99 BATTERY PLACE

TENANT PROTECTION PLAN GENERAL NOTES


BATTERY PLACE
1. EGRESS - AT ALL TIMES DURING THE PERIOD OF CONSTRUCTION A PROTECTED PATHWAY THAT MEETS THE MINIMUM REQUIREMENTS OF BC 3307
SHALL BE MAINTAINED FOR EGRESS. ALL AREAS NOT REQUIRED FOR EGRESS WILL BE LIMITED TO CONSTRUCTION PERSONNEL.
1. SCOPE OF WORK: RENOVATIONS OF EXISTING APARTMENT 27A. ARCHITECTURAL PARTITIONS, DOORS, CABINETRY, INTERIOR DEMOLITION,
MECHANICAL AND PLUMBING WORK. NO CHANGE OF USE, OCCUPANCY OR EGRESS.
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
RENOVATION TO UNIT A, 27TH FLOOR 2. FIRE SAFETY - AT ALL TIMES DURING CONSTRUCTION THE REQUIREMENTS FOR FIRE SAFETY OUTLINED UNDER BC 3033 ARE TO BE MAINTAINED.
A. ALL BUILDING MATERIALS WHICH ARE STORED AT THE SITE OR ANY AREA OF THE BUILDING ARE TO BE STORED IN A LOCKED AREA.
2. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE NEW YORK CITY BUILDING CODE, FIRE DEPARTMENT RULES AND REGULATIONS,
UTILITY COMPANY REQUIREMENTS, AND THE BEST TRADE PRACTICES.
335 MADISON AVENUE
ACCESS TO THE AREA TO BE CONTROLLED BY THE OWNER, OR THE GENERAL CONTRACTOR. NEW YORK, NY 10017
B. ALL MATERIALS TO BE STORED IN AN ORDERLY FASHION. 3. BEFORE COMMENCING WORK, THE CONTRACTOR SHALL FILE ALL REQUIRED INSURANCE CERTIFICATES WITH THE DEPARTMENT OF BUILDINGS, (212) 308-7200
INDEX OF DRAWINGS C. ALL FLAMMABLE MATERIALS TO BE TIGHTLY SEALED IN THEIR RESPECTIVE MANUFACTURER'S CONTAINERS. SUCH MATERIALS ARE TO BE OBTAIN ALL REQUIRED PERMITS, AND PAY ALL FEES REQUIRED BY THE GOVERNING NEW YORK CITY AGENCIES.
KEPT AWAY FROM HEAT.
SHEET NUMBER DRAWING # DRAWING NAME D. ALL FLAMMABLE MATERIALS TO BE USED AND STORED IN AN ADEQUATELY VENTILATED SPACE. 4. MINOR DETAILS NOT USUALLY SHOWN OR SPECIFIED, BUT REQUIRED FOR PROPER CONSTRUCTION OF ANY PART OF THE WORK SHALL BE
ARCHITECTURE E. ALL ELECTRICAL POWER TO BE SHUT OFF WHERE THERE ARE EXPOSED CONDUITS. INCLUDED AS IF THEY WERE INDICATED IN THE DRAWINGS.
1 T001.00 COVER SHEET, NOTES, PLOT & LOCATION PLANS F. ALL ELECTRICAL POWER IN THE CONSTRUCTION AREA TO BE SHUT OFF AFTER WORKING HOURS. CONTRACTOR, AT ALL T
2 D100.00 PH A - DEMOLITION PLAN 5. THE CONTRACTOR SHALL COORDINATE ALL WORK PROCEDURES WITH THE STIPULATIONS OF LOCAL AUTHORITIES, BUILDING MANAGEMENT OR
3. HEALTH REQUIREMENTS - THE CONTROL OF DUST, DISPOSAL OF DEBRIS, CONTROL OF PEST AND MAINTENANCE OF SANITARY FACILITIES SHALL BOARD OF DIRECTORS.
3 D101.00 PH B - DEMOLITION PLANS
CONFORM TO THE REQUIREMENTS OF BC 3033.
4 D102.00 PH CE - DEMOLITION PLANS A. NOISE RELATED TO CONSTRUCTION SHALL CONFORM TO THE RULES OUTLINED, IN THE CITY WIDE CONSTRUCTION NOISE MITIGATION, 6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL CONDITIONS AND MATERIALS WITHIN THE PROPOSED CONSTRUCTION
5 D103.00 PH H - DEMOLITION PLANS CHAPTER 28 OF TITLE 15 OF THE RULES OF THE CITY OF NEW YORK. AREA. THE CONTRACTOR SHALL DESIGN AND INSTALL ADEQUATE SHORING AND BRACING FOR ALL STRUCTURAL OR REMOVAL TASKS. THE
6 A001.00 WALL TYPES, ADA DIAGRAMS B. CONSTRUCTION SHALL BE PERFORMED WITH RESPECT TO ASBESTOS AS OUTLINED IN SECTION 106 ASBESTOS AND THE ASBESTOS CONTRACTOR SHALL HAVE SOLE RESPONSIBILITY FOR ANY DAMAGE OR INJURIES CAUSED BY OR DURING THE EXECUTION OF THE WORK.
7 A002.00 SPECIFICATIONS CONTROL PROGRAM / ASBESTOS RULES AND REGULATIONS TITLE 15 CHAPTER 1 OF THE RULES OF THE CITY OF NEW YORK.
C. CONSTRUCTION WITH RESPECT TO LEAD SHALL CONFORM TO ALL NYC DOH REQUIREMENTS. 7. THE CONTRACTOR SHALL LAY OUT HIS OWN WORK, AND SHALL PROVIDE ALL DIMENSIONS REQUIRED FOR OTHER TRADES: PLUMBING,
8 A100.00 PH A - CONSTRUCTION PLAN
ELECTRICAL, ETC.
9 A101.00 PH B - CONSTRUCTION PLANS 4. COMPLIANCE WITH HOUSING STANDARDS - CONSTRUCTION SHALL NOT AFFECT ANY OF THE REQUIREMENTS OUTLINED IN THE NEW CITY
10 A102.00 PH CE - CONSTRUCTION PLANS MULTIPLE DWELLING LAW OR NYC HOUSING MAINTENANCE CODE WITHOUT PROVIDING TEMPORARY SOLUTIONS TO THAT MEET THE 8. PLUMBING WORK SHALL BE PERFORMED BY PERSONS LICENSED IN THEIR TRADES, WHO SHALL ARRANGE FOR AND OBTAIN THROUGH THE
11 A103.00 PH H - CONSTRUCTION PLANS REQUIREMENTS OUTLINED IN THE RESPECTIVE LAWS. DEPARTMENT OF BUILDINGS ALL REQUIRED PERMITS, INSPECTIONS AND REQUIRED SIGN OFFS.
12 A200.00 PH A - REFLECTED CEILING PLAN
5. STRUCTURAL SAFETY - TO ENSURE THAT NO STRUCTURAL WORK SHALL BE DONE THAT MAY ENDANGER OCCUPANTS, ANY STRUCTURAL WORK 9. ELECTRICAL WORK SHALL BE PERFORMED BY PERSONS LICENSED IN THEIR TRADES, WHO SHALL ARRANGE FOR AND OBTAIN THROUGH THE
13 A201.00 PH B - REFLECTED CEILING PLANS
TEMPORARY OR PERMANENT TO BE PERFORMED SHALL CONFORM WITH BC 3305 AND SUBMITTED IN THE FORM SHOP DRAWINGS FOR APPROVAL BUREAU OF ELECTRICAL CONTROL ALL REQUIRED PERMITS, INSPECTIONS AND REQUIRED SIGN OFFS.
14 A202.00 PH CE - REFLECTED CEILING PLANS BY THE STRUCTURAL APPLICANT OF RECORD PRIOR TO COMMENCING WORK
15 A210.00 PH A - POWER & FINISH PLAN 10. THE CONTRACTOR SHALL DO ALL CUTTING, PATCHING, REPAIRING AS REQUIRED TO PERFORM ALL OF THE WORK INDICATED ON THE DRAWINGS,
16 A203.00 PH H - REFLECTED CEILING PLANS 6. NOISE RESTRICTIONS - HOURS OF CONSTRUCTION SHALL BE RESTRICTED BASED ON THE GUIDELINES OF AC 28-105.12.5 AND ALL OTHER WORK THAT MAY BE REQUIRED TO COMPLETE THE JOB.
17 A211.00 PH B - POWER & FINISH PLANS
18 A212.00 PH CE - POWER & FINISH PLANS 7. DUST CONTROL: 11. ALL PIPING AND WIRING SHALL BE REMOVED TO A POINT OF CONCEALMENT AND SHALL BE PROPERLY CAPPED OR PLUGGED.
A. DEBRIS, DIRT, AND DUST TO BE KEPT TO A MINIMUM AND CONFINED TO THE IMMEDIATE CONSTRUCTION AREA.
19 A213.00 PH H - POWER & FINISH PLANS B. CONTRACTOR TO ISOLATE CONSTRUCTION AREA FROM OCCUPIED BUILDING AREA BY MEANS OF TEMPORARY PARTITIONS OR HEAVY 12. ALL PLUMBING WORK SHALL BE PERFORMED AND FILED BY A LICENSED PLUMBING CONTRACTOR.
20 A301.00 PHA - ELEVATIONS WEIGHT DROP CLOTHS.
21 A300.00 PHA - ELEVATIONS C. DEBRIS, DIRT, AND DUST TO BE CLEANED UP AND CLEARED FROM THE BUILDING SITE PERIODICALLY TO AVOID EXCESSIVE 13. ALL ELECTRICAL WORK SHALL BE PERFORMED AND FILED BY LICENSED ELECTRICAL CONTRACTOR.
22 A302.00 PHB - ELEVATIONS ACCUMULATION
23 A303.00 PHB - ELEVATIONS 14. ALL MATERIAL AND EQUIPMENT SHALL COMPLY WITH BC 28-113.1. ALL FINISHES SHALL COMPLY WITH TABLE 803.5. ALL EXIT DOORS AND
8. CONSTRUCTION OPERATIONS WILL NOT INVOLVE INTERRUPTION OF HEATING, WATER, OR ELECTRICAL SERVICES TO OTHER TENANTS. ASSEMBLIES SHALL COMPLY WITH BC 1008 & BC 1017.2.
24 A304.00 PHCE - ELEVATIONS
25 A305.00 PHCE - ELEVATIONS 9. CONSTRUCTION WORK WILL BE CONFINED TO THE APARTMENT INTERIOR, AND WILL NOT CREATE DUST, DIRT, OR OTHER SUCH 15. ALL EXITS SHALL BE KEPT READILY ACCESSIBLE AND UNOBSTRUCTED AT ALL TIMES. A MINIMUM AISLE WIDTH OF THREE FEET LEADING TO AN
26 A306.00 PHH - ELEVATIONS INCONVENIENCES TO THE OTHER APARTMENTS UNITS WITHIN THE BUILDING. EXIT SHALL BE MAINTAINED.
27 A307.00 PHH - ELEVATIONS
28 A308.00 PHH - ELEVATIONS 10. THERE WILL BE NO ONE OCCUPYING THE PREMISES TO BE RENOVATED DURING THE COURSE OF THE CONSTRUCTION WORK.
29 A400.00 DETAILS
30 A401.00 DETAILS
SMOKE/CARBON MONOXIDE DETECTOR NOTES DEMOLITION NOTES

1. SMOKE/CARBON MONOXIDE DETECTORS OR DEVICES SHALL BE INSTALLED IN ORDINANCE WITHE THE HOUSING MAINTENANCE CODE, MULTIPLE 1. THE CONTRACTOR SHALL FURNISH ALL LABOR AND MATERIALS AS REQUIRED TO COMPLETE DEMOLITION AND REMOVAL OF ALL ITEMS AS
DWELLING LAW, THE NEW YORK CITY BUILDING CODE, THE NEW YORK CITY ELECTRICAL CODE AND NFPA 72. INDICATED ON THE DRAWINGS.

2. SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS MAY BE COMBINED PROVIDING THE DEVICES COMPLY WITH THE PROVISIONS OF TITLE 2. ALL WORK DEMOLISHED SHALL BE REMOVED FROM THE PREMISES EXCEPT ITEMS TO BE REUSED OR AS OTHERWISE DIRECTED.
28 OF THE ADMINISTRATIVE CODE OF THE CITY OF NEW YORK AND ANY APPLICABLE RULES PROMULGATED THEREUNDER.
3. THE CONTRACTOR SHALL REMOVE ALL WALL CONDUITS LEFT AFTER WALL DEMOLITION, INCLUDING SWITCH BOXES, PLATE BRIDGES OR ANY
3. EACH SMOKE/CARBON MONOXIDE DETECTOR SHALL BE INSTALLED IN ACCORDANCE WITH REFERENCE STANDARD UL 2034 AND UL 2075 OF THE OTHER TELEPHONE, ELECTRICAL OR COMPUTER WIRING AND EQUIPMENT.
NEW YORK CITY BUILDING CODE.
4. IN ALL AREAS WHERE DEMOLITION OF WALLS AND/OR CONCRETE PADS CAUSES AN UNEVENNESS IN FLOORS, THE CONTRACTOR SHALL PATCH
4. EACH SMOKE/CARBON MONOXIDE DETECTOR SHALL BE INSTALLED OUTSIDE OF EACH SLEEPING ROOM IN THE IMMEDIATE VICINITY OR WITHIN THE FLOOR.
15'-0" OF THE ENTRANCE TO A SLEEPING ROOM; INSIDE EACH SLEEPING ROOM; AND ON EACH STORY WITHIN A DWELLING UNIT, INCLUDING
BELOW GRADE STORIES AND PENTHOUSES PER 908.7.1.1.1 5. ALL EXPOSED LIGHT FIXTURES, WIRING, ELECTRICAL PANELS AND METAL MOLDING NOT TO BE REUSED SHALL BE CARTED AWAY BY THE
CONTRACTOR.
5. EACH SMOKE/CARBON MONOXIDE DETECTOR SHALL BE OF A TYPE THAT ALLOWS FOR READILY TESTING FROM EACH LEVEL.
6. THE CONTRACTOR SHALL ERECT ALL NECESSARY PLASTIC DROP CLOTH PARTITIONS TO PROTECT ADJACENT BUILDING PROPERTY WHILE
6. DUPLEX UNITS SHALL HAVE A DEVICE LOCATED ON EACH LEVEL IF ONLY ONE MEANS OF EGRESS IS PROVIDED FROM EACH LEVEL. DEMOLITION AND CONSTRUCTION ARE IN PROGRESS.

7. CEILING MOUNTED DEVICES SHALL BE A MINIMUM DISTANCE OF 4" FROM ANY WALL. 7. THE CONTRACTOR SHALL FURNISH A SYSTEM OF TEMPORARY LIGHTS THROUGHOUT THE SPACE UNDER CONSTRUCTION, AS REQUIRED.

8. WALL MOUNTED DEVICES SHALL BE A MINIMUM OF 4" TO A MAXIMUM OF 12" FROM THE CEILING. 8. UPON COMPLETION OF THE DEMOLITION WORK, THE CONTRACTOR SHALL PROVIDE THAT ALL AREAS ARE TO BE LEFT BROOM CLEAN. ISSUED FOR BID 05/18/2020
9. EACH DWELLING UNIT SHALL BE EQUIPPED WITH AN APPROVED TYPE SMOKE/CARBON MONOXIDE DETECTOR DEVICE RECEIVING PRIMARY 9. THE CONTRACTOR TO PROPERLY CAP ALL PLUMBING LINE WHERE THE FIXTURES ARE TO BE REMOVED. NO. DESCRIPTION DATE
POWER FROM THE BUILDING WIRING WITH NO SWITCHES IN THE CIRCUIT OTHER THAN THE OVER CURRENT DEVICE PROTECTION THE BRANCH
CIRCUIT AS PER NEW YORK CITY BUILDING CODE SEC. 907.2.10.2 THROUGH 907.2.10.4

10. EXISTING BUILDINGS THAT ARE NOT EQUIPPED WITH HARDWIRED CONNECTIONS SHALL BE SUPPLIED WITH BATTERY OPERATED DEVICES.

11. SUCH SMOKE/CARBON MONOXIDE DETECTOR MUST BE EITHER THE IONIZATION CHAMBER TYPE OR THE PHOTOELECTRIC DETECTOR TYPE AS
PER NEW YORK CITY BUILDING CODE SEC. 907 AND 908.

12. A "CERTIFICATE OF SATISFACTORY INSTALLATION FOR SMOKE/CARBON MONOXIDE DETECTORS" MUST BE FILED WITH THE DIVISION OF CODE
ENFORCEMENT H.P.D., 10 DAYS AFTER INSTALLATION.

13. WRITTEN INFORMATION OF TESTING AND MAINTENANCE OF THE DEVICES SHALL BE PROVIDED TO THE DWELLING UNIT OWNER.

14. IN MULTIPLE DWELLINGS (R-2), SMOKE ALARMS SHALL BE ABLE TO SUPPORT VISIBLE ALARM PER ANSI A117.1.

PROJECT INFORMATION

BUILDING ADDRESS: 99 BATTERY PLACE, NEW YORK, NY, 10280 TYPE OF CONSRTUCTION: CLASS A APARTMENTS PROJECT TITLE:
ENERGY CONSERVATION CONSTRUCTION CODE
BLOCK NUMBER: 16 SPRINKLER SYSTEM: NO PENTHOUSE UNITS
LOT NUMBER: 7510 LANDMARK: NO TO THE BEST OF MY KNOWLEDGE, BELIEF AND PROFESSIONAL JUDGEMENT, ALL WORK UNDER THIS APPLICATION IS IN COMPLIANCE WITH THE NYCECC
2016
RENOVATIONS
ZONING DISTRICT: BPC STORY HEIGHT: 28 FLOORS 26, 27, 28
MAP NUMBER: 12B FLOOR AREA: 251,929 SF LIBERTY VIEW
PLOT PLAN 99 BATTERY PLACE
USE GROUP: MIXED RESIDENTIAL AND COMMERCIAL LOT AREA: 24,167 SF
NEW YORK, NEW YORK 10280
OCCUPANCY: R-10

W AY
INSPECTIONS REEN
ER G
O N RIV
HUDS "
203'-9
1. SPECIAL AND PROGRESS INSPECTIONS SHALL BE PERFORMED PRIOR TO SIGN-OFF AND PRIOR TO THE RELEASE OF FINAL PAYMENT TO THE
CONTRACTOR, IN RTICLE 116 OF THE NEW YORK CITY GENERAL ADMINISTRATIVE PROVISIONS FOR CONSTRUCTION CODES.

2. THE CONTRACTOR IS TO NOTIFY THE ARCHITECT, ENGINEER, AND/OR INSPECTOR, A MINIMUM OF 72 HOURS PRIOR TO THE COMPLETION OR DOB SCAN STICKER
COMMENCEMENT OF WORK REQUIRING SPECIAL OR PROGRESS INSPECTIONS.
DRAWING TITLE:
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY REPAIRS, ALTERATIONS, CORRECTIONS, OR ANY OTHER ADDITIONAL WORK THAT MAY BE AREA OF WORK:
COVER SHEET, NOTES,
143'-2"

REQUIRED IN ORDER TO CONFORM TO THE APPROVED SPECIAL AND PROGRESS INSPECTIONS. 26, 27, 28 FLOOR
UNIT PHA, PHB,
4. FINAL INSPECTION AS PER DIRECTIVE 14 SHALL BE PERFORMED AT THE COMPLETION OF THE CONSTRUCTION. PHCE, PHH PLOT & LOCATION PLANS
99'-5"
W. THAMES STREET

THIRD PLACE

PROGRESS INSPECTIONS:

A. FIRE-RESISTANCE RATED CONSTRUCTION BC 110.3.4

B. FINAL BC 110.5 SCALE: AS NOTED PAGE: 1 of 30


199'-0"
ENERGY CODE PROGRESS INSPECTIONS:

A.

B.
ELECTRICAL ENERGY CONSUMPTION (IC1), (IIC1)

INTERIOR LIGHTING POWER (IC2), (IIC2)


BATTERY PLACE
T001.00
C. LIGHTING CONTROLS (IC5)

SPECIAL INSPECTIONS:

A. FIRE RESISTANT PENETRATION AND JOINTS BC 1704.27


N

B. MECHANIACL SYSTEMS BC 1704.16

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200

NOT FOR CONSTRUCTION

DEMOLITION PLAN LEGEND ISSUED FOR BID 05/18/2020


NO. DESCRIPTION DATE

EXISTING NONBEARING WALL TO BE REMOVED EXISTING WALL TO REMAIN

EXISTING DOORS, FRAME AND EXISTING DOORS, FRAME AND


HARDWARE TO BE REMOVED HARDWARE TO BE REMAIN

C PROJECT TITLE:
DEMOLITION NOTES PENTHOUSE UNITS
1. G.C. SHALL REMOVE ALL EXISTING WALLS, DOORS, FRAMES, HARDWARE AS INDICATED ON DEMOLITION PLAN. RENOVATIONS
LV/D 2. G.C. SHALL REMOVE ALL EXISTING ELECTRICAL OUTLETS, THERMOSTATS, SWITCHES ON WALLS BEING DEMOLISHED. PULL ALL WIRES BACK TO FLOORS 26, 27, 28
PANEL.
BR BR LIBERTY VIEW
B 3. G.C. SHALL REMOVE ALL EXISTING CARPET, TILE AND MISC. FLOORING AND VINYL BASE AND PREPARE WALLS AND FLOORS TO RECEIVE NEW 99 BATTERY PLACE
CHASE 2

FINISHES.
NEW YORK, NEW YORK 10280
REMOVE EXISTING 4. REFER TO PLUMBING, SPRINKLER, MECHANICAL, ELECTRICAL & FIRE ALARM DRAWINGS FOR EXTENT OF DEMOLITION.
CEILINGS, TYP.
5. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT AS REQUIRED TO COMPLETE DEMOLITION AND REMOVAL OF ALL
ITEMS SHOWN ON DRAWINGS.
C
6. ALL DEMOLITION DEBRIS SHALL BE REMOVED FROM THE PREMISES EXCEPT THOSE ITEMS TO BE REUSED, RETURNED TO THE LANDLORD /
OWNER, OR AS OTHERWISE DIRECTED.

7. THE CONTRACTOR SHALL CAREFULLY REMOVE, PROTECT AND STORE ALL CONSTRUCTION ELEMENTS TO BE REUSED OR RETURNED TO THE
R
LANDLORD / OWNER.
DOB SCAN STICKER
8. UPON COMPLETION OF THE DEMOLITION WORK, ALL AREAS SHALL BE BROOM CLEAN.
C DRAWING TITLE:
9. ALL CORE AREAS, ELEVATORS, STAIRWELLS AND EXISTING ELEMENTS TO REMAIN SHALL BE CAREFULLY SEALED AND PROTECTED FROM
DAMAGE AND DIRT. PH A - DEMOLITION PLAN
10. ALL PERIMETER FAN COIL AND EQUIPMENT, RADIATOR ENCLOSURE AND WINDOWS SHALL BE CAREFULLY COVERED AND PROTECTED FROM GRIT,
EXISTING WATERLINE. K RUBBISH AND DAMAGE.
PRTOECT DURING DEMO
11. WHERE EXISTING SWITCHES, OUTLETS AND PHONE / DATA OUTLETS ARE REMOVED, G.C. SHALL PATCH, SPACKLE AND SAND SMOOTH WALL FOR
PAINT. NO COVER PLATES SHALL BE USED.
CHASE 1

C 12. ALL DEMOLITION WORK INCLUDING FLOOR PENETRATIONS SHALL BE PERFORMED DURING HOURS PERMITTED BY THE BUILDING MANAGER AND /
OR THE CLIENT. SEE MEP DRAWINGS FOR MORE DETAILS.
SCALE: AS NOTED PAGE: 2 of 30
13. IN ALL AREAS WHERE DEMOLITION OR CUTS AND PATCHES CAUSE A UNEVENNESS IN THE SLAB, THE CONTRACTOR SHALL FLASH PATCH AS
REQUIRED TO RECEIVE THE NEW FLOOR FINISH. COORDINATE WITH FLOORING CONTRACTOR.

D100.00
G

14. THE GENERAL CONTRACTOR SHALL ERECT A PLASTIC DUST PARTITION TO PROTECT AREAS NOT INCLUDED IN THE SCOPE OF WORK.

15. PRIOR TO DEMOLITION, THE CONSTRUCTION AREA SHALL BE INSPECTED FOR PRESENCE OF ASBESTOS. IF PRESENT IT SHALL BE REMOVED IN
EXISTING GAS LINE.
COMPLIANCE WITH THE STATE OF NEW YORK REQUIREMENTS AND FEDERAL NESHAP (NATIONAL EMISSION STANDARD FOR HAZARDOUS AIR
PRTOECT DURING DEMO
POLLUTANTS) REGULATION. (NESHAP - PHONE: 1-617-565-9055).

16. WHERE REMOVALS ARE NOT POSSIBLE WITHOUT DAMAGE TO EXISTING TO REMAIN. G.C. SHALL REPAIR OR REPLACE DAMAGED ITEMS AS
REQUIRED.

PHA - DEMOLITION PLAN


1 1/4" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
REMOVE EXISTING WINDOW.
PROTECT OPENING DURING
(212) 308-7200
CONSTRUCTION

REMOVE EXTERIOR DOOR.


SAVE FOR RELOCATION.
PROTECT OPENING
DURING CONSTRUCTION.

CHASE 8
B

NOT FOR CONSTRUCTION


BR

C REMOVE EXISTING
CEILINGS, TYP.

RELOCATE EXAUST DUCT.


B SEE MECHANICAL

C
BR
CHASE 9

DEMOLITION PLAN LEGEND

EXISTING NONBEARING WALL TO BE REMOVED EXISTING WALL TO REMAIN

PHB - DEMOLITION PLAN UPPER


2 1/4" = 1'-0" NO.
ISSUED FOR BID
DESCRIPTION
05/18/2020
DATE
EXISTING DOORS, FRAME AND EXISTING DOORS, FRAME AND
HARDWARE TO BE REMOVED HARDWARE TO BE REMAIN

DEMOLITION NOTES
G

1. G.C. SHALL REMOVE ALL EXISTING WALLS, DOORS, FRAMES, HARDWARE AS INDICATED ON DEMOLITION PLAN.
CHASE 7

2. G.C. SHALL REMOVE ALL EXISTING ELECTRICAL OUTLETS, THERMOSTATS, SWITCHES ON WALLS BEING DEMOLISHED. PULL ALL WIRES BACK TO
PANEL. PROJECT TITLE:
PR 3. G.C. SHALL REMOVE ALL EXISTING CARPET, TILE AND MISC. FLOORING AND VINYL BASE AND PREPARE WALLS AND FLOORS TO RECEIVE NEW PENTHOUSE UNITS
FINISHES.
RENOVATIONS
4. REFER TO PLUMBING, SPRINKLER, MECHANICAL, ELECTRICAL & FIRE ALARM DRAWINGS FOR EXTENT OF DEMOLITION.
C FLOORS 26, 27, 28
5. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT AS REQUIRED TO COMPLETE DEMOLITION AND REMOVAL OF ALL
ITEMS SHOWN ON DRAWINGS. LIBERTY VIEW
99 BATTERY PLACE
6. ALL DEMOLITION DEBRIS SHALL BE REMOVED FROM THE PREMISES EXCEPT THOSE ITEMS TO BE REUSED, RETURNED TO THE LANDLORD /
LV/D OWNER, OR AS OTHERWISE DIRECTED. NEW YORK, NEW YORK 10280
7. THE CONTRACTOR SHALL CAREFULLY REMOVE, PROTECT AND STORE ALL CONSTRUCTION ELEMENTS TO BE REUSED OR RETURNED TO THE
LANDLORD / OWNER.

8. UPON COMPLETION OF THE DEMOLITION WORK, ALL AREAS SHALL BE BROOM CLEAN.
C REMOVE EXISTING
CEILINGS, TYP. 9. ALL CORE AREAS, ELEVATORS, STAIRWELLS AND EXISTING ELEMENTS TO REMAIN SHALL BE CAREFULLY SEALED AND PROTECTED FROM
DAMAGE AND DIRT.

10. ALL PERIMETER FAN COIL AND EQUIPMENT, RADIATOR ENCLOSURE AND WINDOWS SHALL BE CAREFULLY COVERED AND PROTECTED FROM GRIT,
RUBBISH AND DAMAGE.
DOB SCAN STICKER
11. WHERE EXISTING SWITCHES, OUTLETS AND PHONE / DATA OUTLETS ARE REMOVED, G.C. SHALL PATCH, SPACKLE AND SAND SMOOTH WALL FOR
PAINT. NO COVER PLATES SHALL BE USED.
DRAWING TITLE:

12. ALL DEMOLITION WORK INCLUDING FLOOR PENETRATIONS SHALL BE PERFORMED DURING HOURS PERMITTED BY THE BUILDING MANAGER AND / PH B - DEMOLITION
OR THE CLIENT. SEE MEP DRAWINGS FOR MORE DETAILS.
PLANS
13. IN ALL AREAS WHERE DEMOLITION OR CUTS AND PATCHES CAUSE A UNEVENNESS IN THE SLAB, THE CONTRACTOR SHALL FLASH PATCH AS
REQUIRED TO RECEIVE THE NEW FLOOR FINISH. COORDINATE WITH FLOORING CONTRACTOR.

14. THE GENERAL CONTRACTOR SHALL ERECT A PLASTIC DUST PARTITION TO PROTECT AREAS NOT INCLUDED IN THE SCOPE OF WORK.
EXISTING WATERLINE. K
PRTOECT DURING DEMO 15. PRIOR TO DEMOLITION, THE CONSTRUCTION AREA SHALL BE INSPECTED FOR PRESENCE OF ASBESTOS. IF PRESENT IT SHALL BE REMOVED IN
COMPLIANCE WITH THE STATE OF NEW YORK REQUIREMENTS AND FEDERAL NESHAP (NATIONAL EMISSION STANDARD FOR HAZARDOUS AIR SCALE: AS NOTED PAGE: 3 of 30
POLLUTANTS) REGULATION. (NESHAP - PHONE: 1-617-565-9055).

D101.00
16. WHERE REMOVALS ARE NOT POSSIBLE WITHOUT DAMAGE TO EXISTING TO REMAIN. G.C. SHALL REPAIR OR REPLACE DAMAGED ITEMS AS
REQUIRED.

EXISTING GAS LINE.


PRTOECT DURING DEMO

PHB - DEMOLITION PLAN LOWER


1 1/4" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200

CHASE 9
C

BR
NOT FOR CONSTRUCTION
C
REMOVE EXISTING
CEILINGS, TYP.

BR BR

CHASE 10
C

PHCE - DEMOLITION PLAN UPPER DEMOLITION PLAN LEGEND


2 1/4" = 1'-0" NO.
ISSUED FOR BID
DESCRIPTION
05/18/2020
DATE

EXISTING NONBEARING WALL TO BE REMOVED EXISTING WALL TO REMAIN

EXISTING WATERLINE. EXISTING DOORS, FRAME AND


EXISTING DOORS, FRAME AND
PRTOECT DURING DEMO HARDWARE TO BE REMAIN
HARDWARE TO BE REMOVED

G
C
PR
EXISTING WATERLINE.
B PRTOECT DURING DEMO
K
PROJECT TITLE:
EXISTING GAS LINE.
PRTOECT DURING DEMO DEMOLITION NOTES PENTHOUSE UNITS
CHASE 6

RENOVATIONS
CHASE 5

1. G.C. SHALL REMOVE ALL EXISTING WALLS, DOORS, FRAMES, HARDWARE AS INDICATED ON DEMOLITION PLAN.

C
C
2. G.C. SHALL REMOVE ALL EXISTING ELECTRICAL OUTLETS, THERMOSTATS, SWITCHES ON WALLS BEING DEMOLISHED. PULL ALL WIRES BACK TO FLOORS 26, 27, 28
PANEL.
LIBERTY VIEW
K
3. G.C. SHALL REMOVE ALL EXISTING CARPET, TILE AND MISC. FLOORING AND VINYL BASE AND PREPARE WALLS AND FLOORS TO RECEIVE NEW 99 BATTERY PLACE
FINISHES.
NEW YORK, NEW YORK 10280
EXISTING GAS LINE. 4. REFER TO PLUMBING, SPRINKLER, MECHANICAL, ELECTRICAL & FIRE ALARM DRAWINGS FOR EXTENT OF DEMOLITION.
PRTOECT DURING DEMO
5. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT AS REQUIRED TO COMPLETE DEMOLITION AND REMOVAL OF ALL
ITEMS SHOWN ON DRAWINGS.

6. ALL DEMOLITION DEBRIS SHALL BE REMOVED FROM THE PREMISES EXCEPT THOSE ITEMS TO BE REUSED, RETURNED TO THE LANDLORD /
OWNER, OR AS OTHERWISE DIRECTED.

