You are on page 1of 7

Improvement in Cable Rating Calculations by

Consideration of Dependence of Losses on


Temperature
George .J. Anders, Fellow IEEE Heinrich. Brakelmann

Abstract. In this paper a new method is proposed that allows There are several important implications of the proposed
estimation of conductor temperature and cable losses as a change. Two of those will be discussed in this paper. One is a
function of conductor current and some parameters prediction of the conductor temperature and losses from the
corresponding to the nominal loading conditions. Such
current measurements alone and the other is the modification
parameters include cable rating and loss factors computed by
cable manufacturer for the laying conditions specified by the of the Neher-McGrath procedure for the calculation of the
user. There are two major applications of the proposed external thermal resistance.
approach. One relates to rating of power cables with current We will start by presenting mathematical apparatus
measurements alone and the other to the computation of the required to make these modifications and conclude by
external thermal resistance with a non unity load factor used in considering several practical examples.
the Neher/McGrath approach. Both applications are examined
in this paper.
Index terms. Power cables, real time rating systems, Neher- II. PREDICTION OF CONDUCTOR TEMPERATURE FROM THE
McGrath method, loss factor. CONDUCTOR CURRENT
Conductor temperature rise is related to the conductor
I. INTRODUCTION losses through the following equation (see Chapter 4 of [1])
The losses in a cable conductor are dependent on the
∆θ = n (WcTt + ∆θ d ) − θ x (1)
operating temperature. Since in field installations this
temperature is unknown, the estimation of the losses is a where
difficult task and, therefore, usually not performed at all or n = number of conductors in the cable.
some approximations are used [2]. The losses are also a ∆θ d = temperature rise caused by dielectric losses, (ºC).
function of daily load fluctuations. In the Neher/McGrath
Tt = total thermal resistance defined in (2), (K·m/W).
method these fluctuations are taken into account in the
calculation of the external thermal resistance by considering a T1
loss-load factor (referred to as a loss factor, for short). In Tt = + (1 + λ1 ) T2 + (1 + λ1 + λ2 )(T3 + T4 ) (2)
n
rating computations, the loss factor is calculated from the load
shape alone without consideration of the conductor A possible drying-out of the surrounding soil is taken into
temperature. In reality, the definition of the loss factor account in (1), following the two-layer-model of Cox and
requires consideration of the conductor resistance that is Coates [3] (see Section 4.2 in [1]), by means of the variables
temperature dependent. ν and θx with
The aim of this paper is to propose an improvement in the
accuracy of the rating calculations by an introduction of the ρ2
θ x = (vx − 1) ⋅ ∆θ cr and vx = (θ x = θ xT ) for ∆θ e > ∆θ cr
temperature dependence of the conductor losses in the rating ρ1 (3)
formulae. Since, as mentioned above, the conductor vx = 1 (θ x = 0) for ∆θ e ≤ ∆θ cr T
temperature is usually unknown, we will need some other
information to account for the absence of the real time where
temperature values. The additional information comes from ∆θ e = temperature rise at the cable surface, (ºC).
standard rating conditions as specified by the cable ∆θ cr = critical temperature rise of the soil, (ºC).
manufacturer and involves cable rating values at nominal θ xT = correction temperature, (ºC).
conditions.
ρ1 , ρ 2 = thermal resistivities of the moist and dry soils,
