You are on page 1of 6

Bulletin No.

AEQM/96

AEQM Spring-Flex
Seismic Isolators
Deflections to 2"

Typical Applications: Air Handling Units • Fans


Pumps • Chillers • Cooling Towers
VMC AEQM & AEQM–R Spring Flex Seismic Isolators
VMC Series “AEQM” Spring Flex Seismic Pre-Approval Number R-0189.
Isolators are designed for restrained and seismic VMC has designed two versions of the AEQM for
applications through zone 4. These mountings are use in different applications. When attaching the
capable of withstanding a minimum of 1.0 g accel- baseplate to structural steel, the standard version
erated force in all directions, and provide static can be utilized to obtain adequate restraint capaci-
deflections up to 2 inches and loads to 2500 lbs. ty. However, when attaching to concrete or when
When properly installed and adjusted, the AEQM increased strength in steel attachments are
series will restrain mechanical equipment during a required, the AEQM-R has been designed with a
seismic event. This is accomplished through their larger baseplate to allow for proper anchor bolt
inherent restrained design and internal upward spacing. All ratings are based on destructive testing
rebound plate which limits motion to 1/4” in all and analyses which have been approved by
directions. AEQM isolators are approved by the OSHPD in the State of California, and are certified
State of California Office of State-wide Health by a licensed Professional Engineer registered in
Planning and Development Anchorage the State of California.

1/4" Operating Clearance 'J' Dia.High Strength


Cap Screw
(SAE Grade 8 – with standard washer)
'H' Dia.
'G' Adjustment
Free & Bolt
Operating Down Stopwasher
Spring Height
Neoprene Grommet
Inspection/
Adjustment Adjustable Upward
Port Rebound Plate
Neoprene Acoustical Cup
Steel
Base Plate Interchangeable
Steel Spring
Ductile Iron Housing

'E' Dia. Hole,


4 Plcs.

'B'

'A'
'D'
'C'

