneider or equivalent make), of the following ways complete with making necessary
connection as approved, specified and directed by the dept.
Surge protection Max operating voltage 340V Standard type
1P+N
654 3P+N Each 61
655 Supplying, installation of pre galvanised sheet steel std thickness 1.6mm under floor trunking Metre 367.00
including necessary nuts & bolts, washer etc. as required, as directed and specified by the
department. ( MK/ LEGRAND make) Size
100X38X1.6/1 compartment
656 150X38X1.6/2 compartment Metre 112.00
657 225X38X1.6/3 compartment Metre 73.00
658 250X38X1.6/3 compartment Metre 85.00
659 300X38X1.6/3 compartment Metre 85.00

[39/80]
Page - 40
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


660 JUNCTION BOX Each 43
150X150X60 - 75 mm Depth
661 250X250X60 - 75 mm Depth Each 33
662 300X300X60 - 75 mm Depth Each 14
663 350X350X60 - 75 mm Depth Each 2
664 JOINT SLEEVE Each 122
100/1/6 FOR 38mm
665 150/2/6 FOR 38mm Each 37
666 225/3/6 FOR 38mm Each 24
667 250/3/6 FOR 38mm Each 28
668 300/3/6 FOR 38mm Each 28
669 Cross over/ Junction box Each 3
Cross over 250X250X60 - 75mm 3 compartments
670 Cross over 300X300X60 - 75mm 3 compartments Each 1
671 Cross over 350X350X60 - 75mm 3 compartments Each 1
672 Supplying including fitting and fixing of TV SOCKET, MODEL RANGE LEGRAND (ARTEOR), Each 36
ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) including
making necessary connections as per direction of department.
673 Supplying including fitting and fixing of following star rated A.C. ceiling fan complete with all Each 4220
accessories like down rod, canopy etc of following sweeps with making necessary connection
cable as approved by Deptt.s etc as required complete and as directed by the department as
required complete etc. (Without regulator). (Orient / PSPO / Usha / Crompton / Havells/ ATC / V
Gaurd.)
Energy efficient 5-star 1200 mm sweep. (Orient / PSPO / Usha / Crompton / Havells/ ATC / V
Gaurd.)
674 Supply and fixing of 25 mm dia 1.50mm to 2.0mm average wall thickness heavy rigid PVC IS: Metre 11254.80
9537 Part - III conduit (Berlia / AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make
as approved by the deptt.) on surface system including painting ets as required:
675 Supply and fixing of 32 mm dia 2.0mm average wall thickness heavy rigid PVC IS: 9537 Part - III Metre 2814.00
conduit (Berlia / AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by
the deptt.) on surface system including painting ets as required:
676 Supply and fixing of 19 mm dia 2.0mm average wall thickness heavy rigid PVC IS: 9537 Part - III Metre 2813.60
conduit (Berlia / AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by
the deptt.) in recessed system including cutting the wall and making good the some as required:

677 Supply and fixing of 25 mm dia 2.0mm average wall thickness heavy rigid PVC IS: 9537 Part - III Metre 7503.20
conduit (Berlia / AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by
the deptt.) in recessed system including cutting the wall and making good the some as required:

678 Supply and fixing of 32 mm dia 2.0mm average wall thickness heavy rigid PVC IS: 9537 Part - III Metre 1876.00
conduit (Berlia / AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by
the deptt.) in recessed system including cutting the wall and making good the some as required:

679 S.H.- II DISTRIBUTION PANELS- Set 1


VENTILATION PANEL-1 (BASEMENT FLOOR )
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's,
internal wiring with suitable size wires / cable, interconnection, painting complete as per
specification & drawing. All the dual source energy meter shall be with maximum demand and
RS 485 port for BMS Connectivity.
INCOMING
1 No. 160 Amp FP Moulded Case Circuit Breaker
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
1 No. 150 Amp digital ammeter with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set of Digital KWH Meter with Maximum Demand Recorder facility.
BUS BARS
200 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
680 INCOMMING / OUTGOING Each 2
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
63A
681 100A Each 2
682 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 5
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A
683 63A Each 3

[40/80]
Page - 41
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


684 40A Each 3
685 SMOKE EXT PANEL-1 & 2 Set 2
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof, compartmenlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's, internal
wiring with suitable size wires / cable, interconnection, painting complete as per specification &
drawing. All the dual source energy meter shall be with maximum demand and RS 485 port for
BMS Connectivity.
INCOMING
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.1 No. 100 Amp digital ammeter
with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set of Digital KWH Meter with Maximum Demand Recorder facility.
BUS BARS
150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as
above (Incoming / Outgoing MCCB / MCB shall be paid separately. However the fabrication cost
for Incoming / Outgoing shall be included in above.)
686 INCOMMING / OUTGOING Each 2
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept. 36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T,
Siemens make)
100A
687 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 28
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)C Series
6 to 32A
688 LIGHT + POWER PANEL-1 Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's,
internal wiring with suitable size wires / cable, interconnection, painting complete as per
specification & drawing. All the dual source energy meter shall be with maximum demand and
RS 485 port for BMS Connectivity.
INCOMING
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
1 No. 60 Amp digital ammeter with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set of Digital KWH Meter with Maximum Demand Recorder facility.
4 Set of Digital KWH Meter.
BUS BARS100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
689 INCOMMING / OUTGOING Each 1
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
63A
690 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 4
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A
691 40A Each 3

[41/80]
Page - 42
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


692 LIGHT + POWER PANEL-2 Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including, indicating lamps, CT's,
internal wiring with suitable size wires / cable, interconnection, painting complete as per
specification & drawing. All the dual source energy meter shall be with maximum demand and
RS 485 port for BMS Connectivity. INCOMING
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
1 No. 150 Amp digital ammeter with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set of Digital KWH Meter with Maximum Demand Recorder facility.
8 Set of Digital KWH Meter.
BUS BARS
200 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
693 INCOMMING / OUTGOING Each 1
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
160A
694 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 5
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A
695 40A Each 3
696 63A Each 6
697 LIGHT + POWER PANEL-3 & 4 Set 2
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's, internal
wiring with suitable size wires / cable, interconnection, painting complete as per specification &
drawing. All the dual source energy meter shall be with maximum demand and RS 485 port for
BMS Connectivity.
INCOMING
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
1 No. 125 Amp digital ammeter with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set of Digital KWH Meter with Maximum Demand Recorder facility.
7 Set of Digital KWH Meter.
BUS BARS
150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
698 INCOMMING / OUTGOING Each 2
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
160A
699 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 10
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A
700 40A Each 6
701 63A Each 12

[42/80]
Page - 43
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


702 LIGHT + POWER PANEL-5 &6 Set 2
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's, internal
wiring with suitable size wires / cable, interconnection, painting complete as per specification &
drawing. All the dual source energy meter shall be with maximum demand and RS 485 port for
BMS Connectivity.
INCOMING
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
1 No. 60 Amp digital ammeter with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set of Digital KWH Meter with Maximum Demand Recorder facility.
4 Set of Digital KWH Meter.
BUS BARS
100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
703 INCOMMING / OUTGOING Each 2
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept. 36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T,
Siemens make)
63A
704 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 8
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)
C Series6 to 32A
705 63A Each 6
706 LIGHT + POWER PANEL ( AUDITORIUM ) Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's,
internal wiring with suitable size wires / cable, interconnection, painting complete as per
specification & drawing. All the dual source energy meter shall be with maximum demand and
RS 485 port for BMS Connectivity.
INCOMING
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.1 No. 100 Amp digital ammeter
with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set of Digital KWH Meter with Maximum Demand Recorder facility.
6 Set of Digital KWH Meter.
BUS BARS
150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
707 INCOMMING / OUTGOING Each 1
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
100A
708 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 6
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A
709 40A Each 6
710 63A Each 4

[43/80]
Page - 44
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


711 LIFT PANEL Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's,
internal wiring with suitable size wires / cable, interconnection, painting complete as per
specification & drawing. All the dual source energy meter shall be with maximum demand and
RS 485 port for BMS Connectivity.
INCOMING
1 Nos 250 Amp 4P ATS
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
1 No. 250 Amp digital ammeter with inbuilt selector switch and CT's.
2 Set of phase indicating lamps with Single Pole MCB.
2 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set of Digital KWH Meter with Maximum Demand Recorder facility.
BUS BARS
300 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
712 INCOMMING / OUTGOING Each 7
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
63A
713 250A Each 2
714 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 4
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)
C Series
40A
715 63A Each 4
716 LIFT DB- Set 6
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, indicating lamps, CT's, internal wiring
with suitable size wires / cable, interconnection, painting complete as per specification &
drawing. All the dual source energy meter shall be with maximum demand and RS 485 port for
BMS Connectivity.
INCOMING
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
BUS BARS
100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
717 INCOMMING / OUTGOING Each 6
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
63A
718 Supplying with fitting and fixing 30/100/300mA sensitivity 240/415V 50Hz 4P RCCB of the Each 6
following capacity complete with making necessary connection as approved, specified and
directed by the dept. ( ABB, Schneider MG, legrand, Hager, Crabtree xpro make)
100/300mA sensitivity FP RCCB
63A
719 Supplying with fitting and fixing DP 10KA 240/415V 50Hz MCB of the following capacity complete Each 12
with making necessary connection as approved, specified and directed by the dept. (ABB,
Schneider MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A

[44/80]
Page - 45
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


720 EMERGENCY LIGHT PANEL-2 Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's,
internal wiring with suitable size wires / cable, interconnection, painting complete as per
specification & drawing. All the dual source energy meter shall be with maximum demand and
RS 485 port for BMS Connectivity.
INCOMING
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
BUS BARS
100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
721 INCOMMING / OUTGOING Each 1
Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)
C Series
40A
722 Supplying with fitting and fixing DP 10KA 240/415V 50Hz MCB of the following capacity complete Each 9
with making necessary connection as approved, specified and directed by the dept. (ABB,
Schneider MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A
723 EMERGENCY LIGHT PANEL-1 Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's, internal
wiring with suitable size wires / cable, interconnection, painting complete as per specification &
drawing. All the dual source energy meter shall be with maximum demand and RS 485 port for
BMS Connectivity.
INCOMING
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
1 No. 60 Amp digital ammeter with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set of Digital KWH Meter with Maximum Demand Recorder facility.
BUS BARS
100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
724 INCOMMING / OUTGOING Each 1
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
63A
725 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 2
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)
C Series
40A
726 Supplying with fitting and fixing DP 10KA 240/415V 50Hz MCB of the following capacity complete Each 11
with making necessary connection as approved, specified and directed by the dept. (ABB,
Schneider MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A

[45/80]
Page - 46
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


727 MAIN UPS O/G PANEL- Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's, internal
wiring with suitable size wires / cable, interconnection, painting complete as per specification &
drawing. All the dual source energy meter shall be with maximum demand and RS 485 port for
BMS Connectivity.
INCOMING
3 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
3 No. 150 Amp digital ammeter with inbuilt selector switch and CT's.
3 Set of phase indicating lamps with Single Pole MCB.
3 Set of ON / OFF indicating lamps with Single Pole MCB.
3 Set of Digital KWH Meter with Maximum Demand Recorder facility.
BUS BARS
400 Amp FP aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
728 INCOMMING / OUTGOING Each 4
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
100A
729 160A Each 3
730 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 3
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A
731 40A Each 4
732 Supplying with fitting and fixing DP 10KA 240/415V 50Hz MCB of the following capacity complete Each 5
with making necessary connection as approved, specified and directed by the dept. (ABB,
Schneider MG, legrand, Hager, Crabtree xpro make)
C Series
40A
733 UPS POWER PANEL-1 Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, indicating lamps, CT's, internal wiring
with suitable size wires / cable, interconnection, painting complete as per specification &
drawing. All the dual source energy meter shall be with maximum demand and RS 485 port for
BMS Connectivity.
INCOMING
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
1 No. 100 Amp digital ammeter with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
BUS BARS
150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
734 INCOMMING / OUTGOING Each 1
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
100A
735 Supplying with fitting and fixing 4P 10KA 240/415V 50Hz MCB of the following capacity complete Each 4
with making necessary connection as approved, specified and directed by the dept. ( Schneider
MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A
736 40A Each 4
737 Supplying with fitting and fixing DP 10KA 240/415V 50Hz MCB of the following capacity complete Each 2
with making necessary connection as approved, specified and directed by the dept. (ABB,
Schneider MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A

[46/80]
Page - 47
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


738 UPS POWER PANEL-2 (AUDI. BLOCK) Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's, internal
wiring with suitable size wires / cable, interconnection, painting complete as per specification &
drawing. All the dual source energy meter shall be with maximum demand and RS 485 port for
BMS Connectivity.
INCOMING
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
1 No. 100 Amp digital ammeter with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
BUS BARS
150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
739 INCOMMING / OUTGOING Each 2
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
100A
740 Supplying with fitting and fixing DP 10KA 240/415V 50Hz MCB of the following capacity complete Each 2
with making necessary connection as approved, specified and directed by the dept. (ABB,
Schneider MG, legrand, Hager, Crabtree xpro make)
C Series
40A
741 MAIN PANEL ( GROUND FLOOR) Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm
thick CRCA sheet complete with following equipments, including indicating lamps, CT's,
internal wiring with suitable size wires / cable, interconnection, painting complete as per
specification & drawing. All the dual source energy meter shall be with maximum demand and
RS 485 port for BMS Connectivity.
INCOMING
2 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
2 No. 600 Amp digital ammeter with inbuilt selector switch and CT's.
2 Set of phase indicating lamps with Single Pole MCB.
2 Set of ON / OFF indicating lamps with Single Pole MCB.
2 Set of Digital KWH Meter with Maximum Demand Recorder facility.
BUS BARS
800 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.
Panel described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing shall be included in above.)
742 BUSCOUPLER Each 1
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
630A
743 INCOMMING / OUTGOING Each 5
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, without
enclosure of the following capacity complete with making necessary connection as approved,
specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
63A
744 100A Each 3
745 160A Each 9
746 250A Each 2
747 630A Each 2
748 SH: III: MAIN & SUB MAIN CABLES Meter 4800.00
Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded
conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour
(Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to
2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2
sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable
trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the
cable by using crimping tool and making good damaged done as specified and directed by the
department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.)
Core-2 (A2XWay, A2XFaY)
6 sq.mm two core armoured cable

[47/80]
Page - 48
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


749 10 sq.mm two core armoured cable Meter 750.00
750 50 sq.mm 3 and 1/2 core armoured cable Meter 50.00
751 70 sq.mm 3 and 1/2 core armoured cable Meter 450.00
752 95 sq.mm 3 and 1/2 core armoured cable Meter 125.00
753 150 sq.mm 3 and 1/2 core armoured cable Meter 275.00
754 240 sq.mm 3 and 1/2 core armoured cable Meter 720.00
755 300 sq.mm 3 and 1/2 core armoured cable Meter 2765.00
756 Core-4 (A2XWY, A2XFY) Meter 240.00
25 sq.mm four core armoured cable
757 Supply and laying of following size power / control copper cables, solid copper conductor, XLPE Meter 817.00
Insulated, cores laid up, PVC tape inner sheathed, unarmoured/armoured (Galvanised for cable
up to 10x1.5 sq.mm, 8x2.5 sq.mm, 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm, balance all
galvanised steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1)
1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting
required size of lugs at the both end of the cable by using crimping tool and making good
damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI /
Polycab / Gloster / Finolex make or equivalent.)
2 Core-2, 2XFaY
6 sq.mm two core armoured cable
758 10 sq.mm two core armoured cable Meter 75.00
759 4 Core-4, 2XWY, 2XFY Meter 250.00
4 sq.mm four core armoured cable
760 6 sq.mm four core armoured cable Meter 2910.00
761 10 sq.mm four core armoured cable Meter 684.00
762 16 sq.mm four core armoured cable Meter 1337.00
763 Supply & Laying of following sizes of 1.1KV grade multistranded copper conductor FRLS Meter 600.00
insulated cable including termination complete as required in existing cable tray.
1C x 70 sq.mm PVC Insulated cu wire including end termination.
764 1C x 25 sq.mm PVC Insulated cu wire including end termination. Meter 60.00
765 1C x 16 sq.mm PVC Insulated cu wire including end termination. Meter 440.00
766 Supply, Installation, Testing & Commissioning of Earthing Junction Box size - 400mm x 300mm x Set 2
80mm made out of 16 SWG CRCA sheet with seven tank process & powder coating, earthing
link (32mmx6mm copper strip), front door with glass as complete as required.

767 Supplying Fitting and Fixing of (Dowells / Commet make) Double compression brass gland with Each 206
nickel.
Weatherproof (CBW) Size:8-10, 3/4''
768 Supplying Fitting and Fixing of (Dowells / Commet make) Single compression brass gland heavy Each 474
duty.
Single Compression Brass Gland Heavy Duty. Size:1''
769 Single Compression Brass Gland Heavy Duty. Size:1-1/8'' Each 84
770 Single Compression Brass Gland Heavy Duty. Size:1-1/2'' Each 14
771 Single Compression Brass Gland Heavy Duty. Size:1-3/4'' Each 8
772 Single Compression Brass Gland Heavy Duty. Size:2-1/4'' Each 8
773 Single Compression Brass Gland Heavy Duty. Size:2-3/4'' Each 86
774 Perforated RM30 Medium Duty Return Flange Cable Tray with Nos Splice RM 30 8-M6 X Gutter Metre 475.00
Bolt & Nuts upto 300mm and 3 Nos Splice, RM30 12 -M6 X Gutter Bolt & Nuts Above 300mm
including stand off bracket.
Size of Tray (in mm)
100
775 150 Metre 565.00
776 300 Metre 210.00
777 450 Metre 180.00
778 600 Metre 235.00
779 750 Metre 50.00
780 900 Metre 140.00
Bend
781 100 Each 48
782 150 Each 57
783 300 Each 21
784 450 Each 19
785 600 Each 24
786 750 Each 5
787 900 Each 14
Inter/Exter Bend
788 100 Each 24
789 150 Each 28
790 300 Each 11
791 450 Each 9
792 600 Each 12
793 750 Each 3
794 900 Each 7
Tee
795 100 Each 13
796 150 Each 14
797 300 Each 6
798 450 Each 5

[48/80]
Page - 49
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


799 600 Each 7
800 750 Each 2
801 900 Each 4
4 Way
802 100 Each 7
803 150 Each 8
804 300 Each 3
805 450 Each 3
806 600 Each 4
807 750 Each 1
808 900 Each 2
STAND OFF BRACKET
809 100 Each 48
810 150 Each 57
811 300 Each 21
812 450 Each 19
813 600 Each 24
814 750 Each 5
815 900 Each 14
816 SH: IV: SUPPLY & FIXING OF LIGHT FIXTURES & FANS INTERNAL LIGHTING. Each 287
Supply, Installation, Testing & Commissioning of Recess LED Down lighter made of pressure die
cast aluminum housing with high efficiency reflector, LED Used shall be SMD type and fixture
should have minimum efficacy at System level (Not Chip Level) >=90lumens/watt, 650 Lumen,
Life of fixture (Including Driver) : 50K Hrs. @ L70B50 Lumen maintenance, CCT - 6500
(SDCM<5), CRI >80, PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270
V.Minimum Internal Surge Protection 2.0KV The fixture design should comply with IS10322,
EMC / EMI compliance maintaining driver leakage current as per as per IEC 60598,Minimum
system Lumens 600.Philips DN 191B LED6S-6500 PSU WH or equivalent.
817 Supply, Installation, Testing & Commissioning of Recess LED Down lighter made of pressure die Each 7
cast aluminum housing with high efficiency reflector, LED Used shall be SMD type and fixture
should have minimum efficacy at System level (Not Chip Level) >=100lumens/watt, 1200 lumen,
Life of fixture (Including Driver) : 30K Hrs. @ L70B50 Lumen maintenance, CCT up to 6500
(SDCM<5), CRI >80, PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270
V.Minimum Internal Surge Protection 2.0KV The fixture design should comply with IS10322,
EMC / EMI compliance maintaining driver leakage current as per as per IEC 60598,Minimum
system Lumens 1200.Philips DN193B LED12S-6500 PSU WH S1 or equivalent.

818 Supply, Installation, Testing & Commissioning of Surface Mounted LED Down lighter made of Each 154
pressure die cast aluminum housing with high efficiency reflector, LED Used shall be SMD type
and fixture should have minimum efficacy at System level (Not Chip Level) >=100lumens/watt,
1200 Lumen Life of fixture (Including Driver) : 30K Hrs. @ L70B50 Lumen maintenance, CCT up
to 6500 (SDCM<5), CRI >80, PF >0.90, an operating Voltage Range of 140 - 270 V.Minimum
Internal Surge Protection 2.0KV The fixture design should comply with IS10322, EMC / EMI
compliance maintaining driver leakage current as per as per IEC 60598,Minimum system
Lumens 1200.Philips SM250C LED12S- 6500 PSU WH or equivalent.