E C 7. THE CONTRACTOR SHALL CAREFULLY REMOVE, PROTECT AND STORE ALL CONSTRUCTION ELEMENTS TO BE REUSED OR RETURNED TO THE
LANDLORD / OWNER.
DOB SCAN STICKER
REMOVE EXISTING 8. UPON COMPLETION OF THE DEMOLITION WORK, ALL AREAS SHALL BE BROOM CLEAN.
CEILINGS, TYP.
LV/D DRAWING TITLE:
BR 9. ALL CORE AREAS, ELEVATORS, STAIRWELLS AND EXISTING ELEMENTS TO REMAIN SHALL BE CAREFULLY SEALED AND PROTECTED FROM
DAMAGE AND DIRT. PH CE - DEMOLITION
LV/D
10. ALL PERIMETER FAN COIL AND EQUIPMENT, RADIATOR ENCLOSURE AND WINDOWS SHALL BE CAREFULLY COVERED AND PROTECTED FROM GRIT,
RUBBISH AND DAMAGE.
PLANS
11. WHERE EXISTING SWITCHES, OUTLETS AND PHONE / DATA OUTLETS ARE REMOVED, G.C. SHALL PATCH, SPACKLE AND SAND SMOOTH WALL FOR
PAINT. NO COVER PLATES SHALL BE USED.

12. ALL DEMOLITION WORK INCLUDING FLOOR PENETRATIONS SHALL BE PERFORMED DURING HOURS PERMITTED BY THE BUILDING MANAGER AND /
OR THE CLIENT. SEE MEP DRAWINGS FOR MORE DETAILS.
SCALE: AS NOTED PAGE: 4 of 30
13. IN ALL AREAS WHERE DEMOLITION OR CUTS AND PATCHES CAUSE A UNEVENNESS IN THE SLAB, THE CONTRACTOR SHALL FLASH PATCH AS
REQUIRED TO RECEIVE THE NEW FLOOR FINISH. COORDINATE WITH FLOORING CONTRACTOR.

14.

15.
THE GENERAL CONTRACTOR SHALL ERECT A PLASTIC DUST PARTITION TO PROTECT AREAS NOT INCLUDED IN THE SCOPE OF WORK.

PRIOR TO DEMOLITION, THE CONSTRUCTION AREA SHALL BE INSPECTED FOR PRESENCE OF ASBESTOS. IF PRESENT IT SHALL BE REMOVED IN
D102.00
COMPLIANCE WITH THE STATE OF NEW YORK REQUIREMENTS AND FEDERAL NESHAP (NATIONAL EMISSION STANDARD FOR HAZARDOUS AIR
POLLUTANTS) REGULATION. (NESHAP - PHONE: 1-617-565-9055).

16. WHERE REMOVALS ARE NOT POSSIBLE WITHOUT DAMAGE TO EXISTING TO REMAIN. G.C. SHALL REPAIR OR REPLACE DAMAGED ITEMS AS
REQUIRED.

PHCE - DEMOLITION PLAN LOWER


1 1/4" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200
B

CHASE 2
C

BR
BR
EXISTING GAS LINE. C
PRTOECT DURING DEMO C
K

SLAB OPENING.
SEE STRUCTURAL
C
NOT FOR CONSTRUCTION

CHASE 4
10'-6 1/4" 3'-0 3/4"
EXISTING WATERLINE.

3'-0"
PRTOECT DURING DEMO

REMOVE EXISTING
CEILINGS, TYP.

CHASE 3
C B
H
LV/D

PHH - DEMOLITION PLAN UPPER DEMOLITION PLAN LEGEND


2 1/4" = 1'-0" NO.
ISSUED FOR BID
DESCRIPTION
05/18/2020
DATE

EXISTING NONBEARING WALL TO BE REMOVED EXISTING WALL TO REMAIN

B EXISTING DOORS, FRAME AND EXISTING DOORS, FRAME AND

CHASE 2
HARDWARE TO BE REMOVED HARDWARE TO BE REMAIN

PROJECT TITLE:
BR
BR
DEMOLITION NOTES PENTHOUSE UNITS
C
EXISTING GAS LINE.
PRTOECT DURING DEMO C 1. G.C. SHALL REMOVE ALL EXISTING WALLS, DOORS, FRAMES, HARDWARE AS INDICATED ON DEMOLITION PLAN. RENOVATIONS
K
2. G.C. SHALL REMOVE ALL EXISTING ELECTRICAL OUTLETS, THERMOSTATS, SWITCHES ON WALLS BEING DEMOLISHED. PULL ALL WIRES BACK TO FLOORS 26, 27, 28
PANEL.
LIBERTY VIEW
SLAB OPENING ABOVE.
3. G.C. SHALL REMOVE ALL EXISTING CARPET, TILE AND MISC. FLOORING AND VINYL BASE AND PREPARE WALLS AND FLOORS TO RECEIVE NEW 99 BATTERY PLACE
FINISHES.
SEE STRUCTURAL NEW YORK, NEW YORK 10280
C
4. REFER TO PLUMBING, SPRINKLER, MECHANICAL, ELECTRICAL & FIRE ALARM DRAWINGS FOR EXTENT OF DEMOLITION.
CHASE 4

5. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT AS REQUIRED TO COMPLETE DEMOLITION AND REMOVAL OF ALL
EXISTING WATERLINE. ITEMS SHOWN ON DRAWINGS.
PRTOECT DURING DEMO
6. ALL DEMOLITION DEBRIS SHALL BE REMOVED FROM THE PREMISES EXCEPT THOSE ITEMS TO BE REUSED, RETURNED TO THE LANDLORD /
OWNER, OR AS OTHERWISE DIRECTED.

7. THE CONTRACTOR SHALL CAREFULLY REMOVE, PROTECT AND STORE ALL CONSTRUCTION ELEMENTS TO BE REUSED OR RETURNED TO THE
LANDLORD / OWNER.
DOB SCAN STICKER
8. UPON COMPLETION OF THE DEMOLITION WORK, ALL AREAS SHALL BE BROOM CLEAN.
REMOVE EXISTING DRAWING TITLE:
9. ALL CORE AREAS, ELEVATORS, STAIRWELLS AND EXISTING ELEMENTS TO REMAIN SHALL BE CAREFULLY SEALED AND PROTECTED FROM
CEILINGS, TYP. DAMAGE AND DIRT. PH H - DEMOLITION
CHASE 3

C B 10. ALL PERIMETER FAN COIL AND EQUIPMENT, RADIATOR ENCLOSURE AND WINDOWS SHALL BE CAREFULLY COVERED AND PROTECTED FROM GRIT,
PLANS
H 11.
RUBBISH AND DAMAGE.

WHERE EXISTING SWITCHES, OUTLETS AND PHONE / DATA OUTLETS ARE REMOVED, G.C. SHALL PATCH, SPACKLE AND SAND SMOOTH WALL FOR
PAINT. NO COVER PLATES SHALL BE USED.
LV/D
12. ALL DEMOLITION WORK INCLUDING FLOOR PENETRATIONS SHALL BE PERFORMED DURING HOURS PERMITTED BY THE BUILDING MANAGER AND /
OR THE CLIENT. SEE MEP DRAWINGS FOR MORE DETAILS.
SCALE: AS NOTED PAGE: 5 of 30
13. IN ALL AREAS WHERE DEMOLITION OR CUTS AND PATCHES CAUSE A UNEVENNESS IN THE SLAB, THE CONTRACTOR SHALL FLASH PATCH AS
REQUIRED TO RECEIVE THE NEW FLOOR FINISH. COORDINATE WITH FLOORING CONTRACTOR.

14.

15.
THE GENERAL CONTRACTOR SHALL ERECT A PLASTIC DUST PARTITION TO PROTECT AREAS NOT INCLUDED IN THE SCOPE OF WORK.

PRIOR TO DEMOLITION, THE CONSTRUCTION AREA SHALL BE INSPECTED FOR PRESENCE OF ASBESTOS. IF PRESENT IT SHALL BE REMOVED IN
D103.00
COMPLIANCE WITH THE STATE OF NEW YORK REQUIREMENTS AND FEDERAL NESHAP (NATIONAL EMISSION STANDARD FOR HAZARDOUS AIR
POLLUTANTS) REGULATION. (NESHAP - PHONE: 1-617-565-9055).

16. WHERE REMOVALS ARE NOT POSSIBLE WITHOUT DAMAGE TO EXISTING TO REMAIN. G.C. SHALL REPAIR OR REPLACE DAMAGED ITEMS AS
REQUIRED.

PHH - DEMOLITION PLAN LOWER


1 1/4" = 1'-0"

SEAL
WALL TYPES
BATTERY PLACE
8 1/4" 3 3/4" 5" ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
UNDERSIDE OF SLAB UNDERSIDE OF SLAB UNDERSIDE OF SLAB
NEW YORK, NY 10017
SCHEDULED CEILING SCHEDULED CEILING SCHEDULED CEILING (212) 308-7200
SEE RCP SEE RCP SEE RCP

SEALANT AND TAPE BOTH SIDES SEALANT AND TAPE BOTH SIDES SEALANT AND TAPE BOTH SIDES

STEEL TRACK, FASTEN 2'-0" O.C. STEEL TRACK, FASTEN 2'-0" O.C. STEEL TRACK, FASTEN 2'-0" O.C.
MAX. AS REQUIRED MAX. AS REQUIRED MAX. AS REQUIRED

1 5/8" MTL STUDS @ 16" OC 2 1/2" MTL STUDS @ 16" OC 2 1/2" MTL STUDS @ 16" OC

2" SOUND ATTENUATION BLANKET 2" SOUND ATTENUATION BLANKET 2" SOUND ATTENUATION BLANKET

5/8" GYP. BD. EACH SIDE, USE 5/8" GYP. BD. EACH SIDE, USE TWO LAYERS 5/8" GYP. BD. EACH SIDE,
CEMENTITIOUS BOARD AT WET AREAS CEMENTITIOUS BOARD AT WET AREAS TYPE X FIRECODE "C"
STEEL TRACK, FASTEN 2'-0" O.C. STEEL TRACK, FASTEN 2'-0" O.C. STEEL TRACK, FASTEN 2'-0" O.C.
MAX. AS REQUIRED MAX. AS REQUIRED MAX. AS REQUIRED

SEALANT AND TAPE BOTH SIDES SEALANT AND TAPE BOTH SIDES SEALANT AND TAPE BOTH SIDES
FINISH FLOOR FINISH FLOOR FINISH FLOOR
CONCRETE FLOOR CONCRETE FLOOR CONCRETE FLOOR

3A TYP. NON-RATED DOUBLE STUD


1 1/2" = 1'-0"
2A TYP. INTERIOR NON-RATED
1 1/2" = 1'-0"
1A 2-HR. RATED AT CORRIDOR
1 1/2" = 1'-0"

3B TYP.
1 1/2" =AS
SAME
PLUMBING CHASE (9" UON)
1'-0"
3A EXCEPT WIDTH VARIES
2B RECESSED
1SAME
1/2" =AS
1'-0"
BOX WALL (5" NOM.)
2A EXCEPT REPLACE 2 1/2" STUD WITH 3 5/8" STUD

2C TYP.
1SAME
1/2" =AS
FURRING NON-RATED
1'-0"
2A EXCEPT OMIT ONE LAYER OF GWB AND
REPLACE WITH 1 5/8" STUD

ISSUED FOR BID 05/18/2020


NO. DESCRIPTION DATE

PROJECT TITLE:
PENTHOUSE UNITS
RENOVATIONS
ACCESSIBILITY DIAGRAMS (ICC/ANSI 117.1 - 2009) FLOORS 26, 27, 28
CLEAR FLOOR SPACE REACH RANGES BUILDING BLOCKS LIBERTY VIEW
60" MIN. 60" MIN. 99 BATTERY PLACE
8" MIN.
(1525) (1525) (205) NEW YORK, NEW YORK 10280

1/4" - 1/2"
(6.4-13)
30" MIN.
(760)

(X > 380)
48" MIN.

30" MIN.

X > 15"
(X > 610)
X > 24"
(1220)

2
36" MIN.

(760)

27" MIN.
48" MIN.
(915)

(1220)

(685)

1
60" MIN.
(1525)

48" MAX.

48" MAX.

48" MAX.

48" MAX.

46" MAX.
44" MAX.

(1220)

(1220)
(1220)

(1220)

MAX.
(1120)

(6.4)
(1170)

1/4"
30" MIN. 48" MIN. 17" MIN.
11" MIN.
9" MIN.

9" MIN.
(230)

(1220) 36" MIN. 60" MIN.


(230)

(760) (280) (430)


(915) (1525)
12" MIN. 36" MIN. 12" MIN. FIG. 303.3 FIG. 303.2
15" MIN.

(305) (915) (305) (A) FORWARD (B) PARALLEL (A) FORWARD APPROACH (B) PARALLEL APPROACH FIG. 306.3 FIG. 306.2 20" MAX. 20" - 25" 10" MAX. 24" MAX. BEVELED CHANGES IN LEVEL VERTICAL CHANGES IN LEVEL
(380)

KNEE CLEARANCE TOE CLEARANCE (510) (510-635) (255) (610)


(A) CIRCULAR (B) T-SHAPED DOB SCAN STICKER
FIG. 304.3 FIG. 405.5 FIG. 305.7 FIG. 308.2.1 FIG. 308.2.2 FIG. 308.3.1 FIG. 308.3.2
SIZE OF WHEELCHAIR TURNING SPACE POSITION OF CLEAR FLOOR OR GROUND SPACE MANEUVERING CLEARANCE IN AN ALCOVE UNOBSTRUCTED FORWARD REACH OBSTRUCTED HIGH FORWARD REACH UNOBSTRUCTED SIDE REACH OBSTRUCTED HIGH SIDE REACH DRAWING TITLE:

DOORS AND DOORWAYS 54" MIN. PLUMBING ELEMENTS AND FACILITIES ACCESSIBLE ROUTES 32" min.
WALL TYPES, ADA
32" min.
DIAGRAMS
(430-485)
(815)

(430-485)
(1370)

17"-19"

17"-19"
(815)
(230)

42" min.
(230)

(1065)
18" MIN. 36" MIN. 42" MIN.
60" MIN.
60" MIN.

12" MIN. 24" max. 48" min. 24" max.


9"

9"
54" MIN.

24" MIN.
(1525)

(1525)

(1370)

(915) (1065)
48" MIN.
48" MIN.

(445) 90
(1220)

24" MIN.
(1065)
42" MIN.

42" MIN
(1220)

(305) (610) (1220) (610) (B) SLIDING DOOR


(1065)

(610)
(610)
12" max. 15" max. 12" max. 24" max. 32" min.
(305) (815)

(X < 1220)
(610) SCALE: AS NOTED 30
PAGE: 6 of 23
34" max.

(380) (305) (A) HINGED DOOR

X < 48"
42" min.
36" min.

32" min.
(865)

(1065)
back wall back wall 48" min.

(815)
12" min.

(915)
head end
(1220)
head end
foot end wall

foot end wall

wall
wall

(C) FOLDING DOOR


24" min.

A001.00
24" min.
(610)

(610)

(A) FRONT APPROACH, PULL SIDE (B) FRONT APPROACH, PUSH SIDE (C) HINGE APPROACH, PULL SIDE (D) HINGE APPROACH, PULL SIDE (E) HINGE APPROACH, PUSH SIDE (F) LATCH APPROACH, PULL SIDE (G) LATCH APPROACH, PUSH SIDE FIG. 606.3
HEIGHT OF LAVATORIES AND SINKS FIG. 403.5 FIG. 403.5.1 FIG. 404.2.3
FIG. 404.2.4.1 15"-16" CLEAR WIDTH OF AN ACCESSIBLE ROUTE CLEAR WIDTH AT TURN CLEAR WIDTH OF DOORWAYS
30" min.

30" min.
(760)

(760)
MANEUVERING CLEARANCE AT SWINGING DOORS (380-405)
48" MIN. 48" MIN.
(1220) (1220) 54" MIN. length of tub 12" min.
(1370) length of tub
(305)
FIG. 607.4.1 FIG. 607.4.2
GRAB BARS FOR BATHTUBS GRAB BARS FOR BATHTUBS
48" MIN.
(1220)

42" MIN.
42"MIN.

24" MIN. WITH PERMANENT SEATS WITHOUT PERMANENT SEATS


(1065)

(1065)

(610)

(A) (B) (A) FRONT APPROACH (B) POCKET OR HINGE APPROACH (C) STOP OR LATCH APPROACH
FIG. 404.2.6 FIG. 404.2.4.2
TWO DOORS IN A SERIES MANEUVERING CLEARANCE AT SLIDING AND FOLDING DOORS SEAL
GENERAL NOTES CONSTRUCTION NOTES REFLECTED CEILING PLAN NOTES PAINT AND FINISH NOTES CABINET WORK NOTES