'F' Thickness
AEQM Mount - Loads, Ratings, Dimensions

Rated Rated Horizontal


Model # Color Code Seismic Dimensions, inches
Capacity (lbs.) Deflection (in.)
‘G’ Rating* A B C D E F G H J
AEQM-11 BLUE 60 1.3 14.1 6 5 4 2¹⁄₂ ¹⁄₂ ¹⁄₄ 5³⁄₄ ⁵⁄₈ ³⁄₈
AEQM-12 ORANGE 100 1.3 8.5 6 5 4 2¹⁄₂ ¹⁄₂ ¹⁄₄ 5³⁄₄ ⁵⁄₈ ³⁄₈
AEQM-13 BROWN 165 1.2 5.1 6 5 4 2¹⁄₂ ¹⁄₂ ¹⁄₄ 5³⁄₄ ⁵⁄₈ ³⁄₈
AEQM-14 BLACK 260 1.0 3.2 6 5 4 2¹⁄₂ ¹⁄₂ ¹⁄₄ 5³⁄₄ ⁵⁄₈ ³⁄₈
AEQM-16 YELLOW 370 0.8 2.3 6 5 4 2¹⁄₂ ¹⁄₂ ¹⁄₄ 5³⁄₄ ⁵⁄₈ ³⁄₈
AEQM-92 BROWN 125 1.3 16 7 5¹⁄₂ 4¹⁄₂ 2¹⁄₂ ⁵⁄₈ ¹⁄₄ 7¹⁄₄ ⁵⁄₈ ³⁄₈
AEQM-93 ORANGE 225 1.3 8.9 7 5¹⁄₂ 4¹⁄₂ 2¹⁄₂ ⁵⁄₈ ¹⁄₄ 7¹⁄₄ ⁵⁄₈ ³⁄₈
AEQM-94 GREEN 325 1.2 6.1 7 5¹⁄₂ 4¹⁄₂ 2¹⁄₂ ⁵⁄₈ ¹⁄₄ 7¹⁄₄ ⁵⁄₈ ³⁄₈
AEQM-95 RED 450 1.2 4.4 7 5¹⁄₂ 4¹⁄₂ 2¹⁄₂ ⁵⁄₈ ¹⁄₄ 7¹⁄₄ ⁵⁄₈ ³⁄₈
AEQM-96 BLACK 600 1.2 3.3 7 5¹⁄₂ 4¹⁄₂ 2¹⁄₂ ⁵⁄₈ ¹⁄₄ 7¹⁄₄ ⁵⁄₈ ³⁄₈
AEQM-97 WHITE 750 1.1 2.6 7 5¹⁄₂ 4¹⁄₂ 2¹⁄₂ ⁵⁄₈ ¹⁄₄ 7¹⁄₄ ⁵⁄₈ ³⁄₈
AEQM-98 GRAY 900 1.0 2.2 7 5¹⁄₂ 4¹⁄₂ 2¹⁄₂ ⁵⁄₈ ¹⁄₄ 7¹⁄₄ ⁵⁄₈ ³⁄₈
AEQM-99 BLUE 1100 1.0 1.8 7 5¹⁄₂ 4¹⁄₂ 2¹⁄₂ ⁵⁄₈ ¹⁄₄ 7¹⁄₄ ⁵⁄₈ ³⁄₈
AEQM-200 BLUE 125 1.3 32 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-400 BLACK 400 1.3 10 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-600 RED 600 1.1 6.6 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-1000 GREEN 1060 1.1 3.7 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-1300 YELLOW 1300 1.0 3 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-1600 GRAY 1600 1.0 2.5 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-1625 GRAY/RED 1970 1.0 2 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-1628 GRAY/GREEN 2500 1.0 1.6 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-100 BROWN 100 1.5 30 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-101 ORANGE 200 1.5 15 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-102 GREEN 400 1.5 7.5 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-103 RED 600 1.5 5 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-104 BLACK 800 1.5 3.7 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-105 WHITE 1000 1.5 3 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-106 GRAY 1250 1.5 2.4 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-107 BLUE 1500 1.5 2 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-108 YELLOW 1750 1.5 1.7 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-109 PINK 2000 1.5 1.5 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-81 BLUE 20 2.0 100 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-82 ORANGE 26 2.0 77 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-83 PURPLE 36 2.0 55 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-84 YELLOW 52 2.0 38 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-85 GRAY 65 2.0 30 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-86 RED 84 2.0 23 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-87 GREEN 114 2.0 17 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 8³⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-401 BLUE 110 2.0 27 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-402 YELLOW 140 2.0 21 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-403 BLACK 180 2.0 16.6 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-404 PURPLE 240 2.0 12.5 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-405 BROWN 330 2.0 9 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-406 RED 460 2.0 6.5 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-407 RED/BLACK 660 2.0 4.5 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-408 RED/GREEN 960 2.0 3.1 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-409 RED/GRAY 1174 2.0 2.5 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-411 ORANGE/GRAY 1400 2.0 2.1 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-412 Orange/Gray/Orange 1550 2.0 1.9 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-413 Orange/Gray/Brown 1680 2.0 1.8 8¹⁄₂ 6¹⁄₂ 6 4¹⁄₂ ³⁄₄ ³⁄₈ 9⁵⁄₈ ⁷⁄₈ ¹⁄₂

*Seismic rating is for quick reference only and is based on attachment to steel structure. Use OSHPD rated curves for actual seismic rating . For concrete attachment refer to AEQM–R Series.
OSHPD Pre-Approval applies to 1” and 1¹⁄₂” deflection mountings only.

VMC Engineering Specification— How to specify:


Steel spring isolator incorporating elastomeric snubbing in all directions. The snubber shall be adjustable in the vertical direction and allow a maxi-
mum of 1/4 inch travel in all directions before contacting the elastomer cushion.
Spring diameters shall be no less than 0.8 times the compressed height of the spring at rated load. Springs shall also have a minimum additional
travel to solid equal to 50% of the rated deflection. Housing shall have provision to adjust the rebound plate and to inspect the spring. Housing
shall be of cast ductile iron, malleable cast iron or welded steel construction. Gray iron castings are not permitted.
Springs shall be color coded for proper identification of rated load capacity. Springs shall be coated with a polyester epoxy powder. Hardware shall
be stainless steel, or zinc plated.
Mounting shall be Series AEQM as manufactured by Vibration Mountings & Controls. Inc.