respectively, (K·m/W).
The thermal resistivity of the dry soil is normally larger
than that of the moist soil by a factor of 2 to 6. An example of
G.J. Anders is with Kinectrics Inc., Toronto, Ontario, Canada (e-mail: the standard values of these quantities is given in Table 1 [5]]:
george.anders@kinectrics.com
H. Brakelmann is with the Department of Electrical Engineering,
Duisburg University, Germany, (email: brakelmann@uni-duisburg.de).
TABLE 1 STANDARD VALUES FOR SOIL PROPERTIES
cm = 1 + α T ⋅ (θ max − 20 )  (11)
variable unit value The values Tt , R , ∆θ d , R , θ x , R are defined above, but here
θ amb °C 20
they are related to the rated load. We will compute now the
∆θ cr K 15 value of Rt 20 from equations (10) and (9) and substitute it in
ρ1 (K·m)/W 1 equation (7).
ρ2 (K·m)/W 2.5
∆θ − ∆θ d + θ x = Tt , x ⋅ n ⋅ Rt 20 ⋅ I 2 ⋅ (α T ⋅ ∆θ + cα )
θx K 22.5
(12)
2
We will rewrite (1) to relate conductor losses to the current vT  I 
= (∆θ max − ∆θ d , R + θ x , R ) ⋅ ⋅   ⋅ (α T ⋅ ∆θ + cα )
as a straightforward multiplication of the a.c. resistance and cm  I R 
squared current I 2 R . In order to achieve this, we will first
introduce the following revised designation of the total In equation (12) the variable ν T is given by
thermal resistance of the cable
Tt , x
T1 T ⋅ (1 + λ1 ) νT = for ∆θ e ≤ ∆θ cr , and
Tt , x = + 2 + T3 + vx ⋅ T4 = TI + vx ⋅ T4 (4) Tt , R
n ⋅ (1 + λ1 + λ2 ) 1 + λ1 + λ2
(13)
and the electrical resistance representing all ohmic losses in ν T = 1 for ∆θ e > ∆θ cr
the cable
A caution is required when interpreting equation (13).
Rt 20 = R20 ⋅ (1 + λ1 + λ2 ) (5) Three different situations may arise. If there is already drying
out for current I (we assume that I ≤ I R ) then ν T = 1 for both
R is temperature-dependent. Hence, the conductor
temperature θ changes the total ohmic losses of the cable, currents. In another case, we may have no drying out for
WI , according to current I but the soil dries out for the rated current. In this
case, the nominator in the first equation in (13) corresponds to
WI = Wt − Wd = W20 ⋅ 1 + α T ⋅ (θ − 20 )  the moist soil and the denominator to the dried out soil. The
temperature inequality associated with the first equation holds
(6) only for current I but not for the rated current. Finally, the
= n ⋅ Rt 20 ⋅ I ⋅ 1 + α T ⋅ (θ − 20 ) 
2 third possibility exists when no drying out occurs for the rated
current. In this case, ν T = 1 . In the reasoning made above we
where W20 are conductor losses at 20ºC, (W/m) and αT is the implicitly assumed that the loss factors that appear in the
temperature coefficient of resistance (1/ºC) of the conductor definition of the total thermal resistances (2) and (4) do not
material. depend on the current values. In reality, this is not true but the
With these notations, equation (1) can be rewritten as error introduced by this assumption is negligible.
Solving now equation (12) for the temperature rise, we
∆θ = Tt , x ⋅ n ⋅ Rt 20 ⋅ (α T ⋅ ∆θ + cα ) ⋅ I 2 + ∆θ d − θ x obtain
(7) 2
 I 
= Tt , x ⋅ (Wt − Wd ) + ∆θ d − θ x vT ⋅ cα ⋅ (∆θ max − ∆θ d , R + θ x , R ) ⋅   − cm (θ x − ∆θ d )
∆θ =  IR  (14)
with 2
 I 
cm − vT ⋅ α T ⋅ (∆θ max − ∆θ d , R + θ x , R ) ⋅  
cα = 1 + α T ⋅ (θ amb − 20 ) (8)  IR 
For the nominal load, characterized by the rated current I R Making substitutions
and the nominal total losses WtR , the cable conductor reaches θ1 = cα ⋅ (θ max − θ amb − ∆θ d , R + θ x , R ) ⋅ vT (15)
its maximum stationary temperature θ max . In this case,
equation (7) takes the form θ 2 = cm ⋅ (∆θ d − θ x ) (16)
∆θ max = Tt , R ⋅ (WtR − WdR ) + ∆θ d , R − θ x , R (9)
 (
c1 = 1 + α T ⋅ θ amb − 20 + ∆θ d , R − θ x , R 
 ) (17)
whereas