1. THE GENERAL CONTRACTOR AND ALL THE SUBCONTRACTORS USING THESE DRAWINGS, SHALL COMPLY WITH ALL
STATE AND LAW CODES, ORDINANCES AND REGULATIONS BEARING ON THE SCOPE OF WORK.
1. THE GENERAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND OTHER ITEMS NECESSARY
TO COMPLETE THE WORK SHOWN, CALLED FOR OR INFERRED BY THESE DRAWINGS UNLESS OTHERWISE NOTED.
1. THE GENERAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND OTHER ITEMS NECESSARY
TO COMPLETE THE WORK SHOWN, CALLED FOR, OR INFERRED BY THESE DRAWINGS UNLESS OTHERWISE NOTED.
1. THE GENERAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND OTHER ITEMS NECESSARY
TO COMPLETE THE WORK SHOWN, CALLED FOR OR INFERRED BY THESE DRAWINGS UNLESS OTHERWISE NOTED.
1. THE GENERAL CONTRACTOR SHALL COORDINATE HIS WORK WITH THAT OF THE CABINETRY CONTRACTOR. BATTERY PLACE
2. ALL WORK SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF THE BUILDING CODES, 2. THE GENERAL CONTRACTOR AND HIS SUBCONTRACTORS SHALL INSPECT AND VERIFY ALL CONDITIONS AND 2. THE GENERAL CONTRACTOR SHALL INSPECT AND VERIFY ALL CONDITIONS AND DIMENSIONS AT THE BUILDING 2. THE GENERAL CONTRACTOR SHALL VERIFY ALL CONDITIONS AT THE BUILDING SITE AND NOTIFY ARCHITECT OF
2. ALL MILLWORK SHALL BE SHOP FINISHED AND STAINED PRIOR TO INSTALLATION, UNLESS CONTRACTOR HAS
WRITTEN APPROVAL FROM OWNER AND ARCHITECT.
ASSOCIATES, LLC
NATIONAL BOARD OF FIRE UNDERWRITERS, PUBLIC SERVICE COMPANY, BOARD OF HEALTH, AMERICAN WITH DIMENSIONS AT THE BUILDING SITE AND NOTIFY ARCHITECT OF ANY DISCREPANCY PRIOR TO THE AWARD OF SITE AND NOTIFY THE ARCHITECT OF ANY DISCREPANCY. ANY DISCREPANCY. C/O MILSTEIN PROPERTIES
DISABILITIES ACT (A.D.A.) AND ALL OTHER AUTHORITIES HAVING JURISDICTION. CONTRACTS. 3. ALL BLOCKING REQUIRED SHALL BE SCRIBED TO WALL OR CEILING. CONTRACTOR TO COORDINATE WORK WITH 335 MADISON AVENUE
3. ELECTRICAL INSTALLATION SHALL CONFORM TOT HE ELECTRICAL CODE AND TO ANY REGULATIONS OF THE LOCAL 3. ALL PAINT COLORS AND WALL COVERINGS SHALL CONFORM TO ARCHITECT'S SPECIFICATIONS AND BE INSTALLED OTHER TRADES INVOLVED.
3. THE ARCHITECT'S RESPONSIBILITY IN GENERAL ADMINISTRATION OF CONSTRUCTION IS FOR THE PURPOSE OF 3. THE GENERAL CONTRACTOR SHALL INCLUDE IN HIS PRICE ALL OVERTIME WORK REQUIRED, IF ANY. DEPARTMENT OF WATER SUPPLY, GAS AND ELECTRICITY. PER MANUFACTURE'S INSTRUCTIONS. NEW YORK, NY 10017
DETERMINING THAT THE WORK WHEN COMPLETED WILL BE IN CONFORMANCE WITH THE CONTRACT DOCUMENTS 4. CONTRACTOR SHALL SUBMIT ALL REQUIRED SHOP DRAWINGS TO ARCHITECT FOR REVIEW. SAMPLES OF (212) 308-7200
AND ENDEAVOR TO GUARD THE OWNER AGAINST DEFECTS AND DEFICIENCIES IN THE WORK. THE ARCHITECT WILL 4. THE GENERAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND LIGHTS AT ALL PHASES OF THE PROJECT 4. CONTRACTORS SHOP DRAWINGS OF ALL DUCTWORK, DIFFUSERS, REGISTERS, ACCESS PANELS (IF REQUIRED) 4. ALL PAINT SHALL BE DELIVERED TO JOB SITE IN UNOPENED CONTAINERS OF MANUFACTURER SPECIFIED, AND MILLWORK AND FINISHES SHALL BE SUBMITTED TO ARCHITECT FOR REVIEW.
NOT HAVE CONTROL OVER OR CHARGE OF AND WILL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS, UNTIL FINAL POWER AND LIGHTING IS COMPLETED. SHALL BE SUBMITTED TO THE ENGINEER AND ARCHITECT FOR REVIEW PRIOR TO FABRICATION AND/OR SHALL BE APPLIED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES, OR FOR SAFETY PRECAUTIONS AND PROGRAMS IN INSTALLATION. 5. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS IN FIELD PRIOR TO FABRICATION OF
CONNECTION WITH THE WORK. THESE ARE SOLELY THE CONTRACTOR'S RESPONSIBILITY. 5. ALL DIMENSIONS SHOWN ON PLANS ARE FROM FINISH TO FINISH. UNLESS OTHERWISE NOTED. 5. ALL ELECTRIC SWITCH AND OUTLET PLATES SHALL BE INSTALLED WHEN FINISHING HAS BEEN COMPLETED. CABINETS/MILLWORK.
5. G.C. SHALL COORDINATE ALTERATIONS & INSTALLATIONS OF NEW DUCTWORK AND AIR CONDITIONING EQUIPMENT
4. THE CONTRACTOR SHALL COORDINATE AND SUPERVISE THE WORK OF ALL TRADES AND SUBCONTRACTORS. 6. ALL NEW AND EXISTING PARTITIONS TO REMAIN SHALL RECEIVE PAINT OR WALL COVERING AS SPECIFIED PER WITH OTHER PHASES OF CONSTRUCTION. 6. ALL EXISTING AND NEW HARDWARE, SWITCH AND RECEPTACLE PLATES SHALL BE FREE OF PAINT OR ADHESIVE. 6. ALL JOINTS SHALL BE SECURED IN A MANNER TO ENSURE AGAINST JOINT OPENINGS.
CONTRACTOR SHALL LAY OUT HIS OWN WORK, AND SHALL PROVIDE ALL DIMENSIONS REQUIRED FOR OTHER FINISH PLAN.
TRADES: PLUMBING, ELECTRICAL, CABINETRY, ETC. 6. GENERAL CONTRACTOR SHALL PROVIDE NEW CEILINGS AS INDICATED ON DRAWINGS. ALL DEFECTIVE TILES SHALL 7. ALL NEW AND EXISTING WALL SURFACES SHALL BE PATCHED, SPACKLED AND SANDED SMOOTH PRIOR TO 7. ALL BLOCKING FOR CABINET WORK OR ASSEMBLIES SHALL BE FIRE-RETARDANT AS REQUIRED BY CODE.
7. ALL NEW AND EXISTING WALL SURFACES REQUIRING FINISHES SHALL BE PATCHED, TAPED, SPACKLED AND SAND BE REPLACED AT END OF CONSTRUCTION. APPLICATION OF WALL FINISHES (PAINT, VINYL, ETC..) AS SPECIFIED ON DRAWINGS.
5. UPON COMPLETION OF THIS JOB, THE GENERAL CONTRACTOR SHALL SUBMIT CERTIFICATES OF INSPECTION AND SMOOTH. UNLESS OTHERWISE NOTED. REPAIR ALL WALLS TO REMAIN DAMAGED DURING DEMOLITION. 8. ALL VISIBLE WOOD CORNER JOINTS SHALL BE MITERED.
A CERTIFICATE OF SUBSTANTIAL COMPLETION (A.I.A. DOC. #G-704) 7. ALL SUSPENDED CEILING SHALL BE INSTALLED TO COMPLY WITH SEISMIC CODE REQUIREMENTS. 8. CONTRACTOR SHALL PROVIDE TWO (2) SAMPLES OF ALL FINISHES SPECIFIED, PRIOR TO ORDERING OF ANY
8. ALL WOOD BLOCKING AND WOOD WORK SHALL BE FIRE RETARDANT AND/OR FIREPROOFED WHERE REQUIRED BY MATERIAL, FOR ARCHITECTS FINAL APPROVAL. FAILURE TO DO SO WILL RESULT IN THE CONTRACTOR TAKING 9. CONTRACTOR SHALL PROVIDE SHOP FINISHED FILLER PIECES FOR ALL CABINETRY AND FILE CABINETRY NICHES.
6. THE CONTRACTOR SHALL PROVIDE ALL SHORING, BRACING, BARRICADES, AND TEMPORARY INSTALLATIONS TO CODE. 8. CEILING IN CLOSETS SHALL BE OF THE SAME HEIGHT AND CONSTRUCTION AS THAT OF ADJOINING SPACE, UNLESS TOTAL RESPONSIBILITY FOR INCORRECT ORDERS OR INSTALLATION.
COMPLETE ALL WORK IN THE APPROVED MANNER. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONS NECESSARY OTHERWISE NOTED. 10. THE GENERAL CONTRACTOR SHALL PROVIDE WALL BLOCKING INSIDE PARTITIONS FOR ALL WALL HUNG CABINETS,
TO PREVENT SETTLEMENT, COLLAPSE, OR MOVEMENT OF ANY PART OF THE EXISTING STRUCTURES. 9. ALL DOORS, BUCKS, HARDWARE AND DOOR FINISHES SHALL BE AS NOTED IN DOOR SCHEDULE, SUPPLIED AND 9. ALL METAL DOORS, METAL BUCKS, WINDOWS, CONVECTOR ENCLOSURES AND OTHER METAL SURFACES, EXCEPT COUNTERS, SHELVES, ETC., FOR PROPER SUPPORT.
INSTALLED BY GENERAL CONTRACTOR.. 9. THE CONTRACTOR SHALL SUBMIT CUTS OF ALL FIXTURES TO ARCHITECT, THREE (3) COPIES OF EACH FOR AS NOTED, SHALL RECEIVE TWO (2) COATS OF SEMI-GLOSS ENAMEL AS SPECIFIED.
7. THE CONTRACTOR SHALL DAILY REMOVE FROM THE PREMISES ALL RUBBISH AND DEBRIS AND MAINTAIN BUILDING REVIEW. 11. THE ARCHITECT SHALL REVIEW AND APPROVE ALL FINISHES, INCLUDING WOOD VENEER CUT AND GRAINING.
CORRIDORS, SIDEWALKS, AND ROADWAYS FREE FROM ANY OBSTRUCTIONS. PREMISES SHALL BE MAINTAINED IN 10. IF FLOOR ELEVATION IRREGULARITIES OCCUR AT NEW DOORS, FLARE-FLASH PATCH FLOORING AREA TO DOOR 10. ALL NEW AND EXISTING PAINTED WALL SURFACES SHALL RECEIVE ONE (1) PRIME COAT & TWO (2) FINISH COATS WITHOUT APPROVAL GENERAL CONTRACTOR AND MILLWORK CONTRACTOR ACCEPT FULL RESPONSIBILITY AND
A NEAT CONDITION. THE CONTRACTOR SHALL RESTORE AND CLOSE UP ALL OPENINGS OR PENETRATIONS OPENINGS WHERE REQUIRED. TO ACHIEVE UNIFORM ELEVATION. COORDINATE THIS WORK WITH FLOORING 10. CONTRACTOR SHALL PROVIDE TWO (2) SAMPLES EACH OF ALL MATERIALS SPECIFIED FOR ARCHITECT'S REVIEW. OF PAINT AS SPECIFIED. MILLWORK IS SUBJECT FOR REMOVAL & REPLACEMENT.
UNCOVERED AS A RESULT OF DEMOLISHED FURRED WALLS OR PARTITIONS AND ABANDONED PIPING AND DUCTS. CONTRACTOR.
11. ALL CEILING DIFFUSERS, LOUVERS AND REGISTERS SHALL HAVE BAKED WHITE ENAMEL FINISH TO MATCH CEILING 11. METAL DOOR BUCKS SHALL BE PAINTED WITH TWO (2) COATS OF SEMI-GLOSS ENAMEL TO MATCH ADJACENT WALL 12. THE HANDICAP (A.D.A.) CONFORMING BASE CABINETS SHALL BE NO HIGHER THAN 34" ABOVE FINISH FLOOR AND A
8. THE CONTRACTOR SHALL GUARANTEE ALL WORK UNDER CONTRACT TO BE FREE FROM DEFECTS FOR A PERIOD 11. ALL DOOR OPENINGS IN CARPET AREAS SHALL BE UNDERCUT AND COORDINATED WITH FINISH FLOOR THICKNESS. GRID & TILE COLOR UNLESS OTHERWISE NOTED. COLOR UNLESS OTHERWISE NOTED. MAXIMUM OF 24" DEEP FOR LATERAL ACCESS. IT SHALL HAVE A 30" x 29" UNDER COUNTER OPENING FOR ACCESS
OF ONE YEAR FOLLOWING THE ACCEPTANCE OF THE COMPLETED PROJECT. ALL UNSATISFACTORY WORK SHALL AT COUNTER SINK.
BE CORRECTED BY THE CONTRACTOR AT NO COST TO THE OWNER. 12. ALL WORK SHALL CONFORM TO WORK LETTER AND LEASE AGREEMENT, UNLESS OTHERWISE NOTED. 12. ALL LIGHT FIXTURES SHALL BE INDEPENDENTLY SUPPORTED AS PER CODE. 12. ALL MILLWORK SPECIFIED TO BE STAINED, SHALL BE STAINED TO MATCH SAMPLE PROVIDED BY THE ARCHITECT.
TWO (2) SAMPLES OF STAINED FINISH TO BE SUBMITTED TO ARCHITECT FOR FINAL APPROVAL. ALL STAINED AND 13. ARCHITECT SHALL REVIEW AND APPROVE ALL VENEER CUTS AND GRAINING AND ALL FINISHES PRIOR TO NOT FOR CONSTRUCTION
9. ANY ADDITIONAL WORK, NOT NOTED IN THE ORIGINAL CONTRACT MUST BE APPROVED BY THE OWNER AND 13. WHEREVER EXISTING STRUCTURE IS TO REMAIN, IMPERFECTIONS IN WALLS, CEILING OR FLOOR SHALL BE 13. ALL LAMPS SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR. UNLESS OTHERWISE NOTED. PLAIN MILLWORK SHALL BE SHOP FINISHED. INSTALLATION. INSTALLED MILLWORK WITHOUT APPROVAL SHALL BE REMOVED AT ARCHITECT'S DISCRETION AT
ARCHITECT, IN WRITING,PRIOR TO THE COMMENCEMENT OF WORK. THE CONTRACTOR SHALL PROVIDE AND PAY REPAIRED BY THE GENERAL CONTRACTOR. CONTRACTOR'S COST.
FOR ALL LABOR, EQUIPMENT, TOOLS, MACHINERY TRANSPORTATION, RUBBISH REMOVAL AND OTHER FACILITIES 14. WHERE BEAMS, PIPES AND/OR DUCTS OR OTHER CONSTRUCTION ELEMENTS PREVENT USE OF STANDARD 13. ALL ELEVATORS SHALL BE FINISHED PER LANDLORDS REQUIREMENTS. (U.O.N.).
NECESSARY FOR THE PROPER EXECUTION OF THE WORK. 14. ALL OVERTIME FOR FLOOR DRILLING, ETC., TO BE FIGURED IN ORIGINAL BIDDING. OWNER/TENANT SHALL NOT RECESSED FIXTURES, SHALLOW FIXTURES SHALL BE USED. VERIFY DECISION WITH ARCHITECT. ELECTRIC & TELEPHONE NOTES
INCUR ANY COSTS FOR WORK SHOWN ON THESE DRAWINGS. 14. ALL NEW PARTITIONS SHALL RECEIVE VINYL BASE 1/8" GAUGE UNLESS OTHERWISE NOTED.
10. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL NECESSSARY PERMITS AND APPROVALS AS REQUIRED BY 15. GC SHALL COORDINATE ROUTING OF PIPES AND/OR DUCTS OR OTHER CONSTRUCTION ELEMENTS TO NOT 1. THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND OTHER ITEMS
LAW FOR ALL ACTIVITIES AND COMPLETION OF THE WORK. 15. ARCHITECT TO VERIFY LAYOUT OF ALL FINISH PARTITIONS BY MEANS OF CHALK LINE PRIOR TO METAL TRACK INTERFERE WITH RECESSED FIXTURES. 15. ALL PERIMETER CONVECTOR ENCLOSURES SHALL BE CLEANED, WHERE NEW FINISH IS NOT SPECIFIED. NECESSARY TO COMPLETE THE WORK SHOWN, CALLED FOR OR INFERRED BY THESE DRAWINGS. ELECTRICAL
INSTALLATION. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL CIRCUITING TO NEW ELECTRIC AND TELEPHONE
11. THE CONTRACTOR SHALL PROTECT AND BE RESPONSIBLE FOR ADJACENT STRUCTURES AND SPACES WITHIN THE 16. IF PATTERN OF LIGHTING FIXTURES CAN NOT BE OBTAINED, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT FOR 16. ALL CLOSET INTERIORS SHALL RECEIVE THE SAME FINISHES AS ADJACENT AREAS UNLESS OTHERWISE NOTED. OUTLETS.
AREA OF OPERATION UNDER THIS CONTRACT. ANY DAMAGE OR DISTURBANCE RESULTING FROM WORK UNDER 16. GENERAL CONTRACTOR AND HIS SUBCONTRACTORS SHALL NOT SCALE DRAWINGS. ARCHITECT SHALL BE DIRECTION AND SOLUTION PRIOR TO INSTALLATION.
THIS CONTRACT SHALL BE PROMPTLY RESTORED, REPLACED, OR REPAIRED AT NO EXTRA COST TO THE OWNER. NOTIFIED OF ANY DISCREPANCIES OR QUESTIONS BY GENERAL CONTRACTOR. 17. ALL CEILING AIR CONDITIONING DIFFUSERS AND REGISTERS SHALL HAVE BAKED WHITE ENAMEL FINISH TO MATCH 2. ELECTRICAL AND PLUMBING CONTRACTOR SHALL PERFORM THEIR WORK TO COMPLY WITH THE MANUFACTURE'S
17. ALL CEILINGS SHALL BE LAID OUT BY MEANS OF A LASER BEAM LEVEL. CEILING TILE & GRID. SPECIFICATIONS REQUIREMENTS.
12. BEFORE COMMENCING WORK, THE CONTRACTOR SHALL FILE ALL REQUIRED INSURANCE CERTIFICATES WITH THE 17. GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL SOUND PROOF SEALANT WHEREVER SOUND PROOF
DEPARTMENT OF BUILDINGS, OBTAIN AND PAY FOR ALL REQUIRED PERMITS, AND PAY ALL FEES REQUIRED BY THE PARTITIONS MEET THE FLOOR SLAB, CEILING SLAB ABOVE AND WINDOW MULLIONS OR AS SPECIFIED BY 18. FOR ELECTRICAL RECEPTACLE AND SWITCH PLATE FINISHES SEE PAINT AND FINISH GENERAL NOTES. G.C. TO 18. ALL GYP. BD. CEILINGS SHALL BE PAINTED FLAT WHITE. (U.O.N.). 3. ALL ELECTRICAL WORK SHALL BE COORDINATED WITH AIR CONDITIONING WORK, CABINET WORK, ALL PARTITION
GOVERNING NEW YORK CITY AGENCIES. PARTITION TYPES. IN NO CASE SHALL THE GENERAL CONTRACTOR SECURE NEW METAL STUD FRAMING TO COORDINATE WITH LV/TELEPHONE SUB. AND MATCH PLATE COVERS. WORK, ETC.. WHERE REQUIRED.
PERIMETER WINDOWS/CURTAIN WALL, UNLESS OTHERWISE NOTED. 19. ALL EXISTING AREAS NOT MARKED ON/OR NOTED SHALL REMAIN AS IS.
13. MINOR DETAILS NOT USUALLY SHOWN OR SPECIFIED, BUT REQUIRED FOR PROPER CONSTRUCTION OF ANY PART 19. G.C. SHALL PROVIDE OPENINGS FOR AIR TRANSFER GRILLES WHEREVER SLAB TO SLAB PARTITIONS OCCUR. 4. ALL ELECTRICAL WIRING CONDUIT SHALL BE CONCEALED UNLESS OTHERWISE NOTED. ALL CONDUITS SHALL BE
OF THE WORK SHALL BE INCLUDED AS IF THEY WERE INDICATED IN THE DRAWINGS. 18. GENERAL CONTRACTOR SHALL PROVIDE SOUND PROOF INSULATION IN PERIMETER RADIATOR ENCLOSURES 20. PAINTING CONTRACTOR SHALL INSPECT ALL NEW WALL COVERINGS FOR FLAWS PRIOR TO INSTALLATION. SUPPORTED BY STANDOFFS WIRED TO CEILING SUPPORTS. ALL WORK SHALL BE IN ACCORDANCE WITH
WHEREVER INTERSECTIONS WITH PARTITIONS OCCUR. 20. THERMOSTATS ARE NOT TO BE INSTALLED OVER DIMMER SWITCHES OR OTHER HEAT RADIATING ELEMENTS. GOVERNING STATE AND LOCAL CODES.
14. THE SUBMISSION OF A PROPOSAL BY THE CONTRACTORS WILL BE CONSTRUED AS EVIDENCE THAT A CAREFUL 21. ACCESS DOORS ON WALLS, COLUMNS AND CEILINGS SHALL BE FLUSH WITH AND FINISHED TO MATCH ADJACENT
AND THOROUGH EXAMINATION OF THE PREMISES HAS BEEN MADE. IT SHALL ALSO CONSTITUTE A 19. GENERAL CONTRACTOR SHALL PROVIDE BUILDING STANDARD COAT ROD AND HAT SHELF WITH INTERMEDIATE 21. WHEN EXISTING SUSPENDED CEILINGS ARE REUSED, NEW CEILINGS SHALL ALIGN AND MATCH EXISTING UNLESS FINISH. 5. FOR ELECTRICAL RECEPTACLE AND SWITCH PLATE FINISHES SEE PAINT AND FINISH PLAN AND NOTES.
REPRESENTATION THAT THE CONTRACTOR HAS CHECKED AND VERIFIED ALL QUANTITIES, WORK AND MATERIALS SUPPORTS WHERE REQUIRED. OTHERWISE NOTED.
INVOLVED AND THAT HE SHALL TAKE RESPONSIBILITY FOR ANY DEFICIENCIES THEREIN. 22. WALLS INCLUDE SURFACES FROM FLOOR TO CEILING INCLUDE FASCIAS AND PILASTERS. 6. ALL NEW FLOOR OUTLETS SHALL BE FURNISHED WITH CAST ALUMINUM BOX.
20. ALL DOORS, BUCKS AND CABINET BASES SHALL BE UNDERCUT OR ADJUSTED WHEREVER FLOOR SLAB IS NOT 22. GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL CONCEALED METAL ACCESS PANELS FOR MAINTENANCE OF
15. BEFORE ORDERING ANY MATERIAL OR DOING ANY WORK, EACH TRADE SHALL VERIFY ALL MEASUREMENTS AT THE EVEN. ALL A/C, PLUMBING, TELEPHONE PHONE, AND ELECTRICAL CONTROLS WHEN CEILING SYSTEM IS NOT ACCESSIBLE. 23. PAINTED SURFACES SHALL BE SMOOTH WITHOUT BRUSH MARKS OR RIDGES. 7. GENERAL CONTRACTOR AND/OR ELECTRICAL CONTRACTOR SHALL FILE FOR AND OBTAIN ALL REQUIRED PERMITS
BUILDING AND SHALL BE RESPONSIBLE FOR THE CORRECTNESS OF SAME. NO EXTRA CHARGE OR COMPLY WITH FIRE RATINGS WHERE REQUIRED. AND SHALL CLOSE OUT ALL PERMITS WITH BUILDING DEPARTMENT PRIOR TO ISSUANCE OF FINAL PAYMENT.
COMPENSATION WILL BE ALLOWED ON ACCOUNT OF DIFFERENCE BETWEEN ACTUAL DIMENSIONS AND THE 21. GENERAL CONTRACTOR SHALL PROVIDE AIR TRANSFER GRILLES WHEREVER FULL HEIGHT (SLAB TO SLAB) 24. UPON COMPLETION, THE CONTRACTOR SHALL REMOVE ALL PAINT FROM WHERE IT HAS SPILLED, SPLASHED OR
MEASUREMENTS INDICATED ON THE DRAWINGS; ANY DISCREPANCIES BETWEEN THE DRAWINGS AND FIELD PARTITIONS OCCUR. 23. ALL INCANDESCENT LIGHTS SHALL BE ON DIMMERS. IF NOT SHOWN ON PLANS, ELECTRICAL CONTRACTOR SHALL SPLATTERED ON SURFACES OTHER THAN THOSE RECEIVING A PAINT FINISH. 8. ALL POWER AND COMMUNICATIONS OUTLETS INDICATED ON DRAWINGS SIDE BY SIDE SHALL BE MOUNTED AS
CONDITIONS WHICH MAY BE FOUND SHALL BE SUBMITTED TO THE ARCHITECT FOR CONSIDERATION AND INCLUDE DIMMERS AS ADD ALTERNATE IN BASE BID AND CALL TO ARCHITECT'S ATTENTION. CLOSE TOGETHER HORIZONTALLY AS PERMITTED BY CODE, UNLESS OTHERWISE NOTED.
CLARIFICATION BEFORE PROCEEDING WITH THE WORK. 22. GENERAL CONTRACTOR SHALL PROVIDE FIRE RATED DAMPERS FOR AIR TRANSFERS WHEREVER FIRE RATED 25. WALL COVERING SHALL BE SMOOTH, WITHOUT WRINKLES, BUBBLES OR LOOSE EDGES. ALL BRUSH MARKS SHALL
PARTITIONS OCCUR. 24. ALL LIGHTING AND FAN SWITCHES INDICATED ON DRAWINGS SIDE BY SIDE SHALL BE 5" CENTER TO CENTER BE THOROUGHLY REMOVED. WALL COVERING INSTALLER TO USE NEW BLADE FOR EACH CUT. 9. ALL EXISTING TO REMAIN OR RELOCATED LIGHT FIXTURES SHALL BE REFURBISHED, CLEANED AND RELAMPED
16. ALL OF THE ARCHITECT'S DRAWINGS AND CONSTRUCTION NOTES ARE COMPLIMENTARY AND WHAT IS CALLED MOUNTED VERTICALLY 3'-2" A.F.F. IN COMPLIANCE WITH A.D.A. REGULATIONS. (DELUXE WARM WHITE LAMP) AS REQUIRED. ELECTRICAL CONTRACTOR SHALL ALSO PROVIDE NEW BALLAST'S
FOR BY EITHER WILL BE BINDING AS IF CALLED FOR BY ALL. ANY WORK SHOWN OR REFERRED TO ON ANY ONE 23. GENERAL CONTRACTOR SHALL PROVIDE CONTINUOUS HORIZONTAL WOOD REINFORCEMENT WHEREVER WALL 26. WHERE TWO DIFFERENT WALL COVERINGS MEET AT AN OUTSIDE CORNER OR WHERE A WALL COVERING MEETS A WHERE REQUIRED.
DRAWING SHALL BE PROVIDED AS THOUGH SHOWN ON ALL DRAWINGS. WHENEVER AN ITEM IS SPECIFIED AND/OR MOUNTED CABINETS OR SHELVES OCCUR. 25. FOR QUANTITIES, TYPES AND LOCATIONS OF OUTLETS REFER TO ARCHITECTURAL DRAWINGS. FOR CIRCUITING, PAINTED SURFACE, A METAL STOP BEAD SHALL BE INSTALLED TO INSURE A CLEAN AND PLUMB INSTALLATION.
SHOWN ON THE DRAWINGS BY DETAIL OR REFERENCE IT SHALL BE CONSIDERED TYPICAL FOR OTHER ITEMS REFER TO ENGINEERING DRAWINGS. IF ANY DISCREPANCIES, CHECK WITH ARCHITECT. 10. THE ELECTRICAL CONTRACTOR SHALL COORDINATE ALL ELECTRICAL WIRING AND LIGHTING IN CABINETS WITH
WHICH ARE OBVIOUSLY INTENDED TO BE THE SAME EVEN THOUGH NOT SO DESIGNATED OR SPECIFICALLY NAMED 24. GENERAL CONTRACTOR SHALL PROVIDE SHOP DRAWINGS AND SAMPLES TO ARCHITECT FOR REVIEW FOR ALL 27. ALL EXISTING LOOSE PAINT SHALL BE REMOVED, SPACKLED, PLASTERED AND PATCHED WHERE NEW FINISHES THE CABINET CONTRACTOR.
BUT DO SERVE THE SAME FUNCTION. WOOD WORK AND EQUIPMENT PRIOR TO ORDERING OR FABRICATION. 26. RELAMPING: IF EXISTING LIGHT FIXTURES ARE BEING REUSED OR RELOCATED, THE ELECTRICAL SUBCONTRACTOR ARE SPECIFIED.
SHALL RELAMP (WITH NEW LAMPS) TO MATCH EXISTING AND CLEAN ALL FIXTURES. PROVIDE AND INSTALL NEW 11. ALL NEW ELECTRICAL OUTLETS AND SWITCHES SHALL BE INSTALLED NO HIGHER THAT 48" A.F.F. TO THE TOP OF
17. THE CONTRACTOR SHALL ABIDE BY AND COMPLY WITH THE TRUE INTENT AND MEANING OF THE DRAWINGS AND 25. GENERAL CONTRACTOR SHALL PATCH SLAB WHERE EXISTING FLOOR OUTLETS AND/OR CONDUITS WERE BALLAST WHERE REQUIRED. THIS SHALL BE PART OF THE BASE CONSTRUCTION CONTRACT WORK. 28. PAINT ALL MECHANICAL, ELECTRICAL AND TELEPHONE ROOMS UNLESS OTHERWISE NOTED. BOX, OR 18" A.F.F. TO THE CENTERLINE OF BOX PER A.D.A. REQUIREMENTS.
NOTES TAKEN AS A WHOLE. SHOULD ANY ERROR OR DISCREPANCY APPEAR OR ANY DOUBT ARISE AS TO THE REMOVED. NO. DESCRIPTION DATE
TRUE MEANING OF THE DRAWINGS OR NOTES, THE CONTRACTOR SHALL BRING SUCH ITEMS TO THE ATTENTION 27. SEE ENGINEERING DRAWINGS AND NOTES FOR CIRCUITING AND TECHNICAL INFORMATION. FOR QUANTITIES & 29. ALL OUTLET AND SWITCH PLATES LOCATED ON WALLS WITH WALL COVERING SHALL BE WRAPPED IN SAME WALL 12. WHERE MORE THAN ONE SWITCH OR RECEPTACLE IS SHOWN IN ONE LOCATION, CONTRACTOR SHALL USE GANG
OF THE ARCHITECT BEFORE SUBMISSION OF PROPOSAL FOR EXPLANATION OR CORRECTION OF SAME. 26. GENERAL CONTRACTOR SHALL PROVIDE TAPABLE GALV. METAL EDGE OR CORNER BEADS WHEREVER GYP. BD. LOCATION REFER TO ARCHITECTURAL DRAWINGS. COVERING. (U.O.N.). TYPE SETUP UNDER ONE COVER PLATE.
CORNERS, EDGES OR BREAKS OCCUR.
18. FULL SIZE OR LARGE SCALE DETAILS OR DRAWINGS SHALL GOVERN SMALL SCALE DRAWINGS WHICH THEY ARE DOORS, FRAMES AND HARDWARE NOTES 30. ARCHITECT SHALL SELECT AND APPROVE COLOR FOR ALL SWITCH PLATE & RECEPTACLE COVERS, TOGGLES & 13. PROVIDE TELEPHONE/DATA OUTLETS AND CONDUIT RUNS WITH DRAG LINES TO TELEPHONE EQUIPMENT AS
INTENDED TO AMPLIFY. DETAILS OR CONDITIONS INDICATED FOR A PORTION OF THE WORK BUT NOT CARRIED 27. GENERAL CONTRACTOR SHALL INCLUDE ALL RELATED FEES FOR REMOVAL OF DEBRIS AND IS RESPONSIBLE FOR PLUGS. PROVIDE SAMPLES. REQUIRED.
OUT FULLY FOR OTHER PORTIONS SHALL APPLY THROUGHOUT TO ALL SIMILAR PORTIONS EXCEPT AS OTHERWISE KEEPING THE JOB SITE BROOM CLEAN AT ALL TIMES, AND CLEANUP AFTER ALL FLOORING IS INSTALLED. 1. THE GENERAL CONTRACTOR SHALL REFER TO PLANS FOR HARDWARE SPECIFICATIONS.
SPECIFICALLY NOTED. IN EVERY CASE A MORE EXPENSIVE ITEM OR METHOD SHALL BE ASSUMED OVER A LESS 31. IN AREAS OF NEW FINISHES, ALL EXISTING SURFACES TO REMAIN, SHALL BE SANDED TO A SMOOTH UNIFORM 14. ALL CONDUITS TO BE SUPPORTED BY STANDOFFS, DO NOT WIRE TO CEILING SUPPORTS.
EXPENSIVE ONE AND DIMENSIONS SHALL BE FIGURED RATHER THAN DETERMINED BY RULE OR SCALE. 28. GENERAL CONTRACTOR SHALL INCLUDE ALL RELATED FEES FOR PROTECTION OF LOBBIES, ELEVATORS, BUILDING 2. THE GENERAL CONTRACTOR SHALL PROVIDE ALL BUCK ASSEMBLIES AS SPECIFIED ON PLANS. SURFACE.
SERVICES AND NEW CONSTRUCTION IN PLACE. 15. THE ELECTRICAL AND GENERAL CONTRACTOR SHALL PROVIDE ALL CUTTING AND PATCHING OF ALL CHASES IN
19. THE PROJECT HAS BEEN DESIGNED AND DETAILED FOR THE SPECIFIC MATERIALS AND EQUIPMENT SPECIFIED. NO 3. ALL LOCK SETS SHALL BE CODED AND KEYED IN ACCORDANCE WITH THE BUILDING AND CLIENT REQUIREMENTS, 32. REMOVE AND CLEAN ALL EXISTING WALL PLATES, THERMOSTATS AND OTHER REMOVABLE WALL ITEMS WHERE FLOORS, WALLS AND CEILINGS AS REQUIRED.
SUBSTITUTIONS SHALL BE MADE WITHOUT THE EXPRESS WRITTEN CONSENT OF THE ARCHITECT AND OWNER. IF 29. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PERMITS AND ASSOCIATED FEES. AND MUST BE PROPERLY TESTED AND TAGGED. GENERAL CONTRACTOR SHALL PROVIDE KEYS TO OWNER/CLIENT EXISTING WALLS ARE TO BE REFINISHED. REINSTALL AS REQUIRED WHEN FINISHES ARE COMPLETE.
THE SPECIFIED MATERIAL IS NOT AVAILABLE, THE CONTRACTOR SHALL PROPOSE AN ALTERNATE MATERIAL AND AT THE END OF JOB COMPLETION. 16. ALL EXISTING OUTLETS NOT BEING USED AND INTERFERING WITH NEW CONSTRUCTION SHALL BE REMOVED
SHALL PROVIDE DRAWINGS, SAMPLES, SPECIFICATIONS, MANUFACTURER'S LITERATURE, PERFORMANCE DATE, 30. GENERAL CONTRACTOR SHALL PROVIDE ARCHITECT/OWNER/TENANT WITH REPRODUCIBLE AND ELECTRONIC AS- 33. PROJECTS WITH REVEALS AT DOOR JAMBS, TOP CAPS OR ANY REVEALS THAT MEET WALL SURFACES, REQUIRE ALONG WITH WIRING ALL BACK TO PANEL.
ETC. IN ORDER THAT THE ARCHITECT CAN EVALUATE THE PROPOSED SUBSTITUTION. IF THE SUBSTITUTION BUILT DRAWINGS AND EQUIPMENT MANUALS FOR ALL TRADES. 4. ALL DOOR HANDLES SHALL BE LEVER TYPE AS PER A.D.A. REQUIREMENTS AND MOUNTED AT 3'-2" ABOVE FINISH WALL COVERING TO BE WRAPPED IN REVEAL PRIOR TO REVEAL BEING INSTALLED SO AS TO HOLD IN WALL
AFFECTS A CORRELATED FUNCTION, ADJACENT CONSTRUCTION, OR THE WORK OF ANY OTHER CONTRACTOR OR FLOOR, UNLESS OTHERWISE NOTED. COVERING. PAINTING CONTRACTOR SHALL BE RESPONSIBLE. 17. ALL A.D.A. OUTLETS OVER COUNTER TOPS SHALL BE NO HIGHER THAN 44" ABOVE FINISH FLOOR TO CENTERLINE
TRADE, THE NECESSARY CHANGES AND MODIFICATIONS TO THE AFFECTED WORK SHALL BE ACCOMPLISHED BY 31. GENERAL CONTRACTOR SHALL PROVIDE OPENINGS AS REQ'D FOR MECHANICAL, ELECTRICAL AND PLUMBING ON OF BOX. UNLESS OTHERWISE NOTED.
THE GENERAL CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER. NO REQUESTS FOR SUBSTITUTES ALL EXISTING WALLS, CORE WALLS AND NEW WALLS AND SHALL PATCH AND CLOSE SUCH WALLS TO THEIR 5. GENERAL CONTRACTOR SHALL COORDINATE ALL SECURITY SYSTEM REQUIREMENTS WITH THE OWNER/CLIENT FLOORING NOTES
WILL BE ENTERTAINED BY THE ARCHITECT DUE TO CONTRACTOR'S FAILURE TO ORDER MATERIALS IN A TIMELY ORIGINAL, EXISTING STATE. AND LANDLORD. 18. ALL NEW ELECTRICAL CONDUIT WHERE REQUIRED SHALL BE 3/4" MINIMUM SIZE THROUGHOUT, UNLESS
MANNER. 1. ALL FLOOR FINISHES SHALL BE INSTALLED AS PER MANUFACTURER INSTRUCTIONS/SPECIFICATIONS. OTHERWISE NOTED. PROJECT TITLE:
32. GENERAL CONTRACTOR SHALL CONDUCT FIELD CONSTRUCTION MEETINGS AND PROVIDE AND DISTRIBUTE 6. GENERAL CONTRACTOR SHALL REFER TO THE PLANS FOR HARDWARE FINISHES.
20. THE CONTRACTOR SHALL SUBMIT ALL FABRICATION SHOP DRAWINGS, SAMPLES, AND FIXTURE CUTS FOR THE
ARCHITECT'S REVIEW AS REQUIRED AND/OR INDICATED ON DRAWINGS. THE ARCHITECT'S REVIEW SHALL NOT BE
MEETING MINUTES TO ALL ATTENDANTS.
7. G.C. SHALL PROVIDE ALL MISCELLANEOUS DOOR HARDWARE REQUIRED FOR PROPER OPERATION AND/OR TO
2. CONTRACTOR SHALL FLASH PATCH HOLES, FLOOR DIPS, CRACKS OR OTHER IMPERFECTIONS AS REQUIRED TO
PROVIDE A SMOOTH AND LEVEL FLOOR FINISH, IN ADDITION TO CONSTRUCTION AND DEMOLITION NOTES.
19. ALL TELEPHONE, COMMUNICATION AND COMPUTER WIRING SHALL BE PROVIDED AND INSTALLED BY TENANT
UNLESS OTHERWISE NOTED. PENTHOUSE UNITS
CONSTRUED AS AN INDICATION THAT SUBMITTAL IS CORRECT OR SUITABLE NOR THAT WORK REPRESENTED BY
SUBMITTAL COMPLIES WITH THE DRAWINGS, EXCEPT AS TO MATTERS OF FINISH, COLOR, AND OTHER ESTHETIC
33. GENERAL CONTRACTOR SHALL PROVIDE SMOKE AND FIRE STOPPING SUBDIVISIONS, REQUIRED RATED AIR
TRANSFER GRILLES AND DAMPERS AS REQUIRED BY CODE AND/OR AS SHOWN ON ENGINEERING DRAWINGS.
MEET CODE REQUIREMENTS.
3. ALL WORKMANSHIP SHALL BE OF THE BEST QUALITY AND FREE OF BUCKLES, BUBBLES, OPEN JOINTS AND OTHER 20. CONTRACTOR SHALL INSTALL 3/4" CONDUIT AT ALL NEW TELEPHONE, COMMUNICATION AND COMPUTER OUTLETS RENOVATIONS
MATTERS. ACTION NOTED ABOVE DOES NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY TO COORDINATE
ALL TRADES AND TO CHECK QUANTITIES AND DIMENSIONS AGAINST CONDITIONS IN THE FIELD. CONTRACTORS 34. WHERE OVERLAPPING/CONFLICTING WORK/REQUIREMENTS ARE DISCOVERED, THE MOST STRINGENT AND MOST
8. ALL DOORS SHALL BE UNDERCUT AS REQUIRED TO ALLOW FOR PROPER CLEARANCE FOR FLOOR FINISH. IMPERFECTIONS. IN PARTITIONS AND STUBBED UP CONDUIT 6" ABOVE FINISHED CEILINGS.
FLOORS 26, 27, 28
AND VENDORS SHALL ASSUME RESPONSIBILITY FOR ALL ERRORS ON THEIR DRAWINGS. COSTLY CODE COMPLIANT INSTALLATION SHALL APPLY AND WILL BE ENFORCED, UNLESS MORE DETAILED 9. G.C. SHALL PROVIDE TO ARCHITECT HARDWARE SPECIFICATION AND SHOP DWGS. FOR REVIEW PRIOR TO 4. SPACES BEING SURFACED SHALL BE CLOSED TO TRAFFIC DURING INSTALLATION. 21. CONTRACTOR SHALL HARDWIRE ELECTRICAL POWER AND COMMUNICATIONS FEED TO FURNITURE SYSTEMS
LANGUAGE IS WRITTEN DIRECTLY INTO CONTRACT DOCUMENTS. ARCHITECT SHALL BE NOTIFIED BEFORE ORDERING OR FABRICATING. AND/OR RACEWAYS TO FURNITURE LOCATIONS. TENANT SHALL PROVIDE WHIP CONNECTOR TO FURNITURE LIBERTY VIEW
21. ALL MATERIALS REQUIRED FOR THE PERFORMANCE OF THIS CONTRACT SHALL BE NEW AND OF THE BEST PROCEEDING. 5. CONTRACTOR AND/OR SUPPLIER, PRIOR TO ORDERING ANY MATERIAL SHALL PROVIDE A SAMPLE OF EACH WOOD, SYSTEMS. 99 BATTERY PLACE
QUALITY OF KINDS SPECIFIED, ALL SUBJECT TO THE APPROVAL OF THE ARCHITECT. THE USE OF OLD OR SECOND- 10. OWNER SHALL BE RESPONSIBLE FOR MASTER KEYING DOOR HARDWARE/LOCKSETS WHERE REQUIRED. WOOD BASE, CARPET, V.C.T., VINYL BASE, TILE AND BASE, ETC FOR ARCHITECTS REVIEW AND APPROVAL.
HAND MATERIALS IS STRICTLY FORBIDDEN. THE CONTRACTOR SHALL, IF REQUIRED, FURNISH SATISFACTORY DEMOLITION NOTES 22. REFER TO ENGINEERING DRAWINGS FOR ADDITIONAL NOTES AND SPECIFICATIONS.
NEW YORK, NEW YORK 10280
EVIDENCE AS TO THE KIND AND QUALITY OF MATERIALS AND WORKMANSHIP. MATERIALS SHALL BE USED IN 11. G.C. SHALL INSTALL DOOR SILENCERS AT ALL DOOR FRAMES. 6. PROVIDE & INSTALL ALL CERAMIC, MARBLE, GRANITE TILE FLOORING & BASE IN ACCORDANCE WITH
ACCORDANCE WITH MANUFACTURER'S PRINTED INSTRUCTIONS. UPON REQUEST, THE MANUFACTURER'S 1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT AS REQUIRED TO COMPLETE MANUFACTURE'S PRINTED INSTRUCTIONS. PLUMBING, FIRE PROTECTION & HVAC NOTES
REPRESENTATIVE SHALL GO TO THE SITE AND INSTRUCT THE MECHANICS IN THE USE OF THE MATERIALS OR DEMOLITION AND REMOVAL OF ALL ITEMS SHOWN ON DRAWINGS. 12. G.C. SHALL SUBMIT TO ARCHITECT (3) SAMPLES OF DOOR STAIN/FINISH FOR REVIEW, PRIOR TO DOOR
SHALL SUPERVISE THEIR USE. FABRICATION/ORDERING AND FINAL FINISH APPLICATION. 7. FLOOR COVERING IN CLOSETS AND TELEPHONE, MECHANICAL AND ELECTRICAL ROOMS SHALL BE THE SAME AS 1. THE GENERAL CONTRACTOR SHALL PROVIDE ALL FIRE PROTECTION, PLUMBING, HEATING, VENTING AND AIR
2. ALL DEMOLITION DEBRIS SHALL BE REMOVED FROM THE PREMISES EXCEPT THOSE ITEMS TO BE REUSED, THAT OF THE SPACE INTO WHICH THE CLOSET OPENS UNLESS OTHERWISE NOTED. CONDITIONING AS CALLED FOR BY THE ENGINEERING DOCUMENTS.
22. FOR THE EXECUTION OF THE WORK TO BE PERFORMED UNDER THIS CONTRACT AND FOR THE MANUFACTURE OR RETURNED TO THE LANDLORD/OWNER, OR AS OTHERWISE DIRECTED. 13. PER FEDERAL REGISTER, RULES AND REGULATIONS SECTION SECTION 4.13.9 DOOR HARDWARE. HANDLES, PULLS,
TRANSPORTATION OF ANY OF THE MATERIALS OR EQUIPMENT TO BE USED OR INSTALLED, THE CONTRACTOR LOCKS, AND OTHER OPERATING DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE THAT IS EASY TO GRASP 8. ALL FLOOR TRANSITIONS SHALL BE LEVEL AND EVEN. 2. THE GENERAL CONTRACTOR SHALL COORDINATE THE INSTALLATION OF NEW AND EXISTING HVAC WITH ALL
SHALL EMPLOY ONLY SUCH LABOR THROUGHOUT AS WILL NOT INTERFERE WITH THE SPEEDY AND 3. THE CONTRACTOR SHALL CAREFULLY REMOVE, PROTECT AND STORE ALL CONSTRUCTION ELEMENTS TO BE WITH ONE HAND AND DOES NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING, OR TWISTING OF THE WRIST TO OTHER PHASES OF CONSTRUCTION.
UNINTERRUPTED COMPLETION OF THE PROJECT. ALL WORK SHALL BE DONE BY MECHANICS SKILLED IN THEIR REUSED OR RETURNED TO THE LANDLORD/OWNER. OPERATE. LEVER-OPERATED MECHANISM, PUSH TYPE MECHANISMS, AND U-SHAPED HANDLES ARE ACCEPTABLE 9. FINISH WOOD FLOORING SHALL BE TONGUE & GROOVE SOLID WHITE OAK 3/4” X 3 ¼” RIFT & QUARTERED, RANDOM
TRADE AND SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER IN ACCORDANCE WITH THE BEST TRADE DESIGNS. WHEN SLIDING DOORS ARE FULLY OPEN, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE LENGTH 60% 6’ AND LONGER 40%. GLUE AND FASTEN TO PLYWOOD SUBFLOOR. WOOD FLOORING SHALL BE 3. ALL SPACES SHALL BE MECHANICALLY VENTILATED AS PER GOVERNING LOCAL AND STATE BUILDING CODES.
PRACTICES. 4. UPON COMPLETION OF THE DEMOLITION WORK, ALL AREAS SHALL BE BROOM CLEAN. FROM BOTH SIDES. HARDWARE USED ON ACCESSIBLE DOOR PASSAGE SHALL BE MOUNTED NO HIGHER THAN 48" FILLED, SANDED, STAINED AND SEALED WITH MIN. THREE (3) COATS OF POLYURETHANE. STAIN COLOR AND FINISH DOB SCAN STICKER
ABOVE FINISHED FLOOR. SHALL BE AS DIRECTED BY OWNER/TENANT. 4. THE HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD SUPERVISION AND PROPER OPERATIONS OF THE
23. ANY MATERIALS DELIVERED OR WORK PERFORMED, CONTRARY TO THE DRAWINGS AND SPECIFICATIONS AND 5. SEE ENGINEERING DRAWINGS FOR EXTENT OF DEMOLITION TO THE EXISTING MECHANICAL SYSTEM, PLUMBING, SYSTEMS DURING INSTALLATION AND ALL TESTING AFTER COMPLETION. DRAWING TITLE:
APPROVED SHOP DRAWINGS, SHALL BE REMOVED BY THE CONTRACTOR AT THIS OWN EXPENSE, AND THE SAME SPRINKLER SYSTEM, ELECTRICAL AND FIRE PROTECTION SYSTEMS. 14. PER FEDERAL REGISTER, RULES AND REGULATIONS SECTION 4.13.10 DOOR CLOSERS, IF THE DOOR HAS A 10. GC SHALL PROVIDE AND INSTALL 3/4" F.R. PLYWOOD SUBFLOOR UNDER ALL WOOD FLOORING. SUBFLOOR SHALL
SHALL BE REPLACED WITH OTHER MATERIALS OR WORK SATISFACTORY TO THE ARCHITECT. THE CONTRACTOR
SHALL ALSO ASSUME THE COST OF REPLACING THE WORK WHICH MAY BE DISTURBED. 6. ALL CORE AREAS, ELEVATOR, LOBBIES, TOILETS, STAIRWELLS AND EXISTING ELEMENTS TO REMAIN SHALL BE
CLOSER, THEN THE SWEEP PERIOD OF THE CLOSER SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 70
DEGREES, THE DOOR WILL TAKE AT LEAST 3 SECONDS TO MOVE TO A POINT 3" FROM THE LATCH, MEASURED TO
BE GLUED AND MECHANICALLY PINNED TO CONCRETE SLAB WITH OWNER-APPROVED ANCHORS. 5. SHOP DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER AND ARCHITECT FOR REVIEW AND APPROVAL PRIOR TO
FABRICATION OF ALL DUCTWORK, PIPING AND EQUIPMENT.
SPECIFICATIONS
CAREFULLY SEALED AND PROTECTED FROM DAMAGE AND DIRT. THE LEADING EDGE OF THE DOOR. 11. PRIOR TO SUBFLOOR INSTALLATION GC SHALL SELF-LEVEL EXISTING CONCRETE SLAB AS REQUIRED/APPLICABLE
24. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY AND ACCURATELY LAYING OUT THE WORK AND FOR FOR EVEN SUBFLOOR INSTALLATION, USING 'MAPEI' NOVAPLAN 2 PLUS OR APPROVED EQUAL. 6. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL POWER WIRING AND SHALL ALSO COORDINATE HIS WORK
THE LINES AND MEASUREMENTS HEREIN. HE SHALL ESTABLISH NECESSARY REFERENCE LINES AND PERMANENT 7. ALL PERIMETER FAN COIL AND EQUIPMENT, RADIATOR ENCLOSURE AND WINDOWS SHALL BE CAREFULLY 15. PER FEDERAL REGISTER, RULES AND REGULATIONS SECTION SECTION 4.13.11 DOOR OPENING FORCE. THE WITH THE HVAC CONTRACTOR AND ENGINEER.
BENCH MARKS FROM WHICH BUILDING LINES AND ELEVATIONS SHALL BE TAKEN. ELEVATION HEIGHTS OF ALL COVERED AND PROTECTED FROM GRIT, RUBBISH AND DAMAGE. MAXIMUM FORCE FOR PUSHING OR PULLING OPEN A DOOR SHALL BE AS FOLLOWS: 12. GC SHALL PROVIDE AND INSTALL 'NOBLESEAL' SIS ACOUSTIC MEMBRANE WITH 'NOBLESEAL' BONDING ADHESIVE
WORK INCLUDING BUT NOT LIMITED TO SOFFITS, CEILINGS, DOORS, HOLLOW METAL SHALL BE TRUE AND LEVEL A. FIRE DOORS SHALL HAVE THE MINIMUM OPEN FORCE ALLOWABLE BY THE APPROPRIATE UNDER ALL PLYWOOD SUBFLOOR RECEIVING FINISH WOOD FLOORING. FOLLOW ALL MAN'F GUIDELINES FOR 7. ANY BUILDING SHUT DOWN AFFECTING NORMAL SERVICE SHALL BE REQUESTED IN WRITING AT LEAST 72 HOURS
WITHIN A MAXIMUM TOLERANCE OF 1/8" OVERALL THE ENTIRE PROJECT. 8. WHERE EXISTING SWITCHES, OUTLETS AND PHONE/DATA OUTLETS ARE REMOVED, G.C. SHALL FILL, PATCH, ADMINISTRATIVE AUTHORITY. INSTALLATION INCLUDING CURING TIME FOR SELF-LEVELING PRODUCT. IN ADVANCE. GENERAL CONTRACTOR SHALL OBTAIN APPROVAL FROM ALL AUTHORITIES HAVING JURISDICTION
SPACKLE AND SAND SMOOTH WALL FOR PAINT. NO COVER PLATES SHALL BE USED. B. OTHER DOORS: PRIOR TO SHUT DOWN. ALL OVERTIME FOR SHUT DOWNS FOR ELECTRICAL, PLUMBING, SPRINKLERS AND HVAC TO
25. ALL HVAC, PLUMBING, SPRINKLER AND ELECTRICAL LINES ARE TO BE COORDINATED SO THAT NO CONFLICTS a. EXTERIOR HINGED DOORS: (RESERVED) 13. GC SHALL PROVIDE AND INSTALL 'NOBLESEAL' TS WATERPROOFING MEMBRANE WITH 'NOBLESEAL' BONDING BE FIGURED IN BID OR PROPOSAL. NO EXTRAS WILL BE PAID.
OCCUR. ANY CONFLICTS WHICH RESULT IN A RELOCATION OF A FINISHED SURFACE WILL BE DONE WITH MINIMUM 9. ALL ELECTRICAL AND LIGHTING TO BE DEMOLISHED AND ASSOCIATED WIRING SHALL BE PULLED BACK TO THE b. NTERIOR HINGED DOORS: 5 lbf (22.2N) ADHESIVE UNDER ALL STONE AND TILE FLOORING. FOLLOW ALL MAN'F GUIDELINES FOR INSTALLATION INCLUDING
SCALE: AS NOTED PAGE: 7 of 30
DISRUPTION TO THE OPERATIONS OF THE EXISTING FACILITY DURING CONSTRUCTION/ RENOVATION AND MUST BE ELECTRICAL PANELS AND REMOVED COMPLETELY. c. SLIDING OR FOLDING DOORS: 5 lbf (22.2N) MIN. EXTENSIONS UP ALL WALLS. STONE FLOOR TILE SHALL BE INSTALLED IN MUDSET OR DRY PACK SETTING ON 8. WHEN EXISTING AIR TROFFERS ARE REMOVED OR RELOCATED, THE CONTRACTOR SHALL ALSO REMOVE DUCT
BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER PRIOR TO INSTALLATION. MEMBRANE. BRANCHES BACK TO THE APPROPRIATE LOCATION.

