FEATURES OF THE SYSTEM


Ease of installation
Smooth surface, suitable for any option of floor
covering (carpet, PVC, natural stone, HPL, etc)
Fire rated material
High design flexibility
High static resistance

THE PANELLED ACCESS FLOOR

Knauf
FLOOR SYSTEMS
Planning the future today
Support and joint

PT. Knauf Gypsum Indonesia Knauf Hong Kong Ltd. Knauf Singapore Pte Ltd
The Landmark Center, Tower A - 19th Floor Unit A, 7/F., 80 Marine Parade Rd #21-03
Jl. Jendral Sudirman No. 1, Jakarta 12910 Empire Land Commercial Centre, Parkway Parade
Indonesia 81-85 Lockhart Road, Singapore 449269
Tel. : (+62 21) 522 9558
Fax. : (+62 21) 522 9942
Wanchai, Hong Kong
Tel. : (852)2964-9311
Tel. : (+65) 6345 9233
Fax. : (+65) 6345 5465 I N T E G R A L R A I S E D AC C E S S F LO O R
website : www.knauf.co.id Fax. : (852)2964-9313 website : www.knauf.co.uk
E-mail: techteam@knauf.co.id
or sales@knauf.co.id
KNAUF INTEGRAL‘S PLASTER FIBRE MATERIAL INSTALLATION GUIDES

Combines the constructive and conditioning qualities of gypsum material 1. Ensure the floor ground is plumb and clean from dust. If necessary, apply
one coat of sealer to ensure the floor ground is applicable for installing
with extreme loadbearing capacity and the highest class of fire resistance,
pedestals.
thanks to its special formulation combining gypsum, fibres and mineral

aggregates. 2. Mark the level of the raised floor using levelling tool and mark the
perimeter of working area where the raised floor system will be installed.
Also mark the pedestal position depending on the layout of the floor panels,
Guarantees a level surface that retains its shape and is pleasant to walk
Technical Data
a continous band of rock wool (minimum thickness : 5mm, width : 200mm,
Thickness 34mm (tolerance : +/- 0.2mm)
density : 80kg/m3) should be applied around the perimeter to seal the gap
on while being statically reliable, thanks to the special technology used Length 600mm (tolerance : +2mm)
Width 600mm (tolerance : +2mm) between the wall abutment and the Knauf raised floor panel. Use a suitable
Working load 3000N (305 kgf ) adhesive.
Breaking load 6000N (612 kgf)
FIELDS OF APPLICATION
Adhesion bond strength 1 MPa (10.2 kgf/cm²) 3. Apply special adhesive to pedestal and install at marked position. Press
The use of Knauf Integral access floors is recommended wherever electric Flexural Strength 2.2 MPa (22.4 kgf/cm²) firmly the pedestals to ensure the adhesive well applied. Check the pedestal
Weight 51 kg/m²
installation is required, in new buildings and when refurbishing and level using levelling tool with minimum length 1 m. The pedestal height can
Density 1.5 g/cm³ +/- 0.05
be adjusted. Lock the adjuster using adhesive. Use a stringer if the pedestal
modernising older buildings : Static Resistance 107 Ω (Ohm)
height is more than 500mm. Use isolator plates to reduce the vibration and
• Offices and administrative buildings Flanking level difference (normalised) 50 dB
Impact sound level (normalised) 64 dB impact noise.
• Electronic data processing and distribution switchboard rooms
Fire Performance Class A1 (as per DIN EN 13 501
• TV and sound studios, computer and training centres Fire Resistance F30 (as per DIN 4102 part2)

Knauf Integral - Access floor panel