819 Supply, Installation, Testing & Commissioning of Recess LED Down lighter made of pressure die Nos 194
cast aluminum housing with high efficiency reflector, LED Used shall be SMD type and fixture
should have minimum efficacy at System level (Not Chip Level) >=100lumens/watt, Life of
fixture (Including Driver) : 30K Hrs. @ L70B50 Lumen maintenance, CCT up to 6500 (SDCM<5),
CRI >80, PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270 V.Minimum Internal
Surge Protection 2.0KV The fixture design should comply with IS10322, EMC / EMI compliance
maintaining driver leakage current as per as per IEC 60598, Minimum system Lumens 1800.
Philips DN195B LED20S-6500 PSU WH S1 or equivalent.
820 Supply, Installation, Testing & Commissioning of 12 watt LED Mirror Light as complete as Nos 94
required. (Philips Make, Cat No - Mirror Light 32047/11 or equivalent.)
821 Supply, Installation, Testing & Commissioning of Surface Mounted Linear LED IP65 fitting made Nos 9
of Virgin Polycarbonate housing & Non Yellowing PC Diffuser ,LED Used shall be SMD type and
fixture should have minimum efficacy at System level (Not Chip Level) >=100lumens/watt, Life
of fixture (Including Driver) : 50K Hrs. @ L70B50 Lumen maintenance, CCT 6500 (SDCM<5),
CRI >80 , PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270 V.Minimum Internal
Surge Protection 3KV The fixture design should comply with IS10322, EMC / EMI compliance
maintaining driver leakage current as per as per IEC 60598,Minimum system Lumens 4000.
Philips WT201C LED40S-6500 PSU L120 or equivalent.

822 Supply, Installation, Testing & Commissioning of Recess LED 600x600mm fitting made of white Nos 466
CRCA powder quoted finish with fully covered by PMMA Acrylic Lumio Diffuser, LED Used shall
be SMD type and fixture should have minimum efficacy at System level >=100lumens/watt, Life
of fixture : 50K Hrs. @ L70B50 Lumen maintenance, CCT up to 6500 (SDCM<5), CRI >80 , PF
>0.95 & THD<10%, Fixture must be office compliant & have to comply to UGR<19 value for
optimum glare.an operating Voltage Range of 140 - 270 V.Minimum Internal Surge Protection
2.5KV The fixture design should comply with IS:10322 & Must be EMC / EMI compliance
maintaining driver leakage current as per as per IEC 60598, Minimum system Lumens 3000.
Philips RC380B LED30S -6500 G4 L60 W60 PSU OD OC LED Office Compliant Panel with Min
Glare Value i.e. UGR<19 or equivalent.

[49/80]
Page - 50
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


823 Supply, Installation, Testing & Commissioning of 1x20 Watt LED Light Fixture surface mounted Nos 775
as per technical specification. (Philips Cat No Linea BN 021C LED20S PSU CW GR S2 or
equivalent).
824 Supply, Installation, Testing & Commissioning ofFor suspended mounting as single luminaire. Nos 5
Suspension length consists of 400-1750 mm. With Binary Light Guide System (BLGS). Optical
system consisting of two fine-prismatic PMMA covers for light emission, one above the other.
With direct-indirect light distribution. Indirect component with extremely wide distribution. VDU-
compliant according to EN 12464-1. LED system with lateral entry of light in the Binary Light
Guide System. Luminaire luminous flux 6400 lm, connected load 53 W, Light colour neutral
white, colour temperature 4000 K, colour rendering index Ra > 80. Service life L80(tq 25 °C) =
70,000 h, service life L85(tq 25 °C) = 50,000 h. Luminaire body of extruded aluminium profile,
End caps of die-cast aluminium. Luminaire body white powder-coated. Dimensions (L x W): 1175
mm x 338 mm, luminaire height 16 mm. Permissible ambient temperature (ta): -20 °C - +25 °C.
Safety class I, protection rating IP20, impact resistance IK02/0,2 J, glow wire resistance
65described as above (Incoming / Outgoing MCCB / MCB shall be paid separately. However the
fabrication cost for Incoming / Outgoing shall be included in above.)cluded in above.)ctrical non
conductive, Novec 1230 (FK5-1-12) required as per NFPA 2001 latest addition 4.7% Design
Concentration. Piping ASTM grade A 106 schedule 40 with fittings & supports and Gas Release
Panel compatible to Fire Alarm Sys
825 Supply, Installation, Testing & Commissioning of Surface/Suspended Linear Slim (width 60mm) Nos 228
LED fitting made of Extusion Alu. Housing with anodised coating ,LED Used shall be SMD type
and fixture should have minimum efficacy at System level (Not Chip Level) >=110lumens/watt,
Life of fixture (Including Driver) : 50K Hrs. @ L70B50 Lumen maintenance, CCT 6500
(SDCM<5), CRI >80 , PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270
V.Minimum Internal Surge Protection 3KV The fixture design should comply with IS10322, EMC
/ EMI compliance maintaining driver leakage current as per as per IEC 60598,Minimum system
Lumens 2300. Philips SP780 LED Channel Light with 60mm Width Standalone 4Ft Version or
equivalent.
826 Supply, Installation, Testing & Commissioning of Surface/Suspended Linear Slim (width 60mm) Nos 210
LED fitting made of Extusion Alu. Housing with anodised coating ,LED Used shall be SMD type
and fixture should have minimum efficacy at System level (Not Chip Level) >=110lumens/watt,
Life of fixture (Including Driver) : 50K Hrs. @ L70B50 Lumen maintenance, CCT 6500
(SDCM<5), CRI >80 , PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270
V.Minimum Internal Surge Protection 3KV The fixture design should comply with IS10322, EMC
/ EMI compliance maintaining driver leakage current as per as per IEC 60598,Minimum system
Lumens 2300. Philips RC780B LED Recessed Channel Light with 60mm Width Continuous
Version in 4Ft Version - Non Dali Dimmable or equivalent.
827 Supply, Installation, Testing & Commissioning of LED Bulkhead Fixture made of pressure die Nos 61
cast aluminum housing with high efficiency reflector, LED Used shall be SMD type and fixture
should have minimum efficacy at System level (Not Chip Level) >=100lumens/watt, Life of
fixture (Including Driver) : 30K Hrs. @ L70B50 Lumen maintenance, CCT - 6500 (SDCM<5), CRI
>70, PF >0.95 , an operating Voltage Range of 140 - 270 V.Minimum Internal Surge Protection
2.0KV The fixture design should comply with IS10322, Minimum system Lumens 700.Philips
WT140W LED7S-CW PSU S1 PC LED Bulkhead or equivalent.
828 Supply, Installation, Testing & Commissioning of Self contained emergency light units 1x9 watt Each 40
double sided for wall / ceiling mounting with suspension / mounting kit, lamps, inbuilt standby
battery (for 2 hours backup) and battery charger etc. in suitable enclosure. Make - Prolite or
equivalent.
829 Supply, Installation, Testing & Commissioning of 2W Steplight suitable for recessed mounting Each 100
made up of Aluminum Base in Anthracite color.
830 Supply, Installation, Testing & Commissioning of 4 watt per meter (300 lumen per meter) LED Meter 560.00
cove Light with high efficiency electronic driver. (Make Philips Cat No- LS150S LED3/WW
L5000 IN or equivalent.)
831 Supply, Installation, Testing & Commissioning of 40w Recess Spot LED Down lighter made of Nos 48
pressure die cast aluminum housing with high efficiency Aluminum reflector, fixture should have
minimum efficacy at System level (Not Chip Level) >=76/85lumens/watt with wide beam angle of
36Deg , Life of fixture (Including Driver) : 40K Hrs. @ L70B50 Lumen maintenance, CCT up to
6500 (SDCM<5), CRI >80, PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270
V.Minimum Internal Surge Protection 2.0KV The fixture design should comply with IS10322,
EMC / EMI compliance maintaining driver leakage current as per as per IEC 60598,Minimum
system Lumens 4000 Philips RS271B LED40 Recessed Down lighter or equivalent.

832 Supply, Installation, Testing & Commissioning of Electronic Buzzer as complete as required. Meter 10.00
833 Supplying, Fitting and fixing of occupancy sensor of the following atageories as per required and Meter 111.00
directed by the department. (ABB/ Panasonic/ mk/ anchor/ crabtree/ Hager/ Panasonic or
equivalent make as approved by deptt.
presence detection with 360 degrees angle of detection with senser head power unit and 2
relays , range up to 4 meter at 2.5 meter ceiling height.

[50/80]
Page - 51
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


834 Supply, Installation, Testing & Commissioning of Recess LED 600x600mm dali dimmable fitting Nos 50
made of white CRCA powder quoted finish with fully covered by PMMA Acrylic Lumio Diffuser,
LED Used shall be SMD type and fixture should have minimum efficacy at System level
>=100lumens/watt, Life of fixture : 50K Hrs. @ L70B50 Lumen maintenance, CCT up to 6500
(SDCM<5), CRI >80 , PF >0.95 & THD<10%, Fixture must be office compliant & have to comply
to UGR<19 value for optimum glare.an operating Voltage Range of 140 - 270 V.Minimum
Internal Surge Protection 2.5KV The fixture design should comply with IS:10322 & Must be EMC
/ EMI compliance maintaining driver leakage current as per as per IEC 60598, Minimum system
Lumens 3000. Philips RC380B LED30S -6500 G4 L60 W60 PSU OD OC LED Office Compliant
Panel with Min Glare Value i.e. UGR<19 or equivalent.
835 Supply, Installation, Testing & Commissioning of Recess LED Down lighter dali dimmable made Nos 30
of pressure die cast aluminum housing with high efficiency reflector, LED Used shall be SMD
type and fixture should have minimum efficacy at System level (Not Chip Level)
>=100lumens/watt, Life of fixture (Including Driver) : 30K Hrs. @ L70B50 Lumen maintenance,
CCT up to 6500 (SDCM<5), CRI >80, PF >0.95 & THD<10%, an operating Voltage Range of
140 - 270 V.Minimum Internal Surge Protection 2.0KV The fixture design should comply with
IS10322, EMC / EMI compliance maintaining driver leakage current as per as per IEC 60598,
Minimum system Lumens 1800. Philips DN195B LED20S-6500 PSU WH S1 or equivalent.

836 SH: V: DATA, TELEPHONE, Wi-Fi SYSTEM Meter 41120.00


Supply, installation, testing and commissioning of following LAN networks equipments.
Solid Copper Cable 6, 4 pair, UTP 305m SCHNEIDER/LEGRAND or equivalent make as
approved by the Deptt.
837 Patch Panel Cat 6 UTP Keystone-24 Port- Loaded SCHNEIDER/LEGRAND or equivalent make Nos. 35
as approved by the Deptt.
838 Patch Cord Cat 6 UTP Gray 1m- Moulded SCHNEIDER/LEGRAND or equivalent make as Nos. 820
approved by the Deptt..
839 Cat 6 Keystone UTP Jack with Dust Cover-White SCHNEIDER/LEGRAND or equivalent make Nos. 820
as approved by the Deptt.
840 Back Box-(Surface Mount Box) For Single and Dual SCHNEIDER/LEGRAND or equivalent make Nos. 820
as approved by the Deptt.
841 APW Cyber Rack Networking Equipment Rack APW President Enclosure, 600mmW Each 2
CYBERACK 42U/800mmD (CRCA Steel Frame with Aluminium Profiles & 2 Nos. of Removable
Side Panels with following items:- Top cover with cable entry-1no.-Bottom cover with cable entry-
1no.-19" Mounting Angles-2 pairs., Finish: Powder coated to 80 microns; Matt Finish. Colour:
BLACK with, Load rating capacity -500 Kgs., Front side vented glass door and rear full perforated
steel door with locks. " PDU 10*5/15A-01 Nos., Fan Housing Unit with 4 Fans-01 Set, Mounting
Hardware (Set of 20)-1 Set, Castor with Brake- 2Nos., Castor without Brake - 2 Nos., Earthing
Kit - 01 Set, Cable Manager 19" 1U - 2 Nos.
842 Patch Cord Cat 6 UTP Gray 2m- Moulded SCHNEIDER/LEGRAND or equivalent make as Nos. 820
approved by the Deptt..
843 Supply, erection, testing and commissioning of following sizes of splitter of aluminium die cast Each 1
body in suitable size of G.I. Box.
4 way
844 6 way Each 5
845 8 way Each 3
846 Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE Meter 1800.00
insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing
surface/ recessed steel/ PVC conduit as required.
847 Supply , Installation , Testing and commissioning of 27U wall mount rack with fans , 2 cable Nos 14
managers, stationary shelf , 2 Nos of hardware pkts. Approved Makes:
Poweride/MTS/Rittal/APC/APW
848 Supply of IP Based voice Communication System with 04 Port Voicemail ,04 Port FXS ,04 Port Nos 1
FXO ,1 PRI Trunk lines (30 Ch) Circuit with CLIP Facility ,320 IP users License ,01 Nos. IP
Operator Console,100 Party Conference ,Speed Dial, Music on Hold , Internal/ External ring
difference ,Call Barring, Call Pickup, - Redundant server in active-Active mode. Approved
Makes: Tadiran/Cisco /Polycom/Juniper/Cambium
849 Supply of Type 1 IP Phone . Graphic LCD display with backlight 3 user accounts with multi-line Nos 300
appearance keys Local and company-wide phone directories. Approved Makes: Tadiran/Cisco
/Polycom/Juniper/Cambium
850 Supply of Type 2 IP Phone 1 VoIP account , Full duplex speaker phone, IPV6, 2xLAN, PoE . Nos 70
Approved Makes: Tadiran/Cisco /Polycom/Juniper/Cambium
851 Supply, Installation, Testing & Commissioning of Core Switch with switching capacity of 1.4Tbps, Nos 2
forwarding performance of 1Bpps with 32x 1/10G SFP+ ports plus 4x 40G QSFP+ ports from
day 1, dual hot swappable internal power supply, 60K IPv6 routes and 48K IPv6 multicast routes.
Should support advance layer 3 (RIPng, OSPF, BGP and MPLS) with 1 year support. Stack
Module/40 Gig Optics and all other Cables should be included in Day 1.
Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista
852 Supply, Installation, Testing & Commissioning of 24 Port POE+ Access Switches with switching Nos 39
capacity of 128 Gbps, forwarding performance 95 Mpps, having 24 x 10/100/1000BASE-T PoE-
plus(RJ45) with minimum PoE budget of 370W and 4x 10G SFP+ uplink ports . Should support
min 2GB internal DRAM, 2GB internal Flash memory,32K MAC address, 1K IPv6 Multicast
Routes, Should have static Routes from day 1.One year support.
Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista
853 Supply, Installation, Testing & Commissioning of fiber Modules 1000BASE Approved Make : Nos 78
Cisco/ Impulse / Juniper / Extreme/ Arista.

[51/80]
Page - 52
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


854 Supply , Installation , Testing and Commissioning of 4X4 MIMO , 802.11 a/b/g/n Indoor Wi-Fi- Nos 5
Access point, dynamic radio management. Approved Makes: Cisco/Juniper/ Extreme/
Cambium/ Der Weiser.
855 Supply , Installation , Testing and commissioning of wireless LAN Controller supportable for AP Nos 1
upgradable for Aps in standalone and 100 Aps in high availability mode. Approved
Makes:Cisco/Juniper/Extreme/Cambium/Der Weiser.
856 Supply, Installation, Testing & Commissioning of Internet Web Security solution with minimum of Nos 1
100 users from day one with one years of subscription / support and flexibility to scale up to 1000
users, having 99.9% uptime with each level redundancy, single pane of glass for reporting with
minimum 6 months of logs and must be Leaders in Gartner Magic Quadrant in the last 3
consecutive years (2015, 2016 and 2017) and includes following features as per detailed
specification: a) Web Security
b) Full SSL Inspection
c) Next Generation Firewall
d) Sandboxing
e) Bandwidth Control
f) Cloud Applications Visibility
g) Mobility
Approved Makes: Zscaler/ Checkpoint/Palo Alto/Cisco/Juniper

857 Supply , Installation , Testing and commissioning of armoured 6 core multimode OFC cable for Meter 1450.00
interfloor switch connectivity.
858 Supply , Installation , Testing and commissioning of 6 port loaded LIU with adaptor plates , pigtel Nos 9
cables for connections.
859 Supply , Installation , Testing and commissioning of 24 port loaded LIU for core switch to access Nos 2
switch connectivity over fiber.
860 Supply , Installation , Testing and commissioning of SC-LC multimode fiber patch cord. Nos 39
861 LIGHTNING PROTECTION AS PER IEC 62305 / IS IEC 62305 Mtr. 1125.00
Supply 8 mm round aluminium conductor for horizontal lightning protection - run in roof. Model :
AL8. Make : Hakel / APS
862 Supply of roof conductor holder for 8 mm round aluminium conductor made of Gun Metal for Nos. 900
horizontal installation. The distance between each holder should be min of 1.5 mtr. Model :
APSRCS50. Make : Hakel / APS
863 Supply of Cross connector for connecting of 8 mm Al round conductor . The connector should be Nos. 90
of Gun Metal with SS nuts and bolt. Model : APSCCRC50 , Make : Hakel /APS
864 Supply of T connector for connecting of 8 mm Al round conductor . The connector should be of Nos. 15
Gun Metal with SS nuts and bolt. Model : APSCCRC50 , Make : Hakel /APS
865 Supply of L connector for connecting of 8 mm Al round conductor . The connector should be of Nos. 12
Gun Metal with SS nuts and bolt. Model : APSCCRC50 , Make : Hakel /APS
866 Supply of straight connector for connecting of 8 mm Al round conductor . The connector should Nos. 4
be of Gun Metal with SS nuts and bolt. Model : APSPCRC50, Make : Hakel / APS
867 Supply of Expansion piece to compensate the expansion of round 8 mm Al conductor when Nos. 4
temperature variation . Connection should be in every 20 mtr. Model : APSEXP50 , Make :
Hakel/APS
868 Supply of fixing glue for fixing of roof conductor holder . Pc 6
869 Supply of Expansion piece connector for connecting of 8 mm Al round conductor . The Nos. 6
connector should be of Gun Metal with SS nuts and bolt.
Model : APSCEP50- Make : Hakel /APS
870 DOWN CONDUCTOR AS PER IEC+D880 62305 Mtr. 705.00
Supply of 8 mm round aluminium conductor as a down conductor mounted in the surface of
wall which will carry the lightning current to earth pit. Model : AL8. Make : Hakel / APS
871 Supply of Down conductor holder for 8 mm round aluminium conductor of min distance Nos. 465
between the wall to the conductor will be of 50 mm. The distance between each holder should
be min of 1.5 mtr. Model : APSRCH50 Make : Hakel /APS
872 Supply of Test Joint Point for 8 mm round aluminium conductor , the size should be of 25 x 3 Nos. 3
x 150 mm copper in ABS boxes. Model : APSTLBCU. Make : Hakel / APS
873 EARTHING AS PER IEC 62561- 2 & 7 Nos. 16
SITC of UL approved low carbon high tensile steel rod with copper coating of min 254 micron
JK Chemrode - 317 CBR the dia should be 17.2 mm with length of 10 feet ( 3000 mm) . The rod
shall be as per IEC 62561-2 and approved by UL 467. The rod shall be tested from NABL lab
for current discharge not less then 46kA peak. The Chemrode shall be surrounded with 50 kg ( 2
bag) of Earth enhance materiel JK Activer+ according to IEC 62561-7 and the Chemical
resistance value shall not increase more then 0.064 Ωm and same will be tested from NABL
lab.
Make :APS/JK