INSTALLATION INSTRUCTIONS FOR VMC SERIES “AEQM” ISOLATORS


1. Isolators are shipped fully assembled and are to be spaced and located in accordance with installation drawings or as otherwise recommended.
Locate spring port facing outward from equipment or base so that spring is visible.
2. To facilitate installation prior to installing, VMC recommends turning the adjusting bolt so that the “Operating Clearance” is approximately 1” to
11⁄2” for 1” deflection units, 11⁄2” to 2” for 11⁄2” deflection units, and 2” to 2¹⁄₂” for 2” deflection units.
AEQM–R Mount - Loads, Ratings, Dimensions

Horizontal
Model # Color Code Rated Rated Seismic Dimensions, Inches
Capacity (lbs.) Deflection (in.) 'G' Rating*
A B C D E F G H J
AEQM-R-11 BLUE 60 1.3 18 8 6 6 4 ⁹⁄₁₆ ³⁄₈ 6 ⁵⁄₈ ³⁄₈
AEQM-R-12 ORANGE 100 1.3 10.8 8 6 6 4 ⁹⁄₁₆ ³⁄₈ 6 ⁵⁄₈ ³⁄₈
AEQM-R-13 BROWN 165 1.2 6.5 8 6 6 4 ⁹⁄₁₆ ³⁄₈ 6 ⁵⁄₈ ³⁄₈
AEQM-R-14 BLACK 260 1.0 4.1 8 6 6 4 ⁹⁄₁₆ ³⁄₈ 6 ⁵⁄₈ ³⁄₈
AEQM-R-16 YELLOW 370 0.8 2.9 8 6 6 4 ⁹⁄₁₆ ³⁄₈ 6 ⁵⁄₈ ³⁄₈
AEQM-R-92 BROWN 125 1.3 12 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-93 ORANGE 225 1.3 6.6 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-94 GREEN 325 1.2 4.6 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-95 RED 450 1.2 3.3 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-96 BLACK 600 1.2 2.5 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-97 WHITE 750 1.1 2.0 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-98 GRAY 900 1.0 1.6 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-99 BLUE 1100 1.0 1.3 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-200 BLUE 125 1.3 24 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-400 BLACK 400 1.3 7.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-600 RED 600 1.1 5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-1000 GREEN 1060 1.1 2.8 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-1300 YELLOW 1300 1.0 2.3 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-1600 GRAY 1600 1.0 1.8 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-1625 GRAY/RED 1970 1.0 1.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-1628 GRAY/GREEN 2500 1.0 1.2 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-100 BROWN 100 1.5 27 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-101 ORANGE 200 1.5 13.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-102 GREEN 400 1.5 6.7 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-103 RED 600 1.5 4.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-104 BLACK 800 1.5 3.3 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-105 WHITE 1000 1.5 2.7 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-106 GRAY 1250 1.5 2.1 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-107 BLUE 1500 1.5 1.8 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-108 YELLOW 1750 1.5 1.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-109 PINK 2000 1.5 1.3 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-81 BLUE 20 2.0 75 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-82 ORANGE 26 2.0 57 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-83 PURPLE 36 2.0 41 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-84 YELLOW 52 2.0 28.8 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-85 GRAY 65 2.0 23 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-86 RED 84 2.0 17.8 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-87 GREEN 114 2.0 13.1 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-401 BLUE 110 2.0 24.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-402 YELLOW 140 2.0 19.2 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-403 BLACK 180 2.0 15 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-404 PURPLE 240 2.0 11.2 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-405 BROWN 330 2.0 8.1 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-406 RED 460 2.0 5.8 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-407 RED/BLACK 660 2.0 4 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-408 RED/GREEN 960 2.0 2.8 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-409 RED/GRAY 1174 2.0 2.3 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-411 ORANGE/GRAY 1400 2.0 1.9 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-412 Orange/Gray/Orange 1550 2.0 1.7 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-413 Orange/Gray/Brown 1680 2.0 1.6 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂

*Seismic rating is for quick reference only and is based on attachment to concrete. Use OSHPD rated curves for actual seismic rating. OSHPD Pre-Approval applies to 1" and 1¹⁄₂" deflection mountings only.