WtR − WdR = n ⋅ Rt 20 ⋅ I R2 ⋅ 1 + α T ⋅ (θ max − 20 )  = n ⋅ Rt 20 ⋅ cm ⋅ I R2 (10) c2 = α T ⋅ (∆θ max − ∆θ d , R + θ x, R ) (18)

and equation (14) takes the form


 I 
2 (21) will change depending whether drying out occurs or not;
θ1 ⋅   + θ2 that is, whether the temperature rise at the cable surface
∆θ =  IR  (19) exceeds the critical temperature rise for drying-out of the soil,
  I  
2
∆θ cr , or not. This can be correlated to a critical current I cr
c1 + c2 ⋅ 1 − vT ⋅  
  I R   and the corresponding critical total losses Wtcr by the relation

Equation (19) represents a crucial relationship that allows ∆θ cr = Wcr ⋅ T4 (24)


calculation of the conductor temperature when the conductor
with
current and certain values corresponding to the rated
conditions are known. The issues related to the practical Wtcr = Wd + n ⋅ Rt 20 ⋅ I cr2 ⋅ (cα + α T ⋅ ∆θ c ,cr ) (25)
application of this formula are discussed in the next Section.
From equations, (6), (10) and (19), we can compute the where ∆θ c , cr is the conductor temperature rise corresponding
total cable losses corresponding to current I, as to the critical current. Its value can be obtained from
 2  ∆θ c ,cr = ∆θ cr + TI ⋅ (Wtcr − Wd ) + Td ⋅ Wd (26)
  I  
2

θ1 ⋅   + θ 2 
 I  c α I
 R where
Wt = Wd + (WtR − Wd ) ⋅   ⋅  α + T ⋅ 
 I R   cm cm   I  
2

 c1 + c2 ⋅ 1 − vT ⋅     T1
Td = + T2 + T3 (27)
   I R    2⋅n
From equations (24) to (27) we can compute the critical
2
 I  current as
= Wd + (WtR − Wd ) ⋅   ⋅ vθ
 IR  1
I cr =
(20) n ⋅ Rt 20
(28)
where the temperature coefficient vθ is defined as ∆θ cr / T4 − Wd

1 + α T ⋅ [ ∆θ cr + θ amb − 20 + TI ⋅ ∆θ cr / T4 − (TI − Td ) ⋅ Wd ]
c3
νθ = (21)
  I  
2

c1 + c2 ⋅ 1 − ν T    III. EXAMPLE OF EVALUATION OF CONDUCTOR TEMPERATURE


  I R   AND LOSSES FROM CURRENT VALUES ALONE

with We will consider a 145 kV, 3-conductor armored cable


with XLPE insulation. We will compute the conductor
c3 = 1 + α T ⋅ θ amb − 20 + ( ∆θ d − θ x )  (22) temperature for various levels of loading of this cable. The
following parameters required for the analysis are computed
An important characteristic of equation (20) is that it takes using a standard rating program.
into account the variation of conductor resistance with The temperature rise caused by the dielectric losses is equal
temperature as well as a possibility of the soil dry out via the to ∆θ d , R = 0.8°C for the moist soil conditions and equal to
coefficient ν θ defined in (21). Up to now, for long cable
1.73°C when soil dries out. The analysis involves calculation
connections (e.g., submarine cables), the practice has been to of the conductor temperature and total losses for a range of
compute cable losses by obtaining the voltage- and current- currents from 0 to 966 A. We will show detailed calculation
distributions by means of the line equations, which furnish the for the current of 600 A and display the remaining results in a
active power at the entry and at the end of the line and by this graphical form.
the total losses of the cable, without consideration of their For the nominal loading conditions, the external cable
temperature dependence. This means that ν θ = 1 in (20). temperature reaches 56.6ºC. This value gives the cable
Such an assumption may lead to an error of more than 50% in surface temperature rise of 41.6°C, which is higher than the
estimating cable losses as illustrated in the following example. critical temperature rise limit of 35°C (the ampacity value in
Equation (20) allows calculation of the total energy losses Table 2 reflects the drying out condition). Hence, in this
E of the cable of length L over a period of time in case the example; ν T ≠ 1 and we will start the analysis by computing
current variations are known. For the duration of the time the value of θ x .
interval τ , these losses can be computed from
From equation (3), we have
(WtR − Wd ) ⋅ L τ
ρ 2 1.8
E = Wd ⋅ L ⋅τ + ∫I
2
⋅ (t ) ⋅ vθ (t ) ⋅ dt (23) vx = = = 3.0
I R2 t =0 ρ1 0.6
Factor ν T as well as the values of ∆θ d and θ x in (19) and
θ x,R = (vx − 1) ⋅ ∆θ cr = (3 − 1) ⋅ 35 = 70°C θ1 = cα ⋅ (θ max − θ amb − ∆θ d , R + θ x , R ) ⋅ vT
TABLE 2 VALUES FOR NUMERICAL EXAMPLE = 0.98 ⋅ (90 − 15 − 1.73 + 70) ⋅ 0.488 = 68.49°C