[52/80]
Page - 53
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


874 FIRE ALARM SYSTEM (ADDRESSABLE TYPE) Set 1
Supply, Installation, Testing & Commissioning of Microprocessor based X loop fire alarm control
panel EN approved fully networkable with each loop capable of taking 125 devices, 4 line x 40
character alpha-numeric liquid crystal display .The panel shall be soft addressable type . The
panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be
able to automatically switch off respective control switches when ever any alarm is triggered. The
panel shall have in built rectifier, Loop cards, provision for external & internal printer(if required),
L C D unit to indicate Fire/Fault Signal with address and analog output, built in printer to log all
fire or fault events complete in all respects, integral SMF lead acid batteries with sealed cells of
24 V capable of running for a minimum of 8 hours with integral battery charger complete as
required and as per specification. The fire alarm panel shall be suitable for software integration
with BMS & PA system.
10 Loops
875 Supply, Installation, Testing & Commissioning of Fire Graphics Software to be loaded on PC to Set 1
monitor the Floor wise Fire Detection System.
876 Supply, Installation, Testing & Commissioning of Networkable Repeater Panel (LCD indicator Set 2
panel) with 2 line X 20 characters alpha numeric LCD display with all commands such as reset,
mute, silence with suitable battery backup complete as required.
877 Supply, Installation, Testing & Commissioning of Analog Addressable Intelligent multisensor Nos. 860
detector with two inbuilt optical smoke sensors with light angles as well as additional heat
detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt
fault isolator as per NFPA style 7 wiring complete with base as required.
878 Supply Installation, Testing & Commissioning of Intelligent addressable photothermal detector Nos. 2
with blue colour LED for very early warning with inbuilt isolator as per NFPA7 style 7 wiring &
standard base complete as per specification.
879 Supply, Installation, Testing & Commissioning of Analogue Addressable Intelligent Heat Nos. 5
Detector with fixed & rate of rise temperature function with decentralise intelligence , soft
addressable type, with inbuilt fault isolator as per NFPA style 7 wiring complete with base as
required.
880 Supply Installation, Testing & Commissioning of Intelligent addressable Manual Call Point / Pull Nos. 34
station complete as per specification.
881 Supply, installation, testing and commissioning of addressable control module complete as per Nos. 11
specification.
882 Supply, installation, testing and commissioning of addressable monitor module complete as per Nos. 18
specification.
883 Supply Installation, Testing & Commissioning of wall mounting loop powered addressable type Nos. 34
hooter with all accessories.
884 Supply Installation, Testing & Commissioning of Response Indicator. Nos. 459
885 Supply Installation, Testing & Commissioning of fire fighter main console at control room Nos. 1
including power supply and accessories.
886 Supply Installation, Testing & Commissioning of Fire fighters telephone handset. Nos. 6
887 Supply Installation, Testing & Commissioning of Fire fighters telephone jack. Nos. 24
888 PUBLIC ADDRESS SYSTEM- Set 2
SITC of EN54-16 compliant IP Based Digital Public Address & Voice Alarm system. The
selected system devices like controllers and Paging Microphones, should use the TCP/IP
technologies and build on the standard network platform to ensure expandability. The individual
systems should be able to play 4 simultaneous audio messages and also be able to be
networked over IP.
SITC of 8 zone IP based, digital Voice Alarm controller expandable upto 128 zones. The voice
alarm controller should be able to connect directly over Ethernet. It should have functions like
the audio playing, zone control, fault monitoring, log recording, volume control and amplifier
switchover. The Voice alarm controller should also have the following functions:
. 255 Priorities
. Time schedule broadcasts
. Its own PTT microphone
. Capable of amplifier redundancy
. 8 trigger inputs/outputs
Approved Makes : Bosch / Honeywell - X618/ Ateis - IDA
889 SITC of IP based Networkable touch screen paging station for selection of zones, supervision of Set 1
system status, setting of scheduled broadcasts with the following functions:
. Built-in monitoring loudspeaker
. Detachable goose-neck microphone
. LCD touchscreen display
. Audio input

890 SITC of 2x250W Class-D Amplifier with 4 independent channels and can provide automatic re- Set 5
settable overcurrent, overload, overheating, overvoltage, under-voltage and DC protection.
Approved Makes : Bosch Praesedio / Honeywell - X618/ Ateis - IDA
891 SITC of Network Resource Interface, 4 channels network audio source, 32 dry contacts in and 8 Set 2
try contacts out for Fire Alarm Interface
892 SITC of 6W Ceiling mount with max SPL1M/1W 96dB . Frequency response of 160Hz-20KHz. Set 265
The speaker shoud have tappings at 6W/3W

[53/80]
Page - 54
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


893 SITC of 6W Wall mount with max SPL1M/1W 96dB . Frequency response of 160Hz-20KHz. The Set 40
speaker shoud have tappings at 6W/3W.

894 Supply Installation Testing and Commissioning of 12 Watt volume controller with G.I. Box, Set 68
modular plate etc as complete as required.
895 Supply, Installation, Testing & Commissioning of 2C x 1.5 sq.mm Fire Survival armoured cable Meter 21535.00
(300/500V) with Class-2 Copper conductor having Mineral ceramic glass fire barrier tape covered
by an extruded layer of Cross-linkable Low Smoke Zero Halogen (LSZH) insulation as per EI-5
Of BS EN 50363 along with ATC drain wire, aluminium tape screening and LSZH outer sheath
as per BS 7629-1 & BS-5839-1 (latest edition). Outer sheath should be Anti Rodent/Anti Termite.
Should retain circuit integrity as per BS 8434-2 (930 deg C for 120 mins on single sample)
including end termination etc as complete as required. (For Fire & PA System)

896 CCTV SYSTEM- Meter 3815.00


Supply, installation, testing and commissioning of following LAN networks equipments. Solid
Copper Cable 6, 4 pair, UTP 305m SCHNEIDER/LEGRAND or equivalent make as approved by
the Deptt.
897 Patch Panel Cat 6 UTP Keystone-24 Port- Loaded SCHNEIDER/LEGRAND or equivalent make Nos. 68
as approved by the Deptt.
898 Patch Cord Cat 6 UTP Gray 1m- Moulded SCHNEIDER/LEGRAND or equivalent make as Nos. 68
approved by the Deptt..
899 Cat 6 Keystone UTP Jack with Dust Cover-White SCHNEIDER/LEGRAND or equivalent make Nos. 68
as approved by the Deptt.
900 Back Box-(Surface Mount Box) For Single and Dual SCHNEIDER/LEGRAND or equivalent make Nos. 68
as approved by the Deptt.
901 APW Cyber Rack Networking Equipment Rack APW President Enclosure, 600mmW Each 1
CYBERACK 42U/800mmD (CRCA Steel Frame with Aluminium Profiles & 2 Nos. of Removable
Side Panels with following items:- Top cover with cable entry-1no.-Bottom cover with cable entry-
1no.-19" Mounting Angles-2 pairs., Finish: Powder coated to 80 microns; Matt Finish. Colour:
BLACK with, Load rating capacity -500 Kgs., Front side vented glass door and rear full perforated
steel door with locks. " PDU 10*5/15A-01 Nos., Fan Housing Unit with 4 Fans-01 Set, Mounting
Hardware (Set of 20)-1 Set, Castor with Brake- 2Nos., Castor without Brake - 2 Nos., Earthing
Kit - 01 Set, Cable Manager 19" 1U - 2 Nos.
902 Supply, Installation, Testing and Commissioning of UL Listed , ONVIF profile S & G , 1/2.8" Nos 55
CMOS, IP Vari Focal Dome Camera , Full, HD 3 MP , 2.8-12 mm Motorized Varifocal Lens, 30
FPS , Triple Stream with Edge Based Analytics , True Day/Night with IR Cut Filter with auto
switch , Shutter Speed 1/5s ~ 1/20,000 s, IR Illuminator 30 Meter Min Effective Range, 120DB
Wide Dynamic Range, Alarm 1/1, Audio 1/1, SD Card, H.265, H264 Compression, PoE, IP66 ,
Vandal Proof IK10 etc. Approved Makes: Allgovision/ Pelco/ Avigilon/ Impulse/ Axis.

903 Supply, installation, testing and commissioning of UL Listed , ONVIF profile S & G ,1/2.8" CMOS, Nos 7
IP Vari Focal Bullet Camera , Full, HD 3 MP Resolution , 2.8-12 mm Motorized Varifocal Lens ,
30 FPS , Triple Stream with Edge Based Analytics , True Day/Night with IR Cut Filter with auto
switch , Shutter Speed 1/5s ~ 1/20,000 s, IR Illuminator 30 Meter Min Effective Range, 120DB
Wide Dynamic Range, Alarm 1/1, Audio 1/1, SD Card, H.265, H264 Compression, PoE, IP66
etc. Approved Makes: Allgovision/ Pelco/ Avigilon / Impulse/ Axis.
904 Supply, installation, testing and commissioning of UL Listed ONVIF profile S &G , 1/2.8" CMOS Nos 1
Box type camera , external lens 5mm to 50 mm, Full, HD 3 MP Resolution ,3MP@25FPS , 2 MP
@ 50 FPS , Quad Stream with Edge Based Analytics, Shutter speed 1 ~ 1/10000 sec, SD card
support , P-iris, ONVIF profile S & G etc. .Approved Makes :Allgovision/ Pelco/ Avigilon /
Impulse/ Axis.
905 Supply , Installation , Testing and Commissioning of 6 MP , Fish eye Camera ,ONVIF profile S & Nos 1
G , UL,CE,FCC certified , 1/1.8" CMOS lens , 1.55 mm focal length , shutter speed :1 ~ 1/10000
sec , Quad stream , Frame rate : 6MP @ 25 fps , 2 MP @ 50 fps , Digital Zoom , Two way audio
support ,Auto white balance ,Inbuilt IR LED , IR Distance upto 5 mtrs ,IP 66 weather proof ,
POE. Approved Makes: Allgovision/ Pelco/ Avigilon / Impulse/ Axis.
906 Supply, installation, Testing and Commissioning of Open Platform ONVIF profile S &G Network Nos 1
Video Recorder, Intel based, Full Rack, RAID 0/1/5/10, @ 2M/30FPS, 1*2.5" SATA + 8 * 3.5"
SATA, Throughput: 640 Mbps.1 X HDMI , 1X VGA ,, 1 X mic in , 1 X line out , USB 3.0 x 2 + USB
2.0 x 3 , 1 X WAN port , 1 X LAN port , pre-installed VMS :Approved Makes :Allgovision/ Pelco/
Avigilon / Impulse/ Axis.
907 Supply, installation, testing and commissioning of UL Listed , ONVIF Compliant 1/2.8" IR PTZ Nos 3
Speed Dome Camera max resolution 3 MP , 0.05 @ F1.6 (Color), 0 (B/W) @ F1.6, Quad
Streams, IR Distance 150m, Edge Analytics, 120DB Wide Dynamic Range, H264 Compression,
IP66 Motorized Lens 4.3-129mm 30x Optical zoom Audio in/out 1/1, Micro SD slot, IP66 etc.
Approved Makes :Allgovision/Pelco/Avigilon / Impulse/Axis.
908 Supply, Installation, Testing & Commissioning of Core Switch with switching capacity of 1.4Tbps, Nos 1
forwarding performance of 1Bpps with 32x 1/10G SFP+ ports plus 4x 40G QSFP+ ports from
day 1, dual hot swappable internal power supply, 60K IPv6 routes and 48K IPv6 multicast routes.
Should support advance layer 3 (RIPng, OSPF, BGP and MPLS) with 1 year support. Stack
Module/40 Gig Optics and all other Cables should be included in Day 1. Approved Make : Cisco/
Impulse / Juniper / Extreme/ Arista

[54/80]
Page - 55
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


909 Supply, Installation, Testing & Commissioning of 24 Port POE+ Access Switches with switching Nos 5
capacity of 128 Gbps, forwarding performance 95 Mpps, having 24 x 10/100/1000BASE-T PoE-
plus(RJ45) with minimum PoE budget of 370W and 4x 10G SFP+ uplink ports . Should support
min 2GB internal DRAM, 2GB internal Flash memory,32K MAC address, 1K IPv6 Multicast
Routes, Should have static Routes from day 1.One year support. Approved Make : Cisco/
Impulse / Juniper / Extreme/ Arista
910 Supply, Installation, Testing & Commissioning of 4TB HD Approved Makes: WD, Seagate / Nos 5
Toshiba.
911 Supply, Installation, Testing and Commissioning of Full HD 65" LED Professional Display Panel. Nos. 5
Approved Makes: Panasonic, Sony, Samsung.
912 Supply, Installation, Testing and Commissioning of Workstation PC: Intel(R) Core(TM) i7-3770 Nos. 1
Processor (8M Cache, up to 3.90 GHz); Memory: 4GB, NON-ECC, 1600MHZ; RAM: 4GB
(1x4GB) Non-ECC DDR3 1600MHz SDRAM Memory; Keyboard: 12 function keys; Chassis:
Tower/Workstation; DVD: 8X Slimline DVD+/-RW, Data Only; 20" TFT Monitor; Dual Graphics
Card; Network interface card: Integrated Intel(R) 82579LM Gigabit1 Ethernet LAN 10/100/1000;
Hard disk: 250GB, 7200 RPM 3.5" SATA 6Gb/s Hard Drive; Operating system: Windows 7
Professional 64 Bit. Approved Makes: HP, Dell, IBM.
913 SH: IX: UPS SYSTEM Each 3
Supply, Installation, Testing & Commissioning of 80 KVA UPS in paralleling mode at 0.99 input
power factor with SNMP card, compatible for BMS connectivity on backnet/MODBUS, Isolation
transformer as per specification given in the document with following broad features. THD(i) shall
be less than 3% in the entire loading range.
UPS shall carry design output at 40 deg.
Shall have soft start and hold of for incoming supply.
Invertor capability to supply 150% load for 5 sec.
Three Phase Input and Three Phase Output. (Input - 340V - 470V, Three Phase, 4 wire. / Output -
400-415 Volt, Three Phase, 4 Wire.)
Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt
cells.
Battery shall be external type with rack and suitable for 30 minute backup on 100% load.
UPS shall be compatible for 4 nos unit in parallel operation. (Synchronize). Parallel operation kit
shall be supplied with UPS.
Suitable size of cable from UPS to battery bank.
UPS described as above
914 Supply, installation, testing & commissioning of 20 KVA UPS at 0.99 input power factor with Each 1
SNMP card, compatible for BMS connectivity on backnet/MODBUS, inbuilt isolation transformer
as per specification given in the document with following broad features.
THD(i) shall be less than 3% in the entire loading range.
UPS shall carry design output at 40 deg.
Shall have soft start and hold of for incoming supply.
Invertor capability to supply 150% load for 5 sec.
Three Phase Input and Three Phase Output. ( Input - 340V - 470V, Three Phase, 4 wire. / Output
- 400-415 Volt, Three Phase, 4 Wire.)
Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt
cells.
Battery shall be external type with rack and suitable for 90 minute backup on 100% load.
Suitable size of cable from UPS to battery bank.
UPS described as above
915 Supply installation , testing & Commissioning of following rating of invertor with battery and Each 1
trolley as complete as required. Invertor shall be suitable for 90 minute backup on full load as
per specification.
1000 VA, 220 Volt

[55/80]
Page - 56
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


916 X: LIFT SYSTEM- Set 6
PASSENGER LIFT -
Supplying, Installation, Testing & Commissioning of 13 Passenger (884 Kg) Lifts (Gearless),
MRL having contract speed of 1.5 MPS serving different floors in the lift shaft as per detailed
specifications enclosed and as under:-
Speed --> 1.5 MPS
Floors --> B+G+3+ ATTIC FLOOR
Travel --> 21.5 Mtrs Approx.
Stops & opening - --> 6/900 mm WideX 2400mm High
Controller: A.C. variable voltage & variable frequency drive.
Automatic rescue device complete with dry maintenance free batteries as required.
Operation: Microprocessor based single automatic push button/duplex selective collective with /
without attendant.
Power-415 V, 3 phase, 50 Hz, 4 wires system
Type of doors
(i) Car Power operated, Two Speed Stainless Steel hail line finish. (SS 304 Grade)
(ii) Landing doors : Stainless Steel hail line finish. (SS 304 Grade)
Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides
adjacent to control panel in the lift car.
The Lift shall be provided with Brail button System.
Ceiling as per manufacturer's standards with Fan & LED Lights.
On each Landing outside the lift, a steel plate with illumination sign shall be provided with written
on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided.
Interlocking provision with Fire detection system shall be provided.
Voice announcement system in the car to announce the position of the elevator in the hoistway
as the car passes or stops at a floor served by the elevator.
IP based CCTV interfaced to be provided.
BMS interface for lift position & 3 way Intercom system.
2 Hour Fire rated door. Manufacturer shall be submit the certificate along with supply of material
from NABL approved Lab.
Lift described as above
917 XI: SUBSTATION WORK- Set 2
750 KVA RADIATOR COOLED D.G. SET
Supplying, including installation. Testing and commissioning of water cooled jackson Diesel
Generator set coupled to suitable alternator of 415 V, AC, 3-Phase 0.8 p.f. mounted on a 1) M.S.
fabricated base frame., 2) M.S. fuel tank of required capacity., 3) Residual Silencer., 4)
AMF/Standard Control Panel. 5) Suitable batteries with lead., 6) First fill of Lube oil., 7) Acoustic
Enclosure complete with all accessories as specified and directed by the department conforming
to IS comprising the following Technical Specification.
GENERATOR SET SPECIFICATIONS 750/600
No. of Phases- 3 Phase
POWER FACTOR-0.8 LAG
JACKSON ENGINE SPECIFICATIONS
1. Make- Cummins
2. Model- KTA-50-G3 with PCC-3.3
3. No. of Cylinders-16
4.Aspirations- TURBO CHARGED after COOLED
5.Cooling- Water Cooled
6.Governor-Electronic
7. Battery Capacity Rating-4X12 Volt
8.FUEL CONSUMPTION LTR?HR @ 75% LOAD 190.8
ALTERNATOR SPECIFICATIONS
1. Make- STAMFORD
2. Voltage Regulation : +/- 1.0%
3. Insulation : Class-H
4. Standard Enclosure : IP 23
5. No. of Phases-3
D.G. Set described as above

[56/80]
Page - 57
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


918 500 KVA RADIATOR COOLED D.G. SET Each 1
Supplying, including installation. Testing and commissioning of water cooled jackson Diesel
Generator set coupled to suitable alternator of 415 V, AC, 3-Phase 0.8 p.f. mounted on a 1) M.S.
fabricated base frame., 2) M.S. fuel tank of required capacity., 3) Residual Silencer., 4)
AMF/Standard Control Panel. 5) Suitable batteries with lead. 6) First fill of Lube oil. 7) Acoustic
Enclosure complete with all accessories as specified and directed by the department conforming
to IS comprising the following Technical Specification.
GENERATOR SET SPECIFICATIONS 500/400
No. of Phases- 3 Phase
POWER FACTOR-0.8 LAG
JACKSON ENGINE SPECIFICATIONS
1. Make- Cummins
2. Model- VTA-28-G5-1 with PCC-3.3
3. No. of Cylinders-12
4.Aspirations- TURBO CHARGED after COOLED
5.Cooling- Water Cooled
6.Governor-Electronic
7. Battery Capacity Rating-2X12 Volt
8.FUEL CONSUMPTION LTR?HR @ 75% LOAD 98.6
ALTERNATOR SPECIFICATIONS
1. Make- CGT (STAMFOR)
2. Voltage Regulation : +/- 1.0%
3. Insulation : Class-H
4. Standard Enclosure : IP 23
5. No. of Phases-3
D.G. Set described as above
919 EXHAUST PIPING Meter 90.00
Supply, Installation, Testing and Commissioning of following sizes MS exhaust piping heavy duty
conforming to IS:3589 complete with all accessories such as bends, flanges, stainless steel
flexible bellows etc. as required.
300 mm dia MS pipe. (5.0 mm thick)
920 250 mm dia MS pipe. (5.0 mm thick) Meter 45.00
921 Providing & Fixing of Insulation and cladding for exhaust piping using 75 mm thick rockool of Sq.M 325.00
density 150 Kg/ M3 & 24 SWG Aluminium Sheet.
922 Fabrication, supply & erection of MS structure for supporting of DG emission, exhaust piping with Kg. 12000.00
RCC foundation etc. complete in all respect.
923 DG Synchronizing Cum Changeover Panel (2x750 KVA + 1X500 KVA)- Set 1
Supply, Erection, Testing & Commissioning of Main DG Control panel with D.G. Synchronizing
relay & Micro PLC, this will be floor mounted, free standing, compartmentalized, indoor duty,
dust proof, vermin proof, front operated, electrical panel fabricated, painted and manufactured
exactly as per specifications laid in this document and will be complete with the main and
auxiliary bus bars, interconnection, earth terminals, earth bus and will be powdered coated
finished. All the busbar joint shall be protected by clip on type sleeve. The DG control panel
shall use all draw out 3 position withdrawn type breakers suitable for 415 V AC, 3 phase, 50 Hz,
4 wire supply system and will have fault level of 50 KA or as required as per consultant
approval. The panel will be made as per detailed specifications and drawings forming part of
this document. (Under no case temperature of LT Panel shall be more at any point of the panel,
otherwise necessary exhaust fan shall be have to provided) Bus bar calculations considering
temperature derating, enclosure derating, sleeving derating must be done and submitted for
checking.

Each incoming / outgoing breaker shall have microprocessor release with adjustable over
current, short circuit & earth fault protection with instantaneous as mentioned in specification.
The Panel will be made as per detailed specifications & drawings forming part of this document.