A002.00
10. ALL DEMOLITION WORK SHALL BE PERFORMED BEFORE OR AFTER BUSINESS HOURS, UNLESS OTHERWISE THESE FORCES DO NOT APPLY TO THE FORCE REQUIRED TO RETRACT LATCH BOLTS OR
26. A SET OF THE INSTRUCTION MANUALS AND INSTALLATION INSTRUCTIONS OF ALL EQUIPMENT AND ACCESSORIES PERMITTED BY THE BUILDING MANAGER AND/OR THE CLIENT. DISENGAGE OTHER DEVICES THAT MAY HOLD THE DOOR IN A CLOSED POSITION. 9. GENERAL CONTRACTOR SHALL PROVIDE FIRE HOSE CABINETS AND FIRE SUPPRESSION SYSTEM AS PER
INSTALLED IN THIS JOB SHALL BE KEPT BY THE CONTRACTOR AND TURNED OVER TO THE OWNER AT THE ENGINEERING DRAWINGS OR PER CODE REQUIREMENTS.
COMPLETION OF THE JOB. THE CONTRACTOR WILL PROVIDE THE OWNER WITH VIDEO TAPED INSTRUCTIONS AND 11. IN ALL AREAS WHERE DEMOLITION OR CUTS AND PATCHES CAUSE AN UNEVENNESS IN THE FLOOR SLAB, THE
DEMONSTRATIONS OF NEW EQUIPMENT START-UP AND MAINTENANCE INSTRUCTIONS. CONTRACTOR SHALL FLASH PATCH AS REQUIRED TO RECEIVE THE NEW FLOOR FINISH. COORDINATE WITH 10. GENERAL CONTRACTOR SHALL PROVIDE FIRE EXTINGUISHERS AND RECESSED CABINETS AS PER ENGINEERING
FLOORING CONTRACTOR. DRAWINGS, FIRE MARSHALL AND CODE REQUIREMENTS.
27. PROVIDE ADEQUATE BACKUP AND BLOCKING FOR ALL WALL OR CEILING MOUNTED EQUIPMENT, ARCHITECTURAL
WOODWORK, HANDRAILS LIGHTING OR OTHER MISCELLANEOUS ITEMS AS SHOWN ON DRAWINGS TO ASSURE A 12. THE GENERAL CONTRACTOR SHALL ERECT A PLASTIC DUST PARTITION TO PROTECT AREAS NOT INCLUDED IN THE 11. PLUMBING FIXTURE INSTALLATION SHALL COMPLY WITH A.D.A. AND HANDICAP CODE REQUIREMENTS. SEE
SECURE INSTALLATION. SCOPE OF WORK. ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS, TOILET AND PANTRY LAYOUTS FOR DIMENSIONS. DO NOT
SCALE DRAWINGS.
28. THE DRAWINGS HEREIN ARE RELATED TO A RENOVATION TO AN EXISTING BUILDING. ASSUMPTIONS HAVE BEEN 13. PRIOR TO DEMOLITION, THE CONSTRUCTION AREA SHALL BE INSPECTED FOR PRESENCE OF ASBESTOS. IF
MADE ABOUT UNKNOWN CONDITIONS. ARCHITECT & OWNER WILL NOT BE RESPONSIBLE FOR ANY FAILURE, PRESENT IT SHALL BE REMOVED IN COMPLIANCE WITH THE STATE OF NEW YORK REQUIREMENTS AND FEDERAL 12. MECHANICAL SUBCONTRACTOR TO VISIT JOB-SITE PRIOR TO BID AND NOTIFY ARCHITECT AND ENGINEER OF ANY
DAMAGE, INJURY DELAY, LOSS OF INCOME, EXTRA COST, OR ANY OTHER LOSS DUE TO EXISTING CONDITIONS. NESHAP (NATIONAL EMISSION STANDARD FOR HAZARDOUS AIR POLLUTANTS) REGULATION. (NESHAP - PHONE: DISCREPANCIES. ALL MECHANICAL SUBCONTRACTORS TO INCLUDE PRICING FOR FIELD CONFLICTS.
1-617-565-9055).
29. GC SHALL REFER TO OWNER'S BID INSTRUCTIONS/DOCUMENTS AND SCOPE FINISHES AND ADDITIONAL WORK 13. SEE ENGINEERING DRAWINGS FOR ADDITIONAL NOTES AND SPECIFICATIONS.
REQUIREMENTS TO COMPLETE WORK HEREIN DEPICTED ON THESE DRAWINGS. 14. WHERE REMOVALS ARE NOT POSSIBLE WITHOUT DAMAGE OF EXISTING TO REMAIN. G.C. SHALL REPAIR OR
REPLACE DAMAGED ITEMS AS REQUIRED. SEAL
PHA - DOOR SCHEDULE
DOOR # TYPE WIDTH HEIGHT MATERIAL FRAME REMARKS BATTERY PLACE
A01
A02
A
B
3' - 0"
2' - 10"
8' - 0"
7' - 0"
HOLLOW METAL
SOLID CORE WOOD
HM
SC WOOD
EXISTING FPSC UNIT ENTRANCE DOOR
ASSOCIATES, LLC
A03 B 2' - 10" 7' - 0" SOLID CORE WOOD SC WOOD C/O MILSTEIN PROPERTIES
A04 B 2' - 10" 7' - 0" SOLID CORE WOOD SC WOOD 335 MADISON AVENUE
A05 B 2' - 10" 7' - 0" SOLID CORE WOOD SC WOOD
NEW YORK, NY 10017
A06 C 4' - 0" 7' - 0" SOLID CORE WOOD SC WOOD
(212) 308-7200
A07 C 4' - 0" 7' - 0" SOLID CORE WOOD SC WOOD
A08 C 4' - 0" 7' - 0" SOLID CORE WOOD SC WOOD
A09 C 4' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
A10 C 4' - 0" 7' - 0" SOLID CORE WOOD SC WOOD

DOOR TYPES

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE
84"

84"

84"

84"
SEE SEE
SCHEDULE36" SCHEDULE
36"
SEE SCHEDULE
72"
SEE SCHEDULE
72"

TYPE A TYPE B TYPE C TYPE D


SWING DOOR POCKET DOOR PAIR SWING PAIR SLIDING
DOORS DOORS

DOOR NOTES

1. ALL DOORS SHALL BE PAINTED AND HAVE PAINTED WOOD CASINGS, DYKES #235 4 1/4" POPLAR, OVER NEW & EXIST. FRAMES

2. ALL BEDROOMS & BATHROOMS SHALL HAVE PRIVACY LEVER HARDWARE: 'ARROW' CL-02-SC-26D500

3. ALL SINGLE CLOSET AND WALK-IN CLOSETS SHALL HAVE PASSAGE LEVER HARDWARE: 'ARROW' CL-01-SC-26D500

4. ALL DOUBLE CLOSET DOORS SHALL HAVE DOUBLE DUMMY LEVER HARDWARE: 'ARROW' CL-08-SC-26D & 'ROCKWOOD' #901 HEAVY DUTY
MAGNETIC CATCH.

5. ALL POCKET DOORS SHALL HAVE HAFELE HEAVY DUTY SLIDING TRACK SYSTEMS.

6. ALL PRIVACY POCKET DOORS SHALL HAVE 'ACCURATE' #2002CPDL HARDWARE WITH #CS2002T & #CS2002E FLUSH PULLS.

7. ALL PASSAGE POCKET DOORS SHALL HAVE 'ACCURATE' #2000 HARDWARE WITH #CS2002B FLUSH PULLS.

8. ALL SWING DOORS SHALL HAVE TWO PAIR OF 'MCKINNEY' #MPB79 FIVE KNUCKLE HINGES, 'IVES' HINGE PIN STOP #70 AND FOUR GRAY 'IVES'
SILENCERS #SR64/65 DEPENDING ON FRAME MATERIAL

9. PROVIDE AND INSTALL FIRE RATED WOOD BLOCKING AT ALL JAMBS.

10. ALL SLIDING CLOSET DOORS SHALL HAVE 'PEMKO' #H200 SLIDING KIT AND FLUSH PULLS.

11. ALL HARDWARE SHALL HAVE US26D SATIN CHROME FINISH.

12. ALL EXISTING FRAMELESS CLOSETS SHALL HAVE NEW PAINTED JAMBS AND HEAD WITH NEW WOOD CASING.

13. ALL EXISTING APARTMENT ENTRY DOORS, FRAMES AND CASINGS ON BOTH SIDES SHALL BE PAINTED.

CONSTRUCTION PLAN LEGEND ISSUED FOR BID 05/18/2020


NO. DESCRIPTION DATE

EXISTING OPERABLE NEW PERIMETER EXISTING


WINDOW, TYP MILLWORK, TYP. PTAC, TYP EXISTING WALL TO REMAIN

DOOR AND FRAME - SEE SCHEDULE


1i DISTANCE FROM PERPENDICULAR WALL WHEN OPEN

1'-4"
NEW NONBEARING PARTITION - SEE TYPES 101 SHALL BE 4" UON.
2C 1'-4"
2C

S NEW HARD-WIRED COMBO SMOKE/CARBON MONOXIDE FIRE PROTECTIVE SELF-CLOSING DOOR 1 HOUR FIRE
1'-4"

DETECTOR FPSC
RATED
2C

2C

CONSTRUCTION NOTES
1'-4"

2C
PROJECT TITLE:
1. PATCH ALL EXISTING FLOOR & CEILING OPENINGS. REPLACE ANY DAMAGED GWB, MTL STUD & INSULATION FURRING AT EXTERIOR WALL.
1'-6"

VANITY 2A
2. ALL EXISTING COLUMNS, MECHANICAL SHAFTS, EXTERIOR WALLS AND DEMISING WALLS SHALL BE SKIM COATED AND/OR LAMINATED WITH NEW PENTHOUSE UNITS
MASTER
GWB AS REQ'D FOR LIKE-NEW STRAIGHT AND PLUMB INSTALLATION.
RENOVATIONS
LAV
MBATH 1 2A BEDROOM 2 LIVING/DINING
BEDROOM 1 3. COORDINATE SELECTIVE LOCALIZED REMOVAL AND REPLACEMENT OF EXISTING DEMISING WALL GWB AS REQ'D TO FACILITATE ELEC WIRING &
DEVICES AND PLUMBING UTILITIES. ALL FIRE RATINGS SHALL BE MAINTAINED. ALL RECEPTACLE BOXES AND PIPING PENETRATIONS SHALL HAVE FLOORS 26, 27, 28
ALIGN

8'-8"
7'-9"

2C FIRE SEALANT AROUND ALL SIDES.


LIBERTY VIEW
9" 1'-10" 4'-2" 14'-11 1/2" 11'-0" 18'-8 1/4" 4. PROVIDE FIRE-STOPPING AS REQUIRED BY NEW YORK CITY BUILDING CODE AT FLOOR & WALL PENETRATIONS THRU FIRE-RATED 99 BATTERY PLACE
CONSTRUCTION.
LAV
NEW YORK, NEW YORK 10280
CHASE 2

2C 2A 5. FRAME TIGHT ALL EXISTING PIPE RISER STACKS WITH NEW PART TYPE 2C. FIRE RATED DEMISING LOCATIONS SHALL BE FRAMED TIGHT WITH
A08 BENCH
PART. TYPE 3C
A05
1'-10" 2'-1" 3'-6" 4'-2 1/2" 2'-3 1/2" 2'-0" 1'-4" 6. ACCESS DOORS IN INTERIOR GWB WALLS AND/OR CEILING SHALL BE 'ACUDOR' #DW-5015 RECESSED SERIES WITH FLUSH DRYWALL FACE.
1'-4"

2'-10 3/4"
2'-4"

2C 2C ACCESS DOORS WITHIN CABINETRY SHALL BE 'ACUDOR' #UF-5000 FLUSH SERIES. SIZE PER PLANS AND NOTES.
3'-7 3/8"

2C 2C 2A 2C 2C
SHOWER
2A 7. FILL, REPAIR, TOUCH-UP & SAND SMOOTH FOR FINISH PAINT ALL EXISTING WINDOW SUBFRAMES.
2C 3A 2C 2C 2C
2C
1'-4"

HUTCH 2C 8. PROVIDE BLOCKING AS REQUIRED FOR IN-WALL CARRIERS FOR WALL HUNG TOILETS.
4'-8"

2C A06 A07 A04 A03


3'-5"

R
3'-0" 3'-0" 4'-6 3/4" 4'-6 3/4" 13'-8 1/8" 2'-5 7/8" 2A 9. PROVIDE PLYWOOD BLOCKING BETWEEN STUDS IN ALL PARTITIONS AT ALL CLOSETS, WALK-IN CLOSETS & LAUNDRY /STORAGE ROOMS. DOB SCAN STICKER
2'-1"

2A
2'-1"

2A
3'-2"

WINE 2C
TOILET 2A 2A HALL 3A 2C REF'G 10. REMOVE ALL ELECTRICAL STUBS AND UNUSED CONDUIT POKE THROUGHS AT DEMOLISHED WALLS AND RELOCATE AS REQ'D TO NEW DRAWING TITLE:
PARTITIONS/CEILINGS.
PH A - CONSTRUCTION
ALIGN

ALIGN

ALIGN
ALIGN

A02 2A FOYER 11. COORDINATE WITH BLDG MGMT, FIXTURE SELECTIONS, AND FIELD CONDITIONS OF ANY AND ALL NEW/MODIFICATION WORK OF EXISTING WALLS,
CEILINGS, CABINETRY AND/OR FINISHES OF APARTMENTS DIRECTLY BELOW THIS APARTMENT AS REQ'D FOR NEW PLUMBING WORK.
PLAN
5'-10 1/2"

4'-8 1/8" 7'-8 3/8" 1'-4"


2A
KITCHEN
TOILET

5'-0 1/2"

12. PROVIDE SHELF & ROD AT ALL COAT CLOSETS AND WALK-IN CLOSETS.
BATH 2 2C 2A
A10
A09 13. ALL EXISTING HVAC UNITS TO REMAIN.
CHASE 1

2C
7'-2"

LAV
2'-0"

2'-11"

1'-10" 2C 14. PROVIDE 'NOBLESEAL' TS WATERPROOFING MEMBRANE AT ALL BATHROOMS AND LAUNDRY ROOMS. FOLLOW MANUFACTURER'S GUIDELINES
AND EXTEND W.P. MEMBRANE UP ALL WALLS AS REQUIRED.
D W D/W 2C SCALE: AS NOTED PAGE: 8 of 30
2'-1"

SINK
1'-1" 5'-6" 1'-9" 2A 5'-1 3/8" 2C PANTRY 15. AT BATHROOM VANITIES & KITCHEN PROVIDE 16"X16" PTO. ACCESS DOOR IN PARTITION, CONCEALED WITHIN BOTTOM CABINET FOR VALVE
A01
ACCESS. COORDINATE LOCATION WITH SINK PIPING & FIELD CONDITIONS. PROVIDE CUT-OUT IN MILLWORK BACK PANEL FOR ACCESS DOOR.

A100.00
BATHTUB
G CABINETS SHALL BE ADAPTABLE FOR FUTURE ACCESSIBILITY.
RECESSED NEW KITCHEN CABINETRY,
W/D BOX COUNTERS & APPLIANCES, TYP 16. ALL PARTITIONS SHALL BE PAINTED. BATHROOMS SHALL HAVE TILED FLOORS & WALLS. ALL EXISTING EXPOSED CONG. CEILINGS SHALL BE SKIM
COATED LEVEL & SMOOTH AS REQ'D.
EXISTING FSPC ENTRY EXISTING FIRE RATED
DOOR TO REMAIN DEMISING WALL, TYP 17. GWB CEILINGS & SOFFITS SHALL BE INSTALLED PER REQUIREMENTS OF NYC BUILDING CODE REFERENCE STANDARD RS 5-16. BATHROOMS,
HALLS, KITCHEN & WALK-IN CLOSETS WHERE NOTED SHALL HAVE GWB CEILINGS AT 7'-6" AFF, UON.

18. BATHROOMS SHALL BE PROVIDED WITH MIN 50CFM FAN MECHANICAL VENTILATION & FUSIBLE LINK FIRE DAMPER AT DUCTWORK, ALL NYC MEA &
BSA APPROVED.

19. BATHTUB/SHOWERS SHALL HAVIE 3/8" GLASS DOOR AND/OR FIXED SCREEN WITH POLISHED CHROME HARDWARE. VIF DOOR SWING CLEARANCE
PHA - CONSTRUCTION FLOOR PLAN WITH ADJACENT FIXTURES. CONFIRM WITH BUILDING MANAGEMENT
1 1/4" = 1'-0"
20. KITCHEN & BATH CABINETRY AND MISC. BUILT-INS SHALL BE CONSTRUCTED OF 3/4" PLYWOOD FRAMES AND M.R. MDF IN WET AREAS

SEAL
PHB - DOOR SCHEDULE
DOOR # TYPE WIDTH HEIGHT MATERIAL FRAME REMARKS BATTERY PLACE
B01
B02
A
A
3' - 0"
3' - 0"
7' - 0"
7' - 0"
HOLLOW METAL
SOLID CORE WOOD
HM
SC WOOD
EXISTING FPSC UNIT ENTRANCE DOOR
ASSOCIATES, LLC
B03 C 4' - 0" 7' - 0" SOLID CORE WOOD SC WOOD C/O MILSTEIN PROPERTIES
B04 A 2' - 0" 7' - 0" SOLID CORE WOOD SC WOOD 335 MADISON AVENUE
B05 3' - 0" 7' - 0" ALUMINUM ALUMINUM EXISTING RELOCATED TERRACE DOOR
NEW YORK, NY 10017
B06 A 3' - 0" 7' - 0" SOLID CORE WOOD SC WOOD
(212) 308-7200
RECESSED TERRACE B07 A 3' - 0" 7' - 0" SOLID CORE WOOD SC WOOD
W/D BOX B08 A 3' - 0" 7' - 0" SOLID CORE WOOD SC WOOD
B09 A 2' - 0" 7' - 0" SOLID CORE WOOD SC WOOD
B10 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
B05 B11 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD

1'-0"
B12 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
B13 C 5' - 0" 7' - 0" SOLID CORE WOOD SC WOOD
D 2C 3A
1'-10" DOOR TYPES
1'-0" 4'-9 1/2" 5'-4 3/4"
W

8'-6 1/4"

8'-0 1/4"
CHASE 7
2C

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE
LAUND.

84"

84"

84"

84"
B10
2C 2C SHOWER 2C 2C

3'-0"
SINK

2A 2C
2C SEE SEE
SCHEDULE36" SCHEDULE
36"
SEE SCHEDULE
72"
SEE SCHEDULE
72"

3'-0" 6'-6" 5'-6 1/4" 14'-7 3/4" 1'-4"


WIC 1

TOILET

3'-0"
TYPE A TYPE B TYPE C TYPE D NOT FOR CONSTRUCTION
SWING DOOR POCKET DOOR PAIR SWING PAIR SLIDING
3A 2A MASTER EXISTING DOORS DOORS
RELOCATED EXAUST DUCT. B12 PTAC, TYP
SEE MECHANICAL BEDROOM 1
VANITY
2C MBATH 1 3A DOOR NOTES

3'-2 1/4"
1'-6" B11

1'-10"
1. ALL DOORS SHALL BE PAINTED AND HAVE PAINTED WOOD CASINGS, DYKES #235 4 1/4" POPLAR, OVER NEW & EXIST. FRAMES
NEW PERIMETER
LAV LAV 3A 2A MILLWORK, TYP. 2. ALL BEDROOMS & BATHROOMS SHALL HAVE PRIVACY LEVER HARDWARE: 'ARROW' CL-02-SC-26D500
1'-6"

2C 2C 2C
LINEN 3. ALL SINGLE CLOSET AND WALK-IN CLOSETS SHALL HAVE PASSAGE LEVER HARDWARE: 'ARROW' CL-01-SC-26D500
B07
2A 4. ALL DOUBLE CLOSET DOORS SHALL HAVE DOUBLE DUMMY LEVER HARDWARE: 'ARROW' CL-08-SC-26D & 'ROCKWOOD' #901 HEAVY DUTY
2C
CORRIDOR MAGNETIC CATCH.

3'-5"
BATHTUB
B08 B06 2C
2C 2A 2C 2A
BATH 2 ALIGN 5. ALL POCKET DOORS SHALL HAVE HAFELE HEAVY DUTY SLIDING TRACK SYSTEMS.
6'-0"

7'-7 3/4"
B09 6. ALL PRIVACY POCKET DOORS SHALL HAVE 'ACCURATE' #2002CPDL HARDWARE WITH #CS2002T & #CS2002E FLUSH PULLS.
2C 2C 2'-8"
1'-10"

LAV
2C 2C 7. ALL PASSAGE POCKET DOORS SHALL HAVE 'ACCURATE' #2000 HARDWARE WITH #CS2002B FLUSH PULLS.
EXISTING OPERABLE
BEDROOM 2 WINDOW, TYP
TOILET B13 8. ALL SWING DOORS SHALL HAVE TWO PAIR OF 'MCKINNEY' #MPB79 FIVE KNUCKLE HINGES, 'IVES' HINGE PIN STOP #70 AND FOUR GRAY 'IVES'
2'-6" CHASE 8 2'-1 3/4" SILENCERS #SR64/65 DEPENDING ON FRAME MATERIAL

9. PROVIDE AND INSTALL FIRE RATED WOOD BLOCKING AT ALL JAMBS.


3'-0" 2'-4 1/2" 3'-0" 2'-2" 13'-9 3/4" 1'-4"
REPLACE STAIR TREADS, 10. ALL SLIDING CLOSET DOORS SHALL HAVE 'PEMKO' #H200 SLIDING KIT AND FLUSH PULLS.
RISERS, AND RAILINGS.
1A
SEE A401.00 FOR DETAILS 2A 11. ALL HARDWARE SHALL HAVE US26D SATIN CHROME FINISH.

12. ALL EXISTING FRAMELESS CLOSETS SHALL HAVE NEW PAINTED JAMBS AND HEAD WITH NEW WOOD CASING.

13. ALL EXISTING APARTMENT ENTRY DOORS, FRAMES AND CASINGS ON BOTH SIDES SHALL BE PAINTED.

CONSTRUCTION PLAN LEGEND


PHB - CONSTRUCTION FLOOR PLAN UPPER
2 1/4" = 1'-0" NO.
ISSUED FOR BID
DESCRIPTION
05/18/2020
DATE
EXISTING WALL TO REMAIN

DOOR AND FRAME - SEE SCHEDULE


1i DISTANCE FROM PERPENDICULAR WALL WHEN OPEN
NEW NONBEARING PARTITION - SEE TYPES 101 SHALL BE 4" UON.

S NEW HARD-WIRED COMBO SMOKE/CARBON MONOXIDE FIRE PROTECTIVE SELF-CLOSING DOOR 1 HOUR FIRE
DETECTOR FPSC
RATED

CONSTRUCTION NOTES
TOILET

1. PATCH ALL EXISTING FLOOR & CEILING OPENINGS. REPLACE ANY DAMAGED GWB, MTL STUD & INSULATION FURRING AT EXTERIOR WALL.
1'-3 1/2"
CHASE 7

5'-6" 2'-1"
2. ALL EXISTING COLUMNS, MECHANICAL SHAFTS, EXTERIOR WALLS AND DEMISING WALLS SHALL BE SKIM COATED AND/OR LAMINATED WITH NEW PROJECT TITLE:
4'-8 1/2"

POWDER 2A GWB AS REQ'D FOR LIKE-NEW STRAIGHT AND PLUMB INSTALLATION.


PENTHOUSE UNITS
LAV
EXISTING
2A PTAC, TYP
2C 3. COORDINATE SELECTIVE LOCALIZED REMOVAL AND REPLACEMENT OF EXISTING DEMISING WALL GWB AS REQ'D TO FACILITATE ELEC WIRING &
DEVICES AND PLUMBING UTILITIES. ALL FIRE RATINGS SHALL BE MAINTAINED. ALL RECEPTACLE BOXES AND PIPING PENETRATIONS SHALL HAVE RENOVATIONS
12'-1 1/4"

2A WINE
LIVING
1'-9"

FIRE SEALANT AROUND ALL SIDES.


2'-5" 3'-8"
FLOORS 26, 27, 28
1'-4"

2C
EXISTING FIRE RATED B02 4. PROVIDE FIRE-STOPPING AS REQUIRED BY NEW YORK CITY BUILDING CODE AT FLOOR & WALL PENETRATIONS THRU FIRE-RATED
DEMISING WALL, TYP B04 CONSTRUCTION. LIBERTY VIEW
2A NEW PERIMETER
2C 1'-4" MILLWORK, TYP. 5. FRAME TIGHT ALL EXISTING PIPE RISER STACKS WITH NEW PART TYPE 2C. FIRE RATED DEMISING LOCATIONS SHALL BE FRAMED TIGHT WITH
99 BATTERY PLACE
FOYER PART. TYPE 3C NEW YORK, NEW YORK 10280
4'-11"

B01
6'-1 1/2" 3'-0" 3'-3 1/2"
EXISTING FSPC ENTRY 6. ACCESS DOORS IN INTERIOR GWB WALLS AND/OR CEILING SHALL BE 'ACUDOR' #DW-5015 RECESSED SERIES WITH FLUSH DRYWALL FACE.
DOOR TO REMAIN 2A 2C 2A
ALIGN ACCESS DOORS WITHIN CABINETRY SHALL BE 'ACUDOR' #UF-5000 FLUSH SERIES. SIZE PER PLANS AND NOTES.
ALIGN
B03 7. FILL, REPAIR, TOUCH-UP & SAND SMOOTH FOR FINISH PAINT ALL EXISTING WINDOW SUBFRAMES.
1'-9"

4'-6 1/2" 2C 2C
8. PROVIDE BLOCKING AS REQUIRED FOR IN-WALL CARRIERS FOR WALL HUNG TOILETS.
3'-3"

2A
4'-9"

9. PROVIDE PLYWOOD BLOCKING BETWEEN STUDS IN ALL PARTITIONS AT ALL CLOSETS, WALK-IN CLOSETS & LAUNDRY /STORAGE ROOMS.
2A HUTCH EXISTING OPERABLE
8'-10 3/4"
7'-6"

2A WINDOW, TYP 10. REMOVE ALL ELECTRICAL STUBS AND UNUSED CONDUIT POKE THROUGHS AT DEMOLISHED WALLS AND RELOCATE AS REQ'D TO NEW
2'-0" 1'-4" PARTITIONS/CEILINGS. DOB SCAN STICKER
2A
3'-0" 2'-4 1/2" DRAWING TITLE:
3'-3"

ALIGN

11. COORDINATE WITH BLDG MGMT, FIXTURE SELECTIONS, AND FIELD CONDITIONS OF ANY AND ALL NEW/MODIFICATION WORK OF EXISTING WALLS,
3'-0"

KITCHEN/DINING CEILINGS, CABINETRY AND/OR FINISHES OF APARTMENTS DIRECTLY BELOW THIS APARTMENT AS REQ'D FOR NEW PLUMBING WORK.
PANTRY
2C PH B - CONSTRUCTION
12. PROVIDE SHELF & ROD AT ALL COAT CLOSETS AND WALK-IN CLOSETS.
BENCH
PLANS
2A 13. ALL EXISTING HVAC UNITS TO REMAIN.
5'-7 1/2"

14. PROVIDE 'NOBLESEAL' TS WATERPROOFING MEMBRANE AT ALL BATHROOMS AND LAUNDRY ROOMS. FOLLOW MANUFACTURER'S GUIDELINES
REF'G 2C
4'-4 1/2"

AND EXTEND W.P. MEMBRANE UP ALL WALLS AS REQUIRED.

2'-1" 11'-1 1/4" 15. AT BATHROOM VANITIES & KITCHEN PROVIDE 16"X16" PTO. ACCESS DOOR IN PARTITION, CONCEALED WITHIN BOTTOM CABINET FOR VALVE
ACCESS. COORDINATE LOCATION WITH SINK PIPING & FIELD CONDITIONS. PROVIDE CUT-OUT IN MILLWORK BACK PANEL FOR ACCESS DOOR. SCALE: AS NOTED PAGE: 9 of 30
CABINETS SHALL BE ADAPTABLE FOR FUTURE ACCESSIBILITY.
2'-1"

A101.00
SINK
16. ALL PARTITIONS SHALL BE PAINTED. BATHROOMS SHALL HAVE TILED FLOORS & WALLS. ALL EXISTING EXPOSED CONG. CEILINGS SHALL BE SKIM
D/W COATED LEVEL & SMOOTH AS REQ'D.

