You are on page 1of 3

<<Contents>> <<Index>>

General RY2
Specifications Wet Contact Relay Input Card

GS 77J06B02-01EN

n GENERAL n I/O SPECIFICATIONS


This unit receives wet contact signal from the field Input signal: Wet voltage contact
and outputs 2 contact signals (1 for use of DCS status Output signal: Relay contact, 2 points
card input and the other is re-transmit contact signal) (Output 1: DCS output
isolated electrically from the field. One unit stores 2 Output 2: Re-transmit signal output)
channels. Contact rating:
• Output contact consists of 2 contacts; 1 for DCS Output 1: 30 V DC 0.2 A (both resistance and
contact and the other for re-transmit contact (transfer inductance loads)
contact) of current capacity 1 A. Output 2: Resistance load: 125 V AC 0.4 A
• The circuits between wet contact input signal and 30 V DC 1 A
output signal is isolated electrically isolated by means Inductance load: 125 V AC 0.2 A
of photo-isolator. 30 V DC 0.5 A
• Furnished with test switch convenient for debugging Maximum voltage used: 250 V AC/125 V DC
of DCS or checking operation and LED for status Relay contact protection: When driving
display. inductance load, erase the noise to
protect contact.

n MODEL AND SUFFIX CODES


n STANDARD PERFORMANCE
RY2- Insulation resistance: 100 MΩ (500 V DC) between
Model CH1 input - CH2 input - [CH1•CH2 output
Wet contact relay input card (2 channels/card) 1•power supply] - CH1 output 2 - CH2
output 2 - alarm contact output
Input Signal
1: 100 V AC Wet voltage contacts (85 to 132 V AC)
Voltage withstand: 1500 V AC/1 minute between CH1
2: 200 V AC Wet voltage contacts (170 to 264 V AC) input - CH2 input - CH1 output 2 - CH2
3: 24 V DC Wet voltage contacts ( 24 V DC±10%) output 2 - [CH1•CH2 output 1•power
4: 100 V DC Wet voltage contacts (100 V DC±10%) supply] - alarm contact output
(Contact Marketing Dept when code 4 is required)
However, except between [CH1•CH2
Test switch output1•power supply] and alarm contact
0: No test switch output.
1: With test switch (AUT-OFF-ON) F01.ai
500 V AC/ 1 minute between [CH1•CH2
output 1•power supply] - alarm contact
output
n ORDERING INFORMATION Ambient temperature & humidity
(Example) Type Code: RY2-11 Normal operating condition: 0 to 50°C, 5
to 90% RH
Operating limit: -10 to 60°C, 5 to 95%RH
n DEVICE SPECIFICATIONS Storing condition: -40 to 70°C, 5 to
Structure: Nest storing type, connector connection 95%RH (no condensation)
structure card type, front by terminal Power supply voltage: 24 V DC±10% (ripple content
and rear by connector. Terminal cover below 5% p-p)
furnished. Current dissipation: 24 V DC 50 mA
Isolation: Between input - output 1 - output 2 - alarm
terminal - power supply
(Isolation by photo isolator between input n MOUNTING, SHAPE &
and relay circuit) ACCESSORIES
Power fuse: 0.5 A alarm fuse installed at power lines Mounting method: Store in exclusive nest (RYH or
for relay RYV)
Alarm: Output of dry contact is generated from alarm Connection method:
terminals of nest when power fuse is OFF. Input: M3.5 screw terminal connection
Test switch: Output 1 (DCS output): Connector connection
AUT: Output contact ON/OFF through Output 2 (re-transmit output): M3.5 screw terminal
external contact input connection
OFF: O  utput contact compulsorily OFF in Alarm terminal: Connector connection
case of a-contact. Power supply: Connector connection
ON: O utput contact compulsorily ON in Material of terminal screw: Nickel plated on iron
case of a-contact. (fastening torque below 8 kgf.cm)
LED indication: Light on (green) when relay External dimension: 108 (H) × 21.4 (W) × 129.6 (D) mm
magnetized Mass: About 150 g
Accessories: Tag number label 1

GS 77J06B02-01EN
©Copyright Dec. 2015
1st Edition Dec. 2015
<<Contents>> <<Index>> 2

n TERMINAL ARRANGEMENT

×
9 10
Ter m inal Si gnal LED ( C h- 1)
No. 7 8
1 Contac t i nput ( − ) 5 6
( Fi el d s i de) Tes t s w i tc h
C 3 Contac t i nput ( + ) ( C h- 2)
H ( Fi el d s i de)
1 5 b- c ontac t output
7 a- c ontac t output
9 Common Tes t s w i tc h
2 Contac t i nput ( − ) ( C h- 1)
( Fi el d s i de)
C 4 Contac t i nput ( + ) 3 4
H ( Fi el d s i de)
1 2 LED ( C h- 1)
2 6 b- c ontac t output
8 a- c ontac t output
10 Common
×
F02.ai

n BLOCK DIAGRAM
Mul ti -poi nt status i nput card

Output-1 Output-1

RL1 RL2

Alarm contact
output

F1 Alarm fuse F2

24 V relay power
RL1 RL2
supply


Test SW
AUT ON AUT ON

OFF OFF

RL1 RL2

Input circuit Input circuit

1 3 5 7 9 2 4 6 8 10
NC NO COM NC NO COM
Input Output-2 Input Output-2
(Re-transmit output) (Re-transmit output)
Ch1 Ch2
Odd number channel Even number channel
when nest storing when nest storing
F03.ai

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 77J06B02-01EN Dec. 25, 2015-00
<<Contents>> <<Index>> 3

n EXTERNAL DIMENSION
Unit: mm
129.6 21.4

45.5 10.7
2-M3 mounting screw

92.6
108 96.8

10-M3.5×7 screw
F04.ai

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 77J06B02-01EN Mar. 31, 2015-00
Subject to change without notice.