All the MCCB up to 250 Amp shall have thermal release with adjustable overload, short circuit &
earth fault protection and above shall have microprocessor release with adjustable overload,
short circuit & earthfault protection. The panel shall be manufactured as per BOQ, tech
specification and drawing.
INSTRUMENTS
3 Nos. 0 to 500 Volt digital voltmeter with builyin selector switch & Protective SP MCB (96mm
square) (one for each Incoming Breaker).
2 No. 0 to 1250 Amp digital ammeter (96mm square) with CT's & ASS (one for each 750 KVA
D.G. Set Incoming Breaker).
1 No. 0 to 800 Amp digital ammeter (96mm square) with CT's &ASS (one for each 500 KVA D.G.
Set Incoming Breaker).
3 Sets of phase indicating lights (RYB) with protection SP MCB's (one set for each incoming
924 INCOMMING / OUTGOING / BUSCOUPLER AIR CIRCUIT BREAKER: Each 1
Supplying with fitting and fixing panel mounting open execution 4 pole Air Circuit Breaker type
(MDO/EDO) with guide frame and 4 standard auxillary contacts in the existing cubical panel
board of the following capacity complete with making necessary connection as specified and
directed by the Dept. (ABB Emax/L & T U Power/ Siemens 3 WL/ Schneider Master pact NW)
6A trip system.
800A Breaking capacity @ Ics=50 KA (EDO)

925 1250A Breaking capacity @ Ics=50 KA (EDO) Each 2


926 1600A Breaking capacity @ Ics=50 KA (MDO) Each 2

[57/80]
Page - 58
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


927 MAIN L.T. PANEL Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, Installation, Testing &
commissioning of Main LT Panel. The panel will be totally enclosed type with, free standing, floor
mounted, indoor duty, dust & vermin proof, compartmentlized, front operated, electrical panel
fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and
will be complete with the main and auxiliary bus bars, ammeter, ammeter selector switch,
voltmeter, voltmeter selector switch, indication lamps, CT's, protection MCB, interconnection
wiring, earth bus and will be powder coated finish with 70 micron thickness. All the busbar joint
shall be protected by clip on type sleeve. The Main LT Panel shall use all draw out type breakers
suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall have
changeover facility & interlocking through PLC to achieve electrical interlocking, buscoupler
switching, auto operation of incommer and bus coupler etc and having following incoming and
outgoing Air Circuit Breakers, MCCB as per the drawing and specification. Fault level shall be 50
KA.
Each incoming / outgoing breaker shall have microprocessor release with adjustable over
current, short circuit & earth fault protection with instantaneous as mentioned in specification.
The Panel will be made as per detailed specifications & drawings forming part of this document.

(Each Incoming / Outgoing MCCB shall have microprocessor release and variable current setting
from front, adjustable overcurrent, short circuit & earth fault protection, front extended lockable
handle, pad lockable in off position, shrouding on incomer side, termination shall be suitable for
aluminium bus bars / cables and as per specification.)

INSTRUMENTS
4 Nos. 0 to 500 Volt digital voltmeter with Voltmeter Selector Switch & Protective SP MCB
(96mm square) (one for each Incoming Breaker).
4 No. 0 to 1600 Amp digital ammeter (96mm square) with CT's.
4 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).
4 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).
4 Sets trip circuit healthy indicating lamp (one set for each incoming breaker).
4 Sets auto trip indicating lamp (one set for each incoming breaker).
928 INCOMMING / BUSCOUPLER AIR CIRCUIT BREAKER: Each 5
Supplying with fitting and fixing panel mounting open execution 4 pole Air Circuit Breaker type
(MDO/EDO) with guide frame and 4 standard auxillary contacts in the existing cubical panel
board of the following capacity complete with making necessary connection as specified and
directed by the Dept. (ABB Emax/L & T U Power/ Siemens 3 WL/ Schneider Master pact NW)
6A trip system.
1000A Breaking capacity @ Ics=50 KA (EDO)
929 1600A Breaking capacity @ Ics=50 KA (MDO) Each 5
930 OUTGOING MCCB: Each 6
4P MCCB with Microprocessor release (Adj Over Load, Short Ckt & neutral setting incl earth
protection)
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, neutral
adjustable with earth fault protection without enclosure of the following capacity complete with
making necessary connection as approved, specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
63A

931 50KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make) Each 4
100A
932 160A Each 3
933 250A Each 4
934 400A Each 2
935 630A Each 5
936 EXTERNAL LIGHTING PANEL (OUTDOOR TYPE)- Set 1
Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing &
commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin
proof Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet
complete with following equipments, including digital ammeter with inbuilt ammeter selector
switch, digital voltmeter with inbuilt voltmeter selector switch, indicating lamps, CT's, internal
wiring with suitable size wires / cable, interconnection, painting complete as per specification &
drawing.
INCOMING
1 No. 0 to 500 Volt digital voltmeter with inbuilt selector switch.
1 No. 100 Amp digital ammeter with inbuilt selector switch and CT's.
1 Set of phase indicating lamps with Single Pole MCB.
1 Set of ON / OFF indicating lamps with Single Pole MCB.
1 Set 24 Hrs TSQ Timer
1 Set 100 Amp, 4P Contactor & A/M switch and Push Button.
BUS BARS
100 Amp TPN aluminium busbar.
Panel described as above. (Incoming / Outgoing MCCB / MCB shall be paid separately. However
the fabrication cost for Incoming / Outgoing MCCB / MCB shall be included in above.)

[58/80]
Page - 59
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


937 INCOMMING MCCB: Each 1
4P MCCB with Microprocessor release (Adj Over Load, Short Ckt & neutral setting incl earth
protection)
Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with
microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, neutral
adjustable with earth fault protection without enclosure of the following capacity complete with
making necessary connection as approved, specified and directed by the dept.
36KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make)
100A

938 OUTGOING MCB: Each 17


Supplying with fitting and fixing DP 10KA 240/415V 50Hz MCB of the following capacity complete
with making necessary connection as approved, specified and directed by the dept. (ABB,
Schneider MG, legrand, Hager, Crabtree xpro make)
C Series
6 to 32A

939 63A Each 5


940 11KV, H.T. METERING PANEL- (INDOOR TYPE) Set 1
Supply, erection, testing and commissioning of Metering cubicle with 11 KV PTs 11 KV/110V,
11 KV CTs 200/5A & 60/5 with trivector meter indoor type as per local Electricity board, getting
approval and calibration as required by the Department. complete etc.
941 11KV, SINGLE BREAKER PANEL- (INDOOR TYPE) Set 1

Supply, Receiving, Unloading, Shifting, Installation Testing & Commissioning of 11 KV VCB


Single Breaker Panel Board as Incoming / Outgoing shall be metal clad floor mounting complete
as per specification and as described.
630 A VCB Breaker of (350 MVA) 18.4 KA ruputuring capacity at 11 KV rated, totally enclosed,
air insulated metal clad housing, floor mounting, horizontal isolation, vermin proof, fully
interlocked horizontal drawout type having isolation features and control devices complete with
the following:
Manually and motor operated, spring charged (release closing mechanism) trip free type, triple
pole truck mounted draw out, VCB, incorporating mechanical as well as electrical ON/OFF
indication. Spring charge/discharge mechanical indication "OFF" push buttons for emergency
trip (shrouded) test/service position limit switches with 6 NO/6NC breaker auxiliary contacts in
service position, 24 Volts DC shunt trip coil and strip heater to prevent moisture absorption.

INCOMMING / OUTGOING PANEL - 1 NO. (Incoming Panel shall have following)-


1 No 630 A VCB Breaker of (350 MVA) 18.4 KA ruputuring capacity at 11 KV rated, totally
enclosed, air insulated metal clad housing, floor mounting, horizontal isolation, vermin proof, fully
interlocked horizontal drawout type having isolation features and control devices complete with
the following:
3 No. Single Phase double core current transformer 120/5-5 Amp epoxy cast resin insulated
class of insulation E.
Core 1-15VA burden class 1.0 for metering.
Core 2-15VA burden class 5P10 for protection.
P.T's of 11KV/1.732, 110V/1.732, 100VA with suitable rating H.T. & L.T. fuse conforming to
relevant IS Standards and complete as required.
One no. numerical microprocessor based three phase over current (IDMT element) with earth
fault relay with instantaneous elements.
1 No. Anti Pumping device.
1 No. Circuit breaker control switch for electrical (T/N/C).
1 No. limit switch for test & service position.

[59/80]
Page - 60
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


942 11KV, 3 BREAKER PANEL- (INDOOR TYPE) Set 1
Supply, Receiving, Unloading, Shifting, Installation Testing & Commissioning of 11 KV VCB Four
Breaker Panel Board as 1 Incoming & 2 Outgoing shall be metal clad floor mounting complete as
per specification and as described.
630 A VCB Breaker of (350 MVA) 18.4 KA ruputuring capacity at 11 KV rated, totally enclosed,
air insulated metal clad housing, floor mounting, horizontal isolation, vermin proof, fully
interlocked horizontal drawout type having isolation features and control devices complete with
the following:
Manually and motor operated, spring charged (release closing mechanism) trip free type, triple
pole truck mounted draw out, VCB, incorporating mechanical as well as electrical ON/OFF
indication. Spring charge/discharge mechanical indication "OFF" push buttons for emergency
trip (shrouded) test/service position limit switches with 6 NO/6NC breaker auxiliary contacts in
service position, 24 Volts DC shunt trip coil and strip heater to prevent moisture absorption.
INCOMMING PANEL - 1 NO. (Incoming Panel shall have following)-
1 No 630 A VCB Breaker of (350 MVA) 18.4 KA ruputuring capacity at 11 KV rated, totally
enclosed, air insulated metal clad housing, floor mounting, horizontal isolation, vermin proof, fully
interlocked horizontal drawout type having isolation features and control devices complete with
the following:
3 No. Single Phase double core current transformer 120/5-5 Amp epoxy cast resin insulated
class of insulation E.
Core 1-15VA burden class 1.0 for metering.
Core 2-15VA burden class 5P10 for protection.
P.T's of 11KV/1.732, 110V/1.732, 100VA with suitable rating H.T. & L.T. fuse conforming to
relevant IS Standards and complete as required.
One no. numerical microprocessor based three phase over current (IDMT element) with earth
fault relay with instantaneous elements.
1 No. Anti Pumping device.
1 No. Circuit breaker control switch for electrical (T/N/C).
1 No. limit switch for test & service position.
1 No. Voltmeter (0-12KV) with selector switch. (96mm square).
1 No. Ammeter (0-120Amp) with selector switch. (96mm square).
943 TRANSFORMER Each 2
Design, manufacture, supply, installation, testing and commissioning of 11 KV/415V, 3 phase, 50
Hz delta/star-11 connected, indoor type, transformer 1000 KVA, dry type Cast Resin AN cooled,
complete with all fittings such as winding temperature controller, on Load Tap changing
arrangement on HV side with Tapping for variations of high voltage from (+) 5 % to (-) 15% in
steps of 2.5 % each, bi-directional roller, diagrams & rating plate, Marshalling Box, lifting lugs,
H.T /LV cable termination box etc. complete as per specification. The losses of Transformer shall
be as per latest ECBC-2007.
1000 KVA 11/0.433 KV. Dry transformer with on load tap changer.

944 Supply and laying of following size power / control copper cables, solid copper conductor, HLPE Meter 200.00
Insulated, cores laid up, PVC tape inner sheathed, unarmoured, extruded PVC ST2 sheathed,
650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct /
cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using
crimping tool and making good damaged done as specified and directed by the department.
(Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.)
Core-2, 2 XY
10.00 Sq.mm 2 Core Unarmoured U.G. Cable

945 Armoured 2 XY Meter 350.00


2.5 Sq.mm 6 Core Unarmoured
946 Unarmoured 2 XY Meter 400.00
2.5 Sq.mm 12 Core Unarmoured
947 Supply and laying 11/33 KV HT 3 core stranded compact circular Aluminium Conductor, Meter 140.00
Conductor screen with extruded semi conducting compound, XLPE Insulated, Insulation
Screening with extruded semi conducting compound in combination with copper tape (0.3KA for
1 sec, cores laid up, inner sheath of PVC tape, galvanized flat steel strip armoured and overall
PVC sheathed cable confirming to IS 7098 / (PART-I 1985 with latest amendment cable laid in
air or through existing cable trench/ duct/ cable tray/ HDPE pipe including fitting required size of
lugs at the both end of the cable by using crimping tool and making good damaged done as
specified and directed by deptt. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make
or equivalent.)
240 Sq.mm 3 Core Armoured 11 KV (E) H.T. U.G. Cable
948 SAFETY EQUIPMENT Nos. 1
First aid box as approved by St. John Ambulance Brigade /Indian Red Cross society conforming
to IS : 2217 - 1963.
949 Shock treatment chart duly mounted on a wooden frame with glass on, as required in 2 Nos. 2
languages (Hindi & English).
950 Rubber mat 1000 mm. Wide to withstand 1.1 KV dielectric strength as per latest IS 15652-2006. Meter 60.00

951 Rubber mat 1000 mm. Wide to withstand 11 KV dielectric strength as per latest IS 15652-2006. Meter 25.00

[60/80]
Page - 61
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


952 Supplying installation testing and commissioning of Grid interactive roof top solar photo voltaic KWP 80
power generation system including all the required accessories like Solar PV module, Grid Tie
invertor, arrey junction box, cabling & wiring, earthing, surge protection device, FRLSame
structure for mounting of solar panel. The cell shall be poly crystaline silicon cells of 6 inch each
and module efficiency shall be more than 17%. Solar module shall have linear output warranty
with degradation not exceeding 0.7% FRLSom 2nd Year onwards. Minimum 80% power output
must be assured at end of 25 years. The FRLSont glass of solar module shall be low iron
tempered glass ARC type. Termination box shall be Thermo-plastic, IP 67 or better, UV resistant
with built-in-bypass. The nominal power of a single PV module shall be minimum 325 Wp or
higher. Positive power tolerance modules only to be used. RF identification tag for each solar
module shall be provided inside the module and must be able to withstand environmental
conding following incoming and outgoing Air Circuit Breakers, MCCB as per the drawing and
specification. Fault level shall be 50 KA.
Each incoming / outgoing breaker shall have microproce
953 XII: EXTERNAL LIGHTING WORK- Each 22
Supply and Erection of 6 metre height Hot-Dip galvanized octagonal street light pole with
following arm with top dia 70 mm and bottom dia A/F 130 mm, made of 3 mm thick sheet along
with base plate of size 220mm x 220mm x 12mm, small door opening for junction box mounting
and suitable size foundation bolts with template and all complete as required. (Single Arm).

954 Supply, Installation, Testing & commissioning of Bollard Light 170 mm dia, 780 mm height made Each 20
out of cast aluminium lighting fixture, glass diffuser, stainless steel screw, extruded aluminium
poles, corrossion & UV resistant coation of 1 x 18 watt.
955 Supply, Installation, Testing & commissioning of Bollard Light 120 mm dia, 1000 mm height Each 15
made out of cast aluminium lighting fixture, glass diffuser, stainless steel screw, extruded
aluminium poles, corrossion & UV resistant coation of 1 x 18 watt.
956 Supply, Installation, Testing & Commissioning of LED street light fixture 40 watt, clour cool white Each 22
, integral driver, protection IP 65, CLASS I as complete as required. (Make Philips, Cat No-
BRP409 LED 040 CW HO MR FG S1 PSU GR or equivalent)
957 Supply, Installation, Testing & Commissioning of 1x21W Solar LED Lighting System consists of Each 10
PV Module, battery 12V, 100 Ah, grid charger unit, pole etc as per technical specification.
(Philips Make, Cat No - Philips BRP402 / 21W or equivalent).
958 Supply, Installation, Testing & commissioning of LED spike light. (Make-Philips, Cat No-BGP 310 Each 20
3XLED-HP/WW 220-240V 12 IN or equivalent).
959 SH: XIII: ACCESS CONTROL SYSTEM Nos 2
Supply, Installation, Testing & Commissioning of Motor power supply- 24V, Max. motor current-
12A, Motor power- 350 W, Max. torque- 750 nm, Max. boom length- 6250mm Max opening-
100deg, Max opening- 6 sec, Protection level- IP54, Weight- 50 kg as complete as required.

960 Supply, Installation, Testing, Commissioning of microprocessor based control panel having LED Set 6
indicators and audio buzzer, with 125khz hgh security format 2 door controller suitable for 4
readers including management software. (The controller shall be compatible for hardware
integration with fire alarm panel.)
961 Supply, Installation, Testing, Commissioning of 3"-4" read range proximity reader having LED Nos 12
indicators, with 125khz hgh security format. Power requirements 5-16V DC.
962 Supply of an Emergency Key. Nos 1
963 Supply, Installation, Testing, Commissioning of 600Lbs suitable for Single Leaf Door Nos 12
Electromagnetic Lock with magnetic contacts.
964 Supply, Installation, Testing, Commissioning of proximity card with 125 khz high security format . Nos 100
(HID Make.)
965 Supply, Laying of 0.75X 8 mm Multistand shielded copper tinned cable in an existing surface / Mtr 720.00
recessed conduit as required.
966 Supply, Installation, Testing, Commissioning of Exit Push Button Nos 12
967 SH: XIV: EARTHING Each 28
Supply with installation &commissioning of readymade maintenance free CPRI approved
chemical earthing system with 50 mm dia. 3.00 Meters length corrosion free dual pipe technology
G.I. CHEMRODE ELECTRODE Complete with raslow Grounding Minerals 25 k and Advance
Earth Pit cover including excavation of earth pit and construction brick earth chamber including
plastering both inner & outer surface of brick wall as specified and directed by the deptt.

968 Supply with installation &commissioning of readymade maintenance free CPRI approved Each 38
chemical earthing system with 50 mm dia. 3.00 Meters length corrosion free Single pipe
technology- Copper CHEMRODE ELECTRODE Complete with raslow Grounding Minerals 25 k
and Advance Earth Pit cover including excavation of earth pit and construction of brick earth
chamber including plastering both inner & outer surface of brick wall as specified and directed by
the deptt.
969 Supplying & laying of 6 SWG G.I. earth from EarthEletrode (below G.L.) to electrical switch gears Metre. 3410.00
or electrical machineries including making necessary connection as approved, specified and
directed by the deptt.
970 Supplying & laying of 25X6 mm size G.I. strips drawn on surface from earth electrode to Metre. 3040.00
Electrical switch gears, machineries etc complete with supply of G.I. nuts & bolts, screws etc
including riveting, soldering & making necessary connection as approved, specified and directed
by the deptt.

[61/80]
Page - 62
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


971 Supplying & laying of 50X6 mm size G.I. strips drawn on surface from earth electrode to Metre. 870.00
Electrical switch gears, machineries etc complete with supply of G.I. nuts & bolts, screws etc
including riveting, soldering & making necessary connection as approved, specified and directed
by the deptt.
972 Supplying & laying of 25X5 mm size Copper strips drawn on surface from earth electrode to Metre. 1070.00
Electrical switch gears, machineries etc complete with supply of Brass nuts & bolts, screws etc
including riveting, soldering & making necessary connection as approved, specified and directed
by the deptt.
973 Supplying & laying of 40X6 mm size Copper strips drawn on surface from earth electrode to Metre. 130.00
Electrical switch gears, machineries etc complete with supply of Brass nuts & bolts, screws etc
including riveting, soldering & making necessary connection as approved, specified and directed
by the deptt.
974 SH: XV: LIGHTING AUTOMATION SYSTEM No. 20
SITC of DIN-Rail Mountable 2 Channel DALI Dimmer controls maximum 128 DALI ballasts per
unit and at least 64 ballast per loop capable to control all the connected DALI ballasts individually
regardless of their channel or loop. Has USB, LAN or properiatory connectivity options to
connect with same OEM control processor so that it can be integrated with other systems like
occupancy sensors, AV distribution, etc. configurable and controllable from a software via
LAN/USB. has in-built option to give power to all the 128 ballasts for their processing and
feedback LEDs and control buttons on the front panel for turning the lights on/off. Make :
Crestron/ AMX/ Philips. Preferred system integrator: Interioarch Solutions/Techtron India/ times
Info system
975 SITC of DIN rail mounted data manager having at least 3 segments of connectivity ports for No. 20
Lighting Dimmer, Keypads or Occupancy Sensors capable to manage data-traffic of at least 20
devices. Make : Crestron/ AMX/ Philips. Preferred system integrator: Interioarch
Solutions/Techtron India/ times Info system
976 SITC of DIN-rail, addressable 8- channel lighting control module with dry-contact relay output for No. 40
switching of non-dimmable lighting and fans. supporting SNMP Active Directory authentication,
IIS v.6.0 Web Server, SMTP e-mail client for complete network integration. 8 channels of power
switching to support 220-240 Volt applications having Isolated Class 1 SPST relay switch
circuits. Relay having slave bus port to be powered by the master bus or external power supply
and support bidirectional communication having 10 Amps incandescent, 5 Amps fluorescent, 16
Amps resistive, 0.5 HP @ 240 Volts AC (per channel); Has sensing input for external low-voltage
contact closure as a control override trigger; Minimum Closure Rating: 10mA (per module) at 24
Volts. Make : Crestron/ AMX/ Philips. Preferred system integrator: Interioarch Solutions/Techtron
India/ times Info system
977 SITC of Wall-mounted LCD keypad with lighting, shades, climate, and media control capabilities No. 50
with 16-bit high color and white LED backlights with lighting, shades, climate, and media control
capabilities. Has an Internal temperature sensor. Make : Crestron/ AMX/ Philips. Preferred
system integrator: Interioarch Solutions/Techtron India/ times Info system
978 Programming, downloading, configuration and commissioning of the latest application for IOS No. 11
and Android. Make : Crestron/ AMX/ Philips. Preferred system integrator: Interioarch
Solutions/Techtron India/ times Info system
979 SITC of Centralized Automation Control Processor with SSL controls any devices based one IR, No. 1
RS-232, RS-485, Relay, General Purpose IO and IP having Bacnet license and capabilities for
HVAC control. Has at least 8x IR, 8x GPIO, 8x 30 Volts Relays, 1x RJ-45, 1x USB, 1xSD/SDHC
Card Slot supporting upto 32 GB, 1x RS-232/422/485, 2x RS-232 supporting up to 115.2k
baudrate, Along with in-built web-server for running custom GUI for control and Management
with Program uploading, It should also have one dedicated USB port for easy configuration and
program management from a PC. Centralized Automation Control Processor with SSL controls
any devices based one IR, RS-232, RS-485, Relay, General Purpose IO and IP having Bacnet
license and capabilities for HVAC control. Has at least 8x IR, 8x GPIO, 8x 30 Volts Relays, 1x RJ-
45, 1x USB . Make : Crestron/ AMX/ Philips. Preferred system integrator: Interioarch
Solutions/Techtron India/ times Info system
980 SITCC of Centralized Automation Control Processor with SSL SITC of DIN-RAIL mounting No. 10
having Bacnet license and capabilities for HVAC control and controlling any devices based on
IR, RS-232, RS-485, Relay, Genral Purpose IO and IP . Has at least 4x IR, 8x GPIO, 4x Low
Voltage Relays, 1x RJ-45, 1x USB, 1xSD/SDHC Card Slotsupporting upto 32 GB, 2x RS-
232/422/485 supporting up to 115.2k baudrate, Along with in-built web-server for running custom
GUI for control and Management with Program uploading, It should also have one dedicated
USB port for easy configuration and program management from a PC. provides feature of using
any of the 4x IR ports as 1-way RS-232 port for device control supporting up to 115.2k baudrate
and has at least 512MB RAM and 4 GB In-built storage for programs. It should also support
storage-expansion as USB mass storage devices up to 1 TB with option to communiate with a
centralized server for management and monitoring of the devices connected to it over RS-
232/422/485 and IP . supports eption.
INCOMMING PANEL - 1 NO. (Incoming Panel shall have following)-
1 No 630 A VCB Breaker of (350 MVA) 18.4 KA ruputuring capacity at 11 KV rated, totally
enclosed, air insulated metal clad housing, floor mounting, horizontal isolation, vermin