17. GWB CEILINGS & SOFFITS SHALL BE INSTALLED PER REQUIREMENTS OF NYC BUILDING CODE REFERENCE STANDARD RS 5-16. BATHROOMS,
HALLS, KITCHEN & WALK-IN CLOSETS WHERE NOTED SHALL HAVE GWB CEILINGS AT 7'-6" AFF, UON.
NEW KITCHEN CABINETRY,
COUNTERS & APPLIANCES, TYP 18. BATHROOMS SHALL BE PROVIDED WITH MIN 50CFM FAN MECHANICAL VENTILATION & FUSIBLE LINK FIRE DAMPER AT DUCTWORK, ALL NYC MEA &
BSA APPROVED.

19. BATHTUB/SHOWERS SHALL HAVIE 3/8" GLASS DOOR AND/OR FIXED SCREEN WITH POLISHED CHROME HARDWARE. VIF DOOR SWING CLEARANCE
WITH ADJACENT FIXTURES. CONFIRM WITH BUILDING MANAGEMENT

PHB - CONSTRUCTION FLOOR PLAN LOWER 20. KITCHEN & BATH CABINETRY AND MISC. BUILT-INS SHALL BE CONSTRUCTED OF 3/4" PLYWOOD FRAMES AND M.R. MDF IN WET AREAS
1 1/4" = 1'-0"

SEAL
PHCE - DOOR SCHEDULE
DOOR # TYPE WIDTH HEIGHT MATERIAL FRAME REMARKS BATTERY PLACE
CE01
CE02
A
A
3' - 0"
2' - 10"
7' - 0"
7' - 0"
HOLLOW METAL
SOLID CORE WOOD
HM
SC WOOD
EXISTING FPSC UNIT ENTRANCE DOOR
ASSOCIATES, LLC
CE03 A 3' - 0" 7' - 0" SOLID CORE WOOD SC WOOD C/O MILSTEIN PROPERTIES
CE04 C 3' - 4" 7' - 0" SOLID CORE WOOD SC WOOD 335 MADISON AVENUE
CE05 A 2' - 10" 7' - 0" SOLID CORE WOOD SC WOOD
NEW YORK, NY 10017
CE06 A 2' - 6" 7' - 0" SOLID CORE WOOD SC WOOD
(212) 308-7200
CE07 A 3' - 0" 7' - 0" SOLID CORE WOOD SC WOOD
CE08 B 2' - 10" 7' - 0" SOLID CORE WOOD SC WOOD
CE09 B 2' - 10" 7' - 0" SOLID CORE WOOD SC WOOD
2C CE10 3' - 0" 7' - 0" ALUMINUM ALUMINUM EXISTING TERRACE DOOR
REPLACE STAIR TREADS, CE11 A 3' - 0" 7' - 0" SOLID CORE WOOD SC WOOD

10"

1'-9"
CHASE 8
RISERS, AND RAILINGS. CE12 A 3' - 0" 7' - 0" SOLID CORE WOOD SC WOOD
TOILET SEE A401.00 FOR DETAILS CE13 A 3' - 0" 7' - 0" SOLID CORE WOOD SC WOOD

1'-10"
CE15
LAV
CE14 A 3' - 0" 7' - 0" SOLID CORE WOOD SC WOOD

5'-6"
CE15 C 3' - 4" 7' - 0" SOLID CORE WOOD SC WOOD
2'-6" 2'-2 1/2" CE16 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
1A
2A CE17 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
BATH 3 CE14 CE18 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
BATHTUB 2A CE19 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD

3'-0"
3A
4'-8" 11'-10 1/2" DOOR TYPES

4"
2A 2C

ALIGN
WIC 3

4'-6"

3'-0"
CE10 2C CE16
2A 2A 1'-4"

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE
11'-2"
BEDROOM 3

84"

84"

84"

84"
1'-4"
2C
NOT FOR CONSTRUCTION
2C ALIGN
CORRIDOR CE13
2A 2C

3'-0"
4'-3" 1'-4" 10'-9 1/2" 3'-7"
SEE SEE
SCHEDULE SCHEDULE SEE SCHEDULE SEE SCHEDULE
2A

4'-8"

5'-2"
WIC 4
36" 36" 72" 72"

CE11 CE12 ALIGN


TYPE A TYPE B TYPE C TYPE D
CE19 3A SWING DOOR POCKET DOOR PAIR SWING PAIR SLIDING
DOORS DOORS

4'-11 1/2"
2A
TERRACE
3A 2A
WIC 2 CE17 2C
DOOR NOTES
2A
11'-5" 6'-0 1/2" 5'-10"
3A 1. ALL DOORS SHALL BE PAINTED AND HAVE PAINTED WOOD CASINGS, DYKES #235 4 1/4" POPLAR, OVER NEW & EXIST. FRAMES

9'-5 1/4"
9'-4 3/4"
CE18
SHOWER
2. ALL BEDROOMS & BATHROOMS SHALL HAVE PRIVACY LEVER HARDWARE: 'ARROW' CL-02-SC-26D500
2C
BEDROOM 4 BEDROOM 2

3'-0"
CHASE 9

2'-8"
3. ALL SINGLE CLOSET AND WALK-IN CLOSETS SHALL HAVE PASSAGE LEVER HARDWARE: 'ARROW' CL-01-SC-26D500
3A 3A
LINEN
2C 2C 4. ALL DOUBLE CLOSET DOORS SHALL HAVE DOUBLE DUMMY LEVER HARDWARE: 'ARROW' CL-08-SC-26D & 'ROCKWOOD' #901 HEAVY DUTY
8" 5'-4 1/2" 3'-4" 1'-10" 13'-10 3/4" 1'-4" MAGNETIC CATCH.

TOILET

3'-0"

3'-0"
2C BATH 2 2C 5. ALL POCKET DOORS SHALL HAVE HAFELE HEAVY DUTY SLIDING TRACK SYSTEMS.

7 3/4"
LAV
2C
1'-4"

1'-4"
6. ALL PRIVACY POCKET DOORS SHALL HAVE 'ACCURATE' #2002CPDL HARDWARE WITH #CS2002T & #CS2002E FLUSH PULLS.

7. ALL PASSAGE POCKET DOORS SHALL HAVE 'ACCURATE' #2000 HARDWARE WITH #CS2002B FLUSH PULLS.

8. ALL SWING DOORS SHALL HAVE TWO PAIR OF 'MCKINNEY' #MPB79 FIVE KNUCKLE HINGES, 'IVES' HINGE PIN STOP #70 AND FOUR GRAY 'IVES'
SILENCERS #SR64/65 DEPENDING ON FRAME MATERIAL
NEW PERIMETER EXISTING EXISTING OPERABLE
MILLWORK, TYP. PTAC, TYP WINDOW, TYP 9. PROVIDE AND INSTALL FIRE RATED WOOD BLOCKING AT ALL JAMBS.

10. ALL SLIDING CLOSET DOORS SHALL HAVE 'PEMKO' #H200 SLIDING KIT AND FLUSH PULLS.

11. ALL HARDWARE SHALL HAVE US26D SATIN CHROME FINISH.

PHCE - CONSTRUCTION FLOOR PLAN UPPER 12. ALL EXISTING FRAMELESS CLOSETS SHALL HAVE NEW PAINTED JAMBS AND HEAD WITH NEW WOOD CASING.
2 1/4" = 1'-0" 13. ALL EXISTING APARTMENT ENTRY DOORS, FRAMES AND CASINGS ON BOTH SIDES SHALL BE PAINTED. NO.
ISSUED FOR BID
DESCRIPTION
05/18/2020
DATE

CONSTRUCTION PLAN LEGEND

EXISTING FIRE RATED EXISTING FSPC ENTRY EXISTING WALL TO REMAIN


DEMISING WALL, TYP DOOR TO REMAIN
DOOR AND FRAME - SEE SCHEDULE
1A 1i DISTANCE FROM PERPENDICULAR WALL WHEN OPEN
NEW NONBEARING PARTITION - SEE TYPES 101 SHALL BE 4" UON.
CE01
1'-6"

VANITY SHOWER 2C
5'-0"
TOILET
3'-0"

G
2C PWDR S NEW HARD-WIRED COMBO SMOKE/CARBON MONOXIDE FIRE PROTECTIVE SELF-CLOSING DOOR 1 HOUR FIRE
LAV 1'-10" DETECTOR FPSC
3A CE02 RATED
1'-10" 5'-9 3/8" 6'-1 1/8" 10" LAV 5'-6" 6'-1 1/2"
2C
2'-0"

ALIGN

2C 2C CONSTRUCTION NOTES
WIC 1 MBATH 1 PROJECT TITLE:
7'-0"

CHASE 6

ALIGN
4'-5"

3A
CE09
8'-11"
TOILET

LAV
2A 1. PATCH ALL EXISTING FLOOR & CEILING OPENINGS. REPLACE ANY DAMAGED GWB, MTL STUD & INSULATION FURRING AT EXTERIOR WALL. PENTHOUSE UNITS
12'-5 1/2"
ALIGN

D
2A CE03
3A 2C 2. ALL EXISTING COLUMNS, MECHANICAL SHAFTS, EXTERIOR WALLS AND DEMISING WALLS SHALL BE SKIM COATED AND/OR LAMINATED WITH NEW
RENOVATIONS
CHASE 5

CE04 1A
GWB AS REQ'D FOR LIKE-NEW STRAIGHT AND PLUMB INSTALLATION.
3'-9"

2A
CE08
2C 2C W
6'-4 1/2" 1'-11 1/2" 3. COORDINATE SELECTIVE LOCALIZED REMOVAL AND REPLACEMENT OF EXISTING DEMISING WALL GWB AS REQ'D TO FACILITATE ELEC WIRING &
FLOORS 26, 27, 28
2A DEVICES AND PLUMBING UTILITIES. ALL FIRE RATINGS SHALL BE MAINTAINED. ALL RECEPTACLE BOXES AND PIPING PENETRATIONS SHALL HAVE
7'-5 1/2"

2A PANTRY LIBERTY VIEW


RECESS FRAMING FOR WINE REF'G FIRE SEALANT AROUND ALL SIDES.
5'-0 1/2"

2C 2A CE06 99 BATTERY PLACE


4'-6 1/2"

2A UNDER STAIR LANDING


2A ALIGN
CE07 LAMINATE 4. PROVIDE FIRE-STOPPING AS REQUIRED BY NEW YORK CITY BUILDING CODE AT FLOOR & WALL PENETRATIONS THRU FIRE-RATED NEW YORK, NEW YORK 10280
3'-0"

GWB ON 2A LAUND. 2A 2C CONSTRUCTION.


6"

CE05 FACE 2C
OF CL 5. FRAME TIGHT ALL EXISTING PIPE RISER STACKS WITH NEW PART TYPE 2C. FIRE RATED DEMISING LOCATIONS SHALL BE FRAMED TIGHT WITH
1'-5 1/2"
1'-10"

PART. TYPE 3C
2'-1"

D/W
2C
2C 2C 2A SINK 2C 2A 2A
HUTCH WINE
2A 6. ACCESS DOORS IN INTERIOR GWB WALLS AND/OR CEILING SHALL BE 'ACUDOR' #DW-5015 RECESSED SERIES WITH FLUSH DRYWALL FACE.
ACCESS DOORS WITHIN CABINETRY SHALL BE 'ACUDOR' #UF-5000 FLUSH SERIES. SIZE PER PLANS AND NOTES.
ALIGN ALIGN
2C
7'-9" 4'-0 3/4" 3'-8" 11'-9 1/4" 4'-6" 1'-3" 3'-6" 3'-6" 15'-1 1/4" 7. FILL, REPAIR, TOUCH-UP & SAND SMOOTH FOR FINISH PAINT ALL EXISTING WINDOW SUBFRAMES.
3'-4"
14'-11 1/4"

REF'G
KITCHEN
ALIGN

2A NEW KITCHEN CABINETRY, 8. PROVIDE BLOCKING AS REQUIRED FOR IN-WALL CARRIERS FOR WALL HUNG TOILETS.
10'-6 3/4"

SINK COUNTERS & APPLIANCES, TYP DOB SCAN STICKER


9. PROVIDE PLYWOOD BLOCKING BETWEEN STUDS IN ALL PARTITIONS AT ALL CLOSETS, WALK-IN CLOSETS & LAUNDRY /STORAGE ROOMS.
2'-6"

11'-9 3/4" 2'-1" 4'-6" 10'-9 1/4" LIVING/DINING DRAWING TITLE:


10. REMOVE ALL ELECTRICAL STUBS AND UNUSED CONDUIT POKE THROUGHS AT DEMOLISHED WALLS AND RELOCATE AS REQ'D TO NEW
PARTITIONS/CEILINGS. PH CE - CONSTRUCTION
PLANS
3'-3 1/4"

2C LAMINATE GWB 11. COORDINATE WITH BLDG MGMT, FIXTURE SELECTIONS, AND FIELD CONDITIONS OF ANY AND ALL NEW/MODIFICATION WORK OF EXISTING WALLS,
ALIGN 2C ON FACE OF CL 11'-9 1/2" CEILINGS, CABINETRY AND/OR FINISHES OF APARTMENTS DIRECTLY BELOW THIS APARTMENT AS REQ'D FOR NEW PLUMBING WORK.
MASTER
BEDROOM 1 12. PROVIDE SHELF & ROD AT ALL COAT CLOSETS AND WALK-IN CLOSETS.
ALIGN

1'-4"

1'-4"

2C 2C 2C
13. ALL EXISTING HVAC UNITS TO REMAIN.

14. PROVIDE 'NOBLESEAL' TS WATERPROOFING MEMBRANE AT ALL BATHROOMS AND LAUNDRY ROOMS. FOLLOW MANUFACTURER'S GUIDELINES SCALE: AS NOTED PAGE: 10 of 30
AND EXTEND W.P. MEMBRANE UP ALL WALLS AS REQUIRED.

15. AT BATHROOM VANITIES & KITCHEN PROVIDE 16"X16" PTO. ACCESS DOOR IN PARTITION, CONCEALED WITHIN BOTTOM CABINET FOR VALVE

A102.00
ACCESS. COORDINATE LOCATION WITH SINK PIPING & FIELD CONDITIONS. PROVIDE CUT-OUT IN MILLWORK BACK PANEL FOR ACCESS DOOR.
1'-4"

EXISTING NEW PERIMETER EXISTING OPERABLE CABINETS SHALL BE ADAPTABLE FOR FUTURE ACCESSIBILITY.
PTAC, TYP MILLWORK, TYP. WINDOW, TYP
16. ALL PARTITIONS SHALL BE PAINTED. BATHROOMS SHALL HAVE TILED FLOORS & WALLS. ALL EXISTING EXPOSED CONG. CEILINGS SHALL BE SKIM
COATED LEVEL & SMOOTH AS REQ'D.

17. GWB CEILINGS & SOFFITS SHALL BE INSTALLED PER REQUIREMENTS OF NYC BUILDING CODE REFERENCE STANDARD RS 5-16. BATHROOMS,
HALLS, KITCHEN & WALK-IN CLOSETS WHERE NOTED SHALL HAVE GWB CEILINGS AT 7'-6" AFF, UON.

18. BATHROOMS SHALL BE PROVIDED WITH MIN 50CFM FAN MECHANICAL VENTILATION & FUSIBLE LINK FIRE DAMPER AT DUCTWORK, ALL NYC MEA &
BSA APPROVED.
PHCE - CONSTRUCTION FLOOR PLAN LOWER
1 1/4" = 1'-0"
19. BATHTUB/SHOWERS SHALL HAVIE 3/8" GLASS DOOR AND/OR FIXED SCREEN WITH POLISHED CHROME HARDWARE. VIF DOOR SWING CLEARANCE
WITH ADJACENT FIXTURES. CONFIRM WITH BUILDING MANAGEMENT

20. KITCHEN & BATH CABINETRY AND MISC. BUILT-INS SHALL BE CONSTRUCTED OF 3/4" PLYWOOD FRAMES AND M.R. MDF IN WET AREAS
SEAL
PHH - DOOR SCHEDULE
DOOR # TYPE WIDTH HEIGHT MATERIAL FRAME REMARKS BATTERY PLACE
EXISTING OPERABLE
WINDOW, TYP
H01
H02
A 3' - 0"
3' - 0"
7' - 0"
7' - 0"
HOLLOW METAL
ALUMINUM
HM
ALUMINUM
EXISTING FPSC UNIT ENTRANCE DOOR
EXISTING TERRACE DOOR
ASSOCIATES, LLC
H03 D 6' - 0" 7' - 0" SOLID CORE WOOD SC WOOD C/O MILSTEIN PROPERTIES
H04 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD 335 MADISON AVENUE
2C LAV
H05 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD

3'-0"
NEW YORK, NY 10017
H06 A 3' - 0" 7' - 0" SOLID CORE WOOD SC WOOD
EXISTING NEW PERIMETER H24 2C (212) 308-7200
PTAC, TYP MILLWORK, TYP. H07 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD

1'-4"
1'-10" H08 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD

CHASE 2
2C
BATH 2 H09 A 3' - 0" 8' - 0" HOLLOW METAL HM EXISTING FPSC UNIT ENTRANCE DOOR

TOILET
10'-1 3/8" 3'-0" 5'-6" 9" H10 3' - 0" 7' - 0" ALUMINUM ALUMINUM EXISTING TERRACE DOOR
2C
H11 A 3' - 0" 8' - 0" SOLID CORE WOOD SC WOOD
H12 A 3' - 0" 8' - 0" SOLID CORE WOOD SC WOOD

1'-4"
1'-4" 3A

4'-0"
H13 A 3' - 0" 8' - 0" SOLID CORE WOOD SC WOOD

3'-0"
2C H22 H14 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
2A BEDROOM 2 SHOWER
2C H15 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD

3 1/4"
3A H16 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
VANITY
2C 2C H17 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
2A
LAV 3A BEDROOM 3 BATHTUB
H21 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
H22 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
ALIGN 7'-9 3/4" 10'-4" 3'-6 5/8" 13'-1 3/8" 5'-0" 1'-3" H23 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD
3'-0" H24 B 2' - 8" 7' - 0" SOLID CORE WOOD SC WOOD

TOILET
1'-10" H23
3A
BATH 3

8'-3"
6'-0"
MBATH 1 1'-10" DOOR TYPES
3A
LAV H13
2C 4"
ALIGN 2C
2A 2A LAV

3'-0"
HALL

3'-4"
SHOWER 2A H14
2C

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE
H17
H16 H12 NOT FOR CONSTRUCTION

CHASE 4
2C 2C

3'-0"

84"

84"

84"

84"
ALIGN

TOILET
2C 2C 3A H11

3'-0"
4" 5'-6 3/4" 8" 7'-4" 5'-7" 6'-9 3/8" 10'-3 1/2" 3'-3 1/2"

4'-8 1/2"
SEE SEE
2A 3A SCHEDULE SCHEDULE SEE SCHEDULE SEE SCHEDULE

2'-1"
2A
36" 36" 72" 72"

1'-0 3/4" 2A
1'-4"

UC
2A 2C
REF'G
H15 TYPE A TYPE B TYPE C TYPE D
SWING DOOR POCKET DOOR PAIR SWING PAIR SLIDING
DOORS DOORS
2C 4'-2 3/8" 4'-0"
D
7"
4'-0"

5'-4"
3A 2C DOOR NOTES
2'-1" LAUNDRY
16'-0 1/2" 7'-6 1/2" 7'-8 1/2"

CHASE 3
W

6'-5 3/8"

7'-2"
2A 1. ALL DOORS SHALL BE PAINTED AND HAVE PAINTED WOOD CASINGS, DYKES #235 4 1/4" POPLAR, OVER NEW & EXIST. FRAMES
H21 2C 2. ALL BEDROOMS & BATHROOMS SHALL HAVE PRIVACY LEVER HARDWARE: 'ARROW' CL-02-SC-26D500
H10 MASTER DESK
ALIGN

2'-6"
BEDROOM 1 1A 3. ALL SINGLE CLOSET AND WALK-IN CLOSETS SHALL HAVE PASSAGE LEVER HARDWARE: 'ARROW' CL-01-SC-26D500
2A H09 SINK
4. ALL DOUBLE CLOSET DOORS SHALL HAVE DOUBLE DUMMY LEVER HARDWARE: 'ARROW' CL-08-SC-26D & 'ROCKWOOD' #901 HEAVY DUTY
7'-3 1/8"

MAGNETIC CATCH.
2A
1'-4" 5. ALL POCKET DOORS SHALL HAVE HAFELE HEAVY DUTY SLIDING TRACK SYSTEMS.
WIC 1
5'-4"

EXISTING FIRE RATED RELOCATED FSPC ENTRY


DEMISING WALL, TYP DOOR 6. ALL PRIVACY POCKET DOORS SHALL HAVE 'ACCURATE' #2002CPDL HARDWARE WITH #CS2002T & #CS2002E FLUSH PULLS.

7. ALL PASSAGE POCKET DOORS SHALL HAVE 'ACCURATE' #2000 HARDWARE WITH #CS2002B FLUSH PULLS.

8. ALL SWING DOORS SHALL HAVE TWO PAIR OF 'MCKINNEY' #MPB79 FIVE KNUCKLE HINGES, 'IVES' HINGE PIN STOP #70 AND FOUR GRAY 'IVES'
SILENCERS #SR64/65 DEPENDING ON FRAME MATERIAL

9. PROVIDE AND INSTALL FIRE RATED WOOD BLOCKING AT ALL JAMBS.

10. ALL SLIDING CLOSET DOORS SHALL HAVE 'PEMKO' #H200 SLIDING KIT AND FLUSH PULLS.

11. ALL HARDWARE SHALL HAVE US26D SATIN CHROME FINISH.


PHH - CONSTRUCTION FLOOR PLAN UPPER EXISTING OPERABLE
2 1/4" = 1'-0"
WINDOW, TYP
12. ALL EXISTING FRAMELESS CLOSETS SHALL HAVE NEW PAINTED JAMBS AND HEAD WITH NEW WOOD CASING.
NO.
ISSUED FOR BID
DESCRIPTION
05/18/2020
DATE
13. ALL EXISTING APARTMENT ENTRY DOORS, FRAMES AND CASINGS ON BOTH SIDES SHALL BE PAINTED.

2C CONSTRUCTION PLAN LEGEND


LAV

3'-0"
EXISTING NEW PERIMETER EXISTING WALL TO REMAIN

1'-4"
H08
PTAC, TYP MILLWORK, TYP.
1'-10" DOOR AND FRAME - SEE SCHEDULE
1'-11 3/4" BATH 4

CHASE 2
1i DISTANCE FROM PERPENDICULAR WALL WHEN OPEN
NEW NONBEARING PARTITION - SEE TYPES 101

TOILET
3'-2"
SHALL BE 4" UON.
2C 2C
2C 2C
1'-4"

2C 2A
6'-6" 8'-1 5/8" 3'-2 3/8" NEW HARD-WIRED COMBO SMOKE/CARBON MONOXIDE
S FIRE PROTECTIVE SELF-CLOSING DOOR 1 HOUR FIRE

3'-0"
DETECTOR FPSC

ALIGN
2C 2A RATED
2C BEDROOM 4
1'-4"

SHOWER

CONSTRUCTION NOTES
8'-3 1/8"

2A PROJECT TITLE:
3'-1 1/2"

DINING 2A 3A
D/W

9'-2 1/4" 2'-1" 16'-0 5/8" 11'-4" 1. PATCH ALL EXISTING FLOOR & CEILING OPENINGS. REPLACE ANY DAMAGED GWB, MTL STUD & INSULATION FURRING AT EXTERIOR WALL. PENTHOUSE UNITS
2A NEW KITCHEN CABINETRY, 2A 2. ALL EXISTING COLUMNS, MECHANICAL SHAFTS, EXTERIOR WALLS AND DEMISING WALLS SHALL BE SKIM COATED AND/OR LAMINATED WITH NEW RENOVATIONS
TERRACE KITCHEN GWB AS REQ'D FOR LIKE-NEW STRAIGHT AND PLUMB INSTALLATION.
COUNTERS & APPLIANCES, FLOORS 26, 27, 28

8'-2"
5'-1 1/2"

4'-9 1/2"

TYP 3. COORDINATE SELECTIVE LOCALIZED REMOVAL AND REPLACEMENT OF EXISTING DEMISING WALL GWB AS REQ'D TO FACILITATE ELEC WIRING &
SINK
DEVICES AND PLUMBING UTILITIES. ALL FIRE RATINGS SHALL BE MAINTAINED. ALL RECEPTACLE BOXES AND PIPING PENETRATIONS SHALL HAVE LIBERTY VIEW
3'-6"

5 1/4" 2C 1'-1 3/4" WIC 4 FIRE SEALANT AROUND ALL SIDES. 99 BATTERY PLACE
2'-1" 3'-6 1/2" 4'-6" 2'-5" 6'-2 1/4" 3'-8 7/8" 3'-4" 2'-9 1/2" 2'-0" H06 H07
2C NEW YORK, NEW YORK 10280
ALIGN 4. PROVIDE FIRE-STOPPING AS REQUIRED BY NEW YORK CITY BUILDING CODE AT FLOOR & WALL PENETRATIONS THRU FIRE-RATED
2A
2C CONSTRUCTION.
2C 2A
CHASE 4

2'-1"
2'-5"

2'-5"

10"
ALIGN

2C 5. FRAME TIGHT ALL EXISTING PIPE RISER STACKS WITH NEW PART TYPE 2C. FIRE RATED DEMISING LOCATIONS SHALL BE FRAMED TIGHT WITH
2C
PART. TYPE 3C
3'-4"

6'-4 3/8"
REF'G
3'-4"

2'-6"

2A 6. ACCESS DOORS IN INTERIOR GWB WALLS AND/OR CEILING SHALL BE 'ACUDOR' #DW-5015 RECESSED SERIES WITH FLUSH DRYWALL FACE.
2C DESK
2C 3A 2A HALL 2C ACCESS DOORS WITHIN CABINETRY SHALL BE 'ACUDOR' #UF-5000 FLUSH SERIES. SIZE PER PLANS AND NOTES.
H02 4'-5" 13'-4 1/2"
7. FILL, REPAIR, TOUCH-UP & SAND SMOOTH FOR FINISH PAINT ALL EXISTING WINDOW SUBFRAMES.
1'-4"

2A
2'-1"

2C H04 H05 8. PROVIDE BLOCKING AS REQUIRED FOR IN-WALL CARRIERS FOR WALL HUNG TOILETS.
WINE
SINK
2A
2A
2C
NEW STAIR. SEE A401.00 DOB SCAN STICKER
FOR DETAILS
9. PROVIDE PLYWOOD BLOCKING BETWEEN STUDS IN ALL PARTITIONS AT ALL CLOSETS, WALK-IN CLOSETS & LAUNDRY /STORAGE ROOMS.
3'-5 3/8"

1'-10" 2'-1" DRAWING TITLE:


FOYER 2A LAV 3A
H03
2C
10. REMOVE ALL ELECTRICAL STUBS AND UNUSED CONDUIT POKE THROUGHS AT DEMOLISHED WALLS AND RELOCATE AS REQ'D TO NEW
PARTITIONS/CEILINGS. PH H - CONSTRUCTION
7'-10"

CHASE 3

PWDR BUTLER
1'-4" 10'-9 1/4" 4'-4 1/2" 6'-4 1/2"
11. COORDINATE WITH BLDG MGMT, FIXTURE SELECTIONS, AND FIELD CONDITIONS OF ANY AND ALL NEW/MODIFICATION WORK OF EXISTING WALLS, PLANS
CEILINGS, CABINETRY AND/OR FINISHES OF APARTMENTS DIRECTLY BELOW THIS APARTMENT AS REQ'D FOR NEW PLUMBING WORK.
6'-3 1/2"

1'-10 1/8" 4'-9" 5'-3 1/2" 9"


12'-1 3/4"

ALIGN

ALIGN

TOILET

6" 2'-1"

2C 12. PROVIDE SHELF & ROD AT ALL COAT CLOSETS AND WALK-IN CLOSETS.
3'-0"

LIVING 1A
H01
13. ALL EXISTING HVAC UNITS TO REMAIN.

14. PROVIDE 'NOBLESEAL' TS WATERPROOFING MEMBRANE AT ALL BATHROOMS AND LAUNDRY ROOMS. FOLLOW MANUFACTURER'S GUIDELINES SCALE: AS NOTED PAGE: 11 of 30
ALIGN
4'-7 3/8"

1A AND EXTEND W.P. MEMBRANE UP ALL WALLS AS REQUIRED.

A103.00
RELOCATED FSPC ENTRY EXISTING FIRE RATED 15. AT BATHROOM VANITIES & KITCHEN PROVIDE 16"X16" PTO. ACCESS DOOR IN PARTITION, CONCEALED WITHIN BOTTOM CABINET FOR VALVE
1A DOOR DEMISING WALL, TYP ACCESS. COORDINATE LOCATION WITH SINK PIPING & FIELD CONDITIONS. PROVIDE CUT-OUT IN MILLWORK BACK PANEL FOR ACCESS DOOR.
CABINETS SHALL BE ADAPTABLE FOR FUTURE ACCESSIBILITY.

16. ALL PARTITIONS SHALL BE PAINTED. BATHROOMS SHALL HAVE TILED FLOORS & WALLS. ALL EXISTING EXPOSED CONG. CEILINGS SHALL BE SKIM
COATED LEVEL & SMOOTH AS REQ'D.

17. GWB CEILINGS & SOFFITS SHALL BE INSTALLED PER REQUIREMENTS OF NYC BUILDING CODE REFERENCE STANDARD RS 5-16. BATHROOMS,
HALLS, KITCHEN & WALK-IN CLOSETS WHERE NOTED SHALL HAVE GWB CEILINGS AT 7'-6" AFF, UON.

18. BATHROOMS SHALL BE PROVIDED WITH MIN 50CFM FAN MECHANICAL VENTILATION & FUSIBLE LINK FIRE DAMPER AT DUCTWORK, ALL NYC MEA &
BSA APPROVED.
PHH - CONSTRUCTION FLOOR PLAN LOWER
1 1/4" = 1'-0"
19. BATHTUB/SHOWERS SHALL HAVIE 3/8" GLASS DOOR AND/OR FIXED SCREEN WITH POLISHED CHROME HARDWARE. VIF DOOR SWING CLEARANCE
WITH ADJACENT FIXTURES. CONFIRM WITH BUILDING MANAGEMENT

20. KITCHEN & BATH CABINETRY AND MISC. BUILT-INS SHALL BE CONSTRUCTED OF 3/4" PLYWOOD FRAMES AND M.R. MDF IN WET AREAS
SEAL
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL COMMENTS BATTERY PLACE
LT-1
LT-3
SURFACE CEILING MOUNTED
BATHROOM VANITY WALL MOUNTED
ASSOCIATES, LLC
LT-3.1 BATHROOM VANITY WALL MOUNTED C/O MILSTEIN PROPERTIES
LT-4 CLOSET/STORAGE WALL MOUNTED 335 MADISON AVENUE
LT-6 RECESSED CEILING MOUNTED
NEW YORK, NY 10017
LT-7 RECESSED CLG MTD WET LOCATION
(212) 308-7200
LT-8 UNDER CABINET STRIP LED
LT-9 OUTDOOR SCONCE

ISSUED FOR BID 05/18/2020


NO. DESCRIPTION DATE

CEILING PLAN LEGEND


a
WALL MOUNTED LIGHT SWITCH. LOWERCASE RECESSED CEILING MOUNTED LIGHT FIXTURE
LETTER OR ARC DENOTES FIXTURE SWITCHING

3 WALL MOUNTED 3-WAY SWITCH SURFACE CEILING MOUNTED LIGHT FIXTURE


GFI

SR WALL MOUNTED SWITCHED RECEPTACLE TO TOP PLUG WALL MOUNTED LIGHT FIXTURE
OUTLET ONLY
3'-6"
EQ EQ JS DOOR JAMB SWITCH UNDERCABINET LIGHT FIXTURE
PROJECT TITLE:

LIVING/DINING HARD-WIRED COMBINATION SMOKE/CARBON MONOXIDE INDICATES CEILING HEIGHT CHANGE PENTHOUSE UNITS
EQ

GFI S DETECTOR
LT-3 c LT-1 a
RENOVATIONS

EQ
9' - 6"
LT-6 a EQ EQ
NEW CEILING JUNCTION BOX INDICATES NEW SUSPENDED CEILING. SEE PLAN FOR
CL VANITY J CEILING HEIGHT FLOORS 26, 27, 28
BEDROOM 2 LIBERTY VIEW
7'-2"

LT-1 a LT-1 f NEW WALL MOUNTED THERMOSTAT AT 54" AFF WIRED TO INDICATES EXISTING CONCRETE SLAB W/ SKIM COAT
LT-3 c LT-6 a T 99 BATTERY PLACE
CHASE 2

9' - 0" EXISTING PTAC UNIT(S). VIF COMPATIBILITY WITH EXISTING FINISH. PATCH, REPAIR & PROVIDE NEW LEVEL SKIM
VERIFY EXACT LOCATIONS PTAC(S). WIRING SHALL BE CONCEALED WITHIN WALLS. COAT PLASTER FINISH. BUILD-UP WITH MESH AS
MBATH 1 NEW YORK, NEW YORK 10280

EQ
WITH MILLWORK PATCH & REPAIR WALLS AS REQ'D REQUIRED
CL VANITY MASTER DRAWINGS. LOCATED
BEDROOM 1 CL DOOR
SWITCH WITHIN MILLWORK
EQ

LT-6 a 9' - 0" TO CONTROL LIGHTS


SR

T JS
8' - 6" LT-4
T a
a
a
S SR
S
b
1'-6"

1'-6"

c
CL DOOR CL DOOR CEILING PLAN NOTES
LT-6
SR

LT-6 a
LT-7 c JS JS LT-6 a
LT-4 LT-4 3a
HALL e
f
LT-6 c LT-6 c LT-6 c
1. EXISTING CONCRETE SLAB W/ SKIM COAT FINISH. PATCH, REPAIR & PROVIDE NEW LEVEL SKIM COAT PLASTER FINISH. DOB SCAN STICKER
3a

c
T
S LT-6 e b 2. ALL SWITCHES SHALL BE DIMMABLE EXCEPT STORAGE, & CLOSETS. ALL SWITCHES LOCATED AT 48" AFF U.O.N. AND 8" FROM ADJACENT DRAWING TITLE:
LT-6 a LT-6 a LT-6 a DOOR/WALL OPENING U.O.N.
8' - 0"
8' - 6"
3. REMOVE EXHAUST GRILLE, CAP EXISTING DUCT BRANCH AT RISER & PATCH FIRE-RATED WALL AT ALL DEMOLISHED & ABANDONED KITCHENS &
PH A - REFLECTED
LT-6 b LT-6 b LT-6 b
a b KITCHEN
BATHROOMS. CEILING PLAN
BATH 2 LT-6 a LT-6 a LT-6 a 8' - 6" 4. REROUTE NEW BRANCH DUCT FOR KITCHEN EXHAUST FROM NEAREST EXISTING KITCHEN RISER TO NEW KITCHEN ABOVE REFRIGERATOR AND
LT-6 a LT-4 CL DOOR PROVIDE NEW ANOD. ALUM. GRILLE. SEE ELEVATIONS. PROVIDE NEW FIRE DAMPER, DUCT ACCESS DOOR & CEILING ACCESS DOOR AT RISER.
GFI

LT-3 b 8' - 6" CL DOOR


CHASE 1

LT-6 b LT-6 b LT-6 b 5. REROUTE NEW BRANCH DUCT FOR TOILET EXHAUST FROM NEAREST EXISTING TOILET RISER AND PROVIDE NEW ANOD. ALUM. GRILLE. SEE RCP
CL VANITY JS & ELEVATIONS. PROVIDE NEW FIRE DAMPER, DUCT ACCESS DOOR & CEILING ACCESS DOOR AT RISER. OMIT ACCESS DOOR & NEW DUCTWORK
LT-6 a LT-4 WHERE GRILLE IS LOCATED AT RISER AND DAMPER CAN BE REACHED THROUGH OPENING.
d
SCALE: AS NOTED PAGE: 12 of 530
3a
JS

LT-8 d LT-8 d 6. GC SHALL VIF ALL FIXTURE LOCATIONS, SWITCHING AND LOADS. ALL LIGHT FIXTURES SHALL BE NEW. LOWERCASE LETTER OR ARC DENOTES
GFI GFI GFI
LT-7 a SWITCHING.