θ 2 = cm ⋅ (∆θ d − θ x ) = 1.275 ⋅ (0.8 − 0) = 1.02°C


cable ampacity I (A) 966
conductor resistance at R (ohm/km) 0.033
c1 = 1 + α T ⋅ θ amb − 20 + ( ∆θ d , R − θ x , R ) 
θ max
= 1 + 0.00393 ⋅ (15 − 20 + 1.73 − 70) = 0.712
concentric/skid wires λ1 0.123
loss factor
pipe loss factor λ2 0.210 c2 = α T ⋅ (∆θ max − ∆θ d , R + θ x , R )
thermal resistance of T1 (K⋅m/W) 0.754 = 0.00393 ⋅ (90 − 15 − 1.73 + 70) = 0.563
insulation
thermal resistance of T2 (K⋅m/W) 0.040 We can now compute the conductor temperature rise
between sheath and caused by 600 A current. From equation (19), we have
armour
thermal resistance of T3 (K⋅m/W) 0.047 2
jacket  I   600 
2
θ1 ⋅   +θ2 68.49 ⋅   + 1.02
external thermal T4 (K⋅m/W) 0.299 I
 R  966 
∆θ = = = 23.5°C
resistance of moist soil   I  
2
  600  
2

c1 + c2 ⋅ 1 − vT ⋅    0.712 + 0.563 ⋅  1 − 0.488 ⋅  966  


external thermal T4 (K⋅m/W) 0.896
  I R      
resistance of dry soil
losses in the conductor Wc (W/m) 30.76
Hence, conductor temperature for this current is equal to
dielectric losses per core Wd (W/m) 0.52
total joule losses per WI (W/m) 41.01 θ c = ∆θ + θ amb = 23.5 + 15 = 38.5°C .
conductor
Repeating the calculations for other values of the current,
total losses per cable Wt (W/m) 124.58
we obtain the results shown in Figure 1. Note that for I = 0 A
the conductor temperature reaches 15.8ºC because we
The equivalent thermal resistances corresponding to the assumed that the cable is energized all the time and the
moist and dry conditions, respectively, are obtained from (4) dielectric losses are present.
as
T1 T ⋅ (1 + λ1 )
Tt , x = + 2 + T3 + vx ⋅ T4
n ⋅ (1 + λ1 + λ2 ) 1 + λ1 + λ2

0.754 0.04 ⋅ (1 + 0.123)


= + + 0.047 + 1 ⋅ 0.299
3 ⋅ (1 + 0.123 + 0.210) 1 + 0.123 + 0.210

= 0.269 + 0.299 = 0.568 K ⋅ m/W

T1 T ⋅ (1 + λ1 )
Tt , R = + 2 + T3 + vx ⋅ T4
n ⋅ (1 + λ1 + λ2 ) 1 + λ1 + λ2
Figure 1 Conductor temperature as a function of conductor current for the 3-
conductor armored cable
= 0.269 + 3 ⋅ 0.299 = 1.165 K ⋅ m/W
The temperature coefficient ν T is calculated from equation The cable losses are computed next. First, we obtain the
temperature coefficient from equation (21)
(13) as
c3 0.983
νθ = = = 0.841
Tt , x 0.568   I  
2
  600  
2

νT = = = 0.488 c1 + c2 ⋅ 1 − ν T    0.712 + 0.563 ⋅ 1 − 0.488 ⋅   


Tt , R 1.165   I R     966  

On the other hand, for the current I = 600 A , no drying out From equation (20), we now compute the total losses in the
occurs and θ x = 0. cable
From equations (15) to (18), we obtain  I 
2
  600 
2