[62/80]
Page - 63
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


981 Supply, Installation and Testing of Programmable and expandable Control System for controlling No. 1
any devices based one IR, RS-232, RS-485, Relay, General Purpose IO and IP having at least
8x IR, 8x GPIO, 8x 30 Volts Relays, 2x RJ-45(10/100/1000 Mbps), 1x USB, 1xSD/SDHC Card
Slot supporting upto 32 GB, 2x RS-232/422/485, 4x RS-232 supporting up to 115.2k baudrate,
with in-built web-server for running custom GUI for control and Management with Program
uploading, It should also have one dedicated USB port for easy configuration and program
management from a PC within-built provision to expand the control ports by adding same OEM
expansion cards for IR, Relay, GPIO and RS-232/422/485 COM ports. provide feature of using
any of the 8x IR ports as 1-way RS-232 port for device control supporting up to 115.2k
baudratewithat least 1GB RAM and 4 GB In-built storage for programs. It should also support
storage-expansion as USB mass storage devices up to 1 TB. has option to communicate with a
centralized server for managption.
INCOMMING PANEL - 1 NO. (Incoming Panel shall have following)-
1 No 630 A VCB Breaker of (350 MVA) 18.4 KA ruputuring capacity at 11 KV rated, totally
enclosed, air insulated metal clad housing, floor mounting, horizontal isolation, vermin proof, fully
interlocked horizontal drawout type having isolation features and control devic
982 SITC of ethernet switch with IGMP V2/V2 with non-blocking ethernet 1Gbps per port. Make : No. 3
Crestron/ cisco/ Philips. Preferred system integrator: Interioarch Solutions/Techtron India/ times
Info system.
983 SITC of Wall-mount keypads featuring customizable buttons with engraving and enhanced No. 50
multicolor RGB colored LED feedback. has Five configurable button positions arranged in one
column; each position should accommodates a single pushbutton or horizontal rocker button.
Has a Photo sensor with adjustable sensitivity, detects the ambient light level to activate day or
night mode. Has adjustable brightness and RGB color mixing allowing any color or pure white.
Includes color faceplate and gets data and power by same control cable. Each button should be
programmable for any system function and supports tap, double-tap, and press-and-hold button
events. Make : Crestron/ AMX/ Philips. Preferred system integrator: Interioarch
Solutions/Techtron India/ times Info system
984 SITC of Backlit Engravable Pushbutton, Size 1, Black Textured, Includes Custom Engraving. No. 200
Make : Crestron/ AMX/ Philips. Preferred system integrator: Interioarch Solutions/Techtron India/
times Info system
985 SITC of DIN-Rail Mountable power supply to power DIN-RAIL Products. Capable to provide at No. 20
least 60 Watts regulated and limited power at 24 Volts DC not consuming more than 70 W att
at full output having multiple connectivity ports to give power to different devices. Make :
Crestron/ AMX/ Philips. Preferred system integrator: Interioarch Solutions/Techtron India/ times
Info system
986 SH: XVI: External Lighting & Auditorium each 10
MONTUR S LED WW B
Supply of ceiling/wall mounted fixture with melting ice effect ,INCL.GLASS OPAL
INCL.LED CLUSTER 6,3W / CRI>80 / 3000K / 808lm,INCL.LED POWER SUPPLY 350mA-
DC,CRI 80
Colour temp
Warm White (+3000K)
LED Technics
808 lm // 6 W // 128 lm/W ,Class I,IP65
987 Building facade each 21
Supply of ball shaped fixture with linear beam, ADJUSTABLE for building facade,INCL.1 x LED
4,1-8,7W / CRI>80 / 3000K / 420-723lm,INCL.1 x LENS
INCL.1 x CABLE H05 RN-F 2 x 1 mm² 2m,INCL.LED POWER SUPPLY 350-700mA-DC,CRI 80
,Colour temp,Warm White (+3000K)
LED Technics (light source)
723 lm // 8 W // 87 lm/W ,IP65
988 ULTRA X DOWN-UP LED 930 N each 60
Supply of wall mounted up-down fixture ,INCL.2 x LED 7W / CRI>90 / 3000K / 774lm,INCL.2 x
LENS,INCL.LED POWER SUPPLY 350mA-DC,CRI 90 ,Colour temp,Warm White (+3000K)
LED Technics (light source)
1548 lm // 14 W // 116 lm/W ,Class I,IP55

[63/80]
Page - 64
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


989 Tree Uplights each 50
LOGIC R 93011 ANO
Trimless or minimum trim in floor up-lighting system with narrow optics for the column.
Recessed depth
100 mm
Information
INCL.1 x LED WHITE 7,1W / CRI>90 / 3000K / 774lm
INCL.1 x REFLECTOR FL-20°
INCL.1 x CABLE H05 RN-F 2 x 1mm² 0,5m
EXCL.LED POWER SUPPLY 350mA-DC
IEC 60598-2-13 : max.150kg 25N/cm²
ESG 5mm
CRI 90
Colour temp
Warm White (+3000K)
LED Technics (light source)
774 lm // 7 W // 116 lm/W
Nett weight
0.6 Kg
IP67
Make: Delta , Cat No :LOGIC R A 93011 ANO /ERCO/Hoffmeister
990 Landscape lighting each 200
MONTUR S P 65 LED B
Floor mounted cylindrical Bollard with glass top for soft defused lighting.
Specifications :
Information
INCL.GLASS OPAL
INCL.LED CLUSTER 6,3W / CRI>80 / 3000K / 840lm
INCL.LED POWER SUPPLY 350mA-DC
CRI 80
Colour temp
Warm White (+3000K)
LED Technics (light source)
840 lm // 6 W // 133 lm/W
IP55
Make: Delta , Cat No :MONTUR R P 20 LED B/Erco/LEC
991 MONTUR L P 45 LED B each 10
EXTERIOR, Floor Surface mounted
INCL.LED CLUSTER 13,3W / CRI>80 / 3000K / 1250lm
INCL.DIMMABLE LED POWER SUPPLY 500mA-DC
MAINS DIMMING - TRAILING EDGE
CRI 80
Colour temp
Warm White (+3000K)
LED Technics (light source)
1250 lm // 13 W // 94 lm/W
Class II
IP54
992 Open Lawns each 15
STIEVIE 75 N
Supply of floor mounted suitable for soft soil installation 750mm
INCL.1 x LED TUBE 6W / CRI>80 / 3000K / 513lm
INCL.PIN
INCL.1 x CABLE H05 RN-F 2 x 1 mm² 2m
EXCL.LED POWER SUPPLY 24V-DC
CRI 80
Colour temp
Warm White (+3000K)
LED Technics (light source)
513 lm // 5 W // 90 lm/W \
IP65
993 STIEVIE 130 N each 10
Supply of floor mounted suitable for soft soil installation 1302mm
INCL.1 x LED TUBE 9W / CRI>80 / 3000K / 873lm
INCL.PIN
INCL.1 x CABLE H05 RN-F 2 x 1 mm² 2m
EXCL.LED POWER SUPPLY 24V-DC
CRI 80
Colour temp
Warm White (+3000K)
LED Technics (light source)
873 lm // 9 W // 90 lm/W \
IP65

[64/80]
Page - 65
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


994 Auditorium Light each 148
GRAND REO XL OK 930 S1 W-B
Supply of ceiling recessed downlight of 156mm cutout and 165mm depth including 14 deg and
24 deg reflector
ADJUSTABLE 0-30° / 350° specifically for auditorium applications,INCL.1 x LED 16,7-51,1W /
CRI>90 / 3000K / 2096-5349lm,EXCL.1 x REFLECTOR,LED POWER SUPPLY 500-1400mA-
D,CRI 90
Colour temp,Warm White (+3000K) ,LED Technics (light source),5349 lm // 51 W // 107 lm/W

995 REFLECTOR 111/H67 - 28° each 148


996 REFLECTOR 111/H67 - 40° each 148
997 SH: XVII: MISCELLANEOUS ITEMS Per Set 5.00
BAGGAGE SCANNERS
Baggage scanner small: computer based multi energy X-Ray Baggage Inspection System
mounted on castor wheels capable of passing through bags of dimensions 540 mm (W) X 350
mm (H), belt height 750 mm to 850 mm, 22”/24 LCD Monitor, Input / Output rollers with frames

998 DOOR FRAME METEL DETECTOR Per Set 10.00


20 zone or above Door frame Metal detector nominal Size: 760 mm (W) x 2050mm (H) x 700
mm (D) loaded with necessary software
999 BOOM BARRIER Per Set 7.00
Boom Barrier for car: Electromechanical parking barrier with all accessories upto 6 meter length

1000 CAR PARKING SYSTEMS Per Car 200.00


ensor based car parking system with controller, display etc. as required. (Cost based on
minimum car quantity of 250 cars)
1001 IP BASED EPABX SYSTEM per sqm. 13419.88
Supplying, installation, testing and commissioning of IP based EPABX System comprising of of
Core switches & L2 switches with 10 G, 10 Giga SFP modules, Industry Standard Appliance covered
Server, Cloudbased, enterprise-grade UC Solution, MID/ENTRY Level IP/SIP Phone with, Dual 1 area
Gig Ports, Racks, CAT 6A cable, Patch Panels, OFC etc.
NOTE: It will be economical to use common infrastructure of switches, OFC, CAT 6A cable for
both voice and Networking
1002 LAN SYSTEM per sqm. 13419.88
Supplying, installation, testing and commissioning of LAN System comprising of Core switches & of
L2 switches with 10 G, 10 Giga SFP modules, WIFI Access points, WIFI controller, Network covered
Management Software, Racks, CAT 6A cable, Patch Panels, OFC etc. area
1003 IBMS: INTEGRATED BUILDING MANAGEMENT SYSTEM sqm 10000.00
Supplying, installation, testing and commissioning of Integrated Building Management System for
Digital/electronic display and monitoring of all E&M systems like substation, DG sets, Ups, Solar
power, Lifts, AC Plants, Ventilation systems, Fire protection systems, Pumps etc. to include
cabling, monitors, recording, display system, hardware, software support(upto 10,000 sq.m)

1004 MOTORIZED STEEL GATES each 5


1005 SUB HEAD 'D' - HVAC Machinery NO 3
Air Cooled Hi Wall Unit
Supply, Installation, testing and commissioning of Air-cooled Hi-wall split air conditioners BEE
three star rated minimum, each comprising an outdoor unit(s) consisting of rotary / scroll
compressor, air cooled copper condenser, condenser fan along with cooling thermostats etc.
with outer casing and indoor fan coil unit consisting of centrifugal fans, fan motor, DX copper
cooling coil, outer casing, filter, control and power panel with wireless remote controller of latest
generation etc. The refrigerant used shall be ecofriendly. Unit shall be supplied fully refrigerant
charged plus additional top up of refrigerant to suit piping length and electronic stabliser of
required capacity for voltage range of 100 V~300V. Unit shall be suitable for working under long
length of refrigerant piping up to 20 meter minium. The condensing unit shall be painted with two
coats of clear transparent polymer coating for protection against corrosion from ambient air.
2.0 TR Capacity

1006 1.5 TR Capacity NO 3

[65/80]
Page - 66
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1007 Variable Refrigerant Volume / Flow Air-conditioning System NO 2
Supply, Installation, testing and commissioning of Variable Refrigerant Flow modular type air-
conditioning system with stepless modulation complete with indoor and outdoor units,
individual remote controller and centralized controller, interconnected refrigerant piping, full
charge of refrigerant gas including additional top up to suit piping length and oil, control cabling
etc. as per detail given in specifications and having following items. The prices to be given in
Indian rupees including all taxes and duties and delivered at site. Refrigerant to be used shall
be - R 410 A only.
Air Cooled VRV / VRF Outdoor Unit
Supply, Installation, testing and commissioning of modular type outdoor units equipped with
highly efficient scroll compressors (01 No. Compressor upto 12 HP Module & 02 Nos.
Compressors for more than 12 HP Module) with all inverter type compressors with minimum
COP / Efficiency as per ECBC 2017 for single module at 100% load, special heat exchanger,
low noise condenser fan, auto check function for connection error, Y joints, auto address
setting and capacity as mentioned below. All interconnecting piping, joints and U bends within
the condensing unit shall be painted with two coats of clear transparent polymer coating for
protection against corrosion from ambient air.
10 HP Cool / Heat Pump Unit

1008 16 HP Cool / Heat Pump Unit NO 2


1009 22 HP (10 HP + 12 HP) Cool / Heat Pump Unit NO 2
1010 26 HP (8 HP + 18 HP) Cool / Heat Pump Unit NO 1
1011 28 HP (12 HP + 16 HP) Cool / Heat Pump Unit NO 2
1012 30 HP (12 HP + 18 HP) Cool / Heat Pump Unit NO 1
1013 32 HP (12 HP + 20 HP) Cool / Heat Pump Unit NO 2
1014 38 HP (18 HP + 20 HP) Cool / Heat Pump Unit NO 7
1015 40 HP (20 HP + 20 HP) Cool / Heat Pump Unit NO 2
1016 42 HP (12 HP + 12 HP + 18HP) Cool / Heat Pump Unit NO 2
1017 Indoor Units NO 18
Supply, Installation, testing and commissioning of Indoor units equipped with pre-filter,
fan section with suitable static fan to distribute the air as per approved shop drawings,
multispeed motor, coil section with DX coil, outer cabinet / cassette panel, drain pan,
insulation, pipe connections etc. of various capacities as per specifications and drawings.
Hi Wall Unit
2.0 TR, 671 CFM or nearest as per manufacturer's standard

1018 Cassette Unit (700x700 mm) NO 5


0.8 TR, 318 CFM or nearest as per manufacturer's standard
1019 1.0 TR, 335 CFM or nearest as per manufacturer's standard NO 9
1020 1.3 TR, 388 CFM or nearest as per manufacturer's standard NO 30
1021 1.6 TR, 493 CFM or nearest as per manufacturer's standard NO 37
1022 Cassette Unit (900x900 mm) NO 6
1.3 TR, 530 CFM or nearest as per manufacturer's standard
1023 1.6 TR, 565 CFM or nearest as per manufacturer's standard NO 13
1024 2.0 TR, 671 CFM or nearest as per manufacturer's standard NO 21
1025 2.5 TR, 742 CFM or nearest as per manufacturer's standard NO 43
1026 3.2 TR, 1130 CFM or nearest as per manufacturer's standard NO 11
1027 Ductable Unit NO 4
5.5 TR, 2047 CFM or nearest as per manufacturer's standard
1028 8.0 TR, 2825 CFM or nearest as per manufacturer's standard NO 2
1029 Y-joints For Indoor Unit SET 184
Supply, Installation, Testing & Commissioning of Y-joints (2 Nos. in each Set) for Indoor Unit of
sizes as required to suit various capacity of Indoor Unit as specified above.
1030 Self Diagnostic Type Remote Controllers SET 205
Supply, Installation, Testing & Commissioning of Corded Wall Mounted Type Self Diagnostic
Type Digital Touch Screen Programmable Remote Controllers of latest generation for setting
required temperature for various Indoor Unit.
1031 Main Intelligent Programmable Central Controller SET 5
Supply, Installation, Testing & Commissioning of Main Intelligent Programmable Central
Controller of digital touch screen type of latest generation suitable for suitable for above Indoor
and Outdoor Unit to Operate, Monitor, Programme, On / Off, Temperature Setting etc.
1032 Expansion Kit, Communication PCB & Thermostat SET 4
Supply, Installation, Testing & Commissioning of Electronic Type Expansion Kit, Communication
PCB with Sensors, Corded Self Diagnostic Type Digital Thermostat, Controller, control box with
internal wiring, AHU kit for each DX Type Units and other related accessories etc with
connectivity to automation system for A/M status, RUN status & Remote start / stop command
(Bacnet/IP). It should be complete as per manufacturing standards & as per directions of
Engineer-in-charge.
For 11000 CFM F/M AHU with 1x38.0 HP VRV ODU
1033 For 9000 CFM F/M AHU with 1x32.0 HP VRV ODU SET 2
1034 For 8000 CFM F/M AHU with 1x28.0 HP VRV ODU SET 2

[66/80]
Page - 67
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1035 VRV / VRF DX Floor Mounted Double Skinned AHU SET 4
Supply, installation, testing and commissioning of factory fabricated Double Skinned DX Air-
handling unit (FLOOR MOUNTED TYPE) fabricated out of extruded aluminium section with
0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised
steel sheet inside with belt driven centrifugal fans (forward / backward), blower section and
blower motor TEFC type IE-3 grade suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC
supply, 6 Row cooling coil made of Aluminium finned (12-13 FINS/INCH) Copper tube with coil
section of copper header and MS adaptor, pre-filter section with non woven synthetic media of 50
mm thick in extruded aluminium frame of 10 micron particle size with an efficiency of 90% of
suitable MERV 8 rating, filters in aluminium frame. Drain pan (made out of 22G stainless steel
(SS Grade 304) sheet insulated with 19 mm think closed cell insulation (Nitrile / XLPE) complete
with motor, belt drive, fire retardent double layer canvass connection etc. without face and
bypass dampers.
Centrifugal Fan (with min. efficiency as per NBC 2016) with blower motor, drive and flexible duct
connection. The AHU panels shall be insulated with 23 mm thick (For Indoor Applications) & 43
mm thick with thermal break orofile (For Outdoor Application) of 36 Kg/m³ density PU foam. The
motor & blower assembly shall be mounted on Aluminium extruded section only. The complete
AHU shall conform to tender speciation. AHU shall be supplied with commissioning filter which
shall be replaced with actual pre filters. The face velocity across coil & filters shall be limited to
152 MPM maxm. The capacity of Air-handlers shall be as follows. Motor Kw is indicative only,
actual as per requirement to be included during installation. DB level to comply as per relevant
standard / codes. Necessary foundation along with anti vibration pads for AHU will be in the
scope of the contractor.
11,000 CFM, 60 mm St. Pr., 6 Row DX CC, 1 x 560 Dia Fan with 5.60 Kw Fan Motor IE-3 Rating,
Pre Filter, F/M Type, To be connected with 1x38 HP VRV / VRF ODU

