Engine Side
Key switch
Panel Lockk → Disable all DSE7310 buttons
Reset → Simulate DSE7310 Reset buttons
Active
Starting
DSE 7310 Sequence
Auto Modek
Manual Mode → Not allowed for normal
operation Motor Starter
Engaged
Emergency 3x attempts to crank.
Stop If speed and voltage not
built then “fail to start”
Speed alarm will appear.
and N
GCP Side Voltage
raise
DSE 8610
Auto Modek Y
Manual Mode
Speed and Voltage ramp up
to nominal, Generator set
Engine Operation goes to safety on delay and
warming up state
Selector
Start
Stop
Generator
Available
Loadsharing
Mode
Manualk
I
DSE8610
Loadshare Start Button
Baseload
Emergency
Stop
Pict 1 . Starting Sequence In Manual Mode
GCP Side
DSE 8610
Generator
Auto Modek Available
Manual Mode
Bus live N
?
CB
“ Fail to Close “ N Succeed
Alarm to close
?
Y
Loading
Process
Engine Operation
Selector
Start
Load ramping
Stop
down
DSE8610 Gen
Loadsharing Open Button
Mode Normal Opening Sequence :
Manualk Manual Decrease Load by adjusting
potentiometer.
Loadshare
Loadshare Load ramp down automatically
Baseload Base load Load ramp down automatically
Emergency
Stop
Electrical Fault
u/o Voltage
u/o Frequency
Mains decoupling
Reverse Power
Over Current
Over Load
Negative Phase Sequence
Emergency
Stop
Engine Operation O
Selector DSE8610
Start Start Button
Stop
Mechanical Fault
Loadsharing
Mode
Manualk Low Oil Pressure
High Engine Temperature
Loadshare
Over Speed
Baseload Under
Under Speed
Emergency
Stop
Emergency Y
Stop
Speed and Voltage ramp up
to nominal, Generator set
goes to safety on delay and
GCP Side warming up state
DSE 8610
Auto Modek Generator
Available
Manual Mode
Emergency
Stop
Pict 5 . Starting Sequence In Auto Mode
Engine Side
Stopping
Key switch sequence
Panel Lockk → Disable all DSE7310 buttons
Reset Return Delay
Active Time
Cooling Down
Time
GCP Side
DSE 8610 Engine
Stopping
Auto Modek
Manual Mode
Engine Operation
Selector
Start
Stop