Wt = Wd + (WtR − Wd ) ⋅   ⋅ vθ = 3 ⋅ 0.52 + (41.53 − 0.52) ⋅   ⋅ 0.841 = 41.49 W/m
I
 R   966  
The cable losses computed from (20) as a function of IV. PRACTICAL APPLICATION OF THE TEMPERATURE
conductor current are shown in Figure 2 (dashed line). The PREDICTION EQUATION
solid line represents the joule losses computed without A profitable use of equations (19), (23) and (28) is possible,
considerations of temperature variation of resistance; i.e., for if the corresponding cable data are known. In this case, for all
νθ = 1 . operating conditions, the stationary conductor temperature as
well as the cable losses can be determined by inserting the
actual current values into these simple analytical formulae.
One possibility is to execute a complete current rating
analysis, thus determining all thermal resistances, loss factors
and other relevant parameters. This is normally done by the
cable manufacturer, since they have to their disposal all
construction data as well as a suitable rating program.
The extraction of the necessary coefficients
θ1 ,θ 2 , c1 and c2 from the cable data without any rating
calculations is possible, if the following nominal values for
full-load operation are given:
• the rated current , I R
Figure 2 Total losses for the 3-conductor armored cable as a function of
conductor current and the ratio of losses. • the dielectric losses (p.u.l.), We ,
• ambient soil temperature, θ amb .
The line at the top of the graph shows the ratio of the losses
computed without and with the temperature correction. The These three parameters are easily obtainable from the cable
maximum error, in this case, exceeds 20% for the currents in specifications. With these values, equation (19) can be used
the usual loading range of this type of the cable; that is, for the prediction of conductor temperature for a given current
between 300 and 600 A. with an assumption that the soil dry out does not occur. Since
Assuming that the critical temperature rise at which drying this is the situation most often encountered in practice, the
out starts for this installation is 35ºC, the critical loading method presented in this paper can be used as a simple
current can be computed from (28). In order to perform this alternative to the full real-time temperature monitoring
calculation, we need to obtain first the internal thermal system.
resistances from (4) and (27), and the conductor resistance at If, on the other hand, there is a need for the calculation of
20ºC. The internal equivalent thermal resistance was cable losses, or if a soil dry out may occur during cable
computed above as TI = 0.269 K ⋅ m/W . operation, we will require two additional quantities; namely,
• the total rated losses (p.u.l.), WtR of the cable
T1 0.754 system, and
Td = + T2 + T3 = + 0.04 + 0.047 = 0.213 K ⋅ m/W • the cable surface temperature, θ e .
2⋅n 6
R ⋅ (1 + λ1 + λ2 ) From these data, the external thermal resistance T4 can be
Rt 20 = computed as
1 + αT ⋅ (θ max − 20°C)
θ e − θ amb
T4 = (29)
0.000033 ⋅ (1 + 0.123 + 0.210) WtR
= = 0.0000345 ohm/m
1 + 0.00393 ⋅ (90 − 20)
The total thermal resistances of the cable can be
approximated by
The critical conductor current is equal to
′ = (θ max − θ e ) / WtR + T4
Tt , x ≈ Td , x ≈ Tapp (30)
1
I cr = The approximation given by equation (30) results in a very
n ⋅ Rt 20 small error for the cables with small dielectric losses.
∆θ cr / T4 − Wd As a substitute for the cable surface temperature and the
⋅ total cable losses, we can assume soil thermal resistivities for
1 + α T ⋅ [ ∆θ cr + θ amb − 20 + TI ⋅ ∆θ cr / T4 − (TI − Td ) ⋅ Wd ]
moist and dry conditions, and proceed with the calculations
accordingly.
1
=
3 ⋅ 0.0000345 V. EVALUATION OF THE LOSS FACTOR CALCULATIONS IN
RATING STANDARDS
35 / 0.299 − 0.52
⋅ = 952A
1 + 0.00393 ⋅ [35 + 15 − 20 + 0.269 ⋅ 35 / 0.299 − (0.269 − 0.213) ⋅ 0.52] A. Modification to the Neher-McGrath formula
The developments presented in the preceding sections will
now be used to discuss an issue of loss factor application in
cable rating.
In North America1, the variations of the daily load cycle are
taken into account by modifying the external thermal
resistance T4 , as follows [4].