1036 9,000 CFM, 60 mm St. Pr., 6 Row DX CC, 1 x 500 Dia Fan with 5.60 Kw Fan Motor IE-3 Rating, SET 2
Pre Filter, F/M Type, To be connected with 1x32 HP VRV / VRF ODU
1037 8,000 CFM, 70 mm St. Pr., 8 Row DX CC, 1 x 500 Dia Fan with 5.60 Kw Fan Motor IE-3 Rating, SET 2
Pre Filter, F/M Type, To be connected with 1x28 HP VRV / VRF ODU, Ducted Return
1038 Acoustically Insulated Box Type Inline Fans NO. 5
Supply, installation, testing and commissioning of single phase box type Inline fans with motor,
fire retardent double layer canvass connection etc complete in all respect & of following
capacities. The casing of inline fans shall be acoustically lined & shall be selected for lower noise
level. Fan motor shall have inbuilt speed controller.
100 CFM (8mm static pressure, single phase)
1039 300 CFM (8mm static pressure, single phase) NO. 2
1040 500 CFM (10mm static pressure, single phase) NO. 13
1041 750 CFM (10mm static pressure, single phase) NO. 10
1042 1000 CFM (15mm static pressure, single phase) NO. 5
1043 1500 CFM (20mm static pressure, single phase) NO. 3
1044 2500 CFM (20mm static pressure, single phase) NO. 2
1045 Plastic Propeller Fans NO 6
Supply, installation, testing and commissioning of propeller exhaust fans of various capacities
as given below suitable for 240 volts, 50 Hz, single phase AC supply complete with gravity
louvers & speed regulator etc.
Up to 125 CFM, 6 Inch Dia, 3 mm St. Pr.
1046 Above 125 CFM and Up to 250 CFM, 8 Inch Dia, 3 mm St. Pr. NO 2
1047 Above 250 CFM and Up to 500 CFM, 10 Inch Dia, 3 mm St. Pr. NO 2
1048 GI Propeller Fans NO 2
Supply, installation, testing and commissioning of GI propeller exhaust fans of various
capacities as given below suitable for 240 volts, 50 Hz, 900 RPM single phase AC supply
complete with gravity louvers & speed regulator etc.
750 CFM, 300 mm Dia, 3 mm St. Pr.
1049 1000 CFM, 380 mm Dia, 3 mm St. Pr. NO 2
1050 1500 CFM, 450 mm Dia, 3 mm St. Pr. NO 8

[67/80]
Page - 68
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1051 Axial Flow Fan NO 4
Supply, installation, testing and commissioning of ceiling mounted Tube Axial flow fans with
adjustable pitch blade, MS / GI long casing (2mm thick up to 800 mm dia fan, 3 mm thick from
900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy impeller complete
with TEFC IE3 Sq. Cage Induction motor suitable for 415 volts ± 10%, 50Hz ± 3 %, three
phase A.C supply with support, mountings, vibration isolators, fire retardant flexible canvass
connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) etc.
& of following capacity. The complete fan along with motor shall be suitable for 250 °C
temperature rated for 2 hours. Fan outlet velocity shall be limited to maximum of 16 m/sec. Fan &
Fan motor KW given below are for guideline & actual Dia / KW shall be as per manufacturer
selection based on maximum 16 m/sec outlet velocity.
Axial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA 210
and AMCA 300. Complete certified model appearing on AMCA web site shall be accepted.
Complete Fan shall be tested and approved by UL in accordance with "Power Ventilators for
Smoke Control Systems" for 250 °C for 2 hours. Manufacturer shall furnish AMCA Test
Certificate for air & sound performance along with UL fire test certificate (Latest) for each fan
sourced from that particular factory. The noise level of axial fan shall be less than 80 dBa at a
distance of 3.0 mt from the fan.
Parking Ventilation, Exhaust
30000 CFM (25mm static pressure, 1000 RPM, 9.33 Kw Fan Motor, 1200 MM Fan Dia, Exhaust
Air Application)

1052 Pump Room / STP Room Ventilation, Supply & Exhaust NO 2


8000 CFM (25mm static pressure, 1000 RPM, 2.24 Kw Fan Motor, 900 MM Fan Dia, Exhaust Air
Application)
1053 7000 CFM (25mm static pressure, 1000 RPM, 2.24 Kw Fan Motor, 900 MM Fan Dia, Supply Air NO 2
Application)
1054 Pressurisation - Lift Well, Staircase, Lobby etc, Supply NO 1
35000 CFM (25mm static pressure, 1000 / 1500 RPM, 9.33 Kw Fan Motor, 1200 MM Fan Dia,
Supply Air Application)
1055 20000 CFM (25mm static pressure, 1000 / 1500 RPM, 5.60 Kw Fan Motor, 1000 MM Fan Dia, NO 2
Supply Air Application)
1056 15000 CFM (25mm static pressure, 1000 / 1500 RPM, 3.73 Kw Fan Motor, 900 MM Fan Dia, NO 2
Supply Air Application)
1057 10000 CFM (15mm static pressure, 1000 / 1500 RPM, 3.73 Kw Fan Motor, 900 MM Fan Dia, NO 6
Supply Air Application)
1058 Smoke Ventilation, Supply & Exhaust NO 2
30000 CFM (25mm static pressure, 1000 / 1500 RPM, 9.33 Kw Fan Motor, 1200 MM Fan Dia,
Supply Air Application)
1059 12000 CFM (25mm static pressure, 1000 / 1500 RPM, 3.73 Kw Fan Motor, 900 MM Fan Dia, NO 4
Supply / Exhaust Air Application)
1060 7000 CFM (25mm static pressure, 1000 / 1500 RPM, 2.24 Kw Fan Motor, 900 MM Fan Dia, NO 1
Exhaust Air Application)
1061 5000 CFM (20mm static pressure, 1000 / 1500 RPM, 1.50 Kw Fan Motor, 600 MM Fan Dia, NO 12
Exhaust Air Application)
1062 Sub Head 'B' - Plumbing RMT 145
Condensate Drain Piping with Nitrile Rubber Insulation
Supply, installation, testing and commissioning of condensate drain water piping of GI
'Medium' class complete with fittings like elbows, tees, reducers, bends, MS flanges,
supports, welding, painting etc. as required conforming to tender specifications and of following
sizes. Complete pipe shall be duly insulated with fire retardent Closed Cell Elastomeric Nitrile
Rubber of specified pipe section of specified thickness in the tender specification & suitable for
indoor / outdoor application. Complete pipe insulation shall also have 200 g/m² factory
laminated, treated woven Glass Cloth coating for mechanical protection or manufacturer supplied
jacketing or with aluminium metalised surface.
25 mm dia pipe, 13 mm Insulation
1063 32 mm dia pipe, 13 mm Insulation RMT 165
1064 40 mm dia pipe, 13 mm Insulation RMT 140
1065 50 mm dia pipe , 19 mm Insulation RMT 115
1066 65 mm dia pipe, 19 mm Insulation RMT 110
1067 Refrigerant Piping for Non VRV Hi Wall Unit RMT 180
Supply, installation, testing and commissioning of refrigerant piping (two lengths) duly insulated
with fire retardent 6 mm thick nitrile rubber insulation of density 60+/-10% Kg/m3 to interconnect
indoor & outdoor units for each circuit with supports etc as required. Indoor & Outdoor insulation
shall be mechanically protected with two layers (07 mil thick each layer) of adhesive and Glass
Cloth / CSM or manufacturer supplied jacketing or with aluminium metalised surface and
Outdoor insulation shall have two coats of special UV resistant paint.
For Non VRV Hi Wall Unit

[68/80]
Page - 69
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1068 Refrigerant Piping for VRV / VRF System RMT 25
Supply & fixing of interconnecting copper refrigerant pipe work including the additional amount of
refrigerant gas required for charging the system, duly insulated with elastomeric nitrile rubber
type tubular insulation of fire retardent grade of conductivity less than 0.22 Btu.in./(h.ft² °F) and
density 50 Kg/CMT with thickness 25 mm up to 51 mm dia pipe and with 32 mm for more than
51 mm dia pipe, between Indoor Unit & outdoor units as per specifications. All piping inside the
building shall be properly supported on trays and all external piping shall run in covered tray
(tray quantified separately).
Indoor & Outdoor insulation shall be mechanically protected with two layers (07 mil thick each
layer) of adhesive and Glass Cloth / CSM or manufacturer supplied jacketing or with aluminium
metalised surface and Outdoor insulation shall have two coats of special UV resistant paint.
50.8 mm O.D. (Min. Wall Thickness - 1.64 mm)

1069 44.5 mm O.D. (Min. Wall Thickness - 1.64 mm) RMT 30


1070 41.3 mm O.D. (Min. Wall Thickness - 1.43 mm) RMT 350
1071 34.9 mm O.D. (Min. Wall Thickness - 1.21 mm) RMT 450
1072 28.6 mm O.D. (Min. Wall Thickness - 0.99 mm) RMT 460
1073 22.2 mm O.D. (Min. Wall Thickness - 0.80 mm) RMT 495
1074 19.1 mm O.D. (Min. Wall Thickness - 0.80 mm) RMT 525
1075 15.9 mm O.D. (Min. Wall Thickness - 0.80 mm) RMT 540
1076 12.7 mm O.D. (Min. Wall Thickness - 0.80 mm) RMT 460
1077 9.5 mm O.D. (Min. Wall Thickness - 0.80 mm) RMT 495
1078 6.4 mm O.D. (Min. Wall Thickness - 0.80 mm) RMT 405
1079 Condendate Drain Piping for Non VRV Hi Wall Unit RMT 25
Supply, installation, testing & commissioning PVC hard drain piping with fittings, insulation etc as
required to suit site condition.
19 mm Dia. of pipe, PVC Hard Pipe

1080 25 mm Dia. of pipe, PVC Hard Pipe RMT 25


1081 32 mm Dia. of pipe, PVC Hard Pipe RMT 20
1082 Supports of Outdoor / Indoor Unit NO. 12
Supply & fixing of GI frames for outdoor units, Choki / Cantilever Type and for indoor unit as
required to suit site conditions.
For Non VRV Hi Wall ODU

1083 For VRV / VRF Unit ODU for each module NO. 44
1084 Sub Head 'C' - HVAC Ducting & Grilles SMT 2325
Rectangular GI Ducting (Factory Made - L Shape)
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal
rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers,
vanes, hangers, supports etc. as per approved drawings and specifications of following sheet
thickness complete as required.
24 G, Thickness 0.63 mm sheet (Up To 750 mm)

1085 22 G, Thickness 0.80 mm sheet (751 to 1500 mm) SMT 1775


1086 20 G, Thickness 1.00 mm sheet (1501 to 2250 mm) SMT 1210
1087 18 G, Thickness 1.25 mm sheet (Above 2250 mm) SMT 575
1088 Site Fabricated GI Ducting SMT 275
Supply, installation, balancing and commissioning of site fabricated GSS sheet metal
rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers,
vanes, hangers, supports etc. as per approved drawings and specifications of following sheet
thickness complete as required.
24 G, Thickness 0.63 mm sheet (Up To 750 mm)

1089 22 G, Thickness 0.80 mm sheet (751 to 1500 mm) SMT 200


1090 20 G, Thickness 1.00 mm sheet (1501 to 2250 mm) SMT 150
1091 18 G, Thickness 1.25 mm sheet (Above 2250 mm) SMT 115
1092 Duct Acoustic Lining SMT 160
Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded
glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600
mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated
aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins,
CPRX compound etc. complete as required and as per specifications.
1093 Duct Insulation SMT 1600
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell
Nitrile rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile
rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber
tape insulation complete as per specifications and as required.
19 mm

1094 25 mm SMT 500

[69/80]
Page - 70
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1095 Fire Dampers & Actuator SMT 13
Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/main branch and
return air path as and where required of required sizes i/c control wiring, the damper shall be
motorized and spring return so as to close the damper in the event of power failure automatically
and open the same in case of power being restored. The spring return action shall be inbuilt
mechanism and not externally mounted. The damper shall also be closed in the event of fire
signal complete as required and as per specifications.
Fire Damper

1096 Actuator NO. 26


1097 Grilles, Diffusers, VCD SMT 90
Supply, installation and testing of Powder coated Aluminium extruded grills / diffusers
as per specifications given in tender and of following sizes.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume
control dampers as per specifications.

1098 Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without SMT 28
volume control dampers complete as required.
1099 Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with SMT 30
aluminium volume control dampers with anti smudge ring & removable core.
1100 Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium SMT 20
without volume control dampers with anti smudge ring & removable core.
1101 Fresh / Exhaust air louvers with bird screen & damper SMT 13
1102 Volume control GI Dampers to be provided in supply & Exhaust air registers / terminals. SMT 15
1103 Fixed bar linear air register of following sizes RMT 130
100 mm
1104 125 mm RMT 135
1105 150 mm RMT 125
1106 Supply, installation and testing of GI Louvers constructed with casing in 14 G & louvers in 18 G SMT 45
construction for supply / exhaust air application for ventilation fan including bird screen, fixing
members, rain protector, free area of 55% etc as required to suit the site conditions.
1107 GSS Duct Damper SMT 65
Supply, installation, testing and commissioning of GI volume control duct damper complete with
neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. Back
draft damper / Non return damper etc shall be considered under this item only.

1108 Acoustic Insulation of AHU Room SMT 600


Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with 50mm thick, density 32
kg/cu.m resin bonded glass fiber insulation friction fixed in 610mm x 610 mm frame work made
of 25X50X50X50X25 mm made out of 0.6mm thick GI sheet U shaped channel and covered with
reinforced fiber glass tissue and finished with 0.80 mm perforated aluminium sheet etc. complete
as required and as per specifications.
1109 Under Deck Insulation of Exposed Roof SMT 2360
Supplying and fixing of thermal insulation on exposed roof (under deck) with 23 mm thick Cross
Linked Closed Cell Polyethylene FR-XPE insulation of density 33 Kg/m³ with adhesive etc. as
required & finally fixed with the help of rawl plug, dash fasteners & adhesive in ceiling of pieces in
size of 900x900 mm or 1200x1200 mm.
1110 Sub Head 'D' - HVAC Electric Work NO. 1
Electrical Sub Panel
Supply, installation, testing and commissioning of cubical wall / floor mounted type suitable for
indoor / outdoor application switch board as detailed below & switch gears suitable for AC-23
duty including making interconnection etc as required.
VRV / VRF ODU Panel, Audi Side, Outdoor Type
2x16 HP VRV / VRF Outdoor Unit
1x26 HP (8 HP + 18 HP) VRV / VRF Outdoor Unit
2x28 HP (12 HP + 16 HP) VRV / VRF Outdoor Unit
1x30 HP (12 HP + 18 HP) VRV / VRF Outdoor Unit
1x32 HP (12 HP + 20 HP) VRV / VRF Outdoor Unit
4x38 HP (18 HP + 20 HP) VRV / VRF Outdoor Unit
1x40 HP (20 HP + 20 HP) VRV / VRF Outdoor Unit
1x42 HP (12 HP + 12 HP + 18HP) VRV / VRF Outdoor Unit
Incomer
1000 A TPN MCCB with (0-1000A) ammeter with three CT and selector switch, (0 - 500 V)
voltmeter with selector switch, phase indication light with SP MCB, automation compitable
energy meter with maximum demand. SET-01
Outgoing
a) For Each Module of VRV Outdoor Unit
32 A / 40 A / 63A TPN MCB with overload & short circuit protection. SET 25 + SPARE 5

[70/80]
Page - 71
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1111 VRV / VRF ODU Panel, Non Audi Side, Outdoor Type NO. 1
2x10 HP VRV / VRF Outdoor Unit
2x22 HP (10 HP + 12 HP) VRV / VRF Outdoor Unit
1x32 HP (12 HP + 20 HP) VRV / VRF Outdoor Unit
3x38 HP (18 HP + 20 HP) VRV / VRF Outdoor Unit
1x40 HP (20 HP + 20 HP) VRV / VRF Outdoor Unit
1x42 HP (12 HP + 12 HP + 18HP) VRV / VRF Outdoor Unit
Incomer
800 A TPN MCCB with (0-800A) ammeter with three CT and selector switch, (0 - 500 V)
voltmeter with selector switch, phase indication light with SP MCB, automation compitable
energy meter with maximum demand. SET-01
Outgoing
a) For Each Module of VRV Outdoor Unit
32 A / 40 A / 63A TPN MCB with overload & short circuit protection. SET 19 + SPARE 5

1112 For Fan Motor Up to 3.73 Kw NO. 25


32 A TPN MCCB with 16 A DOL starter, overload relay, start / stop push buttons, phase
indication lights with SP MCB, on / off / trip indication lights with SP MCB, single phase preventer
& auto / manual mode selector switch . SET-01
1113 For Fan Motor of 5.5 Kw NO. 10
40 A TPN MCCB with 25 A DOL starter, overload relay, start / stop push buttons, phase
indication lights with SP MCB, on / off / trip indication lights with SP MCB, single phase preventer
& auto / manual mode selector switch . SET-01
1114 For Fan Motor of 7.5 Kw NO. 1
40 A TPN MCCB with16 A Star Delta Starter, overload relay, start / stop push buttons, phase
indication lights with SP MCB, on / off / trip indication lights with SP MCB, single phase preventer
& auto / manual mode selector switch. SET-01
1115 For Fan Motor of 9.33 Kw NO. 3
63 A TPN MCCB with 25 A Star Delta Starter, overload relay, start / stop push buttons, phase
indication lights with SP MCB, on / off / trip indication lights with SP MCB, single phase preventer
& auto / manual mode selector switch. SET-01
1116 Fan Motor 2x9.33 Kw, Parking Ventilation NO. 2
Incomer
100 A TPN MCCB with (0-100A) ammeter with three CT and selector switch, (0 - 500 V)
voltmeter with selector switch, phase indication light with SP MCB. SET-01
Outgoing
a) For Fan Motor of 9.33 Kw
63 A TPN MCCB with 25 A Star Delta Starter, overload relay, start / stop push buttons, phase
indication lights with SP MCB, on / off / trip indication lights with SP MCB, single phase preventer
& auto / manual mode selector switch. SET-02

1117 Fan Motor 2x Upto 3.73 Kw STP / Pump Room Ventilation NO. 2
Incomer
40 A TPN MCCB with (0-40A) ammeter with three CT and selector switch, (0 - 500 V)
voltmeter with selector switch, phase indication light with SP MCB. SET-01
Outgoing
a) For Fan Motor of Upto 3.73 Kw
32 A TPN MCCB with 16 A DOL starter, overload relay, start / stop push buttons, phase
indication lights with SP MCB, on / off / trip indication lights with SP MCB, single phase preventer
& auto / manual mode selector switch . SET-02
Controls & interlocking accessories as required for all the above panel shall be included in above
costing.

1118 Single Phase MCB for Inline Fan / Propeller Fan / VRV IDU NO. 254
Supply, Installation, testing & Commissioning of single phase MCB of following capacity:
6A / 10A / 16 A SP MCB, SET-01

1119 Isolators For VRV ODU / Hi Wall ODU NO. 1


Isolator switch with ELCB for VRV ODU IDU with enclosure for rain protection etc. as required to
suit the site condition.
32 A Three Phase

1120 40 A Three Phase NO. 4


1121 63 A Three Phase NO. 15
1122 100 A Three Phase NO. 24
1123 32 A Single Phase NO. 12
1124 Power & Control Cabling RMT 405
Supply, laying, testing and commissioning of power and control cabling as per specification
given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables
of 1.1 KV Grade including cable end termination with brass compression glands &
aluminium lugs etc as per specification.
A) Power Cabling
For Motor Up to 3.73 Kw
1 x 3C x 4 Sq. mm

1125 For Motor of 5.5 Kw RMT 150


1 x 3C x 6 Sq. mm

[71/80]
Page - 72
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1126 For Motor of 7.5 to 11.19 Kw RMT 120
2 x 3C x 6 Sq. mm
1127 For Inline Fan / VRV IDU / Propeller Fan RMT 635
1 x 3C x 2.5 Sq. mm Copper Flexible Cable
1128 For VRV Outdoor / Normal Hi Wall ODU RMT 80
1 x 3 C x 4.0 Sq. mm Copper Flexible Cable
1129 1 x 3 C x 6.0 Sq. mm Copper Flexible Cable RMT 80
1130 1 x 3 C x 10.0 Sq. mm Copper Flexible Cable RMT 300
1131 1 x 3 C x 25.0 Sq. mm Copper Flexible Cable RMT 480
1132 B) Control cabling (PVC insulated Copper conductor of 1.1 KV Grade armoured cable) 3C x 1.5 RMT 90
Sq. mm
1133 4C x 1.5 Sq. mm RMT 120
1134 5C x 1.5 Sq. mm RMT 100
1135 5C x 2.5 Sq. mm RMT 180
1136 C) Transmission & Control Wiring For VRV System RMT 3200
Providing & fixing of control cum trans-mission wiring of copper between indoor and out door
unit in 25 mm PVC Conduit.
3C / 2C x 1.5 Sq mm

1137 Earthing Strip / Wires as per specs. RMT 500


Supply & laying of 32 x 5 mm GI strip recess / surface as strip earth lead including soldering
etc. as required.
1138 Supply & laying of 25 x 5 mm GI strip recess / surface as strip earth lead including soldering RMT 450
etc. as required.
1139 Supply & laying of 8 SWG GI wire or in recess for loop earthing as required. RMT 1230
1140 Supply & laying of 6 SWG GI wire or in recess for loop earthing as required. RMT 670
1141 Rubber mat 1000 mm. Wide to withstand 1.1 KV dielectric strength as per latest IS 15652-2006. RMT 20

1142 Cable Tray RMT 255


Supplying and installing following size of perforated GI cable trays including bends. tee, reducers
etc with perforation not more than 17.5%, in convenient sections, joined with connectors,
suspended from the ceiling with GI suspenders including bolts & nuts, suspenders etc as
required.
100 mm wide x 50 mm depth x 1.6 mm thickness.

