You are on page 1of 2

ANNEXURE - II

BHEL/ISG VOLTAGE DROP CALCULATION SHEET FOR LT POWER CABLES Doc No: IS-4-DC-598-100-E10
BUDGE BUDGE UNIT - 3 CHP & AHP Rev. 0.0 Date: 17.10.07

Sl.no Equipment Rating of Min Size of the No. of Res/KM Reac./Km Current Length of % drop during % drop at start Remarks
the current cable ( Core run (Ohm/km) (ohm/km) rating of the the cable run
equipment carrying X Sqmm) cable (Ic) in (L) in Mts.
(KW) capacity of Amp (as per
cable catalogue)
(Min.Ic)
Amp
1 Conv - 9 75 289.5 3CX95 2 0.384 0.083 155 150 1.6065 5.12319816
2 Conv - 13 45 173.7 3CX50 2 0.770 0.086 105 150 1.80252 4.631828832
3 Motor for DS 37 142.82 3CX95 1 0.384 0.083 155 100 1.05672 3.369925901
Motor for DS 75 289.5 3CX95 2 0.384 0.083 155 150 1.6065 5.12319816
4 Fdr for Scoop 5.5 21.23 3CX16 1 2.290 0.090 51 500 4.1492 8.65152288
Coup.(SFU)
5 Welding Socket 23.5305 63A 3.5C X 50 1 0.770 0.093 105 250 3.16155798 No starting drop
considered. Feeder rating
considered as 63 A,
corresponding KW has
been taken.
6 Lighting 90 240.96386 3CX70 2 0.532 0.083 130 30 0.513432 No starting drop
Feeder(100KVA considered. Feeder rating
) considered as 100 A,
corresponding KW has
been taken.
7 RIO Feeder 11.952 32A 3CX16 1 2.290 0.090 51 50 0.90165888 No starting drop
considered. Feeder rating
considered as 32 A,
corresponding KW has
been taken.
8 Hooter feeder 3.7 14.282 3CX2.5(Cu) 1 8.71 0.234 24 100 2.1040864 4.201177444
9 LCP for Sump 15.5 59.83 3C X 25 1 1.440 0.088 70 200 2.987904 6.682115174
Pump (SFU)
10 Ventilation MCC 3.7 14.282 3CX2.5(Cu) 1 8.71 0.234 24 50 1.0520432 2.100588722

11 C102A 75 289.5 3CX95 2 0.384 0.083 155 200 2.142 6.83093088


12 C103A 75 289.5 3CX95 2 0.384 0.083 155 150 1.6065 5.12319816
13 C104A 90 347.4 3CX120 2 0.305 0.082 180 250 2.6388 9.15906528

Prepared and Checked by: P.JANA


Apprd by: M.A.KAMATH Page: 1 of 2
ANNEXURE - II

Sl.no Equipment Rating of Min Size of the No. of Res/KM Reac./Km Current Length of % drop during % drop at start Remarks
the current cable ( Core run (Ohm/km) (ohm/km) rating of the the cable run
equipment carrying X Sqmm) cable (Ic) in (L) in Mts.
(KW) capacity of Amp (as per
cable catalogue)
(Min.Ic)
Amp
14 DE Feeder 23.5305 63A 3.5C X 50 1 0.770 0.093 105 200 2.529246384 No starting drop
(SFU) considered. Feeder rating
considered as 63 A,
corresponding KW has
been taken.
15 Electric Hoist 11.952 32A 3CX16 1 2.290 0.090 51 150 2.70497664 No starting drop
considered. Feeder rating
considered as 32 A,
corresponding KW has
been taken.
16 Tripper Feeder 30 115.8 3CX70 1 0.532 0.083 130 300 3.42288 9.731581056

17 Clinker Grinder 5.5 21.23 3CX10 1 3.60 0.099 40 100 1.293336 2.588256634
18 Conv Air 160 617.6 3CX300 2 0.123 0.079 315 50 0.46656 2.350176768
compressor
19 ESP Fluidising 18 69.48 3CX25 1 1.44 0.088 70 100 1.734912 3.879937843
Blower
20 Heater for 16 61.76 3CX25 1 1.44 0.088 70 100 1.542144 3.448833638
fluidising air
21 IA compressor 160 617.6 3CX300 2 0.123 0.079 315 100 0.93312 4.700353536
22 Air drier 9.3 29.9088 3C X 16 1 2.290 0.090 51 100 1.403184 2.925787738
23 Over flow 75 289.5 3CX95 2 0.384 0.083 155 150 1.6065 5.12319816
transfer pump

Prepared and Checked by: P.JANA


Apprd by: M.A.KAMATH Page: 2 of 2