Refrigeration

Refrigerent = R-12
tons = 5 tons
Condensor temperature = 40 deg C
Evaporator temperature = -10 deg C
P1 = (Psat)-10 deg C = 2.1912 bar
h1 = 183.19 kJ/kg
s1 = 0.7019 kJ/kgK
v1 = 0.077 m3/kg
P2 = (Psat)40 deg C = 9.6066 bar
s2 = s1 = 0.7019 kJ/kgK
t2 = 48 deg C
h2 = 209.41 kJ/kg
capacity of the plant = 70000 kJ/h
h3 = h4 = 74.59 kJ/kg
hf = 26.87 kJ/kg
hfg = 156.31 kJ/kg

w(h1-h4) = 19.44444 kW
w = 0.179046 kg/s
Volumetric flow rate = 0.013787 m3/s
Compressor discharge temp = 48 deg C
Pressure ratio = 4.384173
Heat rejected to condensor = 24.13904 kW
h4 = hf + x4*hfg
x4 = 0.305291
Flash gas percentage = 30.52908 %
COP = 4.141876
Power required to drive
compressor = 4.694598 kW
COP (reversible) = 5.26
COP (vaour compression = 0.787429
cycle) / COP (Carnot cycle)
1-2 = Isentropic compression
2-3 = Heat rejection at constant pressure
3-4 = Isenthalpic throttling
4-1 = Evaoration at constant pressure

P2

P1

Evaporator temperature = -10 deg C


Condensor temperature = 40 deg C

At -10 deg C means at point 1

(P1)sat = 2.191 bara


v1 = 0.076646 m3/kg
h1 = 183.058 kJ/kg
s1 = 0.7014 kJ/kgK

At point 2

s2 = 0.7014 kJ/kgK
(P2)sat = 9.607 bara
0.8 0.9
40 205.924 0.7016 204.17 0.6982
50 213.29 0.7249 211.765 0.7131
45.37057

t2 = 45.37057 deg C
h2 = 207.2589 kJ/kg

At P2 = 9.607 bara
hf = 74.527 kJ/kg
hfg = 128.525 kJ/kg
hg = 203.051 kJ/kg

Heat rejected in condensor = 23.01177 kW


h4 = 74.527 kJ/kg
At P = 2.192 bar
hf = 26.851 kJ/kg
hfg = 156.207 kJ/kg
hf + x4*hfg = 74.527
Therefore
x4 = 0.30521
Therefore flash percentage is 30.5 %
COP = heat removed from the refrigerated
COP = (h1-h4)/(h2-h1)
= 4.484582
Power required to drive the compressor = 4.333089 kW
COP reversible = 5.26
COP vapor compression cycle/COP Carnot cycle
= 0.852582
Entropy at point 1 and 2 are same. Isentropic compression.

0.9607
203.1053 0.696136
210.8393 0.705937
207.2589 0.7014

difference
0.1 -0.0034
0.0607 -0.002064

0.1 -0.0118
0.0607 -0.007163

10 0.009801
5.370567 0.005264

0.1 -1.754
0.0607 -1.064678

0.1 -1.525
0.0607 -0.925675

10 7.734003
5.370567 4.153598
oved from the refrigerated space / Work done in compressor
0.8 0.9
h s h s
40 205.924 0.7016 204.17 0.6982
50 213.29 0.7248 211.765 0.7131

45.84117

133.0965
0.96066 0.7019 difference
s 0.1 -0.0034
203.106 0.696138 0.06066 -0.002062
210.8399 0.706003
0.1 -0.0117
0.06066 -0.007097
207.6235 0.7019
10 0.009865
5.841167 0.005762

10 0.009865
5.841167 0.005762

0.1 -1.754
0.06066 -1.063976

0.1 -1.525
0.06066 -0.925065

10 7.733911
5.841167 4.517507

10 0.009865
5.841167 0.005762