1143 150 mm wide x 50 mm depth x 1.6 mm thickness. RMT 255


1144 300 mm wide x 50 mm depth x 1.6 mm thickness. RMT 265
1145 450 mm wide x 50 mm depth x 2.0 mm thickness. RMT 230
1146 600 mm wide x 50 mm depth x 2.0 mm thickness. RMT 325
NOTE:
Fire shunt relay contact to be included in panel wherever necessary along with auto / manual
mode selector switch for all fire mode fans to take fire input signal (Potential Free Contact). Cost
shall be included in the panel price quoted by them.

1147 SUB HEAD: 'E': SIGNAGE: Each 3


Supplying & fixing of retro reflective sign board of size 1800 mm x 1200 mm. The board made of
High intensity prismatic grade type IV retro reflective sheeting of 3M /Avery Denison or equivalent
make approved by I.R.C. / M.O.S.T. with message and graphics to be overlay film of same make
duly plotter cut, letters written (both side) in white colour, to be pasted on 3mm thick ACP sheet
of make Alstone / Alstrong / Eurobond / Alucobond or equivalent. Frame made of 38mm dia pipe
& 2nos. 63mm diavertical posts, 3 Mtr. high, all made of 304 series (Jindal or equivalent)
stainless steel. Pipe fixed on ground including necessary excavation and sign board fixed with in
ground in 600 mm depth with all excavation & cement aggregate concrete 1 : 2 : 4 {1 cement : 2
coarse sand : 4 graded stone 20 mm nominal size) as per direction of Unit Incharge.

1148 Supplying & fixing of retro reflective sign board of size 1200 mm x 900 mm. The board made of Each 3
High intensity prismatic grade type IV retro reflective sheeting of 3M /Avery Denison or equivalent
make approved by I.R.C. / M.O.S.T. with message and graphics to be overlay film of same make
duly plotter cut, letters written (single side) in white colour, to be pasted on 3mm thick ACP sheet
of make Alstone / Alstrong / Eurobond / Alucobond or equivalent. Frame made of 40mm dia pipe
& 2nos. 63mm diavertical posts, 2.10 Mtr. high, all made of 304 series (Jindal or equivalent)
stainless steel. The pipe shall be standing on hard concrete surface with the help of SS holdfast/
Hilti or equallent flush anchor (Fasteners) of as per required size and numbers and thickness and
nut bolts on 02 Nos.5 mm thick 200mm x 200 mm size SS plate welded with 63mm dia SS pipe
as per direction of Unit Incharge.
1149 Supplying & fixing of retro reflective sign board of size 900 mm x 600 mm. The board made of Each 4
High intensity prismatic grade type IV retro reflective sheeting of 3M /Avery Denison or equivalent
make approved by I.R.C. / M.O.S.T. with message and graphics to be overlay film of same make
duly plotter cut, letters written (both side) in white colour, to be pasted on 3mm thick ACP sheet
of make Alstone / Alstrong / Eurobond / Alucobond or equivalent. Frame made of 38mm dia pipe
& 2nos. 63mm diavertical posts, 1.80 Mtr. high, all made of 304 series (Jindal or equivalent)
stainless steel. The pipe shall be standing on hard concrete surface with the help of SS holdfast/
Hilti or equallent flush anchor (Fasteners) of as per required size and numbers and thickness and
nut bolts on 02 Nos.5 mm thick 200mm x 200 mm size SS plate welded with 63mm dia SS pipe
as per direction of Unit Incharge.

[72/80]
Page - 73
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1150 Supplying & fixing of retro reflective sign board of size 1200 mm x 600 mm. The board made of Each 2
High intensity prismatic grade type IV retro reflective sheeting of 3M /Avery Denison or equivalent
make approved by I.R.C. / M.O.S.T. with message and graphics to be overlay film of same make
duly plotter cut, letters written (single side) in white colour, to be pasted on 3mm thick ACP sheet
of make Alstone / Alstrong / Eurobond / Alucobond or equivalent. Frame made of 40mm dia pipe
& 1no 63mm diavertical posts, 1.90 Mtr. high, all made of 304 series (Jindal or equivalent)
stainless steel. The pipe shall be standing on hard concrete surface with the help of SS holdfast/
Hilti or equallent flush anchor (Fasteners) of as per required size and numbers and thickness and
nut bolts on 02 Nos.5 mm thick 200mm x 200 mm size SS plate welded with 63mm dia SS pipe
as per direction of Unit Incharge.
1151 Supplying & fixing of retro reflective sign plates of required size. The plate made of High intensity Sqft 300.00
prismatic grade type IV retro reflective sheeting of 3M / Avery Denison or equivalent make
approved by I.R.C. / M.O.S.T. with message and graphics to be overlay film/High intensity
prismatic grade type IV retro reflective sheeting of 3M / Avery Denison or equivalent make
approved by I.R.C. / M.O.S.T Reflective tape of same make duly plotter cut, of approved color,
letters (single side) in white colour, to be pasted on 3mm thick ACP sheet of make Alstone /
Alstrong / Eurobond / Alucobond or equivalent etc. as per drawings. The sign boards shall fixed
on wall/ roof duly fixed with rawls plugs stainless steel srew/ double side tape 3M make/ SS
chain of required size of required nos of holes, wherever required complete as per direction of
Unit Incharge
1152 Supply and fixing of 18 gauge Stainless Steel plates with water jet cutting of grade 304 etching Sq Inch 30000.00
(engraved)signage plate of required size and letters duly bordered . Engraved portion painted of
as per required colour/ approved colour (DUCO) of approved brand and filling with required
matt/ mirror finish polish on base and border with shining polish of required shade and colour and
duly fixed with required nos of rawls plugs stainless steel srew/ double side tape of 3M make/
nut bolt/ spacer required nos of holes, wherever required complete as per direction of Unit
Incharge. (make Jindal or Equivalent)
1153 Supply and fixing of Powder coated Aluminum Panel for directory of size 900mm x 750mm with Nos. 12
partition of required Nos supported on aluminum channel 2 nos backside with ACP sheet .Matter
will Be digital print, matter covered with transparent polycarbonate sheet 0.5 mm wherever
required complete and duly fixed with required nos of rawls plugs stainless steel srew/ spacer
required nos of holes, wherever required complete as per direction of Unit Incharge

1154 Supply and fixing of Amuminium Silver powder coated signage of required size complete with SQ INCH 10000.00
message. Matter will be digital print written single sides, matter covered with transparent
polycarbonate sheet 0.5mm. and duly fixed with required nos of rawls plugs stainless steel srew/
double side tape of 3M make/ screw required nos of holes, wherever required complete as per
direction of Unit Incharge
1155 Supply and fixing of Amuminium Silver powder coated signage two plates ( vertical type) of SQ INCH 3000.00
required size complete with message. Matter will be digital print written both sides, matter
covered with transparent polycarbonate sheet 0.5mm. and duly fixed with required nos of rawls
plugs stainless steel srew/ double side tape of 3M make/ screw required nos of holes, wherever
required complete as per direction of Unit Incharge
1156 Providing/Laying 2.5 mm thick road marking strips (Retro reflecting) oRoad marking paints with Sqm 300.00
applied thermo plastic compound with reflectorized glass beads on bituminous surface, providing
and laying of hot applied thermo plastic compound 2.5 mm thick including reflectorising glass
beads @ 250gm per sq. mtr. area thickness of 2.5 mm is exclusive of surface applied glass
beats as per IRC – 35. The finished surface should be level, uniform and free from streaks and
holes as per relevant clauses of section 800 in addition where arrows or letters are to be
provided thermo plastic compound may be hand sprayed. The colour of the compound shall be
white or yellow (IS Colour No. 356) as specified in the drawings or directed by the Unit Incharge.
15cm widths on bituminous surface/ Concrete, complete all as specified.

1157 Supply and installation of Raised pavement marker(RPM) with polycarbonate lens electronically Nos 100
welded with the RPM body. Marker shall be scratch proof and abrasion resistant micro prismatic
polycarbonate lens with polycarbonate Reflective panels with dual prismatic cubes capable of
providing total internal reflection. Dimensions: Dimensions of the marker is Height: 15.88
,Width: 101.6 ,Length: 89.2 .The marker conforms to ASTM D4280 and is in accordance with
MOSRTH Circular Ref No. RW/NH 33023/10/97-DO III Dated 11th June 1997. Markers shall be
fixed with adhesives and no nails shall be used to affix the marker and shall be marked with
manufacturers name, complete all as specified. Make 3M/ Avery Dennison C-8 Series/Simsonite
or equallent
1158 Providing & fixing of emergency sign boards single side of required size made of Photo Sq Inch 20000.00
luminescent film having glow power of 4 hours with message and graphics to be screen printing /
vinyl cut film of 3M / Avery Denison / LG / Oracle or equivalent make to be pasted on 3mm thick
Sun Board sheet all complete and duly fixed with required numbers of rawls plugs stainless steel
srew/ double side tape of 3M make required nos of holes, wherever required complete as per
direction of Unit Incharge
1159 Supply & Fixing Display notice pin up board or white writing board of required size, aluminum Sq Ft 600.00
beeding of 12 mm and fixed with required numbers of rawls plugs stainless steel srew as per
direction of Unit Incharge.
1160 Supply & Fixing Key ring holder stand of size 900mm x 600mm. Front door covered with Each 8
transparent acrylic sheet and locking arrangement. Fixed with required numbers of rawls plugs
stainless steel srew as per direction of Unit Incharge.

[73/80]
Page - 74
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1161 Supplying and fixing of 18 gauge Stainless Steel Key Rings 1.245 mm thick (18 gauge) Nos. 600
Stainless Steel plates of grade 304 etching (engraved)signage plate of Size 50mm x 38mm of
and letters duly bordered as per sample approved and all as per sample. Engraved portion
painted of as per required colour/ approved colour (DUCO) of approved brand written both sides
and filling with required matt/ mirror finish polish on base and border with shining polish of
required shade and colour as per direction of Unit Incharge
1162 Supply & placing of Stainless Steel 304 series Dustbin of size 300 x 175 as per direction of Unit Nos. 40
Incharge.
1163 Supply & placing of Stainless Steel 304 series Dustbin with foot operated of size 356 mm x 584 Nos. 10
mm with plastic bucket as per direction of Unit Incharge.
1164 Supply & place Road side bin moon (90 LTR PLASTIC ) with SS stand as per direction of Unit Nos 10
Incharge. (Make Sheetal / Sintex or equivalent)
1165 Supply and fixing of Solar Studs of width 122.5mm, length 132.5 mm height with stump 55.00 Nos. 12
mm, stump dia 26.00 mm electronically operated with solar cell LEDS pcs. Battery Nl-cd 1400
AE Main Frame Aluminium, Bottom Frame Aluminium, Reflective. The studs shall be fixed to the
Road surface using the adhesive conforming to IS, as per procedure recommended by the
manufacturer complete and as per direction of Unit Incharge. For Solar stud fixing firstly clean
the surface, grout as per requirement & filled with epoxy. Make 3M/ Avery Denson/ Dark eye/ or
equivalent
1166 Supplying of Q Manager made of hollow stainless steel pipe of 18 gauge and 900 mm high Nos. 20
including 1.30 mtr and 50mm width long ribbon etc. all complete as per direction of Unit
Incharge.
1167 Supply & Fixing signages for exit of size 375mm x 200mm x 8mm in acrylic sheet LED light with Each 24
battery backup
1168 SH: F: AV SYSTEM: Nos. 2
Auditorium
Supply, installation, testing & Commissioning of Trapezoidal, Box type High SPL, 2 Way, Bi-
ampable, Mid-High Loudspeaker with at least 2.5" HF transducer and multiple MF drivers with -
Dispersion Angle of 90x60 or better with rotatable horn for mounting flexibility Free field operating
Frequency Range of 170 Hz – 18kHz or better, Free Field Axial Sensitivity >= 105 dB
SPL(1W/1m), Max. Continuous SPL >= 126 dB & Peak SPL >132dB. Continuous power
handling of 125W (MF) + 75W (HF) or more. Multiple rigging / suspension points shall be
available. Exterior Grade Baltic Birch Plywood construction with IPX5 outdoor operational rating.
at least 12 rigging / suspension points for flexible installation.
Approved Make: Bose / EAW / d&b audiotechnik
Bose LT 9702
1169 Supply, installation, testing & Commissioning of fly kit for multipoint suspension for FOF Nos. 2
Loudspeaker modules.
Approved Make: Custom
1170 Supply, installation, testing & Commissioning of Modular Dual 12" Installation friendly subwoofer Nos. 2
with a free field Freq. Range of 36 Hz - 250Hz or better. It should have an axial Sensitivity of > =
94dB (1W/1m) or more delivering a Max. Calculated SPL(Continuous) of >=123 dB (129dB
Peak). The loudspeaker should have a nominal impedance of 4ohm or 2x8 ohms or better and
continuous Power Handling of 2x400W (1600+1600W Peak) or more. at least 12 suspension /
rigging points shall be available for flexible installs. The Subwoofer shall be enclosed in Baltic
birch plywood with powder coated steel grille.
Approved Make : Bose / EAW / d&b Audiotechnik
Bose MB 24
1171 Supply, installation, testing & Commissioning of fly kit for multipoint suspension for Bass Nos. 2
Modules.
Approved Make: Custom
1172 Supply, installation, testing & Commissioning of Compact High SPL Fill loudspeakers with 5" LF Nos 4
Driver ; Frequency Range of 90 Hz - 16 kHz or better; Nominal Dispersion : 90°H x 90°V; Long
term Power handling of 150 W or better; Sensitivity : 90 dB; Max SPL : 116dB Peak; Nominal
Impedance : 8Ω; 18-gauge (1.2 mm) perforated steel; Powder-coated finish grille with Two-part
spray polyurethane coating Enclosure. Shall offer optional OEM Input transformer kit for
Distributed system applications. Standard wall bracket shall be included.
Approved Make: Bose/EAW/d&b Audiotechnik
Bose RMU 105
1173 Supply , installation , testing and commissioning of 4.5" IP55 rated Indoor/Outdoor Surface Nos 2
mount Music Loudspeaker: Free field Frequency range (-10dB) of 70Hz to 18kHz; Power
handling of 160 Watt peak; Nominal dispersion of 120 Conical; Free field Sensitivity of 87dB SPL
and Max SPL of 109 dB SPL (peak); Nominal Impedance 8 Ohms; Integral multi-tap Transformer
with tap settings of 5/10/20/40 W @ 100V. with Powder-coated steel grille; Shall include
necessary standard hardware for Surface install.
Approved Make: Bose/EAW/Martin Audio
Bose DS 40SE
1174 Supply, installation, testing & Commissioning of Sound Reinforcement System - Wedge shaped Nos 4
monitor loudspeaker with 2 x 8" or 12" LF Drivers; Frequency range of: 70 Hz - 16 kHz; Nominal
Dispersion : 90°H x 60°V (rotatable horn); Long term Power handling capacity: 300W or better;
free field full range Sensitivity : 94 dB SPL or better; Max SPL : 119dB (125dB Peak); Nominal
Impedance : 8 Ω; 18-gauge (1.2 mm) perforated steel; Powder-coated finish grille with Two-part
spray polyurethane coating and Baltic birch plywood Enclosure. With U bracket for standard
installs.
Approved Make: Bose/EAW/d&b Audiotechnik
Bose RMU 208

[74/80]
Page - 75
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1175 Supply , installation , testing and commissioning of Digital Sound Processor with 8 Mic/Line Nos 1
inputs & 8 analog outputs, 24 Bit A-D and D-A Convertors; Sampling Rate : 48 kHz; THD : <
0.002 % ; Channel Separation (Crosstalk) : < 105 dB ; Frequency Response 20 Hz - 20 kHz ;
Signal-to-Noise Ratio 80 dB ;Dynamic Range : > 115 dB; 5 Control Inputs and Outputs; RS-232
and Ethernet Port for third party Control and Monitoring; Expansion slots for optional Network
Audio formats like Dante/Cobranet; inbuilt DSP features like Input Equalizers, Router, Band Pass
filter, Output Equalizer, Delay, Limiters, gates , Source selectors etc.
Approved Make: Bose / Symetrix / Bi-amp
Bose ESP-880
1176 Supply , installation , testing and commissioning of 8 channel class D Networkable Power Nos 2
amplifier with a Max Output Power of 8x500W@8 ohms, or bridged mode output power of 4x
1000W @ 8/4 ohms. 20Hz - 20 KHz, SNR of 102dB and THD + N of <0.4% with built in
protection such as Limiters, Temperature, DC, Short Circuit, Peak Current Limiters, Turn on
delay etc. Built in DSP for Matrix routing, Speaker equalization, Delays, Array EQs etc complete
with Ethernet Port for Network Control, programming and monitoring. Shall offer optional
Network audio connectivity (Dante or CobraNet) through expansion slot.
Approved Make: Bose/Ashly Audio/Powersoft
Bose PM 8500
1177 Supply, Installation, testing and commissioning of integrated high impedance Class D zone Nos 1
amplifier with output power of upto 90W @ 70/100V. frequency response of 50Hz to 20kHz; THD
<0.3%; Shall include priority override and Fire alarm interface, shall include necessary
loudspeaker EQs.
Approved Make: Bose/Yamaha/Ashly Audio
Bose IZA 190HZ
1178 Supply, installation, testing & Commissioning of programmable Audio DSP controller with Nos 1
Display and programmable encoder knobs. Multiple programmable settings configurable over
Ethernet. Source Selection and Volume Controls ; Supports Upto 256 programmable Functions
Shall include any accessory to make the system functional.
Approved Make: Bose/Bi-amp/Symetrix
Bose CC-64 + PS-1
1179 Supply, Installation, Testing & Commissioning of 20-24 Channel Mixing Console with Input Nos. 1
Configuration 16 mic or better, 2-3 stereo inputs or better, EQ's 2 or better, 4 Aux and group
outputs or better, Fader on each channel.
Approved Make - RCF/ Allen & Heath/ Mackie
RCF
LivePad24CX
1180 Supply, installation, testing & Commissioning of wired handheld microphone. Transducer type Nos 4
Dynamic Polar pattern Super cardioid Frequency response: 30 - 18,000 Hz Nominal impedance
600 Ω Connection 3-pin XLR male
Approved Make: Beyer dynamics / Sennheiser / Shure
Beyer dynamic TG V35d s
1181 Supply, Installation, testing and commissioning of Wireless Handheld with Frequency Response: Nos 4
80 Hz to 16 kHz; Presets: 12; THD: <1%; S/N Ratio: > 103 dB(A), Microphone: Dynamic, SPL:
149 Db with complete standard accessories.
Approved Make: Beyer dynamics / Sennheiser / Shure
Beyer dynamic TG 100 H-Set
1182 Supply, Installation, testing and commissioning of Goosneck Microphonbe for Cardioid polar Nos 1
pattern; Frequency Response: 50 Hz to 20 kHz; Impedance <100 Ohms; Max Sound Pressure
level: 130 dB; RF shielding against intermodulation from wireless devices with table top stand.
complete with standard accessories as per tender specifications.
Approved Make: Beyer dynamics / Sennheiser / Shure
Beyer dynamic Classis GM 105 + GMB 33S
1183 Supply, Installation, testing and commissioning of Wireless Lapel Microphone Frequency Nos 2
response: mic: 100 - 16000 Hz, Line: 60 - 16000 Hz; Presets: 12; THD: <1%; S/N Ratio: > 103
dB(A) complete with standard accessories as per tender specifications.
Approved Make: Beyer dynamics / Sennheiser / Shure
Beyer dynamics TG 100 B Set
1184 Supply , installation , testing and commissioning of 2 core 4.0 sq mm PVC insulated Cu Mtr. 100.00
conduction loudspeaker cable with Conductor 224 x 0.15 mm, Impedance 4.5 Ω/km Capacitance
180 pF/m, Outer dia 11.0 mm, working temperature -20 °C / +70 °C.
Approved Make: Belden / Klotz / Canare
Klotz
LY 240
1185 Supply , installation , testing and commissioning of 2 core 2.5 sq mm PVC insulated Cu Mtr. 700.00
conduction loudspeaker cable with Conductor 50 x 0.25 mm, Impedance 7.0 Ω/km Capacitance
170 pF/m, Outer dia 8.0 mm, working temperature -20 °C / +70 °C.
Approved Make: Belden / Klotz / Canare
Klotz
LY 225
1186 Supply , installation , testing and commissioning of 2 core Shielded mm PVC Insulated Mtr. 600.00
Microphone cable with Ultra low Capacitance 60(Pf/m) ; Outer Jacket : PVC Matt ; Working
Temperature :20 °C / +70 °C ; Diameter : 6.5mm ; extremely flexible.
Approved Make: Belden / Klotz / Canare
Klotz
MY 206

