You are on page 1of 4

CIRED 17th International Conference on Electricity Distribution Barcelona, 12-15 May 2003

DISPERSED GENERATION INFLUENCE ON FAULT PASSAGE INDICATOR RESPONSE

Cong-Duc PHAM1, Bertrand RAISON1, Sylvain MARTINO1, Isabelle GAL2, Sylvie BONNOIT3

(1) GIE-IDEA –Grenoble – France (2) SCHNEIDER Electric (3) EDF R&D
Laboratoire d'Electrotechnique de Grenoble – DMDA Département MIRE
ENSIEG : BP46 – 38402 Saint Martin d’Hères Site M4 1, Avenue du Génégal de Gaulle
Cedex - France 38050 Grenoble Cedex 9 92141 Clamart Cedex

I. Introduction

The main purpose of an electrical network is to transfer Senso Processin Indicatio


electricity from production plants to the customers.
Distribution networks perform the connexion to final
customers and have to fulfil services and a good power Power
quality. The network management is in fact often a grant
given to a distributor who has to ensure safety and security. Figure 1: FPI structure
Faults detection is therefore of first importance in this
management. Sensor: It may measure phase or residual currents, or
voltages. These measurements can be direct (transformers) or
To perform the fault detection, Fault Passage Indicators (FPI) indirect via magnetic field sensors (that give an image of the
can be used. As a permanent fault occurs, they make it currents) and electric field sensors (for the voltage) [1], [3].
possible to locate the faulty part of the network and isolate it Processing: The principle of fault detection consists in
from the sane parts. A FPI may give the following carrying out comparisons between the inputs and specific
information: thresholds like amplitude, di/dt, sometimes with load
- Local visual signs, tracking. It is possible to detect several types of fault.
- Remote information to SCADA [1],[2]. Indication: After the inputs processing, the FPI emits signals
It can also be used to give information in order to isolate non if it has detected a fault. These signals are luminous (red,
permanent faults. green flashes) or sound. They can be sent to SCADA for
remote fault location and purposes.
The combined heat and power production development and
the interest for renewable energies (biomass, wind energy…)
have led to an increase of the auto producers’ number. These B – Algorithm
producers have to be connected to the network. This is the The principle of operation of simulated FPI consists in giving
evolution of the network with the introduction of dispersed an immediate indication when crossing a threshold. The
generation (DG) sources. duration of indication depends on the type of fault [4]:
• Non-permanent fault: reset (return to the state before)
The fault detection subject has already been treated but the after 3s activation of the line,
DG development throws back fault detection methods into • Permanent fault: indication is maintained during 40s.
question. Actually, the power flows are modified and the
signal magnitudes are transformed too. Our study deals with General algorithm of FPI operation is presented at fig. 2.
the influence of DG insertion on the fault detection by FPI.
These devices are simulated and tested on a distribution The block "Fault Passage" is the most significant. It includes
network under different conditions: without or with DG the fault detection as well as the fault direction determination.
sources, with different neutral systems. In this paper, we consider thresholds on amplitude of the
currents and voltages. Two types of detection are studied [3],
[5]:
II. FPI models

A - Generalities
Currently, there are many FPI types in service on the
distribution networks, whose characteristics depend on:
• The type of network (overhead or underground)
• The type of detected faults
• The type of measurement of the electric variables (direct
or indirect)

A FPI can present the following structure (fig. 1):

LEG_Pham_A2 Session 4 Paper No 42 -1-


CIRED 17th International Conference on Electricity Distribution Barcelona, 12-15 May 2003

Sleep
Sleep

Residual current Ir (kA)


Residual voltage Vr (kV)
No
Fault passage

Parameter Calculation of value


Yes
- I : phase current RMS of Ir and of Vr
Indication - Is : thresholds on
phase current
- V : nominal phase
Ir (RMS) > Ir s or
voltage Vr (RMS) > Vrs
Start timer T - Vs : thresholds on No
phase voltage Yes
- Ir : residual current
- Vr : residual voltage
Irs : thresholds on Vr(RMS) > Vr s
Yes -
Line energized residual current during ∆t No
T> 3 sec
Yes
No
Determination of
Yes fundamental (50 Hz) of
T > 40sec Ir and of Vr

No
Calculation of dephasing
of two fundamental (ϕr)
Figure 2: Algorithm of FPI’operation

Determination of fault
Fault passage block for Non directional detection direction
It uses the phase current by comparing its amplitude with a
given threshold. This FPI is called « FPI_ND1 ».
Indication
I current RMS value of
Slee
measurement the current
Figure 4: Directional detection algorithm