3. Locate isolators on floor or sub-base as required, insuring that the isolator centerline matches the equipment or equipment base mounting holes.
Shim and/or grout as required to level all isolator base plates. A 1⁄4" maximum difference in elevation can be tolerated.
4. Anchor all isolators to floor or sub-base as required. For installing on concrete , see “Concrete Rating Information”.
5. Remove cap screw and save. Gently place machine or machine base on top on bolt. Install cap screw but DO NOT tighten.
6. The weight of the machine will cause the spring and thus the adjustment bolt to descend.
7. Adjust all isolators by turning adjustment bolt so that the operating clearance is approximately 1⁄4". NOTE: It may be necessary to adjust rebound
plate for clearance.
8. Check equipment level and fine adjust isolators to level equipment.
9. Adjust rebound plate so that the operating clearance is no more than 1⁄4".
10. Tighten cap screw. Adjustment is complete.
AEQM / AEQM–R OSHPD Rated Load Curves
7000
AEQM OSHPD RATED LOADS
Horizontal and Vertical Ratings are approved by California
OSHPD and have OSHPD Anchorage Pre-Approval "R" Number R-0189,
6000 and are based on properly sized bolts per ASTM A307 attached to support
structure. Testing and analyses have been performed in accordance with
OSHPD approved procedures.

Vertical Loads, lbs. (Compression or Tension)


To use OSHPD rated load curves:
5000
AEQM 1. Calculate vertical and horizontal load forces acting on mountings,
including translations and overturning moments.
2. The intersection of the horizontal load and vertical load
Graph not for use on must fall within the OSHPD curve for the specified
concrete decks or 4000 part and method of attachment.
slabs. For attachment 3500
to concrete use AEQM-R
3000
2800

200–1628

2000

11–16
92–99 100–109
1000

850 2800 3500


1000 2000 3000 4000 5000 6000 7000
Horizontal Loads (Pounds)

8000
AEQM OSHPD RATED LOADS
Horizontal and Vertical Ratings are approved by California OSHPD and
have OSHPD Anchorage Pre-Approval "R" Number R-0189, and are
7000 based on properly sized bolts per ASTM A307 attached to support
structure. Testing and analyses have been performed in
accordance with OSHPD approved procedures.
To use OSHPD rated load curves:
Vertical Loads, lbs. (Compression or Tension)

6000 1. Calculate vertical and horizontal load forces acting


AEQM–R on mountings including translations and
5500 overturning moments.
Graph for use when 2. The intersection of the horizontal load
attaching to steel 5000 and vertical load must fall within the
OSHPD curve for the specified
200-1628 part and method of attachment.
4300
4000

3500

3000 100 Series


11–16
92–99
2300
2000

1000

2300 2800 3500 4300 5100


1000 2000 3000 4000 5000 6000 7000
Horizontal Loads (Pounds)
AEQM–R OSHPD Rated Load Curves
8000
AEQM-"R" OSHPD RATED LOADS
Horizontal and Vertical Ratings are approved by California
OSHPD and have OSHPD Anchorage Pre-Approval "R" Number
7000 R-0189, and are based on properly sized anchor bolts.
Testing and analyses have been performed in accordance with
AEQM–R OSHPD approved procedures.

Vertical Loads, lbs. (Compression or Tension)


To use OSHPD rated load curves:
6000 1. Calculate vertical and horizontal load forces acting on mountings,
Graph for use when
including translations and overturning moments.
mount is anchored to 2. The intersection of the horizontal load and vertical load must fall
concrete within the OSHPD curve for the specified part and method of
5000 attachment.

4000

3500

3000
200-1628

100 Series
2000
11–16

92–99
1000

1080 1500 2700


1000 2000 3000 4000 5000 6000 7000
Horizontal Loads (Pounds)

Concrete Rating Information


Model Number Anchor Bolt (note 2) Embedment Minimum Minimum Edge Distance

AEQM-R-11/-16 ¹⁄₂" 3¹⁄₂" 6³⁄₄"

AEQM-R-92/-99 ⁵⁄₈" 4" 8¹⁄₄"

AEQM-R-200/-1628 ³⁄₄" 4³⁄₄" 9³⁄₄"

AEQM-R-100/-109 ³⁄₄" 4³⁄₄" 9³⁄₄"

Notes:
1. Ratings apply for installation in 3000 psi concrete. To achieve rated load, special inspection is required.
2. HILTI KWIK BOLT II

YOUR VMC/KORFUND FIELD ENGINEER IS;

Vibration Mountings & Controls, Inc.


Korfund Dynamics
Aeroflex, Inc., Companies
113 Main Street, Box 37, Bloomingdale, NJ 07403 Tel: 201/838-1780 Fax: 201/492-8430
© Vibration Mountings & Controls, Inc. 9/96