Professional Documents
Culture Documents
AEQM/96
AEQM Spring-Flex
Seismic Isolators
Deflections to 2"
'B'
'A'
'D'
'C'
'F' Thickness
AEQM Mount - Loads, Ratings, Dimensions
*Seismic rating is for quick reference only and is based on attachment to steel structure. Use OSHPD rated curves for actual seismic rating . For concrete attachment refer to AEQM–R Series.
OSHPD Pre-Approval applies to 1” and 1¹⁄₂” deflection mountings only.
Horizontal
Model # Color Code Rated Rated Seismic Dimensions, Inches
Capacity (lbs.) Deflection (in.) 'G' Rating*
A B C D E F G H J
AEQM-R-11 BLUE 60 1.3 18 8 6 6 4 ⁹⁄₁₆ ³⁄₈ 6 ⁵⁄₈ ³⁄₈
AEQM-R-12 ORANGE 100 1.3 10.8 8 6 6 4 ⁹⁄₁₆ ³⁄₈ 6 ⁵⁄₈ ³⁄₈
AEQM-R-13 BROWN 165 1.2 6.5 8 6 6 4 ⁹⁄₁₆ ³⁄₈ 6 ⁵⁄₈ ³⁄₈
AEQM-R-14 BLACK 260 1.0 4.1 8 6 6 4 ⁹⁄₁₆ ³⁄₈ 6 ⁵⁄₈ ³⁄₈
AEQM-R-16 YELLOW 370 0.8 2.9 8 6 6 4 ⁹⁄₁₆ ³⁄₈ 6 ⁵⁄₈ ³⁄₈
AEQM-R-92 BROWN 125 1.3 12 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-93 ORANGE 225 1.3 6.6 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-94 GREEN 325 1.2 4.6 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-95 RED 450 1.2 3.3 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-96 BLACK 600 1.2 2.5 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-97 WHITE 750 1.1 2.0 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-98 GRAY 900 1.0 1.6 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-99 BLUE 1100 1.0 1.3 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-200 BLUE 125 1.3 24 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-400 BLACK 400 1.3 7.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-600 RED 600 1.1 5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-1000 GREEN 1060 1.1 2.8 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-1300 YELLOW 1300 1.0 2.3 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-1600 GRAY 1600 1.0 1.8 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-1625 GRAY/RED 1970 1.0 1.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-1628 GRAY/GREEN 2500 1.0 1.2 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 8⁵⁄₈ ⁷⁄₈ ¹⁄₂
AEQM-R-100 BROWN 100 1.5 27 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-101 ORANGE 200 1.5 13.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-102 GREEN 400 1.5 6.7 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-103 RED 600 1.5 4.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-104 BLACK 800 1.5 3.3 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-105 WHITE 1000 1.5 2.7 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-106 GRAY 1250 1.5 2.1 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-107 BLUE 1500 1.5 1.8 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-108 YELLOW 1750 1.5 1.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-109 PINK 2000 1.5 1.3 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-81 BLUE 20 2.0 75 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-82 ORANGE 26 2.0 57 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-83 PURPLE 36 2.0 41 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-84 YELLOW 52 2.0 28.8 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-85 GRAY 65 2.0 23 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-86 RED 84 2.0 17.8 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-87 GREEN 114 2.0 13.1 9¹⁄₂ 7¹⁄₂ 7 5 ¹¹⁄₁₆ ³⁄₈ 7¹⁄₂ ⁵⁄₈ ³⁄₈
AEQM-R-401 BLUE 110 2.0 24.5 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-402 YELLOW 140 2.0 19.2 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-403 BLACK 180 2.0 15 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-404 PURPLE 240 2.0 11.2 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-405 BROWN 330 2.0 8.1 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-406 RED 460 2.0 5.8 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-407 RED/BLACK 660 2.0 4 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-408 RED/GREEN 960 2.0 2.8 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-409 RED/GRAY 1174 2.0 2.3 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-411 ORANGE/GRAY 1400 2.0 1.9 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-412 Orange/Gray/Orange 1550 2.0 1.7 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
AEQM-R-413 Orange/Gray/Brown 1680 2.0 1.6 11 9 9 7 ¹³⁄₁₆ ⁵⁄₈ 9³⁄₄ ⁷⁄₈ ¹⁄₂
*Seismic rating is for quick reference only and is based on attachment to concrete. Use OSHPD rated curves for actual seismic rating. OSHPD Pre-Approval applies to 1" and 1¹⁄₂" deflection mountings only.
3. Locate isolators on floor or sub-base as required, insuring that the isolator centerline matches the equipment or equipment base mounting holes.
Shim and/or grout as required to level all isolator base plates. A 1⁄4" maximum difference in elevation can be tolerated.
4. Anchor all isolators to floor or sub-base as required. For installing on concrete , see “Concrete Rating Information”.
5. Remove cap screw and save. Gently place machine or machine base on top on bolt. Install cap screw but DO NOT tighten.
6. The weight of the machine will cause the spring and thus the adjustment bolt to descend.
7. Adjust all isolators by turning adjustment bolt so that the operating clearance is approximately 1⁄4". NOTE: It may be necessary to adjust rebound
plate for clearance.
8. Check equipment level and fine adjust isolators to level equipment.
9. Adjust rebound plate so that the operating clearance is no more than 1⁄4".
10. Tighten cap screw. Adjustment is complete.
AEQM / AEQM–R OSHPD Rated Load Curves
7000
AEQM OSHPD RATED LOADS
Horizontal and Vertical Ratings are approved by California
OSHPD and have OSHPD Anchorage Pre-Approval "R" Number R-0189,
6000 and are based on properly sized bolts per ASTM A307 attached to support
structure. Testing and analyses have been performed in accordance with
OSHPD approved procedures.
200–1628
2000
11–16
92–99 100–109
1000
8000
AEQM OSHPD RATED LOADS
Horizontal and Vertical Ratings are approved by California OSHPD and
have OSHPD Anchorage Pre-Approval "R" Number R-0189, and are
7000 based on properly sized bolts per ASTM A307 attached to support
structure. Testing and analyses have been performed in
accordance with OSHPD approved procedures.
To use OSHPD rated load curves:
Vertical Loads, lbs. (Compression or Tension)
3500
1000
4000
3500
3000
200-1628
100 Series
2000
11–16
92–99
1000
Notes:
1. Ratings apply for installation in 3000 psi concrete. To achieve rated load, special inspection is required.
2. HILTI KWIK BOLT II