I(RMS) > Is III. Performed studies presentation


during ∆τ
No
To study the operation of FPI in distribution networks and
Ye the influence of DG source integration on it, a simulation of
FPI is carried out with ARENE software, developed by EDF
Indicatio (modelling of the considered networks and creation of the
faults) and MATLAB (coding developed for the description
of the operation of FPI in the network).
We use the two types of FPI described above
Figure 3: Non directional detection algorithm
ARENE MATLAB
Fault passage block for Directional detection • Programming
• Simulation of
Directional detection uses the phase current and the phase • Visualization of the
the networks
voltage (FPI_D1) to determine the direction of the fault results
thanks to phase displacement between these two parameters • Creation of
[5]. For asymmetrical faults, this method is applied with the the fault
residual current and the residual voltage (FPI_D0) [6]. Fig. 4 • Recovery of
presents directional detection algorithm thanks to residual the data of MODEL of FPI
current and residual voltage (the algorithm thanks to the current and • Algorithm of detection
phase current and phase voltage is identical). voltage • Software of simulation

LEG_Pham_A2 Session 4 Paper No 42 -2-


CIRED 17th International Conference on Electricity Distribution Barcelona, 12-15 May 2003

Figure 5: Principle of FPI simulation - fault2 is well located after IPD6


- fault3 is well understood after IPD1 (connects
We used the urban distribution network called C0505 set up secondary)
within GIE-IDEA. It has an impedance neutral system (as for
the underground power networks in France). A DG source is Faults FPI_ND1 outputs according to position
also introduced into this network. 1 2 3 4 5 6
Healthy 0 0 0 0 0 0
1 M 1 1 1 1 0 0
Capacitive of the network (3 Io in A) (under 20 37.2
B 1 1 1 1 0 0
kV) 1 1 1 1 0 0
T
Total apparent power (kVA) 4509 2 M 1 1 1 1 1 1
Icc two-phase min. (A) 2251 B 1 1 1 1 1 1
Proportion of buried cable (% overall length) 100 T 1 1 1 1 1 1
Length of the longest line (km) 12.29 3 M 1 0 0 0 0 0
Total length of network (km) 15.65 B 1 0 0 0 0 0
Neutral system impedance T 1 0 0 0 0 0

Table1: Principal characteristics of the network Table 1: FPI_ND1 outputs with faults in C0505 network
without DG sources
We chose 6 different positions for FPI installation (fig. 6).
They are located at the intersections of secondary branches B – C0505 network with DG source
with the main branch and along the main branch of the We insert a DG source (a 10MVA alternator -this value close
network. to the acceptable limit fixed by the French regulations- and a
We also set the points of fault (three-phase, single-phase...). transformer) in this network (fig. 6).
We propose a fault resistance of 1Ω. The fault detection is Table 2 presents the IPD_ND1 simulation results. The
tested for each FPI type. To simulate influence of the circuit thresholds of FPI are identical to the preceding case.
breakers on the operation of FPI, a circuit breaker is placed at It is noted that as three-phase or two-phase faults occur, FPI
the beginning of this network. The principle of operation of located between the DG and the point of fault provide an
the circuit breaker rests on the over current of phase currents indication of fault presence (greyed value 1). This
as fault occur. It will open 300 ms after the fault detection. phenomenon causes bad fault detection: FPI indicates a fault
We have not included the reclosing sequences. after FPI5.

Note: Faults FPI_ND1 outputs according to position


Ο : Networks LV connected to network MV 1 2 3 4 5 6
studied, Fault2
Healthy 0 0 0 0 0 0
1 M 1 1 1 1 0 0
: Customers MV.
B 1 1 1 1 1 0
∆ : Principal source (bond towards HV). T 1 1 1 1 1 0
FPI 6 1 1 1 1 1 1
2 M
B 1 1 1 1 1 1
FPI 3
FPI 1
T 1 1 1 1 1 1
FPI 4 DG source 3 M 1 0 0 0 0 0
C0505
FPI 2
Fault1 B 1 1 1 1 1 0
T 1 1 1 1 1 0