7. WHERE ELECTRICAL PANELS ARE RELOCATED PROVIDE SPLICE BOX(ES) AT FORMER PANEL LOCATION AS REQUIRED. COORDINATE LOCATION
WITH FIELD CONDITIONS AND VERIFY WITH ARCHITECT FINAL PLACEMENT(S). A200.00
8. GROUND FAULT CIRCUIT INTERRUPT DUPLEX RECEPTACLES SHALL BE PROVIDED AT KITCHEN, BATH & LAUNDRY COUNTERS.

9. MULTIPLE SWITCHES SHOWN ADJACENT TO EACH OTHER IN SAME LOCATION SHALL BE INSTALLED WITHIN ONE SINGLE GANG JUNCTION BOX &
COVERPLATE.

10. ALL SWITCH & OUTLET & TEL/CABLE RECEPTACLES SHALL BE 'DECORA' WHITE WITH SCREWLESS FACEPLATES.

11. LOCATE ALL NEW KITCHEN OUTLETS PER APPLIANCE MANUFACTURER GUIDLEINES. GC SHALL CONFIRM COMPATIBILITY WITH EXISTING OUTLET
PHA - REFLECTED CEILING PLAN LOCATIONS SCHEDULED TO REMAIN.
1 1/4" = 1'-0"

SEAL
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL COMMENTS BATTERY PLACE
LT-1
LT-3
SURFACE CEILING MOUNTED
BATHROOM VANITY WALL MOUNTED
ASSOCIATES, LLC
LT-3.1 BATHROOM VANITY WALL MOUNTED C/O MILSTEIN PROPERTIES
LT-4 CLOSET/STORAGE WALL MOUNTED 335 MADISON AVENUE
LT-6 RECESSED CEILING MOUNTED
NEW YORK, NY 10017
LT-7 RECESSED CLG MTD WET LOCATION
TERRACE (212) 308-7200
LT-8 UNDER CABINET STRIP LED
LT-9 OUTDOOR SCONCE
LT-9 b

b
LT-8 b

3a
GFI
LT-6 a
LT-6 a
LAUND.
8' - 6" 8' - 6"

GFI
LT-6 a LT-6 a
b a

LT-7 a WIC 1 MASTER


8' - 6" BEDROOM 1
10' - 1"
LT-6
LT-6 a NOT FOR CONSTRUCTION
LT-6 a
MBATH 1
8' - 6" 8' - 6" LT-1
c

LT-6 a
LT-6 a LT-3 c LT-6 b
a
b b a T
LT-3 b LT-3 b SR

BATH 2 CORRIDOR
8' - 6" BEDROOM 2
LT-6 a LT-6 a 8' - 6" LT-6 a g LT-6 a
10' - 1"
LT-6 a 3a
a
LT-7 a a
b
T

SR
LT-3 b

LT-1
JS
LT-4
LT-6 g LT-6 g

JS
3a

PHB - REFLECTED CEILING PLAN UPPER ISSUED FOR BID 05/18/2020


2 1/4" = 1'-0" NO. DESCRIPTION DATE

CEILING PLAN LEGEND


a
WALL MOUNTED LIGHT SWITCH. LOWERCASE RECESSED CEILING MOUNTED LIGHT FIXTURE
LETTER OR ARC DENOTES FIXTURE SWITCHING

3 WALL MOUNTED 3-WAY SWITCH SURFACE CEILING MOUNTED LIGHT FIXTURE

SR WALL MOUNTED SWITCHED RECEPTACLE TO TOP PLUG WALL MOUNTED LIGHT FIXTURE
OUTLET ONLY

8' - 0" JS DOOR JAMB SWITCH UNDERCABINET LIGHT FIXTURE


LT-3 b
LT-6 a
PROJECT TITLE:

GFI
POWDER
8' - 6" LT-6 e S
HARD-WIRED COMBINATION SMOKE/CARBON MONOXIDE
DETECTOR
INDICATES CEILING HEIGHT CHANGE PENTHOUSE UNITS
e
LIVING RENOVATIONS
NEW CEILING JUNCTION BOX INDICATES NEW SUSPENDED CEILING. SEE PLAN FOR
FLOORS 26, 27, 28
b
a 9' - 0" J CEILING HEIGHT

NEW WALL MOUNTED THERMOSTAT AT 54" AFF WIRED TO INDICATES EXISTING CONCRETE SLAB W/ SKIM COAT LIBERTY VIEW
FOYER T EXISTING PTAC UNIT(S). VIF COMPATIBILITY WITH EXISTING FINISH. PATCH, REPAIR & PROVIDE NEW LEVEL SKIM 99 BATTERY PLACE
PTAC(S). WIRING SHALL BE CONCEALED WITHIN WALLS. COAT PLASTER FINISH. BUILD-UP WITH MESH AS
PATCH & REPAIR WALLS AS REQ'D REQUIRED
NEW YORK, NEW YORK 10280
S
LT-6 a LT-6 a LT-6 a
8' - 6"
3g T 3f 3b
3a SR 3a

JS
LT-4

CEILING PLAN NOTES


LT-6 LT-6 b

1. EXISTING CONCRETE SLAB W/ SKIM COAT FINISH. PATCH, REPAIR & PROVIDE NEW LEVEL SKIM COAT PLASTER FINISH. DOB SCAN STICKER
LT-1f 2. ALL SWITCHES SHALL BE DIMMABLE EXCEPT STORAGE, & CLOSETS. ALL SWITCHES LOCATED AT 48" AFF U.O.N. AND 8" FROM ADJACENT DRAWING TITLE:
DOOR/WALL OPENING U.O.N.

LT-6 b 3. REMOVE EXHAUST GRILLE, CAP EXISTING DUCT BRANCH AT RISER & PATCH FIRE-RATED WALL AT ALL DEMOLISHED & ABANDONED KITCHENS &
PH B - REFLECTED
KITCHEN/DINING
BATHROOMS. CEILING PLANS
9' - 0" 4. REROUTE NEW BRANCH DUCT FOR KITCHEN EXHAUST FROM NEAREST EXISTING KITCHEN RISER TO NEW KITCHEN ABOVE REFRIGERATOR AND
PROVIDE NEW ANOD. ALUM. GRILLE. SEE ELEVATIONS. PROVIDE NEW FIRE DAMPER, DUCT ACCESS DOOR & CEILING ACCESS DOOR AT RISER.

5. REROUTE NEW BRANCH DUCT FOR TOILET EXHAUST FROM NEAREST EXISTING TOILET RISER AND PROVIDE NEW ANOD. ALUM. GRILLE. SEE RCP
LT-8 d
d LT-6 b LT-6 b LT-6 b & ELEVATIONS. PROVIDE NEW FIRE DAMPER, DUCT ACCESS DOOR & CEILING ACCESS DOOR AT RISER. OMIT ACCESS DOOR & NEW DUCTWORK
WHERE GRILLE IS LOCATED AT RISER AND DAMPER CAN BE REACHED THROUGH OPENING.
SCALE: AS NOTED PAGE: 13 of 30
GFI

3b

6. GC SHALL VIF ALL FIXTURE LOCATIONS, SWITCHING AND LOADS. ALL LIGHT FIXTURES SHALL BE NEW. LOWERCASE LETTER OR ARC DENOTES
3f SWITCHING.

A201.00
LT-8 d LT-8 d
GFI GFI GFI
7. WHERE ELECTRICAL PANELS ARE RELOCATED PROVIDE SPLICE BOX(ES) AT FORMER PANEL LOCATION AS REQUIRED. COORDINATE LOCATION
WITH FIELD CONDITIONS AND VERIFY WITH ARCHITECT FINAL PLACEMENT(S).

8. GROUND FAULT CIRCUIT INTERRUPT DUPLEX RECEPTACLES SHALL BE PROVIDED AT KITCHEN, BATH & LAUNDRY COUNTERS.

9. MULTIPLE SWITCHES SHOWN ADJACENT TO EACH OTHER IN SAME LOCATION SHALL BE INSTALLED WITHIN ONE SINGLE GANG JUNCTION BOX &
COVERPLATE.

10. ALL SWITCH & OUTLET & TEL/CABLE RECEPTACLES SHALL BE 'DECORA' WHITE WITH SCREWLESS FACEPLATES.

11. LOCATE ALL NEW KITCHEN OUTLETS PER APPLIANCE MANUFACTURER GUIDLEINES. GC SHALL CONFIRM COMPATIBILITY WITH EXISTING OUTLET
PHB - REFLECTED CEILING PLAN LOWER LOCATIONS SCHEDULED TO REMAIN.
1 1/4" = 1'-0"

SEAL
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL COMMENTS BATTERY PLACE
LT-1
LT-3
SURFACE CEILING MOUNTED
BATHROOM VANITY WALL MOUNTED
ASSOCIATES, LLC
LT-3.1 BATHROOM VANITY WALL MOUNTED C/O MILSTEIN PROPERTIES
LT-4 CLOSET/STORAGE WALL MOUNTED 335 MADISON AVENUE
LT-6 RECESSED CEILING MOUNTED
NEW YORK, NY 10017
LT-7 RECESSED CLG MTD WET LOCATION
(212) 308-7200
LT-8 UNDER CABINET STRIP LED
LT-9 OUTDOOR SCONCE

JS
LT-4
LT-3 b
a
b

3a
LT-6 a
LT-7 a g
BATH 3
8' - 6" LT-6 a

LT-6 g
WIC 3
CORRIDOR
BEDROOM 3
LT-6
LT-6 a 8' - 6" LT-6 a 10' - 1"
8' - 6"
b LT-6 g
3a
S LT-1 a
3a 8' - 6" NOT FOR CONSTRUCTION
LT-9 b WIC 4 S S
8' - 6"
LT-6 a LT-6 a LT-6 a

a
LT-6
SR
T

SR
a
T T a b
S S

SR
WIC 2
TERRACE BEDROOM 4 BEDROOM 2
LT-6 a
10' - 1" 8' - 6" LT-6 8' - 6" 10' - 1"

a
LT-1 a b LT-1 b
LT-7 a

LT-6 a
BATH 2
LT-6 a
8' - 6" LT-3 b

PHCE - REFLECTED CEILING PLAN UPPER ISSUED FOR BID 05/18/2020


2 1/4" = 1'-0" NO. DESCRIPTION DATE

CEILING PLAN LEGEND


a
WALL MOUNTED LIGHT SWITCH. LOWERCASE RECESSED CEILING MOUNTED LIGHT FIXTURE
LETTER OR ARC DENOTES FIXTURE SWITCHING

b 3 WALL MOUNTED 3-WAY SWITCH SURFACE CEILING MOUNTED LIGHT FIXTURE


LT-3.1c c
a

PWDR
3a

LT-3 b LT-7 a
SR WALL MOUNTED SWITCHED RECEPTACLE TO TOP PLUG WALL MOUNTED LIGHT FIXTURE
LT-3 b LT-6 a OUTLET ONLY
LT-6 a LT-6 a
8' - 6"
LT-6 MBATH 1 JS DOOR JAMB SWITCH UNDERCABINET LIGHT FIXTURE

LT-3 b
8' - 6" 8' - 6" LT-6 a PROJECT TITLE:
LT-8 b
8' - 6"
WIC 1 LT-6 a
a LAUND. S
HARD-WIRED COMBINATION SMOKE/CARBON MONOXIDE
DETECTOR
INDICATES CEILING HEIGHT CHANGE PENTHOUSE UNITS
RENOVATIONS
CHASE 1

a b LT-6 a
LT-6 a
LT-6 FOYER NEW CEILING JUNCTION BOX INDICATES NEW SUSPENDED CEILING. SEE PLAN FOR
a 8' - 6"
J CEILING HEIGHT FLOORS 26, 27, 28
a b

T
b
SR 8' - 6" PANTRY 8' - 6" NEW WALL MOUNTED THERMOSTAT AT 54" AFF WIRED TO INDICATES EXISTING CONCRETE SLAB W/ SKIM COAT LIBERTY VIEW
T 99 BATTERY PLACE
JS

EXISTING PTAC UNIT(S). VIF COMPATIBILITY WITH EXISTING FINISH. PATCH, REPAIR & PROVIDE NEW LEVEL SKIM
LT-6 a PTAC(S). WIRING SHALL BE CONCEALED WITHIN WALLS. COAT PLASTER FINISH. BUILD-UP WITH MESH AS
LT-6 LT-6 a S S LT-6 8' - 6" PATCH & REPAIR WALLS AS REQ'D REQUIRED
NEW YORK, NEW YORK 10280
LT-6 a
LT-6 a
3a

LT-8 d LT-8 d 3g
3b 3b
3c LT-6 e LT-6 e
3c 3d f

T SR
8' - 0"

CEILING PLAN NOTES


LT-6 b LT-6 b LT-6 b LT-6 b
10' - 1" KITCHEN
LT-8 d 1. EXISTING CONCRETE SLAB W/ SKIM COAT FINISH. PATCH, REPAIR & PROVIDE NEW LEVEL SKIM COAT PLASTER FINISH. DOB SCAN STICKER
9' - 0"
LT-6 b LT-6 c LT-6 c LT-6 c LIVING/DINING 2. ALL SWITCHES SHALL BE DIMMABLE EXCEPT STORAGE, & CLOSETS. ALL SWITCHES LOCATED AT 48" AFF U.O.N. AND 8" FROM ADJACENT DRAWING TITLE:
GFI

DOOR/WALL OPENING U.O.N.

LT-1 b LT-1 f 3. REMOVE EXHAUST GRILLE, CAP EXISTING DUCT BRANCH AT RISER & PATCH FIRE-RATED WALL AT ALL DEMOLISHED & ABANDONED KITCHENS &
PH CE - REFLECTED
3d
BATHROOMS. CEILING PLANS
GFI

LT-6 b LT-6 b LT-6 b LT-6 b


4. REROUTE NEW BRANCH DUCT FOR KITCHEN EXHAUST FROM NEAREST EXISTING KITCHEN RISER TO NEW KITCHEN ABOVE REFRIGERATOR AND
PROVIDE NEW ANOD. ALUM. GRILLE. SEE ELEVATIONS. PROVIDE NEW FIRE DAMPER, DUCT ACCESS DOOR & CEILING ACCESS DOOR AT RISER.
MASTER
5. REROUTE NEW BRANCH DUCT FOR TOILET EXHAUST FROM NEAREST EXISTING TOILET RISER AND PROVIDE NEW ANOD. ALUM. GRILLE. SEE RCP
BEDROOM 1 & ELEVATIONS. PROVIDE NEW FIRE DAMPER, DUCT ACCESS DOOR & CEILING ACCESS DOOR AT RISER. OMIT ACCESS DOOR & NEW DUCTWORK
WHERE GRILLE IS LOCATED AT RISER AND DAMPER CAN BE REACHED THROUGH OPENING.
SCALE: AS NOTED PAGE: 14 of 30
6. GC SHALL VIF ALL FIXTURE LOCATIONS, SWITCHING AND LOADS. ALL LIGHT FIXTURES SHALL BE NEW. LOWERCASE LETTER OR ARC DENOTES
SWITCHING.

7. WHERE ELECTRICAL PANELS ARE RELOCATED PROVIDE SPLICE BOX(ES) AT FORMER PANEL LOCATION AS REQUIRED. COORDINATE LOCATION
WITH FIELD CONDITIONS AND VERIFY WITH ARCHITECT FINAL PLACEMENT(S). A202.00
8. GROUND FAULT CIRCUIT INTERRUPT DUPLEX RECEPTACLES SHALL BE PROVIDED AT KITCHEN, BATH & LAUNDRY COUNTERS.

9. MULTIPLE SWITCHES SHOWN ADJACENT TO EACH OTHER IN SAME LOCATION SHALL BE INSTALLED WITHIN ONE SINGLE GANG JUNCTION BOX &
COVERPLATE.

10. ALL SWITCH & OUTLET & TEL/CABLE RECEPTACLES SHALL BE 'DECORA' WHITE WITH SCREWLESS FACEPLATES.

11. LOCATE ALL NEW KITCHEN OUTLETS PER APPLIANCE MANUFACTURER GUIDLEINES. GC SHALL CONFIRM COMPATIBILITY WITH EXISTING OUTLET
PHCE - REFLECTED CEILING PLAN LOWER LOCATIONS SCHEDULED TO REMAIN.
1 1/4" = 1'-0"

SEAL
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL COMMENTS BATTERY PLACE
LT-1
LT-3
SURFACE CEILING MOUNTED
BATHROOM VANITY WALL MOUNTED
ASSOCIATES, LLC
LT-3.1 BATHROOM VANITY WALL MOUNTED C/O MILSTEIN PROPERTIES
LT-3 b LT-4 CLOSET/STORAGE WALL MOUNTED 335 MADISON AVENUE
LT-6 RECESSED CEILING MOUNTED
NEW YORK, NY 10017
LT-6 a LT-7 RECESSED CLG MTD WET LOCATION
(212) 308-7200
BATH 2 LT-8 UNDER CABINET STRIP LED
8' - 6" LT-9 OUTDOOR SCONCE
a
b
LT-6 a
BEDROOM 2
9' - 0" 9' - 0"

LT-6 LT-7 a
LT-1 a
BEDROOM 3
9' - 0"
LT-3 b
9' - 0" LT-7 a
LT-6 a
9' - 0" LT-1 a
LT-6 a
S
LT-6 T
MBATH 1 a
LT-6 a
LT-3 b SR
LT-7 c BATH 3
8' - 6" 8' - 6" LT-3 b
LT-6 a HALL
LT-6 a S
a b c T S
a
LT-6 a LT-6 a LT-6 a LT-6 a a b LT-6 a
SR
NOT FOR CONSTRUCTION
9' - 0"

3a
3a
3g

LT-6 LT-6 a LT-6 a LT-6 g


S S
LT-6 a LT-6 a LT-6 a

3a
c

LT-6c
8' - 6" 8' - 0"
a b

MASTER LT-6 a
LT-6 a LT-6 a LT-6 a LT-6 a
BEDROOM 1 b SR T
8' - 0" LAUNDRY
9' - 0" 3a
8' - 6"

LT-1 b WIC 1 d
LT-6 d LT-6 a
LT-8 b LT-8 b

LT-6
8' - 6"

PHH - REFLECTED CEILING PLAN UPPER


2 1/4" = 1'-0" NO.
ISSUED FOR BID
DESCRIPTION
05/18/2020
DATE

LT-3 b
CEILING PLAN LEGEND
LT-6 a
LT-9 b a
BATH 4 WALL MOUNTED LIGHT SWITCH. LOWERCASE RECESSED CEILING MOUNTED LIGHT FIXTURE
8' - 6" LETTER OR ARC DENOTES FIXTURE SWITCHING
a
b

LT-6 a 3 WALL MOUNTED 3-WAY SWITCH SURFACE CEILING MOUNTED LIGHT FIXTURE
BEDROOM 4
10' - 1"
LT-9 b WALL MOUNTED SWITCHED RECEPTACLE TO TOP PLUG WALL MOUNTED LIGHT FIXTURE
SR
OUTLET ONLY
DINING
LT-7
10' - 1"
JS DOOR JAMB SWITCH UNDERCABINET LIGHT FIXTURE
3c LT-1 a PROJECT TITLE:

LT-6 d
LT-6 b
LT-8 c S
HARD-WIRED COMBINATION SMOKE/CARBON MONOXIDE
DETECTOR
INDICATES CEILING HEIGHT CHANGE PENTHOUSE UNITS
LT-6 b
LT-6 b
LT-1 b
RENOVATIONS
KITCHEN a
LT-6 NEW CEILING JUNCTION BOX INDICATES NEW SUSPENDED CEILING. SEE PLAN FOR
LT-6 d 9' - 0" SR J CEILING HEIGHT FLOORS 26, 27, 28
WIC 4
8' - 6" NEW WALL MOUNTED THERMOSTAT AT 54" AFF WIRED TO INDICATES EXISTING CONCRETE SLAB W/ SKIM COAT LIBERTY VIEW
TERRACE
LT-6 b LT-6 b LT-6 b T EXISTING PTAC UNIT(S). VIF COMPATIBILITY WITH EXISTING FINISH. PATCH, REPAIR & PROVIDE NEW LEVEL SKIM 99 BATTERY PLACE
S S PTAC(S). WIRING SHALL BE CONCEALED WITHIN WALLS. COAT PLASTER FINISH. BUILD-UP WITH MESH AS
LT-6 d LT-6
PATCH & REPAIR WALLS AS REQ'D REQUIRED
NEW YORK, NEW YORK 10280
3c
b
d LT-8 c LT-8 c
LT-9 b 8' - 0"
b
b
9' - 0" LT-6 a LT-6 a 3g LT-6 a LT-6 b
HALL
3a

LT-6 a LT-6 a LT-6 a LT-6 a CEILING PLAN NOTES


9' - 0"
b c
LT-6 c a
1. EXISTING CONCRETE SLAB W/ SKIM COAT FINISH. PATCH, REPAIR & PROVIDE NEW LEVEL SKIM COAT PLASTER FINISH. DOB SCAN STICKER
a
b
JS

b
LT-3 b 2. ALL SWITCHES SHALL BE DIMMABLE EXCEPT STORAGE, & CLOSETS. ALL SWITCHES LOCATED AT 48" AFF U.O.N. AND 8" FROM ADJACENT DRAWING TITLE:
LT-6 a LT-6 a DOOR/WALL OPENING U.O.N.
PWDR BUTLER
3. REMOVE EXHAUST GRILLE, CAP EXISTING DUCT BRANCH AT RISER & PATCH FIRE-RATED WALL AT ALL DEMOLISHED & ABANDONED KITCHENS &
PH H - REFLECTED
FOYER 8' - 6"
LIVING 9' - 0" LT-4 LT-6 a
BATHROOMS. CEILING PLANS
LT-6 a
10' - 1" 4. REROUTE NEW BRANCH DUCT FOR KITCHEN EXHAUST FROM NEAREST EXISTING KITCHEN RISER TO NEW KITCHEN ABOVE REFRIGERATOR AND
8' - 6" PROVIDE NEW ANOD. ALUM. GRILLE. SEE ELEVATIONS. PROVIDE NEW FIRE DAMPER, DUCT ACCESS DOOR & CEILING ACCESS DOOR AT RISER.
SR LT-6 a LT-8 b
3a 5. REROUTE NEW BRANCH DUCT FOR TOILET EXHAUST FROM NEAREST EXISTING TOILET RISER AND PROVIDE NEW ANOD. ALUM. GRILLE. SEE RCP
& ELEVATIONS. PROVIDE NEW FIRE DAMPER, DUCT ACCESS DOOR & CEILING ACCESS DOOR AT RISER. OMIT ACCESS DOOR & NEW DUCTWORK
WHERE GRILLE IS LOCATED AT RISER AND DAMPER CAN BE REACHED THROUGH OPENING.
SCALE: AS NOTED PAGE: 16 of 30
6. GC SHALL VIF ALL FIXTURE LOCATIONS, SWITCHING AND LOADS. ALL LIGHT FIXTURES SHALL BE NEW. LOWERCASE LETTER OR ARC DENOTES
SWITCHING.

7. WHERE ELECTRICAL PANELS ARE RELOCATED PROVIDE SPLICE BOX(ES) AT FORMER PANEL LOCATION AS REQUIRED. COORDINATE LOCATION
WITH FIELD CONDITIONS AND VERIFY WITH ARCHITECT FINAL PLACEMENT(S). A203.00
8. GROUND FAULT CIRCUIT INTERRUPT DUPLEX RECEPTACLES SHALL BE PROVIDED AT KITCHEN, BATH & LAUNDRY COUNTERS.

9. MULTIPLE SWITCHES SHOWN ADJACENT TO EACH OTHER IN SAME LOCATION SHALL BE INSTALLED WITHIN ONE SINGLE GANG JUNCTION BOX &
COVERPLATE.

10. ALL SWITCH & OUTLET & TEL/CABLE RECEPTACLES SHALL BE 'DECORA' WHITE WITH SCREWLESS FACEPLATES.

11. LOCATE ALL NEW KITCHEN OUTLETS PER APPLIANCE MANUFACTURER GUIDLEINES. GC SHALL CONFIRM COMPATIBILITY WITH EXISTING OUTLET
PHH - REFLECTED CEILING PLAN LOWER LOCATIONS SCHEDULED TO REMAIN.
1 1/4" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200

NOT FOR CONSTRUCTION

POWER PLAN LEGEND ISSUED FOR BID 05/18/2020


NO. DESCRIPTION DATE
LOCATE RECEPTACLES INSIDE CABINET X"
FOR A/V. CONNECT WITH 1.5" INNER DUCT WALL MOUNTED DUPLEX RECEPTACLE @X" AFF EP ELECTRICAL PANEL. TOP OF HIGHEST BREAKER AT
& PULL STRING TO WALL MOUNTED TV 54"AFF.

GFI
WALL MOUNTED GFI DUPLEX RECEPTACLE NID NETWORK INTERFACE DEVICE TEL/DATA/CABLE
PANEL. TOP OF PANEL AT 48"AFF.

IN BASE
WALL MOUNTED HALF SWITCHED DUPLEX RECEPTACLE
9
LV c
IN CABINET WALL MOUNTED DEDICATED DUPLEX RECEPTACLE
GFI A300.00
11

WALL MOUNTED TEL/DATA/CABLE 3-PORT RECEPTACLE


IN BASE LV c
A300.00 WITH CAT 6 FOR TEL/DATA & RG6 FOR CATV
IN CABINET
LV c LV c IN BASE
IN BASE LOW VOLTAGE PASS THRU WALL PLATE WITH
LV c A300.00 8 LV
RECESSED SCOOP. CONNECT TV AND CABLE BOX
PROJECT TITLE:
2

GFI
IN BASE IN CABINET WALL PLATE LOCATIONS WITH 1.5" INNER DUCT WITH
PULL STRING, TYP. VERIFY WITH BLDG MGMT CABLE PENTHOUSE UNITS
5
LV c
A301.00 BOXES AND OTHER A/V EQUIPMENT LOCATIONS. VENT
CABINETS AS REQ'D INTO PTAC ENCLOSURE WHERE RENOVATIONS
EQUIPMENT IS LOCATED ALONG WINDOW PERIMETER
A301.00 MILLWORK FLOORS 26, 27, 28
MASTER A300.00 LIBERTY VIEW
BEDROOM 1 BEDROOM 2 99 BATTERY PLACE
CHASE 2

4 A301.00 WOOD FLOOR WOOD FLOOR


12 LIVING/DINING NEW YORK, NEW YORK 10280
MBATH 1 WOOD FLOOR
A301.00
TILE FLOOR
A300.00 POWER PLAN NOTES
1 IN BASE
A301.00 1. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION
7
2. GFI IN BATH @ 38" A.F.F HORIZONTAL
3
EP
R 3. GFI IN TYP KITCHEN BACKSPLASH @ 42" A.F.F HORIZONTAL
DOB SCAN STICKER
HALL WINE @36"
4. LOCATE ALL PTAC OUTLETS AS REQUIRED BY PTAC MANUFACTURER (TYP.)
WOOD FLOOR
REF'G
DRAWING TITLE:
4 5. LOCATE ALL KITCHEN & LAUNDRY DEDICATED OUTLETS PER APPLIANCE MANUFACTURER GUIDELINES
FOYER
3 PH A - POWER & FINISH
6. REFER TO MILLWORK ELEVATIONS FOR EXACT LOCATIONS OF KITCHEN & BATHROOM RECEPTACLES AND RECEPTACLES LOCATED IN MILLWORK

A300.00
WOOD FLOOR A300.00 PLAN
10 KITCHEN A300.00 2 7. ALL NEW ELECTRICAL PANELS SHALL BE "SQUARE D" 24 CIRCUIT BREAKER LOAD CENTER PANELS
WOOD FLOOR
BATH 2 5 A300.00 6 8. WALL MOUNTED POWER/DATA RECEPTACLES LOCATED AT 15" AFF, UON.
@36"
GFI

1
CHASE 1

TILE FLOOR
9. ALL SWITCH ES & OUTLETS SHALL BE DECORA WITH SCREWLESS FACEPLATES
HDMI & IR EXTENDER HOME @72"
RUN FROM TOP SHELF TO D W
D/W
10. NEW NID PANEL SHALL BE "SUTTLE" SOHO ACCESS WITH #SE-SADC- 28 COYIER (28"X14"X3.5" BOX) TOP OF PANEL @ 48"AFF. ALL TEL/DATA/CABLE SCALE: AS NOTED PAGE: 15 of 30
EACH BEDROOM & LIVING TV DEVICES SHALL BE LUTRON
NID

LOCATION, TYP. GFI GFI GFI

A210.00
G
11. PROVIDE FR ¾" PLYWOOD BLOCKING WITHIN STUDS FOR WALL MOUNTED TVS: ONE PER EACH BEDROOM AND LIVING ROOM

12. SPLICE AND RELOCATE ALL TELEPHONE TRUNK RISERS AS REQUIRED TO CONCEAL WITHIN WALLS/CEILINGS PER NEW LAYOUT. CHANNEL
FLOOR/CEILING AS REQUIRED

13. RUN NEW CONCEALED LOW VOLTAGE WIRING FOR FUTURE POWERED SHADES FROM SHADE OUTLET TO JUNCTION BOX IN SOFFIT ABOVIE, lYP
AT ALL WINDOWS. SEE RCP

PHA - POWER & FINISH PLAN


1 1/4" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
A401.00
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
1 (212) 308-7200
TERRACE

W
A401.00

GFI
D LOCATE RECEPTACLES INSIDE CABINET
2 FOR A/V. CONNECT WITH 1.5" INNER DUCT
WET & PULL STRING TO WALL MOUNTED TV
LAUND.

GFI
GFI

12 A302.00

13 IN CABINET
WIC 1 LV b
MASTER
14 A302.00 BEDROOM 1 LV b
11 A302.00 NOT FOR CONSTRUCTION

GFI 10 A302.00 9
MBATH 1

EP

GFI
GFI
4
IN CABINET
A303.00 LV c
CORRIDOR
A303.00 BATH 2
BEDROOM 2
5 LV c
3
GFI

2 A303.00 1
GFI

PHB - POWER & FINISH PLAN UPPER POWER PLAN LEGEND


2 1/4" = 1'-0" NO.
ISSUED FOR BID
DESCRIPTION
05/18/2020
DATE
X"
WALL MOUNTED DUPLEX RECEPTACLE @X" AFF EP ELECTRICAL PANEL. TOP OF HIGHEST BREAKER AT
54"AFF.

