Professional Documents
Culture Documents
Cong-Duc PHAM1, Bertrand RAISON1, Sylvain MARTINO1, Isabelle GAL2, Sylvie BONNOIT3
(1) GIE-IDEA –Grenoble – France (2) SCHNEIDER Electric (3) EDF R&D
Laboratoire d'Electrotechnique de Grenoble – DMDA Département MIRE
ENSIEG : BP46 – 38402 Saint Martin d’Hères Site M4 1, Avenue du Génégal de Gaulle
Cedex - France 38050 Grenoble Cedex 9 92141 Clamart Cedex
I. Introduction
A - Generalities
Currently, there are many FPI types in service on the
distribution networks, whose characteristics depend on:
• The type of network (overhead or underground)
• The type of detected faults
• The type of measurement of the electric variables (direct
or indirect)
Sleep
Sleep
No
Calculation of dephasing
of two fundamental (ϕr)
Figure 2: Algorithm of FPI’operation
Determination of fault
Fault passage block for Non directional detection direction
It uses the phase current by comparing its amplitude with a
given threshold. This FPI is called « FPI_ND1 ».
Indication
I current RMS value of
Slee
measurement the current
Figure 4: Directional detection algorithm
Table1: Principal characteristics of the network Table 1: FPI_ND1 outputs with faults in C0505 network
without DG sources
We chose 6 different positions for FPI installation (fig. 6).
They are located at the intersections of secondary branches B – C0505 network with DG source
with the main branch and along the main branch of the We insert a DG source (a 10MVA alternator -this value close
network. to the acceptable limit fixed by the French regulations- and a
We also set the points of fault (three-phase, single-phase...). transformer) in this network (fig. 6).
We propose a fault resistance of 1Ω. The fault detection is Table 2 presents the IPD_ND1 simulation results. The
tested for each FPI type. To simulate influence of the circuit thresholds of FPI are identical to the preceding case.
breakers on the operation of FPI, a circuit breaker is placed at It is noted that as three-phase or two-phase faults occur, FPI
the beginning of this network. The principle of operation of located between the DG and the point of fault provide an
the circuit breaker rests on the over current of phase currents indication of fault presence (greyed value 1). This
as fault occur. It will open 300 ms after the fault detection. phenomenon causes bad fault detection: FPI indicates a fault
We have not included the reclosing sequences. after FPI5.
DT FA
Table 2: FPI_ND1 outputs with faults in C0505 network
FPI 5
with DG sources
fault3
If we replace this DG source by one another one with a
IV. Results
Figure and network
6: Urban discussion
C0505 with the loads, the 1.2MW power, the results of simulation are identical to the
switchgear, the positions of FPI and fault considered case without DG. The fault current starting from the DG
Non directional FPI detecting the fault thanks to the phase source is too weak compared to the threshold selected. This
current (FPI_ND1) are very often used in distribution means that we can detect the fault whilst this DG source
networks. One tests the operation of this FPI type in the functions.
C0505 network without and with DG source for various fault
types: three-phase current (T), two-phase ground (B), and
single-phase current (M). V. Improvements and results
The thresholds on the FPI inputs are identical in all cases.
When a huge power DG source is connected to the network,
A – C0505 network without DG source false indications can be produced with non directional FPI
Table 1 presents the FPI_ND1’ simulation results for the FPI_ND1.
various faults. 0 means that FPI does not see the fault. All the To avoid this problem, directional FPI can be used. We
results are correct; it is possible to determine the fault section: propose to use FPI based on phase current and phase voltage
- fault1 lies well between IPD4 and IPD5 (FPI_D1) or FPI based on residual current and voltage
(FPI_D0). These FPI have three possible values for their in the distribution network: what are the conditions to fulfil in
output: 0 –no fault detected, 1 – the fault is upstream from the order to ensure that a non directional FPI will give correct
FPI, -1- the fault is downstream from the FPI. indications or the fault detection will always be possible?
One can note that DG insertion modifies the power flows and
A – FPI_D1 utilisation leads to possible false indications from non directional FPI.
The thresholds are the same as those used with FPI_ND1. Using directional FPI can be for the moment a solution.
• If the DG source is not connected to the network, the This work will pursue following different directions:
results are the same as those presented in Table 1. • Development of more refined models of FPI (in the
• If the DG source is connected, the results are quite the acquisition stage, the calculation stage).
same as those presented in Table 2: the grey values are • Neutral regimes influence on FPI behaviours.
replaced by -1 (see Table 3). • FPI and DG position influence on produced indications.
It is thus possible to detect the fault in each case.
VI. Conclusions