How to Design Earthing system in substation Search … SEARCH


By admin  On July 26, 2017 In Transmission and Distribution Tagged substation earthing system Leave a comment 

SIGN UP FOR GETTING OUR


The substation grounding system comprises of a grid (earth mat) formed by a horizontal DAILY UPDATES
buried conductors. Before 1960s the design criterion of substation earthing system was
“low earth resistance.” (Earth Resistance< 0.5 ohms for High Voltage installations).
During 1960s, the new criteria for the design and evaluation of Substation Earthing Name
System were evolved particularly for EHV AC and HVDC Substations.
Email
The new criteria are :
SEND
1. Low Step Potential
2. Low Touch Potential JOIN WITH US ON FACEBOOK
3. Low Earth Resistance.
Abu Android Apps
379 likes

Like Page Sign Up

Be the first of your friends to like this

HOME BLOG ABOUT US PRIVACY POLICY CONTACT US SITEMAPRECENT POSTS

How to calculate short circuit current


for transformer

Why we are using carbon brush in


motor
The conventional “Low earth resistance criterion” and Low Current Earth Resistance
Measurement continues to be in practice for Substations and Power Station upto and What is Alternator? How Alternator is
including 220 kV. working?
The parts of the Earthing System include the entire solid metallic conductor system
between various earthed points and the underground earth-mat. The earthed points are di erence between squirrel cage and
held near-earth potential by low resistance conductor connections with earth-mat. slip ring induction motor
Substation Earthing System Design
What is transistor & How transistor
Underground Horizontal Earth Mesh (Mat/Grid) working

The mesh is formed by placing mild steel bars placed in X and Y directions in mesh
Di erence between conductor and
formation in the soil at a depth of about 0.5 m below the surface of substation floor in the
insulator
entire substation area except the foundations.
The crossings of the horizontal bars in X and Y directions are welded. How to get pure sinusoidal AC output
from DC input using PWM inverter
The earthing rods are also placed the border of the fence, surrounding building
foundations, surrounding the transformer foundations, inside fenced areas etc. Slip ring induction motor working
principle
The mesh ensures uniform and zero potential distribution on horizontal surface of the
what is electric car and how electric car
floor of the substation hence low “step potential” in the event of flow of earth fault current.
working

How to connect DC battery charger in


industrial

CATEGORIES

Electrical machines

General Electrical

Power Plants

Question & Answer

Transmission and Distribution


Earthing Electrodes (Spikes)
Several identical earth electrode are driven vertically into the soil and are welded to the ARCHIVES
earthing rods of the underground Mesh. Larger number of earth electrodes gives lower
earth resistance.
August 2018 (2)
The number of Earth-Electrodes (Spikes) Ns for soil resistivity 500 ohm meter and July 2018 (7)
earth fault current Is is :
June 2018 (2)
Ns = Is / 250 Amperes
i.e., approximately 250 Amp per spike, for soil resistivity of 500 ohm-meter. March 2018 (8)

February 2018 (6)

The number of Earth-Electrodes (Spikes) Ns for soil resistivity 5000 ohm meter is
December 2017 (1)
Ns = Is / 500 Amperes
November 2017 (7)
i.e., approximately 500 Amp per spike, for soil resistivity of < 5000 ohm-meter.
Is = Short Circuit level of the substation, A
October 2017 (1)
Example:
33 kV sub stations : 25000 to 31000 A September 2017 (29)

400 kV Substations : 40000 A


August 2017 (49)

July 2017 (52)

June 2017 (38)

RECENT COMMENTS

Mwansa Manda on Maintenance of


power transformer

xwix in ae on What’s the Di erence


Earthing Risers
Between AC and DC Electric Shocks?
These are generally mild steel rods bent in vertical and horizontal shapes and welded to
VIVEKANAND PANDAY on Sulphur
the earthing mesh at one end and brought directly upto equipment / structure foundation.
Hexa ouride (SF6) Circuit Breakers
Earthing Connection

Galvanized Steel Strips or Electrolytic Copper Flats or Strips/Stranded Wires (Cables) JOYDEEP KHAN on Di erence Between
/Flexibles. Circuit breaker and Isolator
These are used for final connection (bolted/welded/clamped) between the Earthing Riser
Faraji on Star-Delta starter Working
and the points to be earthed.
principle

For Transformer Neutral/High Current Discharge paths copper strips/stranded wires are
preferred. TAGS
Galvanised Iron Strips/stranded wires are more common for all other earthing
connections. The earthing strips are finally welded or bolted or clamped to the Earthed
Point. advantages alternator ats electrical
automatic transfer switch wiring battery

calculation capacitor circuit breaker

Related connection construction delta dielectric


test earthing electrical electricity
Why earthing is important in How to measure Earthing Types of Earthing & Electrical electric shock feeder generator
Substation resistance in your Home grounding systems
Grounding induction motor
July 26, 2017 July 9, 2017 August 14, 2017
In "Transmission and In "Electrical machines" In "Electrical machines" inverter maintenance MCB
Distribution" MCCB motor Neutral power factor
protection system relay RTD slip ring
induction motor solar power star star-
delta starter switchgear Synchronous
motor thermocouples

transformer types ups uses


Related Posts VFD voltage working working principle
How to connect DC Why we use 3 phase Di erence between 50Hz
battery charger in power supply, not 4/5/6 and 60Hz frequency
industrial phase

UG CABLE TYPES WHY EARTHING IS IMPORTANT IN


SUBSTATION

Leave a Reply
Your email address will not be published. Required elds are marked *

Comment
Name *

Email *

Website

Notify me of follow-up comments by email.

Notify me of new posts by email.

I'm not a robot


reCAPTCHA
Privacy - Terms

POST COMMENT

SuperAds Lite powered by ThemeCountry

2017- 2018 @ All rights reserved by Electricalmastar.com

You might also like