GFI
WALL MOUNTED GFI DUPLEX RECEPTACLE NID NETWORK INTERFACE DEVICE TEL/DATA/CABLE
PANEL. TOP OF PANEL AT 48"AFF.

WALL MOUNTED HALF SWITCHED DUPLEX RECEPTACLE

WALL MOUNTED DEDICATED DUPLEX RECEPTACLE

WALL MOUNTED TEL/DATA/CABLE 3-PORT RECEPTACLE


WITH CAT 6 FOR TEL/DATA & RG6 FOR CATV
8 A302.00

@42" LOW VOLTAGE PASS THRU WALL PLATE WITH


LV
RECESSED SCOOP. CONNECT TV AND CABLE BOX
PROJECT TITLE:
POWDER LV a

GFI WINE
@60"
WALL PLATE LOCATIONS WITH 1.5" INNER DUCT WITH
PULL STRING, TYP. VERIFY WITH BLDG MGMT CABLE PENTHOUSE UNITS
6 A302.00 7
BOXES AND OTHER A/V EQUIPMENT LOCATIONS. VENT
CABINETS AS REQ'D INTO PTAC ENCLOSURE WHERE RENOVATIONS
EQUIPMENT IS LOCATED ALONG WINDOW PERIMETER
MILLWORK FLOORS 26, 27, 28
LIVING
4 LIBERTY VIEW
99 BATTERY PLACE
A302.00
NEW YORK, NEW YORK 10280
HDMI & IR EXTENDER FOYER LV a
HOME RUN FROM TOP
IN CABINET
SHELF TO EACH
BEDROOM & LIVING TV 5 POWER PLAN NOTES
LOCATION, TYP.
@72"
1. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION
NID

2. GFI IN BATH @ 38" A.F.F HORIZONTAL

3. GFI IN TYP KITCHEN BACKSPLASH @ 42" A.F.F HORIZONTAL


DOB SCAN STICKER
4. LOCATE ALL PTAC OUTLETS AS REQUIRED BY PTAC MANUFACTURER (TYP.)
DRAWING TITLE:
5. LOCATE ALL KITCHEN & LAUNDRY DEDICATED OUTLETS PER APPLIANCE MANUFACTURER GUIDELINES
PH B - POWER & FINISH
6. REFER TO MILLWORK ELEVATIONS FOR EXACT LOCATIONS OF KITCHEN & BATHROOM RECEPTACLES AND RECEPTACLES LOCATED IN MILLWORK
3 A302.00 2
PLANS
7. ALL NEW ELECTRICAL PANELS SHALL BE "SQUARE D" 24 CIRCUIT BREAKER LOAD CENTER PANELS
1 8. WALL MOUNTED POWER/DATA RECEPTACLES LOCATED AT 15" AFF, UON.
REF'G
KITCHEN/DINING
9. ALL SWITCH ES & OUTLETS SHALL BE DECORA WITH SCREWLESS FACEPLATES

10. NEW NID PANEL SHALL BE "SUTTLE" SOHO ACCESS WITH #SE-SADC- 28 COYIER (28"X14"X3.5" BOX) TOP OF PANEL @ 48"AFF. ALL TEL/DATA/CABLE SCALE: AS NOTED PAGE: 17 of 30
GFI

DEVICES SHALL BE LUTRON


D/W

A211.00
11. PROVIDE FR ¾" PLYWOOD BLOCKING WITHIN STUDS FOR WALL MOUNTED TVS: ONE PER EACH BEDROOM AND LIVING ROOM
GFI GFI GFI
12. SPLICE AND RELOCATE ALL TELEPHONE TRUNK RISERS AS REQUIRED TO CONCEAL WITHIN WALLS/CEILINGS PER NEW LAYOUT. CHANNEL
FLOOR/CEILING AS REQUIRED

13. RUN NEW CONCEALED LOW VOLTAGE WIRING FOR FUTURE POWERED SHADES FROM SHADE OUTLET TO JUNCTION BOX IN SOFFIT ABOVIE, lYP
AT ALL WINDOWS. SEE RCP

PHB - POWER & FINISH PLAN LOWER


1 1/4" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200

GFI
12 17
BATH 3
A305.00 A305.00

WIC 3 13 IN CABINET
GFI LV d
WET

14 A305.00
A305.00 10

NOT FOR CONSTRUCTION


BEDROOM 3 LV d
WIC 4 15 CORRIDOR

16 A305.00

WET
GFI
TERRACE WIC 2
LV e 7 A305.00
@60"

LV c
BEDROOM 4 @60"
A304.00 A305.00 9
A305.00
BATH 2
11 8 IN CABINET
IN CABINET LV c
LV e 11 BEDROOM 2
4 A305.00 5 IN BASE

GFI
LOCATE RECEPTACLES INSIDE CABINET
FOR A/V. CONNECT WITH 1.5" INNER DUCT
& PULL STRING TO WALL MOUNTED TV

PHCE - POWER & FINISH PLAN UPPER POWER PLAN LEGEND ISSUED FOR BID 05/18/2020
2 1/4" = 1'-0" NO. DESCRIPTION DATE
X"
WALL MOUNTED DUPLEX RECEPTACLE @X" AFF EP ELECTRICAL PANEL. TOP OF HIGHEST BREAKER AT
54"AFF.

GFI
WALL MOUNTED GFI DUPLEX RECEPTACLE NID NETWORK INTERFACE DEVICE TEL/DATA/CABLE
PANEL. TOP OF PANEL AT 48"AFF.
CHOP, SLICE BOX IN WALL AND
RELOCATE EP AS SHOWN WALL MOUNTED HALF SWITCHED DUPLEX RECEPTACLE

GFI
GFI

WALL MOUNTED DEDICATED DUPLEX RECEPTACLE


SB

8 A304.00
EP
14 WALL MOUNTED TEL/DATA/CABLE 3-PORT RECEPTACLE
WITH CAT 6 FOR TEL/DATA & RG6 FOR CATV
PWDR
A304.00 12 GFI LOW VOLTAGE PASS THRU WALL PLATE WITH
13 A304.00 LV PROJECT TITLE:
3 FOYER RECESSED SCOOP. CONNECT TV AND CABLE BOX

MBATH 1 W
WALL PLATE LOCATIONS WITH 1.5" INNER DUCT WITH
PULL STRING, TYP. VERIFY WITH BLDG MGMT CABLE PENTHOUSE UNITS
1 A305.00 2 @72" BOXES AND OTHER A/V EQUIPMENT LOCATIONS. VENT
CABINETS AS REQ'D INTO PTAC ENCLOSURE WHERE RENOVATIONS
GFI A304.00 7 EQUIPMENT IS LOCATED ALONG WINDOW PERIMETER
FLOORS 26, 27, 28
GFI

D
HDMI & IR EXTENDER HOME MILLWORK
10 9 A304.00 NID RUN FROM TOP SHELF TO
PANTRY EACH BEDROOM & LIVING TV LIBERTY VIEW
WIC 1 LOCATION, TYP. 99 BATTERY PLACE
A304.00 LAUND. NEW YORK, NEW YORK 10280

GFI GFI GFI

EP GFI POWER PLAN NOTES


D/W WINE LV a
2
1. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION
A304.00
2. GFI IN BATH @ 38" A.F.F HORIZONTAL
REF'G
A304.00 LV a
6
LV b 1 @60" 3. GFI IN TYP KITCHEN BACKSPLASH @ 42" A.F.F HORIZONTAL
@60"
DOB SCAN STICKER
3 A304.00 A304.00 4. LOCATE ALL PTAC OUTLETS AS REQUIRED BY PTAC MANUFACTURER (TYP.)
A304.00 DRAWING TITLE:
GFI

5. LOCATE ALL KITCHEN & LAUNDRY DEDICATED OUTLETS PER APPLIANCE MANUFACTURER GUIDELINES
4 5
PH CE - POWER & FINISH
6. REFER TO MILLWORK ELEVATIONS FOR EXACT LOCATIONS OF KITCHEN & BATHROOM RECEPTACLES AND RECEPTACLES LOCATED IN MILLWORK
KITCHEN
IN CABINET LIVING/DINING PLANS
GFI

LV a 7. ALL NEW ELECTRICAL PANELS SHALL BE "SQUARE D" 24 CIRCUIT BREAKER LOAD CENTER PANELS
IN BASE
8. WALL MOUNTED POWER/DATA RECEPTACLES LOCATED AT 15" AFF, UON.
A304.00
MASTER
BEDROOM 1 9. ALL SWITCH ES & OUTLETS SHALL BE DECORA WITH SCREWLESS FACEPLATES

IN CABINET 11 10. NEW NID PANEL SHALL BE "SUTTLE" SOHO ACCESS WITH #SE-SADC- 28 COYIER (28"X14"X3.5" BOX) TOP OF PANEL @ 48"AFF. ALL TEL/DATA/CABLE SCALE: AS NOTED PAGE: 18 of 30
LV b DEVICES SHALL BE LUTRON

A212.00
LOCATE RECEPTACLES INSIDE CABINET 11. PROVIDE FR ¾" PLYWOOD BLOCKING WITHIN STUDS FOR WALL MOUNTED TVS: ONE PER EACH BEDROOM AND LIVING ROOM
FOR A/V. CONNECT WITH 1.5" INNER DUCT
& PULL STRING TO WALL MOUNTED TV 12. SPLICE AND RELOCATE ALL TELEPHONE TRUNK RISERS AS REQUIRED TO CONCEAL WITHIN WALLS/CEILINGS PER NEW LAYOUT. CHANNEL
FLOOR/CEILING AS REQUIRED

13. RUN NEW CONCEALED LOW VOLTAGE WIRING FOR FUTURE POWERED SHADES FROM SHADE OUTLET TO JUNCTION BOX IN SOFFIT ABOVIE, lYP
AT ALL WINDOWS. SEE RCP

PHCE - POWER & FINISH PLAN LOWER


1 1/4" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
GFI
335 MADISON AVENUE
NEW YORK, NY 10017
BATH 2 (212) 308-7200
7
A307.00 9
IN BASE

LV e A307.00
IN CABINET
IN BASE
8

GFI
LV d
IN CABINET A307.00 LV d LV e
GFI
6 @60"

GFI
14
7 BEDROOM 2
A308.00
15 A307.00
A308.00 5 BATH 3
MBATH 1
BEDROOM 3 A307.00 A307.00 10
GFI
HALL
GFI
11
NOT FOR CONSTRUCTION
SB EP A401.00
-

CHOP, SLICE BOX


IN WALL AND 5
RELOCATE EP AS
GFI SHOWN
UC
REF'G

IN BASE IN BASE 4

A308.00

GFI
LV c A308.00 12 A307.00 13

GFI
IN CABINET
2 3 LAUNDRY
MASTER
1 A308.00
BEDROOM 1 LV c
WIC 1
@60"

GFI
10 A308.00 9

PHH - POWER & FINISH PLAN UPPER POWER PLAN LEGEND


2 1/4" = 1'-0" NO.
ISSUED FOR BID
DESCRIPTION
05/18/2020
DATE
X"
WALL MOUNTED DUPLEX RECEPTACLE @X" AFF EP ELECTRICAL PANEL. TOP OF HIGHEST BREAKER AT
54"AFF.
GFI
GFI
WALL MOUNTED GFI DUPLEX RECEPTACLE NID NETWORK INTERFACE DEVICE TEL/DATA/CABLE
PANEL. TOP OF PANEL AT 48"AFF.
W ET A307.00 6
GFI
WALL MOUNTED HALF SWITCHED DUPLEX RECEPTACLE
IN BASE
2
BATH 4
WALL MOUNTED DEDICATED DUPLEX RECEPTACLE
LV b A307.00
IN CABINET
LV b WALL MOUNTED TEL/DATA/CABLE 3-PORT RECEPTACLE
@60" WITH CAT 6 FOR TEL/DATA & RG6 FOR CATV
12
LOW VOLTAGE PASS THRU WALL PLATE WITH
LV
RECESSED SCOOP. CONNECT TV AND CABLE BOX
PROJECT TITLE:
GFI

4 A306.00
IN BASE
D/W
WALL PLATE LOCATIONS WITH 1.5" INNER DUCT WITH
PULL STRING, TYP. VERIFY WITH BLDG MGMT CABLE PENTHOUSE UNITS
A306.00 DINING
5 BOXES AND OTHER A/V EQUIPMENT LOCATIONS. VENT
CABINETS AS REQ'D INTO PTAC ENCLOSURE WHERE RENOVATIONS
EQUIPMENT IS LOCATED ALONG WINDOW PERIMETER
TERRACE KITCHEN
BEDROOM 4 4 A307.00 3 MILLWORK FLOORS 26, 27, 28
5 A306.00 3 LIBERTY VIEW
WIC 4 99 BATTERY PLACE
A306.00 A307.00
2
NEW YORK, NEW YORK 10280

13 1
POWER PLAN NOTES
SB

GFI GFI
CHOP, SLICE BOX A401.00
-
IN WALL AND
REF'G RELOCATE EP AS
WET
SHOWN 1. SEE ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION
GFI 5
HALL 2. GFI IN BATH @ 38" A.F.F HORIZONTAL
EP
GFI 3. GFI IN TYP KITCHEN BACKSPLASH @ 42" A.F.F HORIZONTAL
DOB SCAN STICKER
IN BASE 4. LOCATE ALL PTAC OUTLETS AS REQUIRED BY PTAC MANUFACTURER (TYP.)
WINE
DRAWING TITLE:
GFI
PWDR BUTLER 5. LOCATE ALL KITCHEN & LAUNDRY DEDICATED OUTLETS PER APPLIANCE MANUFACTURER GUIDELINES
PH H - POWER & FINISH
GFI

7 FOYER
6. REFER TO MILLWORK ELEVATIONS FOR EXACT LOCATIONS OF KITCHEN & BATHROOM RECEPTACLES AND RECEPTACLES LOCATED IN MILLWORK
IN
BASE
9
A306.00
A306.00 10
PLANS
1 @72" 7. ALL NEW ELECTRICAL PANELS SHALL BE "SQUARE D" 24 CIRCUIT BREAKER LOAD CENTER PANELS
A306.00 11 8
6 A306.00 8. WALL MOUNTED POWER/DATA RECEPTACLES LOCATED AT 15" AFF, UON.
GFI
9. ALL SWITCH ES & OUTLETS SHALL BE DECORA WITH SCREWLESS FACEPLATES
LIVING NID
10. NEW NID PANEL SHALL BE "SUTTLE" SOHO ACCESS WITH #SE-SADC- 28 COYIER (28"X14"X3.5" BOX) TOP OF PANEL @ 48"AFF. ALL TEL/DATA/CABLE SCALE: AS NOTED PAGE: 19 of 30
DEVICES SHALL BE LUTRON
HDMI & IR EXTENDER HOME

A213.00
RUN FROM TOP SHELF TO 11. PROVIDE FR ¾" PLYWOOD BLOCKING WITHIN STUDS FOR WALL MOUNTED TVS: ONE PER EACH BEDROOM AND LIVING ROOM
LV a
EACH BEDROOM & LIVING TV
LOCATION, TYP. 12. SPLICE AND RELOCATE ALL TELEPHONE TRUNK RISERS AS REQUIRED TO CONCEAL WITHIN WALLS/CEILINGS PER NEW LAYOUT. CHANNEL
FLOOR/CEILING AS REQUIRED
LV a
IN CABINET 13. RUN NEW CONCEALED LOW VOLTAGE WIRING FOR FUTURE POWERED SHADES FROM SHADE OUTLET TO JUNCTION BOX IN SOFFIT ABOVIE, lYP
AT ALL WINDOWS. SEE RCP

LOCATE RECEPTACLES INSIDE CABINET FOR A/V. CONNECT


WITH 1.5" INNER DUCT & PULL STRING TO WALL MOUNTED TV

PHH - POWER & FINISH PLAN LOWER


1 1/4" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200

1'-0"
DOWNLIGHT
CENTERED IN

6"
CL CL CL DOOR

SHELF GLASS PANEL


DOORS

ADJ. SHELVES BEYOND


7"
1'-7"
ADJ SHELF

SHELF 7" 4" SEMI

5'-1 1/4"
ADJ SHELF RECESSED

3"
ROD MEDICINE

3'-0"
CABINET
ADJ SHELF
EQ EQ

8'-6"

8'-6"
ADJ SHELF
WINDOW

7'-0"
TYPE
VARIES

8"
5'-9"
ADJ SHELF

5'-6"
V.I.F.

2'-0"
4'-6"
ADJ SHELF

2'-6 3/4"
3'-6"

6"

2'-5"
NOT FOR CONSTRUCTION

2'-4" VIF

2'-9"
ADJ SHELF

1'-4"
BASE OPEN KICK

4"

4"
2'-6 1/8" 3/4" 2'-5 3/8" 3/4" 1'-4 3/4" 4'-6" 4'-6" 10 3/8" 2'-6" 2'-0" 2'-8" 2'-0"
PTAC
5'-1" 11'-3 1/8" 7'-2"

PHA BEDROOM 2 W PHA BEDROOM 2 E PHA BATH 2 N PHA LIVING/DINING W


12 1/2" = 1'-0" 11 1/2" = 1'-0" 10 1/2" = 1'-0" 7 1/2" = 1'-0"

CROWN CROWN

SHELF

3"
ROD
SHELF

3"
ROD
9'-6"

9'-6"

3'-5"
ISSUED FOR BID 05/18/2020

8'-6"

8'-6"
NO. DESCRIPTION DATE
WINDOW WINDOW WINDOW
TYPE TYPE

6'-8"
TYPE
VARIES VARIES VARIES

5'-9"
5'-6"
V.I.F. V.I.F. V.I.F.

10"

3'-0"
2'-4" VIF

2'-4" VIF
1'-6"
WASHER DRYER
OPEN OPEN OPEN OPEN BASE BASE

2'-8" 4'-6" 4'-3 7/8" 4'-3 7/8" 4'-5 1/2" 4'-5 1/2" 2'-10 5/8" 2'-10 5/8" 2'-10 5/8"
PTAC
15'-9 3/4" 8'-11" 8'-8" 2'-10 3/4"
BENCH
PROJECT TITLE:
PHA LIVING/DINING E PHA LIVING/DINING S PHA ENTRY CLOSET PHA LAUNDRY CLOSET PENTHOUSE UNITS
9 1/2" = 1'-0" 8 1/2" = 1'-0" 5 1/2" = 1'-0" 6 1/2" = 1'-0"
RENOVATIONS
FLOORS 26, 27, 28
LIBERTY VIEW
2'-3 3/4" 1'-6" 2'-6" 1'-6" 3'-0" 2'-0"
99 BATTERY PLACE
NEW YORK, NEW YORK 10280

CROWN CROWN CROWN CROWN CROWN


6"

11 7/8" 6"

6"
VENT

3'-3"
DOB SCAN STICKER

5'-1 1/4"
5'-0"

EQ EQ EQ EQ MICRO
DRAWING TITLE:
PHA - ELEVATIONS
8'-6"

8'-6"

8'-6"
CL CL CL

8'-0"
1'-9"
EQ EQ
7'-0 1/8"

WINDOW
TYPE
VARIES
REF'G
V.I.F.

2'-10 3/4"
SCALE: AS NOTED PAGE: 21 of 30
3'-0"

3'-0"

3'-0"
2'-4" VIF

RANGE DISHWASHER

KICK OPEN KICK KICK BASE A300.00


2 3/4" 2'-0 3/8" 2 3/4" 3'-1 3/4" 2'-5" 2'-5" 2'-5" 2'-5" 11" 4'-6" 9" 2'-3 3/4" 1'-6" 2'-6" 1'-6" 3'-0" 2'-0"
PTAC
2'-5 7/8" 12'-9 3/4" 12'-9 3/4"
6'-2"

PHA BAR PHA KITCHEN W PHA KITCHEN N PHA KITCHEN E


4 1/2" = 1'-0" 3 1/2" = 1'-0" 2 1/2" = 1'-0" 1 1/2" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200

NOT FOR CONSTRUCTION

CL CL CL CL

EQ
MED. MED. MED.
CAB. CAB. CAB.

5'-9"
MIRROR MIRROR ISSUED FOR BID 05/18/2020

8'-6"

8'-6"

8'-6"
EQ
NO. DESCRIPTION DATE
WINDOW

7'-0"
TYPE
MED. MED. MED.
VARIES
CAB. CAB. CAB.
V.I.F.

2'-0"

4'-6"
9"
6"

3'-6"
10"

10"
2'-9"
2'-6"
10"

10"

1'-4"
KICK

4"

4"
10" 2'-6" 11 1/8" 11" 2'-6" 11" 2'-6" 11" 3'-0" 3" 2'-9"
4'-3 1/8" 7'-9" 6'-0"
PROJECT TITLE:
PHA MBATH E PHA MBATH N PHA MBATH W PENTHOUSE UNITS
5 1/2" = 1'-0" 4 1/2" = 1'-0" 3 1/2" = 1'-0"
RENOVATIONS
FLOORS 26, 27, 28
LIBERTY VIEW
99 BATTERY PLACE
NEW YORK, NEW YORK 10280
CROWN

SHELF SHELF

ROD

1'-7"
ADJ SHELF

SHELF SHELF
ADJ SHELF DOB SCAN STICKER
3'-8"

3"
ROD ROD DRAWING TITLE:
ADJ SHELF
PHA - ELEVATIONS
SHELF ADJ SHELF
7'-4"

WINDOW
TYPE
ROD VARIES
5'-9"

ADJ SHELF
5'-6"

V.I.F.

ADJ SHELF
3'-8"

SCALE: AS NOTED PAGE: 20 of 30

2'-4" VIF
ADJ SHELF

BASE BASE OPEN BASE A301.00


2'-3" 3/4" 2'-3" 2'-3" 3/4" 2'-2 1/4" 3/4" 4'-7 1/8" 4'-6" 4'-4 1/8"
PTAC
4'-6 3/4" 4'-6 3/4"
13'-5 1/4"

PHA MBEDROOM W PHA MBEDROOM E


1 1/2" = 1'-0" 2 1/2" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
2'-10 1/8" 2'-10 1/8" 2'-10 1/8"
(212) 308-7200

CL CL CL CL CL

SHELF SHELF SHELF

EQ
CL

3"
ROD

1'-7"

3'-3"
ADJ SHELF
MED.
SHELF 4" 7"
CAB.
3'-8"

ADJ SHELF

3"
ROD

4'-3"
CL
ADJ SHELF MIRROR MIRROR

8'-6"

8'-6"

8'-6"

8'-6"

EQ
CL CL

1'-9"
SHELF
7'-4"

7'-4"
CL

7'-0"
ADJ SHELF MED.
3"

ROD

5'-9"
CAB.

8"
STONE BACKSPLASH

2'-0"

4'-6"
ADJ SHELF

6"
3'-8"

3'-6"

2'-5"
10"
3'-0"
NOT FOR CONSTRUCTION

2'-9"
2'-0"
ADJ SHELF

10"

1'-4"
WASHER DRYER
BASE BASE KICK

4"

4"

4"
2'-0" 3/4" 3'-3 1/4" 2'-2" 3'-10" 4'-8 1/4" 1'-0" 2'-2 3/4" 3'-0" 3" 2'-9" 2'-6" 2'-6" 1'-6"
5'-4" 5'-6 1/4" 8'-6 1/4" 3'-2 3/4" 6'-0" 6'-6"

PHB WIC 1 N PHB WIC 1 E PHB LAUNDRY N PHB MBATH N PHB MBATH W
14 1/2" = 1'-0" 13 1/2" = 1'-0" 12 1/2" = 1'-0" 11 1/2" = 1'-0" 10 1/2" = 1'-0"

CROWN

CROWN
CROWN

SHELF SHELF

5'-0"

3"

3"
10'-1"

ROD ROD
9'-0"

ISSUED FOR BID 05/18/2020

8'-6"

8'-6"

8'-6"
NO. DESCRIPTION DATE
WINDOW WINDOW
TYPE TYPE
VARIES VARIES

5'-6"

5'-6"
V.I.F. V.I.F.

8"

3'-0"
2'-4" VIF
2'-4" VIF

2'-0"
OPEN OPEN BASE KICK BASE BASE

4"
4'-1" 4'-6" 2'-4" 3'-1" 4'-6" 4'-6 1/4" 2'-1" 2'-7 1/2"
PTAC PTAC
4'-8 1/2"
10'-11" 12'-1 1/4" PROJECT TITLE:
PHB MBEDROOM S PHB LIVING S PHB LIVING N PHB FOYER W PHB FOYER E PENTHOUSE UNITS
9 1/2" = 1'-0" 7 1/2" = 1'-0" 6 1/2" = 1'-0" 5 1/2" = 1'-0" 4 1/2" = 1'-0"
RENOVATIONS
FLOORS 26, 27, 28
LIBERTY VIEW
11" 2'-7" 1'-6" 2'-6" 3'-0" 3'-0" 2'-1 1/4" 99 BATTERY PLACE
NEW YORK, NEW YORK 10280
CROWN DOWNLIGHT CROWN
1'-0"

1'-0"
CENTERED IN
CL CL DOOR
11 7/8"

VENT GLASS PANEL


DOORS
ADJ. SHELVES BEYOND

ADJ. SHELVES BEYOND


7"

3'-3"
SEMI
DOB SCAN STICKER
5'-1 1/4"

RECESSED
MEDICINE MICRO
DRAWING TITLE:
3'-0"

CABINET

EQ EQ PHB - ELEVATIONS
8'-6"

CL CL CL

8'-0"
1'-9"
7'-0 1/8"

WINDOW
REF'G
CL TYPE
VARIES
8"

V.I.F.

8"
2'-0"

10"
2'-6 3/4"

SCALE: AS NOTED PAGE: 22 of 30

3'-0"
2'-9"

2'-0"
2'-4"

RANGE DISHWASHER

A302.00
1'-6"
1'-4"

KICK OPEN OPEN OPEN KICK


4"

4"
2'-0" 3'-0" 2'-7" 3'-1 1/2" 4" 3'-3" 4" 3'-3" EQ EQ EQ 1'-6" 2'-6" 1'-0" 2'-0" 3'-0" 1'-2 1/4"
5'-0" 12'-10 1/2" 8'-10 3/4" 11'-3"
BENCH

PHB POWDER N PHB KITCHEN/DINING N PHB KITCHEN/DINING S PHB KITCHEN/DINING W


8 1/2" = 1'-0" 3 1/2" = 1'-0" 2 1/2" = 1'-0" 1 1/2" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200

NOT FOR CONSTRUCTION

ISSUED FOR BID 05/18/2020


NO. DESCRIPTION DATE

PROJECT TITLE:
PENTHOUSE UNITS
RENOVATIONS
FLOORS 26, 27, 28
LIBERTY VIEW
CROWN 99 BATTERY PLACE
NEW YORK, NEW YORK 10280

CL CL CL
SHELF SHELF
CL
7"

1'-7"
ADJ SHELF ADJ SHELF

SEMI 4" 7" SHELF


DOB SCAN STICKER
5'-1 1/4"

RECESSED
ADJ SHELF ADJ SHELF
MEDICINE
DRAWING TITLE:

10'-1"
ROD

3"
3'-0"

CABINET

ADJ SHELF
CL
ADJ SHELF PHB - ELEVATIONS
8'-6"

8'-6"

8'-6"

8'-6"

2'-0"
7'-4"

7'-4"
CL WINDOW
7'-0"

ADJ SHELF ADJ SHELF TYPE


8"

VARIES
5'-9"

V.I.F.
2'-0"

4'-6"

ADJ SHELF CL ADJ SHELF


2'-6 3/4"

3'-6"

SCALE: AS NOTED PAGE: 23 of 30


6"

2'-4" VIF
2'-9"

ADJ SHELF ADJ SHELF

A303.00
1'-4"

BASE BASE OPEN


4"

3/4" 2'-6 1/2" 3/4" 2'-6" 2'-11 3/8" 2'-2 3/8" 2'-1 3/4" 3'-0" 2'-6" 4'-10 1/4" 3/4" 2'-5 1/4" 3/4" 4'-8" 4'-6" 2'-0"
PTAC
2'-8" 7'-7 3/4" 7'-7 3/4" 7'-5" 11'-2"

PHB CORRIDOR W PHB BATH 2 E PHB BATH 2 W PHB BEDROOM 2 N PHB BEDROOM 2 S
5 1/2" = 1'-0" 4 1/2" = 1'-0" 3 1/2" = 1'-0" 2 1/2" = 1'-0" 1 1/2" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
CROWN
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200

CL CL CL CL CL

SHELF

EQ
CL
ADJ SHELF ADJ SHELF
MED. MED. MED.
7" 4"
CAB. CAB. CAB.

5'-9"
ADJ SHELF ADJ SHELF

10'-1"
ADJ SHELF ADJ SHELF
MIRROR MIRROR MIRROR CL
8'-6"

8'-6"

8'-6"

8'-6"
EQ
ADJ SHELF ADJ SHELF

7'-4"
WINDOW

7'-0"
CL
MED. MED. MED. TYPE
CAB. CAB. CAB. VARIES
V.I.F. ADJ SHELF ADJ SHELF
STONE BACKSPLASH

2'-0"
4'-6"
9"
6"

1'-6" ADJ SHELF ADJ SHELF

3'-6"
10"

10"
NOT FOR CONSTRUCTION

2'-4" VIF
2'-9"
2'-6"

ADJ SHELF ADJ SHELF


10"

10"

1'-4"
KICK OPEN
4"

4"
1'-5" 3'-0" 1'-5" 1'-0" 2'-6" 1'-0" 2'-6" 1'-6" 2'-9" 3" 4'-5" 2'-7 3/4" 4'-6" 4'-8" 3/4" 3'-1 1/2" 3/4" 2'-0 1/4" 3/4"
5'-10" 8'-6" 7'-5" 11'-9 3/4" 5'-4"

PHCE MBATH E PHCE MBATH N PHCE MBATH S PHCE MBEDROOM W PHCE BAR E
14 1/2" = 1'-0" 13 1/2" = 1'-0" 12 1/2" = 1'-0" 11 1/2" = 1'-0"
10 1/2" = 1'-0"

2'-5 7/8" 2'-5 7/8" 2'-5 7/8"


CROWN CROWN
CROWN DOWNLIGHT
CL CL
CENTERED IN
DOOR
GLASS PANEL

ADJ. SHELVES BEYOND

ADJ. SHELVES BEYOND


DOORS
7"
3'-3"

SEMI SHELF

5'-1 1/4"
RECESSED

5'-0"
MEDICINE ROD
3"
3'-0"

CABINET

9'-0"
9'-0"
ISSUED FOR BID 05/18/2020
8'-6"

8'-6"

8'-6"

EQ EQ

8'-0"
NO. DESCRIPTION DATE
1'-9"

WINDOW WINDOW
CL CL TYPE TYPE
VARIES VARIES
8"

5'-9"

V.I.F. V.I.F.
8"

8"
2'-0"

2'-10 3/4"
2'-5"
3'-0"

3'-0"

2'-4" VIF
2'-9"
2'-0"

2'-0"
1'-4"

WASHER DRYER
KICK BASE KICK KICK OPEN OPEN
4"

4"

4"
3'-0" 4'-5 1/2" 2'-0" 3'-0" 3'-6" 4" 1'-5 1/4" 2'-0 3/4" 1'-7" 4'-6" 4'-0" 4'-0" 4'-6" 2'-1"
PTAC PTAC
7'-5 1/2" 5'-0" 3'-9" 7'-4" 20'-8"
PROJECT TITLE:
PHCE LAUNDRY N PHCE POWDER N PHCE FOYER S PHCE KITCHEN E Copy 1 PHCE LIVING/DINING W Copy 1 PENTHOUSE UNITS
9 1/2" = 1'-0" 8 1/2" = 1'-0" 7 1/2" = 1'-0" 6 1/2" = 1'-0" 5 1/2" = 1'-0"
RENOVATIONS
FLOORS 26, 27, 28
LIBERTY VIEW
1'-7 5/8" 3'-0" 3'-0" 2'-6" 1'-7 5/8"
99 BATTERY PLACE
NEW YORK, NEW YORK 10280
CROWN CROWN CROWN
1'-0"

1'-0"

1'-0"
11 7/8"

VENT

1'-9"
3'-3"

3'-3"

WATERFALL STONE DETAIL DOB SCAN STICKER


MICRO AT KITCHEN ISLAND. MITER
EDGES BETWEEN TOP AND DRAWING TITLE:
SIDES, TYP.
PHCE - ELEVATIONS
9'-0"

9'-0"

9'-0"
1'-9"

1'-9"
7'-0 1/8"

WINDOW REF'G
TYPE CL CL CL CL CL
VARIES
V.I.F.
8"

8"

8"
SCALE: AS NOTED PAGE: 24 of 30
3'-0"

3'-0"

3'-0"
2'-4" VIF

2'-0"

2'-0"

2'-0"
DISHWASHER RANGE

BASE OPEN KICK KICK KICK A304.00


4"

4"

4"
8 1/2" 4'-6" 2'-7 3/4" 2'-9 3/4" 2'-9 3/4" 3'-1 1/2" 1'-7 5/8" 3'-0" 2'-0" 1'-0" 2'-6" 1'-7 5/8" 1 1/4" 2'-7 3/4" 2'-7 3/4" 2'-7 3/4" 2'-7 3/4" 1 1/4"
PTAC
8'-9" 11'-9 1/4" 10'-9 1/4"
7'-10 1/4"

PHCE LIVING/DINING W2 PHCE KITCHEN N PHCE KITCHEN E PHCE KITCHEN W


4 1/2" = 1'-0" 3 1/2" = 1'-0" 2 1/2" = 1'-0" 1 1/2" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200

CL CL CL

SHELF SHELF SHELF SHELF SHELF

3"
ROD ROD

3"

7"
1'-7"

1'-7"

1'-7"
ADJ SHELF ADJ SHELF ADJ SHELF

SHELF SHELF SHELF 7" 4" SEMI


ADJ SHELF ADJ SHELF ADJ SHELF RECESSED

3'-8"
3"
MEDICINE

3"
ROD ROD

3"
ROD

3'-0"
CABINET
ADJ SHELF ADJ SHELF ADJ SHELF
8'-6"

8'-6"

8'-6"

8'-6"

8'-6"
2'-0"
ADJ SHELF ADJ SHELF SHELF SHELF ADJ SHELF

7'-4"

7'-4"

7'-4"

7'-0"
3"
ROD ROD

3"

8"
5'-9"

5'-9"

5'-9"
ADJ SHELF ADJ SHELF ADJ SHELF

2'-0"
4'-6"
ADJ SHELF ADJ SHELF ADJ SHELF

3'-8"

3'-6"

6"
NOT FOR CONSTRUCTION

2'-9"
ADJ SHELF ADJ SHELF ADJ SHELF

1'-4"
3/4" 2'-0" 3/4" 2'-0 3/4" 3/4" 3/4" 2'-6 1/2" 3/4" 2'-0" 3'-5 1/2" 3/4" 3'-5 1/2" 2'-9 5/8" 3/4" 2'-9 5/8" 2'-0" 3/4" 2'-6 1/2" 3/4" 2'-6" 3'-0" 2'-2 1/2"
4'-3" 4'-8" 6'-11 3/4" 5'-8" 4'-8" 7'-8 1/2"

PHCE CORRIDOR E PHCE WIC 4 N PHCE WIC 4 E PHCE WIC 3 N PHCE WIC 3 E PHCE BATH 3 E
17 1/2" = 1'-0" 16 1/2" = 1'-0" 15 1/2" = 1'-0" 14 1/2" = 1'-0" 13 1/2" = 1'-0" 12 1/2" = 1'-0"

CROWN CROWN CROWN CROWN

SHELF

ROD

3"
1'-7"
SHELF

3'-8"
ROD
10'-1"

10'-1"

10'-1"

10'-1"

3"
ISSUED FOR BID 05/18/2020

8'-6"
SHELF NO. DESCRIPTION DATE
WINDOW WINDOW WINDOW WINDOW
TYPE TYPE TYPE TYPE
VARIES VARIES VARIES VARIES ROD

3"
5'-9"
V.I.F. V.I.F. V.I.F. V.I.F.