ρ s  Dx 4L 
T4 =  ln + µ ln  (31)
2π  De Dx 

where
ρs = soil thermal resistivity, K·m/W,
Dx = diameter at which the effect of daily load
variations starts, mm. Its value is normally taken
to be 211 mm [4].
L = depth of cable center, mm,
De = external diameter of the cable or pipe, mm, and
µ = the loss factor.
The loss factor is defined by
τ
1
µ=
Wmax ⋅τ
⋅ ∫ W (t ) ⋅ dt
t =0
(32)
Figure 3 Two-step load function applied to the 3-conductor armored cable.
This is usually approximated by
The load in Figure 3 is characterized by 8 hours of full load
τ
µI =
1
⋅ ∫I
2
(t ) ⋅ dt (33) ( I = I1 ) , followed by 16 hours of a lower load ( I = I 2 ;
2
I max ⋅τ t =0 possibly an example for an industrial load). It is assumed, that
However, taking into account variations of the resistance the peak value I max of the load cycle corresponds to 60% of
with temperature, equation (33) can be written as the rated current I R of the cable.
τ The load and loss factors calculated from the traditional
1
µθ = ∫I (t ) ⋅ν θ (t ) ⋅ dt
2
⋅ (34) equations (36), (35) and (33), are computed next.
2
I max ⋅τ t =0
τ 24
1 1
In engineering practice, the loss factor is approximated LF =
I max ⋅τ
⋅ ∫ I (t ) ⋅ dt = 1⋅ 24 ∑ I (t ) = 0.73
t =1
from the known or assumed load factor LF as (Anders, 1997) t =0

µ LF = 0.3 ⋅ LF + 0.7 ⋅ LF 2 (35)

The load factor, in turn is defined by


µ LF = 0.3 ⋅ LF + 0.7 ⋅ LF 2 = 0.3 ⋅ 0.73 + 0.7 ⋅ 0.732 = 0.596
τ
1
LF =
I max ⋅τ
⋅ ∫ I (t ) ⋅ dt (36)
1
τ
1 24 2
t =0
µI =
I 2
⋅τ
⋅ ∫I
2
(t ) ⋅ dt = ∑ I (t ) = 0.573
1 ⋅ 24 t =1
Depending on the load variations, the approximations given max t =0

by equations (33) and (35) can introduce a significant error as


shown in the following example. In order to compute the temperature-dependent loss factor
B. Example of application of new loss factor formula we need to evaluate the temperature factor from (21). We will
show the calculations for the maximum current (1 p.u.) with
We will consider the 3-conductor armored cable analyzed
the necessary constants computed in Section III.
in Section III. This time, we will consider a two-step load
applied to this cable. The shape of the load is shown in Figure c3
νθ =
3.   I  
2

c1 + c2 ⋅ 1 − ν T   
  I R  

0.983
= = 0.836
1
Most European standards (excluding Germany), which in the majority of   1  
2

cases are based on the IEC standards, do not introduce a notion of the loss 0.712 + 0.563 ⋅ 1 − 0.488 ⋅   
factor. Instead, calculations involving varying loads are referred to a separate   1/ 0.6  
standard using full time dependent analysis [6].
From equation (34), we have At low load conditions, the error is the largest. It can also be
τ
quite large for the usual cable loading conditions in the range
1 1 24 2
µθ =
I 2
⋅τ
⋅ ∫I
2
(t ) ⋅ν θ ⋅ dt = ∑ I (t ) ⋅νθ = 0.469
1 ⋅ 24 t =1
of 40 to 80% of the rating. The effect on ampacity will
depend on the cable construction. In the case presented in this
max t =0
paper, the error was in the range of 4%. Fortunately,
The corresponding values of the external thermal resistance
traditional calculation methods give conservative ratings.
and the ratings are shown in Table 3.