[75/80]
Page - 76
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1187 Supply , installation , testing and commissioning of professional CD Cum USB Player with Nos 1
Frequency Response - 2 Hz to 20 kHz or better; THD - <0.05% or better; S/N Ratio - 85 dB or
better; Dynamic Range 85 dB or better; IR Remote Control – Yes; Audio CD – Yes; MP 3 – Yes;
Balanced Output- Yes.
Approved Make: Gemini / Tascam
Gemini
CDMP 1400
1188 Supply , installation , testing and commissioning of 16U Equipment rack to house all rack Nos 1
mountable equipment, with internal wiring, front glass door, heat dissipation fans, power
distribution units etc. Complete with standard accessories as per tender specifications.
Approved Make: Chief / Middle Atlantica / Valrack
Valrack 16U
1189 Video Solution Nos. 1
Supply, Installation, testing & commissioning of 8500 ANSI lumens 1 chip DLP projector; 1920 x
1200 WUXGA resolution; 2500:1 contrast ratio; 1 X HDBaseT; 2 x HDMI; 1 x VGA; 1 x DVI.
Approved Make: Christie / Barco / Digital Projection
Christie DWU951-Q

1190 Supply, Installation, testing & commissioning of Projection lens having Throw distance of 20 to Nos. 1
30 mtr.
Approved Make: Christie / Barco / Digital Projection
Christie Lens Std Zm 1.7-2.6/1.6-2.4
1191 Supply, Installation, testing & commissioning of Mounting/hanging arrangement of above Nos. 1
Projector.
Approved Make: Custom
1192 Supply, Installation, testing & commissioning of 240-250" diagonal motorized projection screen Nos. 1
with aspect ratio 16:9.
Approved Make: Suvira / Draper / Liberty
Suvira
1193 Supply, installation, testing & Commissioning of Multi-Format transmitter model with 1 HDMI,1 Nos. 2
VGA-Audio input over a single CATx cable. Shall function as Quick switch technology with Last-
Connected mode. Supports resolutions upto HD for a distance of 90m.
Approved Make: Crestron/Extron/Kramer
Crestron DM-TX-200-C-2G
1194 Supply, installation, testing & Commissioning of 6x2 matrix switcher with Quick switch Nos. 1
technology. HDMI input signal with Deep color, and 4K support. Output on 1 nos CaTx and 1 nos
HDMI scaled. Outout HDMI should be 4K up-scaled with content-adaptive noise reduction, and
widescreen format selection. Should have 512MB RAM and 4GB of flash memory. Should have
at least 2x RS-232, 4x IR & 4x Relays. Device to have DHCP, HDCP 2.2.
Approved Make: Crestron/Extron/Kramer
Crestron DMPS3-4K-200-C

1195 Supply, installation, testing & Commissioning of HDMI Receiver over Twisted Pair, supports Nos. 1
cable length up to 90 mtrs for UHD/4K resolution, supports 4K resolution, IR, RS-232 and
Ethernet Control.
Approved Make: Crestron/Extron/Kramer
Crestron DM-RMC-4K-100-C
1196 Supply, installation, testing & Commissioning of HDMI Extender (Transmitter Receiver Pair Kit). Nos. 1
Approved Make: Crestron/Extron/Kramer
Crestron HD-EXT4-C

1197 Supply, installation, testing & Commissioning of 7.5” Touch Screen with Capacitive touch screen Nos. 1
technology, 960 x 540 qHD resolution, 16:9 aspect ratio, 400 nits (cd/m²) brightness, 750:1
contrast ratio, 24‐bit, 16.7M colors color depth, ±80°H, ±80°V viewing angle, Built‐in 5 MP H.264
IP camera, microphone and speakers, supports H.264 or MJPEG streaming video display.
Approved Make: Crestron/Extron/Kramer
Crestron TSW 760

1198 Supply, installation, testing & Commissioning of Table top kit for Touch Panel. Nos. 1
Approved Make: Crestron/Extron/Kramer
Crestron TSW-ttk
1199 Supply, installation, testing & Commissioning of Power over Ethernet adaptor for Touch panel. Nos. 1
Approved Make: Crestron/Extron/Kramer
Crestron PWE-4803 RU

1200 Supply, installation, testing & Commissioning of programmable 12 button panel for Automation. Nos. 1
Approved Make: Crestron/Extron/Kramer
Crestron CNX-B12B

1201 Supply, installation, testing & Commissioning of IR Probe for device control. Nos. 2
Approved Make: Crestron/Extron/Kramer
Crestron IRP2
1202 Supply, installation, testing & Commissioning of 802.11b/g/n compatible wireless access point, 3- Nos. 1
5W or better Antenna.
Approved Make: CISCO/Netgear / D-Link
Cisco / LinksysWAP

[76/80]
Page - 77
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1203 Supply, installation, testing & Commissioning of Layer - III managed Gigabit switch with at least 8- Nos. 1
10 copper ports.
Approved Make: CISCO/Netgear / D-Link
Cisco / Linksys 8-10 Port network Switch
1204 Supply , installation , testing and commissioning of VGA Micro HR with Audio Cable: 15-pin HD Nos. 10
Male to Male Low-Profile Molded + 3.5mm Stereo Mini Plug Male to Male - 6' (1.8 m) complete
with standard accessories as per tender specifications.
Approved Make: AMX / Crestron / Extron
Crestron CBL-VGA-AUD-6
1205 Supply , installation , testing and commissioning of 4K Premium High Speed HDMI Ultra-Flexible Nos. 2
Cable - 6' (1.8 m) complete with standard accessories as per tender specifications.
Approved Make: AMX / Crestron / Extron
Crestron CBL-HD-6
1206 Supply, installation, testing & Commissioning & Laying of Cat-6 Twisted Pair Cable. Mtr. 100.00
Approved Make: D-Link / Netgear
D-link
1207 Court Rooms Nos. 12
Supply , installation , testing and commissioning of Wall Mount full range Multidriver loudspeaker
with usable frequency range (-10dB) of 90Hz to 17kHz; Cont power: 120W @ 8 Ohms; Nominal
dispersion of 120 H X 60 V; Sensitivity 89 Db SPL ; Max SPL of 115 dB SPL ; inbuilt multiple
drivers with Rugged enclosure with powder coated steel grille.
Approved Make: EAW/Bose/Martin Audio
Bose Panray 402 IV
1208 Supply , installation , testing and commissioning of brackets for OEM wall Mounting for Nos. 12
Loudspeaker Modules. Shall allow Pitch and yaw adjustments.
Approved Make: EAW/Bose/Martin Audio
Bose RMUBRKT1
1209 Supply , installation , testing and commissioning of 10-12 Channel Digital Mixer with at least 8x Nos 5
Combo XLR-¼" inputs, 1x Stereo inputs, 2 x Aux sends, Balanced stereo outputs, dedicated
headphone output, USB A and B type connectors for WAV/MP3 files playback and PC
connection, Protective magnetic cover. Shall also offer built-in Advanced digital audio processing
with Studio-quality effects, Independent effects per channel, Master output EQ, Tap-tempo delay,
Chromatic tuner and recallable scenes, illuminated LED display and controls, Switchable
phantom power.
Approved Make: Yamaha/Bose/Allen & heath/Mackie
Bose T8S
1210 Supply , installation , testing and commissioning of 2 channel class D Power amplifier with a total Nos 5
Max Output Power of 600W independent of load, 8/4 ohms/70-100V operation, with mixed use.
Freq response of 20Hz - 20 KHz, SNR of 98dB and THD + N of <0.5% with built in protection
such as Limiters, Temperature, DC, Short Circuit, Peak Current Limiters, Turn on delay etc. Built
in DSP for Matrix routing, Speaker equalization, Delays, Array EQs etc complete with standard
accessories as required.
Approved Make: Labgrupen/Bose/Powersoft
Bose PS 602
1211 Supply, Installation, testing and commissioning of Goosneck Microphonbe for Cardioid polar Nos 5
pattern; Frequency Response: 50 Hz to 20 kHz; Impedance <100 Ohms; Max Sound Pressure
level: 130 dB; RF shielding against intermodulation from wireless devices with table top stand.
complete with standard accessories as per tender specifications.
Approved Make: Beyer dynamics / Sennheiser / Shure
Beyer dynamic Classis GM 105 + GMB 33S
1212 Supply , installation , testing and commissioning of 2 core 2.5 sq mm PVC insulated Cu Mtr. 600.00
conduction loudspeaker cable with Conductor 50 x 0.25 mm, Impedance 7.0 Ω/km Capacitance
170 pF/m, Outer dia 8.0 mm, working temperature -20 °C / +70 °C.
Approved Make: Belden / Klotz / Canare
Klotz
LY 225
1213 Supply , installation , testing and commissioning of2 core Shielded mm PVC Insulated Mtr. 375.00
Microphone cable with Ultra low Capacitance 60(Pf/m) ; Outer Jacket : PVC Matt ; Working
Temperature :20 °C / +70 °C ; Diameter : 6.5mm ; extremely flexible.
Approved Make: Belden / Klotz / Canare
Klotz
MY 206
1214 Supply , installation , testing and commissioning of 75 inches UHD 3840 x 2160 (16:9) Edge-lit Nos. 5
LED 400 nits (cd/m2) typical with viewing angle 178° h/v complete as tender specifications.
Approved Make: Christie / Barco / Digital projection
Christie UHD751-L

1215 Supply , installation , testing and commissioning of custom VGA-HDMI Input wall plate Nos. 5
Approved Make: Custom
Logic WP-VGA-HDMI
1216 Supply , installation , testing and commissioning of 1:2 HDMI Distribution amplifier with Audio De- Nos. 5
embedder,
Approved Make: Crestron / Extron / Kramer
Crestron HD-DA2
1217 Supply, Installation, testing and commissioning of wall mount bracket for the Display panel Nos 5
complete with standard accessories as required.
Approved Make: Custom

[77/80]
Page - 78
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1218 Conference: Nos. 2
Supply , installation , testing and commissioning of Wall Mount full range Multidriver loudspeaker
with usable frequency range (-10dB) of 90Hz to 17kHz; Cont power: 120W @ 8 Ohms; Nominal
dispersion of 120 H X 60 V; Sensitivity 89 Db SPL ; Max SPL of 115 dB SPL ; inbuilt multiple
drivers with Rugged enclosure with powder coated steel grille.
Approved Make: EAW/Bose/Martin Audio
Bose Panray 402 IV
1219 Supply , installation , testing and commissioning of brackets for OEM wall Mounting for Nos. 2
Loudspeaker Modules. Shall allow Pitch and yaw adjustments.
Approved Make: EAW/Bose/Martin Audio
Bose RMUBRKT1
1220 Supply , installation , testing and commissioning of Ceiling Flush Music/PA Loudspeaker: Free Nos. 12
field Frequency range (-10dB) of 80Hz to 16kHz; Power handling of 64 Watt peak; Nominal
dispersion of 110 Conical; Free field Sensitivity of 84 dB SPL and Max SPL of 103 dB SPL peak;
Nominal Impedance 8 Ohms; Integral multi-tap Transformer with tap settings of 2/4/8/16 W @
100V. with Powder-coated steel grille; Shall include necessary standard hardware for ceiling
install.
Approved Make: Bose/EAW/Martin Audio
Bose DS 16F
1221 Supply , installation , testing and commissioning of AEC capable Digital Audio Conferencing Nos 1
Processor with at least 12 AEC Mic/Line inputs & 8 analog outputs, 24 Bit A-D and D-A
Convertors; Sampling Rate : 48 kHz; THD : < 0.002 % ; Channel Separation (Crosstalk) : < 108
dB ; Frequency Response 20 Hz - 20 kHz ; Signal-to-Noise Ratio 90 dB ;Dynamic Range > 115
dB; 5 Control Inputs and Outputs; RS-232 and Ethernet Port for third party Control and
Monitoring; 64x64 Bidirectional DANTE Audio Networking ports, Shall include standard
Connectivity features like VOIP, POTS, USB Audio etc. inbuilt DSP features like Conference
room Routers, Input Equalizers, Router, Band Pass filter, Output Equalizer, Delay, Limiters,
gates , Source selectors etc. Shall Support at least 15 remote Zone controllers.
Approved Make: Bose / Symetrix / Bi-amp
Bose EX 1280C

1222 Supply, installation, testing & Commissioning of Class D configurable amplifier with total 600W Nos 1
output power or better across 4 outputs, 4/8ohms, 70/100 Volt or mixed use operation;
Frequency Response : 20Hz - 20kHz for LZ mode ; S/N Ratio > 99db and THD <.3% at rated
output complete with standard accessories as required. Built in DSP for Matrix routing, Speaker
EQs, delays etc.
Approved Make: Bose / Labgrupen / Powesoft
Bose PS 604
1223 Supply , installation , testing and commissioning of 2 core 2.5 sq mm PVC insulated Cu Mtr. 200.00
conduction loudspeaker cable with Conductor 50 x 0.25 mm, Impedance 7.0 Ω/km Capacitance
170 pF/m, Outer dia 8.0 mm, working temperature -20 °C / +70 °C.
Approved Make: Belden / Klotz / Canare
Klotz
LY 225
1224 Supply , installation , testing and commissioning of 5,300 ISO lumens, WUXGA resolution and Nos 1
3,000,000:1 on/off contrast ratio Complete with standard accessories as per tender specification.
Approved Make: Christie / Barco / Digital projection
Christie LWU 530 APS

1225 Supply ,installation ,testing and commissioning of 16:10, 120-135" motorised projection screen Nos 1
with IR remote and low Voltage Control Module complete with standard accessories as per
tender specifications.
Approved Make: Suvira / Liberty / draper
Suvira 120" (16:9)
1226 Supply, installation, testing & Commissioning of Full High Definition Video Nos 1
Conferencing System Full HD 1080p Point to point Video conferencing with 12X optical zoom
full HD integrated camera, RF remote control and 1 No. omni directional microphone as per
tender specs.
Approved Make: Cisco / Polycom / Sony
Sony PCS-XG100
1227 Supply, installation, testing & Commissioning of HD MCU Plus Multipoint Software Option Nos 1
License. Allows for 9 (1+8) site MP video calls. Available for FHD.
Approved Make: Cisco / Polycom / Sony
Sony PCSA-MCG109
1228 Supply ,installation ,testing and commissioning of 7" A space-saving wall, lectern, tabletop, or Nos 1
rack mount touch screen featuring a clean, contemporary appearance with edge-to-edge glass
Touch panel to control all the controls provided in system for hassel free operation complete with
standard accessories as per tender specifications.
Approved Make: Crestron / Extron / Kramer
Crestron TSW 760 with brackets
1229 Supply ,installation ,testing and commissioning of Twisted Pair receiver . Input - Twisted Pair, Nos 1
Output - HDMI, Resolution support UPTO 4K, 4:4:4 @ 30Hz, Distance of Transmission
Minimum 50 meters for 4K, Controls 1 Ethernet, 1 RS232, Should be compatible. With HDCP
and EDID complete with standard accessories as per tender specifications.
Approved Make: Crestron / Extron / Kramer
Crestron DM-RMC-4K-100-C

[78/80]
Page - 79
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1230 SITC of custom VGA-HDMI Cable manager in Anodized metallic finish, Shall include LAN, Nos 4
Phone and Power connectors as required.
Approved Make: Custom
Logic Cable manager
1231 Supply ,installation ,testing and commissioning of HDBaseT Transmitter with 2x1 AV switcher Nos 2
and it Can be connected to HDBaseT Receiver or HDBaseT Switcher Input of same oem over a
Single Cat Type Cable complete with standard accessories as per tender specifications.
Approved Make: Crestron / Extron / Kramer
DM-TX-201-C

1232 9x4 matrix switcher with Quick switch technology. HDMI input signal with Deep color, and 4K Nos 1
support. Output on 2 nos CaTx and 2 nos HDMI scaled. Outout HDMI should be 4K up-scaled
with content-adaptive noise reduction, and widescreen format selection. Device should have in-
built control processor. Should have 512MB RAM and 4GB of flash memory. Should have at
least 2x RS-232, 4x IR & 4x Relays. Device to haveDHCP, H.264 decoding, MJPEG decoding,
HDCP 2.2.
Approved Make: Crestron/Extron/Kramer
DMPS-4K-350-C
1233 Supply , installation , testing and commissioning of Microphone control unit/processor for Nos 1
Connection of microphone units in two lines or a ring using standard computer Cat5e cables . A
maximum of 100 microphone unit can be connected (50 per line) without redundancy or a
maximum of 50 microphone units in a ring with redundancy for maximum as per the tender
specifications.
Approved Make: Beyer dynamic / brahler / marconi technologies
Beyer dynamics Orbis CU
1234 Supply , installation , testing and commissioning of Delegate Unit with a soft touch button with Nos 18
tactile feedback for turning the microphone on/off for conferencing system complete with
standard accessories as per tender specification.
Approved Make: Beyer dynamic / brahler / marconi technologies
BeyerdynamicsMU41
1235 Supply , installation , testing and commissioning of chairman Unit for conferencing system. the Nos 1
microphone unit shall be provided with three soft touch buttons with tactile feedback for turning
the microphone on/off, for clearing
all active delegate microphone units and for the priority as per the tender specifications.
Approved Make: Beyer dynamic / brahler / marconi technologies
BeyerdynamicsMU43
1236 Supply , installation , testing and commissioning of 16 Inch condenser gooseneck microphone Nos 19
(electret) with cardioid polar pattern The two flexible goosenecks (8 mm bottom, 6 mm top) shall
have a rigid tube in between Pressure gradient Frequency response Close miking: 40 - 13,000
Hz Distant miking (distance 1 m): 200 - 13,000 Hz.
Approved Make: Beyer dynamic / brahler / marconi technologies
Beyer dynamic Classis GM115Q
1237 Supply , installation , testing and commissioning of System cable CAT5 with RJ45 Connector 2m Nos 18
as per the tender specifications.
Approved Make: Beyer dynamic / brahler / marconi technologies
Beyer dynamics OC2
1238 Supply , installation , testing and commissioning of System cable CAT5 with RJ45 Connector Nos 2
20m as per the tender specifications.
Approved Make: Beyer dynamic / brahler / marconi technologies
Beyer dynamics OC20
1239 Supply , installation , testing and commissioning of 16 Inch condenser gooseneck microphone Nos 19
(electret) with cardioid polar pattern The two flexible goosenecks (8 mm bottom, 6 mm top) shall
have a rigid tube in between Pressure gradient Frequency response Close miking: 40 - 13,000
Hz Distant miking (distance 1 m): 200 - 13,000 Hz as per the tender specifications.
Approved Make: Beyer dynamic / brahler / marconi technologies
Beyer dynamics Classis GM 115Q

1240 Supply of 802.11b/g/n compatible wireless access point, 3-5W or better Antenna. Nos 1
Approved Make: CISCO/Netgear / D-Link
Cisco / LinksysWAP
1241 Supply of LIII managed Gigabit switch with at least 8-10 copper ports. Nos 1
Approved Make: CISCO/Netgear / D-Link
Cisco / Linksys 8-10 Port network Switch
1242 Supply , installation , testing and commissioning of VGA Micro HR with Audio Cable: 15-pin HD Nos 4
Male to Male Low-Profile Molded + 3.5mm Stereo Mini Plug Male to Male - 6' (1.8 m) complete
with standard accessories as per tender specifications.
Approved Make: AMX / Crestron / Extron
Crestron CBL-VGA-AUD-6
1243 Supply , installation , testing and commissioning of 4K Premium High Speed HDMI Ultra-Flexible Nos 8
Cable - 6' (1.8 m) complete with standard accessories as per tender specifications.
Approved Make: AMX / Crestron / Extron
Crestron CBL-HD-6
1244 Supply , installation , testing and commissioning of Shielded Digital Twisted Pair Cable for XTP Mtrs 150.00
& DTP products - Non-Plenum, 1000' (305 m) spool complete with standard accessories as per
tender specifications.
Approved Make: AMX / Crestron / Extron
Crestron DM-CBL-8G-NP-SP

[79/80]
Page - 80
Bill of Quantities (BoQ)

Sl. No Description Unit Quantity. Rate Amount


1245 Supply , installation , testing and commissioning of2 core Shielded mm PVC Insulated Mtrs 300.00
Microphone cable with Ultra low Capacitance 60(Pf/m) ; Outer Jacket : PVC Matt ; Working
Temperature :20 °C / +70 °C ; Diameter : 6.5mm ; extremely flexible.
Approved Make: Belden / Klotz / Canare
Klotz
MY 206
1246 Supply , installation , testing and commissioning of Shielded Cat X Cable complete with Mtrs 50.00
standard accessories as per tender specifications.
Approved Make: D-Link / Netgear
D-Link NCB-C6SGRYR-305
1247 Supply , installation , testing and commissioning of 16U Equipment rack to house all rack Nos 1
mountable equipment, with internal wiring, front glass door, heat dissipation fans, power
distribution units etc. Complete with standard accessories as per tender specifications.
Approved Make: Chief / Middle Atlantica / Valrack
Valrack 16U

[80/80]

You might also like