3'-8"
2'-4" VIF

2'-4" VIF

2'-4" VIF

2'-4" VIF
OPEN OPEN BASE OPEN BASE

11" 4'-6" 3'-2 3/8" 3'-2 3/8" 5'-1" 4'-6" 1'-7" 11 1/4" 4'-6" 5'-0 1/4" 4'-6" 11 1/2" 2'-5 3/8" 3/4" 2'-5 3/8"
PTAC PTAC
11'-2" 10'-5 3/4" 4'-11 1/2"
PROJECT TITLE:
PHCE BEDROOM 4 W PHCE BEDROOM 3 S PHCE BEDROOM 2 S PHCE BEDROOM 2 W PHCE WIC 2 N PENTHOUSE UNITS
11 1/2" = 1'-0" 10 1/2" = 1'-0" 9 1/2" = 1'-0" 8 1/2" = 1'-0" 7 1/2" = 1'-0"
RENOVATIONS
FLOORS 26, 27, 28
LIBERTY VIEW
99 BATTERY PLACE
NEW YORK, NEW YORK 10280
6"

CL CL CL

SHELF SHELF SHELF SHELF


3"

ROD
7"
1'-7"

1'-7"

1'-7"
ADJ SHELF ADJ SHELF ADJ SHELF ADJ SHELF ADJ SHELF

SHELF SEMI SHELF SHELF SHELF


ADJ SHELF ADJ SHELF ADJ SHELF ADJ SHELF ADJ SHELF DOB SCAN STICKER
5'-3 3/4"

RECESSED 3'-8"
MEDICINE
ROD ROD ROD ROD DRAWING TITLE:

3'-8"
3"

3"
3'-0"

CABINET
ADJ SHELF ADJ SHELF ADJ SHELF ADJ SHELF ADJ SHELF
PHCE - ELEVATIONS
8'-6"

8'-6"

8'-6"

8'-6"

8'-6"

8'-6"
ADJ SHELF SHELF SHELF SHELF ADJ SHELF ADJ SHELF
7'-4"

7'-4"
7'-0"

10"
ROD
8"
5'-9"

5'-9"

5'-9"
ADJ SHELF ADJ SHELF ADJ SHELF

10"
2'-0"

4'-6"

ADJ SHELF ADJ SHELF ADJ SHELF


3'-8"
3'-6"

SCALE: AS NOTED PAGE: 25 of 30


2'-8 1/4"

2'-5"

10"
ADJ SHELF ADJ SHELF ADJ SHELF

A305.00

10"
1'-4"
4"

4"
2'-0" 3/4" 1'-11" 1'-11 1/4" 3/4" 2'-8" 3'-0" 3'-0" 3" 2'-9" 3'-8 1/8" 3/4" 3'-8 1/8" 2'-0" 3/4" 2'-10" 3/4" 2'-10" 3/4" 3/4" 2'-6 7/8" 2'-6 7/8" 3/4" 2'-6 1/2" 3/4" 2'-6 1/2" 3/4" 2'-0"
3/4"
6'-0 1/2" 5'-8" 6'-0" 7'-5" 7'-10 1/4" 12'-5 1/2"

PHCE WIC 2 E PHCE BATH 2 S PHCE BATH 2 N PHCE WIC 1 E PHCE WIC1 S PHCE WIC1 N
6 1/2" = 1'-0" 5 1/2" = 1'-0" 4 1/2" = 1'-0" 3 1/2" = 1'-0" 2 1/2" = 1'-0" 1 1/2" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
CROWN CROWN 335 MADISON AVENUE
NEW YORK, NY 10017
2'-3" 2'-3" 11" 11" 3'-3 1/2" (212) 308-7200

CROWN CROWN
CL CL

SEE SHEET A-401 FOR STAIR

7"
AND RAILING DETAILS

3'-3"

3'-3"
SEMI
RECESSED
MEDICINE

10'-1"

10'-1"

3'-0"
CABINET

2'-0"

8'-6"

8'-6"

8'-6"
1'-9"

1'-9"
WINDOW
TYPE CL CL
VARIES

8"
V.I.F.

8"

8"
3'-0 5/8"

2'-0"
2'-5"

3'-0"

3'-0"
NOT FOR CONSTRUCTION

2'-4" VIF

2'-9"

2'-0"

2'-0"
1'-4"
BASE OPEN BASE KICK KICK

4"

4"

4"
2'-8 1/4" 4'-6" 2'-6 5/8" 3'-5 3/8" 3'-0" 2'-3" 2'-3" 1'-0" 2'-3 1/2"
PTAC
6'-5 3/8" 4'-6" 3'-3 1/2"
9'-9"

PHH STAIR W1 PHH DINING E PHH POWDER S PHH BUTLER S PHH BUTLER W
13 1/2" = 1'-0" 12 1/2" = 1'-0" 11 1/2" = 1'-0" 10 1/2" = 1'-0" 8 1/2" = 1'-0"

CROWN CROWN CROWN

CROWN

11 7/8"
VENT
6'-0"
10'-1"

10'-1"

10'-1"

9'-0"
ISSUED FOR BID 05/18/2020
WINDOW
TYPE NO. DESCRIPTION DATE

7'-0 1/8"
WINDOW WINDOW VARIES
TYPE TYPE V.I.F.
VARIES VARIES REF'G
V.I.F. V.I.F.
8"

3'-0"

3'-0"
2'-4" VIF
2'-0"

WINE

KICK BASE OPEN BASE


4"

2'-1" 3'-11 5/8" 2'-1" 4'-6" 4'-6" 1'-0 3/4" 5'-0" 5'-0" 3'-1 1/2"
6'-0 1/2" PTAC
12'-1 3/4" 10'-0"
PROJECT TITLE:
PHH WINE BAR E PHH LIVING N PHH LIVING E PHH KITCHEN N PENTHOUSE UNITS
7 1/2" = 1'-0" 6 1/2" = 1'-0" 9 1/2" = 1'-0" 5 1/2" = 1'-0"
RENOVATIONS
FLOORS 26, 27, 28
LIBERTY VIEW
3'-1 1/2" 3'-0" 1'-9 1/2" 2'-0" 2'-6" 1'-0"
99 BATTERY PLACE
NEW YORK, NEW YORK 10280
CROWN CROWN CROWN

SHELF
1'-9"

1'-7"
3'-3"

3'-3"

SHELF
DOB SCAN STICKER

3"
MICRO ROD DRAWING TITLE:
3'-3"

PHH - ELEVATIONS
9'-0"

9'-0"

9'-0"

9'-0"
1'-9"

1'-9"

WINDOW
TYPE CL CL CL
VARIES

5'-9"
V.I.F.
8"

8"

8"
SCALE: AS NOTED PAGE: 26 of 30
3'-0"

3'-0"

3'-0"
2'-4" VIF

2'-0"

2'-0"
DISHWASHER RANGE

OPEN KICK KICK BASE A306.00


4"

4"
1'-6 3/8" 4'-6" 4'-6" 8" 1'-1 1/2" 2'-0" 4" 3'-0" 1'-9 1/2" 1'-1" 2'-6" 1'-0" 2'-1" 5 1/4" 3'-6 5/8" 3/4" 3'-6 5/8"
PTAC
11'-2 3/8" 8'-3" 4'-7" 2'-6 1/4" 7'-2"

PHH KITCHEN E PHH KITCHEN S PHH KITCHEN W PHH FOYER S


4 1/2" = 1'-0" 3 1/2" = 1'-0" 2 1/2" = 1'-0" 1 1/2" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
2'-4 5/8" 2'-4 5/8" 2'-4 5/8" 2'-1 3/4" 2'-1 3/4" 2'-1 3/4"
(212) 308-7200

CROWN CROWN CROWN

SHELF SHELF

ROD

3'-9"
1'-7"
ADJ SHELF

3'-3"
SHELF
ADJ SHELF

3'-8"
ROD
ADJ SHELF
9'-0"

9'-0"

8'-6"

8'-6"
1'-9"

1'-9"
SHELF ADJ SHELF

7'-4"
CL CL SEE SHEET A-401 FOR STAIR AND RAILING DETAILS
ROD
5'-9"

ADJ SHELF

8"

8"
ADJ SHELF

3'-8"

3'-0"

3'-0"

3'-0"
NOT FOR CONSTRUCTION

2'-0"

2'-0"
ADJ SHELF

WASHER DRYER

4"

4"
2'-4 5/8" 3/4" 2'-4 5/8" 2'-0" 3/4" 1'-5" 3/4" 4'-4" 2'-10" 2'-1 3/4" 2'-1 3/4" 2'-1 3/4"
4'-10" 3'-6 1/2" 7'-2" 6'-5 3/8"

PHH WIC 2 N PHH WIC 2 E PHH LAUNDRY S PHH LAUNDRY N PHH STAIR W2
15 1/2" = 1'-0" 14 1/2" = 1'-0" 13 1/2" = 1'-0" 12 1/2" = 1'-0" 11 1/2" = 1'-0"

CROWN CROWN

CL CL CL CL CL CL CL CL CL

7"
7"

7"

SEMI SEMI 4" 7" SEMI


RECESSED RECESSED RECESSED
MEDICINE MEDICINE MEDICINE

3'-0"
3'-0"

3'-0"

CABINET CABINET CABINET

9'-0"

9'-0"
2'-0" 2'-0" 2'-0" ISSUED FOR BID 05/18/2020
8'-6"

8'-6"
NO. DESCRIPTION DATE
WINDOW WINDOW
7'-0"
7'-0"

7'-0"
TYPE TYPE
VARIES VARIES

8"
8"

8"

V.I.F. V.I.F.

2'-0"
2'-0"

2'-0"

4'-6"

4'-6"
4'-6"
3'-6"

3'-6"

3'-6"
6"

2'-5"

2'-5"

2'-5"
2'-4" VIF

2'-4" VIF
2'-9"

2'-9"

2'-9"
1'-4"

1'-4"

1'-4"
OPEN OPEN BASE
4"

4"

4"
2'-6" 3'-0" 3'-0" 3'-0" 2'-11" 3" 2'-9" 3'-6 1/4" 4'-6" 2'-6 3/4" 2'-5 5/8" 2'-5 5/8" 4'-6" 11" 3'-0" 3'-2" 3" 2'-9"
8'-6" 8'-11" 10'-7" 10'-4 1/4" 9'-2"
PROJECT TITLE:
PHH BATH 3 S PHH BATH 2 S PHH BEDROOM 3 E PHH BEDROOM 2 E PHH BATH 4 S PENTHOUSE UNITS
10 1/2" = 1'-0" 9 1/2" = 1'-0" 8 1/2" = 1'-0" 7 1/2" = 1'-0" 6 1/2" = 1'-0"
RENOVATIONS
FLOORS 26, 27, 28
LIBERTY VIEW
CROWN CROWN 99 BATTERY PLACE
NEW YORK, NEW YORK 10280

SHELF SHELF SHELF

ROD
3"
1'-7"

1'-7"

ADJ SHELF ADJ SHELF

SHELF SHELF
ADJ SHELF ADJ SHELF DOB SCAN STICKER
3'-8"

5'-6"
ROD ROD DRAWING TITLE:
10'-1"

10'-1"
3"
3"

ADJ SHELF ADJ SHELF


PHH - ELEVATIONS
8'-6"

8'-6"

8'-6"

SHELF ADJ SHELF ADJ SHELF


7'-4"

7'-4"

7'-4"

WINDOW
TYPE
ROD VARIES
5'-9"

5'-9"

ADJ SHELF ADJ SHELF V.I.F.

6"
ADJ SHELF ADJ SHELF
3'-8"

SCALE: AS NOTED PAGE: 27 of 30

10"
2'-4" VIF

2'-6"
ADJ SHELF ADJ SHELF

A307.00

10"
OPEN BASE KICK BASE

4"
2'-7 1/2" 3/4" 2'-7 1/2" 3/4" 2'-6 1/2" 3/4" 2'-0" 2'-0" 3/4" 4'-0 1/2" 3/4" 1'-11 1/4" 3/4" 2'-11" 4'-6" 11" 1'-5" 1'-9 1/4" 1'-9 1/4" 1'-5"
5'-3 5/8" 4'-8" 8'-2" 8'-4" 6'-4 3/8"

PHH WIC 4 E PHH WIC 4 N PHH WIC 4 S PHH BEDROOM 4 E PHH BEDROOM 4 W
5 1/2" = 1'-0" 4 1/2" = 1'-0" 3 1/2" = 1'-0" 2 1/2" = 1'-0" 1 1/2" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200

SHELF SHELF

1'-7"
ADJ SHELF ADJ SHELF ADJ SHELF

SHELF
ADJ SHELF ADJ SHELF ADJ SHELF

3'-8"
ROD
ADJ SHELF ADJ SHELF ADJ SHELF

8'-6"

8'-6"
ADJ SHELF SHELF

7'-4"

10"
5'-9"
ADJ SHELF

10"
ADJ SHELF

10"
NOT FOR CONSTRUCTION
ADJ SHELF

10"
4"
2'-0" 3/4" 2'-6 1/2" 3/4" 2'-6 1/2" 3/4" 3/4" 2'-6 7/8" 2'-6 7/8" 3/4" 2'-0"
7'-3 1/8"

PHH WIC 1 N PHH WIC 1 S


10 1/2" = 1'-0"
9 1/2" = 1'-0"

CL CL CROWN
CL
SHELF

EQ
ROD
3"

1'-7"

MED. MED. MED.


CAB. CAB. CAB.
SHELF

6'-3"
7" 4"
3'-8"

5'-0"
ROD
3"

9'-0"

9'-0"

9'-0"
MIRROR MIRROR ISSUED FOR BID 05/18/2020
8'-6"

8'-6"
EQ
SHELF NO. DESCRIPTION DATE
WINDOW
7'-0"

TYPE MED. MED. MED.


ROD VARIES
5'-9"

CAB. CAB. CAB.


V.I.F.

8"
4'-6"

9"
6"
3'-8"

3'-6"

UC

10"

10"

3'-0"
2'-4" VIF

2'-9"

2'-0"
REF'G
2'-6"

10"

10"
OPEN KICK

4"

4"

4"
3'-4 7/8" 3/4" 3'-4 7/8" 2'-9" 3" 4" 2'-3 7/8" 1'-2 1/4" 4'-6" 5 1/8" 1'-1" 2'-6" 1'-1" 2'-6" 1'-1" 2'-0 1/2" 2'-2"
6'-10 3/8" 8'-9 1/4" 8'-3" 4'-2 1/2"
PROJECT TITLE:
PHH WIC 1 W PHH MBATH E2 PHH MBATH E PHH MBATH S PHH MBEDROOM BAR E PENTHOUSE UNITS
8 1/2" = 1'-0" 7 1/2" = 1'-0" 6 1/2" = 1'-0" 5 1/2" = 1'-0" 4 1/2" = 1'-0"
RENOVATIONS
FLOORS 26, 27, 28
LIBERTY VIEW
99 BATTERY PLACE
NEW YORK, NEW YORK 10280
CROWN CROWN
CROWN CROWN

DOB SCAN STICKER


5'-6"

DRAWING TITLE:
PHH - ELEVATIONS
9'-0"

9'-0"
8'-6"

WINDOW WINDOW
TYPE TYPE
VARIES VARIES
V.I.F. V.I.F.
6"

SCALE: AS NOTED PAGE: 28 of 30


10"

2'-4" VIF

2'-4" VIF
2'-6"

A308.00
10"

OPEN BASE OPEN BASE


4"

1'-10 1/4" 2'-0" 2'-0" 1'-10 1/4" 2'-8 3/4" 2'-8 3/4" 4'-6" 3'-0 1/2" 3'-0 1/2" 3'-2 1/4" 3'-2 1/4" 5'-4"
PTAC PTAC
7'-8 1/2" 6'-4 1/2"
16'-0 1/2"

PHH MBEDROOM W PHH MBEDROOM E PHH MBEDROOM N


3 1/2" = 1'-0" 2 1/2" = 1'-0" 1 1/2" = 1'-0"

SEAL
MILLWORK NOTES
BATTERY PLACE
1. CONTRACTOR SHALL SUBMIT ALL REQUIRED SHOP DRAWINGS TO ARCHITECT FOR REVIEW. SAMPLES OF MILLWORK AND FINISHES SHALL BE
SUBMITTED TO ARCHITECT FOR REVIEW. THE ARCHITECT SHALL REVIEW AND APPROVE ALL FINISHES, INCLUDING WOOD VENEER CUT AND ASSOCIATES, LLC
GRAINING. WITHOUT APPROVAL GENERAL CONTRACTOR AND MILLWORK CONTRACTOR ACCEPT FULL RESPONSIBILITY AND MILLWORK IS
SUBJECT FOR REMOVAL & REPLACEMENT. C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
2. KITCHEN, LIVING AND BEDROOM AREAS SHAKER STYLE DOORS & DRAWERS: ALL DOORS, DRAWERS AND EXPOSED SURFACES SHALL RECEIVE NEW YORK, NY 10017
SHOP SPRAYED LACQUER PAINTED FINISH ON 3/4" MOISTURE RESISTANT MDF CENTER PANELS/FLAT FRONT AREAS AND HARDWOOD FRAME
BORDERS. ALL INTERIOR SURFACES SHALL HAVE WHITE LAMINATE FINISH ON PLYWOOD, TYP. (212) 308-7200

3. BATHROOM SHAKER STYLE DOORS & DRAWERS: ALL DOORS AND EXPOSED SURFACES SHALL RECEIVE SHOP SPRAYED LACQUER PAINTED
FINISH ON 3/4" M.R. MDF CENTER PANELS/FLAT FRONT AREAS AND HARDWOOD FRAME BORDERS. ALL INTERIOR SURFACES SHALL HAVE WHITE
LAMINATE FIN ON M.R. MDF, TYP.

4. ALL NEW MEDICINE CABINETS SHALL BE RECESSED AND CUSTOM BUILT MATCHING BUILDING STANDARD AND MODEL APARTMENTS. PROVIDE
AND INSTALL CONTINUOUS BLOCKING/REINFORCING ON ALL SIDES OF CABINETRY OPENING. COORDINATE WITH WALL TILING FOR CLEAN AND
UNIFORM JOINTING AT CABINETRY. IN THE EVENT MEDICINE CABINET CANNOT BE FULLY RECESSED DUE TO FIELD CONDITIONS, PROVIDE AND
INSTALL MATCHING FINISHED CABINETRY TRIM ON ALL EXPOSED SIDES AND NOTIFY ARCHITECT FOR REVIEW AND APPROVAL PRIOR TO
FABRICATION.

5. PERIMETER WINDOW CABINETRY AND OTHER MISCELLANEOUS BUILT-IN CABINETRY THROUGHOUT SHALL MATCH KITCHEN CABINETRY
CONSTRUCTION. CONFIRM WITH BUILDING MANAGEMENT FINISH AND STYLE OF EXTERIOR DOORS, DRAWERS AND SURFACES.

6. ALL MILLWORK SHALL BE SHOP FINISHED AND STAINED PRIOR TO INSTALLATION, UNLESS CONTRACTOR HAS WRITTEN APPROVAL FROM
OWNER AND ARCHITECT.

EXISTING WINDOW 7. ALL SHELVES SHALL BE 3/4" THICK, BIRCH VENEER PLYWOOD WITH CLEAR LACQUER FINISH, UNLESS OTHERWISE NOTED ON PLANS.
SUBFRAME, TYP (PTAC 2'-0"
CABINET IN PHB) 8. ALL BLOCKING REQUIRED SHALL BE SCRIBED TO WALL OR CEILING. CONTRACTOR TO COORDINATE WORK WITH OTHER TRADES INVOLVED.
1'-8" 4"
9. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS IN FIELD PRIOR TO FABRICATION OF CABINETS/MILLWORK.

10. ALL JOINTS SHALL BE SECURED IN A MANNER TO ENSURE AGAINST JOINT OPENINGS.
3/4" PLYWOOD
CABINET FRAME 11. ALL BLOCKING FOR CABINET WORK OR ASSEMBLIES SHALL BE FIRE-RETARDANT AS REQUIRED BY CODE.
CONSTRUCTION, TYP
12. ALL VISIBLE WOOD CORNER JOINTS SHALL BE MITERED.
CUSHIONS BY

1'-1"
OWNER 13. THE GENERAL CONTRACTOR SHALL PROVIDE WALL BLOCKING INSIDE PARTITIONS FOR ALL WALL HUNG CABINETS, COUNTERS, SHELVES, ETC.,
FOR PROPER SUPPORT.
3/4" M.R. MDF
EXTERIOR, TYP

1 1/2"
2"
DRAWER WITH
HEAVY DUTY

4 1/8"
SLIDES WITH SOFT
CLOSE FUNCTION

1'-3"
AND ROUTED FINISH CEILING

3 7/8" 1" 2"


EDGE PULL

FINISH FLOOR

1/4"

1/2"
BLOCKING AS ADJUSTABLE
REQUIRED LEVELING FEET. TYP. FINISH REVEAL, TYP.

3/4" PLYWOOD CABINET


TYP. BENCH SECTION CONSTRUCTION THROUGHOUT, TYP.
6 1 1/2" = 1'-0"

ADJUSTABLE SHELF, TYP.


1 1/8" 3 3/4"

1/2"

3'-3 1/2"
ISSUED FOR BID 05/18/2020
NO. DESCRIPTION DATE
SHAKER STYLE DOORS & DRAWERS NOTE:
ALL DOORS, DRAWERS AND EXPOSED
1/2" PLYWOOD FRAME CONSTRUCTION WITH
SURFACES SHALL RECEIVE SHOP SPRAYED
MOISTURE RESISTENT MDF BORDER AT
LACQUER PAINTED FINISH ON 3/4" MOISTURE
EXPOSED FRAME LAPPING TILE, TYP.
RESISTANT MDF CENTER PANELS/FLAT FRONT
AREAS AND HARDWOOD FRAME BORDERS.
MIRROR ADHERED ON CABINET ALL INTERIOR SURFACES SHALL HAVE WHITE
DOOR, TYP. LAMINATE FINISH ON PLYWOOD, TYP.

ADJUSTABLE GLASS
SHELF, TYP. SCHEDULED
HARDWARE, TYP.

3'-0"

1 1/2"
STONE WATERFALL COUNTER 1'-1" UON
WITH EASED EDGES AND
FINISHED UNDERSIDE, TYP. CABINETRY APRON PROJECT TITLE:
AND UNDERCABINET
8"X8" STEEL ANGLE SUPPORT, LIGHT, TYP. PENTHOUSE UNITS
PAINT EXPOSED AREAS TO
RENOVATIONS

1'-9"
MATCH STONE, TYP. TILE BACKSPLASH,
TYP.
LOW PARTITION WITH FLOORS 26, 27, 28
BLOCKING AS REQUIRED
STONE COUNTER WITH
EASED EDGE, TYP.
LIBERTY VIEW
2'-11" 2'-1" UON
99 BATTERY PLACE

1/2"
STONE COUNTER WITH
NEW YORK, NEW YORK 10280

1 1/4"
1'-10" UON
EXISTING WINDOW EXISTING WINDOW EASED EDGE, TYP.

8"
SUBFRAME, TYP SUBFRAME, TYP

1 1/4"
1/2" SCHEDULED
. 1/2"
ANOD. ALUM. BAR 3/4" PLYWOOD
3/4"

SEE PLAN SEE PLAN HARDWARE, TYP.

6 3/4"

6 3/4"
GRILLE WITH SLEEVE CABINET FRAME 10"
COVERING MDF & CONSTRUCTION, TYP 1/2"
1 1/2"

1 1/2"

PLYWOOD, TYP .ALL DRAWERS SHALL


SCHEDULED
HARDWARE, TYP. HAVE HEAVY DUTY
3/4" M.R. MDF 3/4" M.R. MDF SLIDES WITH SOFT
EXTERIOR, TYP EXTERIOR, TYP CLOSE FUNCTION
1/4"

1/4"
2"

2"

DOB SCAN STICKER


VIF W/ UNDERSIDE OF WINDOW SUBFRAME

VIF W/ UNDERSIDE OF WINDOW SUBFRAME

COORDINATE
CLAMPING SUPPORTS
1/2"

1/2"

FOR UNDERMOUNT DRAWING TITLE:


EXIST. PTAC
3/4" PLYWOOD UNIT TO BE ADJUSTABLE
SINK TYP.
DETAILS

3'-0"

3'-0"
CABINET FRAME REPLACED SHELF, TYP
WITH NEW BLD
2'-9"

CONSTRUCTION,
DOOR

DOOR

2'-0"

2'-0"
TYP STANDARD, IN
EXISTING
2'-4"

2'-4"

3/4" MOISTURE 3/4"


. PLYWOOD CABINET
SLEEV WITH RESISTANT MDF CONSTRUCTION
TOUCHLATCH NEW COILS, TOUCHLATCH
HARDWARE & HARDWARE & CABINET FRAME, THROUGHOUT, TYP.
MOTORIZED DOORS & EXPOSED
CONCEALED HEAVY CONCEALED HEAVY
1/2"

1/2"

VALVE & WALL PANELS, TYP.


DUTY HINGES T STAT, TYP DUTY HINGES
SCALE: AS NOTED PAGE: 29 of 30
BLOCKING AS .BLOCKING AS
1/4"

1/4"
3 7/8" 1" 2"

3 7/8" 1" 2"

REQUIRED REQUIRED

FINISH FLOOR FINISH FLOOR FINISH FLOOR .FINISH FLOOR


A400.00
1/4"

1/4"

4" 4" 4 1/2"


4"

4"

4"
OPEN FOR AIR BLOCKING AS
FLOW. SUPPORT REQUIRED
BEYOND, TYP.

TYP. PTAC CABINET SECTION TYP. WINDOW CABINET SECTION TYP. BATH CABINET SECTION TYP. KITCHEN BAR CABINET SECTION TYP. KITCHEN CABINET SECTION
5 1 1/2" = 1'-0" 4 1 1/2" = 1'-0" 3 1 1/2" = 1'-0" 2 1 1/2" = 1'-0" 1 1 1/2" = 1'-0"

SEAL
BATTERY PLACE
ASSOCIATES, LLC
C/O MILSTEIN PROPERTIES
335 MADISON AVENUE
NEW YORK, NY 10017
(212) 308-7200

NOT FOR CONSTRUCTION

10'-6 1/4"
SLAB OPENING TO BE VERIFIED PER STAIR CLEARANCES

5/8” HILTI POST INSTALLED ANCHORS. ALLOW 1”


MIN. EDGE DISTANCE FROM STRINGER DIMS.,
AND 3” WHERE ANCHORS ARE PLACED AND

1'-1"
CENTERED. MANUFACTURER’S ENGINEER TO
10" DETAIL CONNECTIONS & SUMBIT FOR REVIEW
EQ EQ EQ TREAD

1'-5 1/8"

ALIGN
MANUFACTURE'S ENGINEER TO

10'-9" FLOOR TO FLOOR VIF


INCLUDE WELDED TABS FOR FINISH
TREAT & RISER ATTACHMENT

7'-1 1/4"
FACE SKIRT

ISSUED FOR BID 05/18/2020


NO. DESCRIPTION DATE

1"
EXISTING R
OPENING 0'
ALUMINUM - 0
WINDOW TRIM TO 1/ STEEL STRINGERS: (2)
2"
MC 12 X 10.6

RISER VIF
MATCH EXISTING SEALANT AND 3/4"
1" SQ. RAILING POST

7 5/8"
BACKER ROD
3/4" 10"
BASE FLUSH WITH BASE SKIRT
WINDOW AS
SCHEDULED FIN.
FLR. FINISH FLOOR 5/8" STEEL PLATES WELDED TO THE STRINGER

7 5/8"
ENDS, AND BOLTED TO THE SLAB AT BOTTOM
AND EDGE & UNDERSIDE OF OPENING AT TOP

13'-4"
PROJECT TITLE:
PHB WINDOW HEAD DETAIL RAILING DETAIL STAIR DETAIL PHH STAIR SECTION
8 3" = 1'-0" 7 3" = 1'-0" 6 3" = 1'-0"
5 1/2" = 1'-0"
PENTHOUSE UNITS
RENOVATIONS
3'-4" VIF
FLOORS 26, 27, 28
3'-4" VIF
DOOR AS LIBERTY VIEW
SCHEDULED 99 BATTERY PLACE
WINDOW AS
DOOR SILL SHIMMED & NEW YORK, NEW YORK 10280
1" THICK WOOD TREAD & ANCHORED TO FILL BLOCKS
SCHEDULED RISER SET IN ADHESIVE &
FASTENED TO CONCRETE
SILICON CAULK
ALUMINUM WITH CONCEALED SS
WOOD SILL FRAME SCREWS
PAINTED TO MATCH CONCRETE STEP TO
EXIST. MATCH EXISTING
SILICON CAULK INFILL WALL BRICK VENEER
LIQUID FLASHING COMPATIBLE WITH TO MATCH EXISTING.
ALUMINUM WINDOW
EXISTING ROOFING SYSTEM TOOTH IN BRICK INTO
SILL WITH ANCHORS NEW ALUMINUM RELOCATED
WINDOW TO EXISTING VENEER ALUMINUM DOOR

7'-8" VIF
TERRACE DECK DOB SCAN STICKER
MATCH EXISTING. REFINISHED TO
5/8" GWB ON 1 5/8" SET IN EXISTING MATCH EXISTING. DRAWING TITLE:
EQ

STUDS

9'-4" VIF
FLASHING 5/8" GWB ON 1 5/8" OPENING SET IN EXISTING

VAPOR BARRIER
STUDS OPENING
DETAILS
INSULATION
BRICK TO
MATHC
INSULATION EXISTING

4" CMU
EQ

SCALE: AS NOTED PAGE: 30 of 30


FIN. SOLID CMU FILL INFILL WALL BRICK VENEER
FLR. BLOCKS TO MATCH EXISTING.

A401.00
TOOTH IN BRICK INTO
EXISTING VENEER

5/8" 3 3/8" 3 5/8" 2 3/4" 3 5/8" 1/2" NOSING

1'-2" VIF 10"

PHB WINDOW SILL DETAIL PHB DOOR SILL DETAIL PHB NEW WINDOW ELEVATION PHB RELOCATED DOOR ELEVATION
4 3" = 1'-0" 3 3" = 1'-0" 2 1/2" = 1'-0" 1 1/2" = 1'-0"

SEAL