Professional Documents
Culture Documents
Analysis Report
DP WORLD
Youssef Mohamed
28-Jun-20
DP World Our Ref.: I.YM.J200628
Motors: >>>>> #AN Boom, #AN Hoist 1, #AN Hoist 2, #AN Trolley
Dear Sirs,
With reference to the above subject, kindly find below the comprehensive detailed analysis
report of electrical motor testing MCEmax test for the above motor measured at DP-World
Company.
Sincerely,
Youssef Mohamed
Title
3
AC INDUCTION MOTOR MCE REPORT
4
AC INDUCTION MOTOR MCE REPORT
(Passed)
5
AC INDUCTION MOTOR MCE REPORT
(Passed)
6
AC INDUCTION MOTOR MCE REPORT
➢ AC Standard Test
7
AC INDUCTION MOTOR MCE REPORT
PI Value: 1.190
DA Ratio: 1.129
8
AC INDUCTION MOTOR MCE REPORT
9
AC INDUCTION MOTOR MCE REPORT
(Passed)
10
AC INDUCTION MOTOR MCE REPORT
(Passed)
11
AC INDUCTION MOTOR MCE REPORT
AC Standard Test
12
AC INDUCTION MOTOR MCE REPORT
PI Value: 0.865
DA Ratio: 0.969
13
AC INDUCTION MOTOR MCE REPORT
14
AC INDUCTION MOTOR MCE REPORT
(Passed)
15
AC INDUCTION MOTOR MCE REPORT
(Passed)
16
AC INDUCTION MOTOR MCE REPORT
AC Standard Test
17
AC INDUCTION MOTOR Alarm Limits
PI Value: 1.346
DA Ratio: 1.134
18
AC INDUCTION MOTOR Alarm Limits
o #AN (STS- Hoist 1-116), Electrical motor test Results (Power Circuit, Insulation, Rotor, Stator,
Eccentricity) are considered normal and within limits.
o Power Quality: Exceeding the full loaf amp. rating of the motor could result over heating of the
insulation system.
Recommendation Action: Reduce the load or limit the over current.
o Inductive Imbalance is in caution area,
o Recommendation action: nothing to serve, just trending over time (4-6) weeks.
o Also, we need to perform Rotor influence check Test to isolate the problem if it comes from rotor or
stator.
o #AN (STS -Hoist 2- 116), Electrical motor test Results (Power Circuit, Insulation, Rotor, Stator,
Eccentricity) are considered normal and within limits.
o Power Quality: Exceeding the full loaf amp. rating of the motor could result over heating of the
insulation system.
Recommendation Action: Reduce the load or limit the over current.
o Inductive Imbalance is in caution area,
o Recommendation action: nothing to serve, just trending over time (4-6) weeks.
o Also, we need to perform Rotor influence check Test to isolate the problem if it comes from rotor or
stator.
19
AC INDUCTION MOTOR Alarm Limits
ALARM LIMITS:
Default warning setting are determined by using a combination of accepted industry standards, manufacturing data,
NEMA standards and empirical data collected by PdMA during research and development
20