DT FA
Table 2: FPI_ND1 outputs with faults in C0505 network
FPI 5
with DG sources
fault3
If we replace this DG source by one another one with a
IV. Results
Figure and network
6: Urban discussion
C0505 with the loads, the 1.2MW power, the results of simulation are identical to the
switchgear, the positions of FPI and fault considered case without DG. The fault current starting from the DG
Non directional FPI detecting the fault thanks to the phase source is too weak compared to the threshold selected. This
current (FPI_ND1) are very often used in distribution means that we can detect the fault whilst this DG source
networks. One tests the operation of this FPI type in the functions.
C0505 network without and with DG source for various fault
types: three-phase current (T), two-phase ground (B), and
single-phase current (M). V. Improvements and results
The thresholds on the FPI inputs are identical in all cases.
When a huge power DG source is connected to the network,
A – C0505 network without DG source false indications can be produced with non directional FPI
Table 1 presents the FPI_ND1’ simulation results for the FPI_ND1.
various faults. 0 means that FPI does not see the fault. All the To avoid this problem, directional FPI can be used. We
results are correct; it is possible to determine the fault section: propose to use FPI based on phase current and phase voltage
- fault1 lies well between IPD4 and IPD5 (FPI_D1) or FPI based on residual current and voltage

LEG_Pham_A2 Session 4 Paper No 42 -3-


CIRED 17th International Conference on Electricity Distribution Barcelona, 12-15 May 2003

(FPI_D0). These FPI have three possible values for their in the distribution network: what are the conditions to fulfil in
output: 0 –no fault detected, 1 – the fault is upstream from the order to ensure that a non directional FPI will give correct
FPI, -1- the fault is downstream from the FPI. indications or the fault detection will always be possible?
One can note that DG insertion modifies the power flows and
A – FPI_D1 utilisation leads to possible false indications from non directional FPI.
The thresholds are the same as those used with FPI_ND1. Using directional FPI can be for the moment a solution.
• If the DG source is not connected to the network, the This work will pursue following different directions:
results are the same as those presented in Table 1. • Development of more refined models of FPI (in the
• If the DG source is connected, the results are quite the acquisition stage, the calculation stage).
same as those presented in Table 2: the grey values are • Neutral regimes influence on FPI behaviours.
replaced by -1 (see Table 3). • FPI and DG position influence on produced indications.
It is thus possible to detect the fault in each case.

Faults FPI_D1 outputs according to position References:


1 2 3 4 5 6
Healthy 0 0 0 0 0 0
1 M 1 1 1 1 0 0 [1] Schneider Electrique
B 1 1 1 1 -1 0 Merlin Gerin - Bardin range – Network fault passage
T 1 1 1 1 -1 0 indicator
2 M 1 1 1 1 1 1
B 1 1 1 1 1 1 [2] |SEG – Schaltanlagen-Elektronik-Gerate GmbH &
T 1 1 1 1 1 1 Co.KG
3 M 1 0 0 0 0 0 EFI1 Earth fault indicator for medium voltage systems
B 1 -1 -1 -1 -1 0
T 1 -1 -1 -1 -1 0 [3] N.P. Tobin (Consultant Engineer, Ireland) – M
McCormack – E O’Loughlin – K Tobin (SMF Technology,
Table 3: FPI_D1 outputs with faults in C0505 network with Ireland)
DG sources Remote current sensing on overhead power lines

B – FPI_D0 utilisation [4] User guide: LINETROLL 111K (Programmable fault


These devices are used to detect only asymmetrical faults: current indicator for overhead line)
they cannot detect therefore the three phase faults. NORTROLL AS - September 1995
Their outputs are the same without or with DG sources (see User guide: LINETROLL 3000 (Programmable fault
Table 4). current sensor for overhead line)
NORTROLL AS - September 1999
Faults FPI_D0 outputs according to position
1 2 3 4 5 6 [5] Christophe Prévé
Healthy 0 0 0 0 0 0
1 M 1 1 1 1 -1 -1
Protection des réseaux électriques
B 1 1 1 1 -1 -1 HERMES - 1998
T 0 0 0 0 0 0
[6] Dispositif détecteur de défauts homopolaires sur un
2 M 1 1 1 1 1 1
B 1 1 1 1 1 1 réseau de distribution électrique.
T 0 0 0 0 0 0 Demande de Brevet Européen : N° de dépôt: 94402721.8
3 M 1 -1 -1 -1 -1 -1
B 1 -1 -1 -1 -1 -1
T 0 0 0 0 0 0

Table 4: FPI_D0 outputs with faults in C0505 network with


DG sources

The simulation results are correct: the fault can be detected


between two FPI with opposite signal outputs.

VI. Conclusions

In this paper, models of fault passage indicators have been


presented (non directional and directional FPI models). These
models have been tested with simulation signals from a MV
distribution network without or with dispersed generation
sources.
Our goal is to establish “rules” in FPI use with DG insertion

LEG_Pham_A2 Session 4 Paper No 42 -4-

You might also like