TABLE 3 RATING AS A FUNCTION OF THE APPLIED LOSS FACTOR


VII. .REFERENCES
[1] Anders G. J, “Rating of Electric power cables. Ampacity computations
Loss factor T4 Ampacity for transmission, distributions and industrial applications”, IEEE Press
Power Engineering Series. IEEE Press, New York, 1997, McGraw-Hill
µ LF 0.596 0.185 1112
1998.
µI 0.573 0.179 1120 [2] Brakelmann H, (2002), “Loss determination for long three-phase high-
µθ 0.469 0.150 1159 voltage submarine cables”, to be published in ETEP
[3] Cox, H.N., Coates, R., (1965), “Thermal analysis of power cables in
soils of temperature-responsive thermal resistivity”, Proc. IEE S. pp.
When the temperature dependence of the loss factor is 2275-2283
introduced, the ampacity of the cable increases by 47 A or
[4] Neher, J.H., McGrath, M.H., (1957), “The calculation of the temperature
about 4.2%. rise and load capability of cable systems”, AIEE, Trans. Vol. 76, Pt. III,
We will conclude this example with the analysis of the 1957, pp. 752-772.
possible error that can occur when traditional loss factor [5] IEC 287-1-1, (1994), “Electric cables – Calculation of the current rating
computations are performed. Figure 4 shows the ratio of the – part I: Current Rating Equations (100% Load Factor) and calculations
loss factors obtained from equations (33) and (35) to the one of losses – section 1: General”, IEC Publication 60287.
obtained from equation (34) as a function of I 2 / I max . [6] IEC 287-2-1, (1994), “Electric cables – Calculation of the current rating
– part II: Current Rating Equations (100% Load Factor) and calculations
of thermal resistance”, IEC Publication 60287.

VIII. BIOGRAPHIES
George J. Anders (M’74, SM’84,
F’00) received a M.Sc. degree in EE from
Technical University of Lodz in Poland in
1973, and an M.Sc. degree in Mathematics
and Ph.D. degree in Power System
Reliability from the Univ. of Toronto in
1977 and 1980, respectively. Since 1975,
he has been employed by Ontario Hydro
first as a System Design Engineer in
Transmission System Design Dept. of
System Planning Division and currently as a Principal Engineer in Kinectrics
Inc. (a successor company to Ontario Hydro Technologies). Dr. Anders is the
author of two books “Probability Concepts in Electric Power Systems",
published by John Wiley & Sons, NY, 1990, and “Rating of Electric Power
Figure 4 Ratio of traditional loss factors to the temperature-dependent one. Cables”, published by IEEE Press, New York, 1997 and McGraw-Hill, New
York, 1998. He is a registered Professional Engineer in the Province of
We can observe that substantial errors can occur in the Ontario.
Heinrich Brakelmann (54), VDE, is
evaluation of the loss factor when the temperature dependence head of the Institute for Energy-Transport
is neglected. and -Storage of the faculty for engineering
sciences of the Gerhard-Mercator-University
of Duisburg. His main research fields are the
VI. CONCLUDING REMARKS power cable technologies (ETG-award in
In order to obtain accurate conductor operating temperature 1982). He received a M.Sc. degree in EE
(Dipl.-Ing.) from the Technical University of
and corresponding losses temperature sensing devices are Aachen, where he was promoted to Dr.-Ing.
sometimes installed on a cable or pipe surface. Installation of in the field of circuit-breakers in 1973.
such devices is often very costly, or outright impossible. In Between 1973 and 1977, he was
employed by the cable-company
such cases, an approximate method of real-time rating analysis Felten&Guilleaume, Cologne, as a Principal Engineer for power cable
based on the current measurements alone may prove to be systems. Since 1977 he is a member of the faculty of the Gerhard-Mercator-
very beneficial. Such a method has been presented in this University of Duisburg and since 1992 professor for electrical power
transmission. At time he is a member of CIGRE WG21-05 („transient effects
paper. on long cables“). Prof. Brakelmann is author of more than 100 technical
The calculation of the loss factor as a function of conductor publications and of three book-publications in the field of cable technique as
temperature has also been introduced. The error that is well as high-voltage and high-current problems
obtained in estimating the conductor temperature will depend
on the loading of the cable with reference to the nominal load.

You might also like