Professional Documents
Culture Documents
Presented by
Prof. M. L. Chen
Dept. of Building services Engineering
The Hong Kong Polytechnic University
1
Three-phase a.c Systems
Three-phase Supply
Balanced three-phase system
Unbalanced three-phase systems
Three-phase system in buildings
Power in a three-phase system
Focus on Phasor Expression, /Y
Transformation, Power calculation.
2
1.Three-phase Supply
•Three-phase = three independent ac with same frequency
and their phase voltages have:
VA =V0˚; VB =V-120˚; VC =V-240˚ =V+120˚.
•Phasor diagram & line voltage: VAB = VA -VB =3V30˚;
VBC = VB -VC =3V-90˚;
VA VAB VAC
VCA VAB
VCA = VC -VA =3V-210˚
1200
1200
VCB VBC
=3V150˚.
1200 VA + VB + VC = 0;
VC VB
VAB + VBC +VCA = 0;
VAB = - VBA = VBA-180˚
VBC
VCA VBA
VBlue
VBlue
6
Per-phase equivalent circuit .
Ir R Iline
Z1
Eb Er In Z1 Vs Z2/3
n n’ n
Ey Iy Y
B Ib Z2
8
i)Three-phase four-wire system
R Ir
Er Zr
Eb n In n’ Zy
Zb
Ey Y Iy
B Ib
I r Er Z r
I y Ey Z y
I b Eb Z b
I n Ir I y Ib 9
ii)Three-phase three-wire system –Y/
R Ir
Er Zbr Zry
Eb n
Zyb
Ey Y Iy
B Ib
I ry Ery Z ry I r I ry I br
I yb E yb Z yb I y I yb I ry
I b I br I yb
I br Ebr Z br
10
iii)Three-phase three-wire system -Y/Y
R Ir
Er Zr
Eb n n’ Zy
Zb
Ey Y Iy
B Ib
E rb I r Z r Z b I y Z b Ir
Erb ( Z y Z b ) E yb Z b
E yb I r Z b I y Z y Z b
2
( Z r Z b )( Z y Z b ) Z b
E yb ( Z r Z b ) Erb Z b
Iy
For neutral points n,n’: ( Z r Z b )( Z y Z b ) Z b
2
Vnn' E r I r Z r I b I r I y
11
iv) 3-3-wire system -Y/ Transformation
• Can transform the Y into or into Y connection.
VR VR
Ibr Iry
Zr Ir Zbr Z
Zb
Iy Zyb
ry
VY
VY
Zy
Ib Iyb
VB VB
Y Y
Z ry Zr Z y Zr Z y Zb Z r Z ry Z br Z ry Z yb Z br
Z yb Z y Z b Z y Z b Z r Z y Z yb Z ry Z ry Z yb Z br
Z br Z b Z r Z b Z r Z y Z b Z br Z yb Z ry Z yb Z br
12
4. Three-phase system in buildings
• Loads - Depending on the power rating there are
three-phase and single-phase machines. 3-phase
motors much efficient than 1-phase motors.
• Sources - Three-phase, 380V/220V. Besides
supplying those three-phase loads, three-phase-four
wire supply system can also supply those single-
phase loads inside a building.
• Connection - Single-phase loads are being arranged
in away so as to be evenly distributed among the
three single-phase sources.
13
5. Power in three-phase systems
• Balanced Circuits: 3-phase = 3 single-phase.
1-phase circuit 3-phase circuit
S (kVA) VI or VI* 3V I =3VlIl
P (kW) VI cos =I2R 3V I cos =3VlIl cos
Q (kVar) VI sin =I2X 3V I sin =3VlIl sin
• 1-phase power measurement – Using a wattmeter
(voltage ¤t coils). Reading W=P =Real (S).
• Balanced Y-connected loads – Wtotal=3 x W1-phase
• Unbalanced 4-wires Y-connected loads – Total real
power = sum of wattmeter readings for all 3 phases.
14
Unbalanced 3-wires Y-connected loads
R Ir w
Er Zr
Eb n n’ Zy
Zb
Ey Y Iy
B Ib
w
Two-wattmeter method:
S1 S 2 Ery I r * Eby I b *
( Er E y ) I r * ( Eb E y ) I b *
Er I r * E y ( I r * I b *) Eb I b *
Er I r * E y I y * Eb I b * Stotal
15
Unbalanced 3-wires -connected loads
R Ir
w
Er Zbr Zry
Eb n
Zyb
Ey Y Iy
B Ib
w
Two-wattmeter method:
S1 S 2 Ery I r * Eby I b *
Er I r * E y I y * Eb I b * Stotal
16
Example 1
Q.You are required to design a three-phase 18 kW
instantaneous water heater. Find the resistance of
the three resistors if they are connected in (i) star,
(ii) delta without star/delta transformation, and
(iii) delta with delta/star transformation.
Ans. Given P =18kW, three-phase.
Assume the line voltage is V=380V, line current
is I, and 3 pure resistors R are used. Then,
P =3 VI.
I =18000W/(3*380V) = 27.3A.
17
Example 1 – Answer (i)
(i) For star connected resistors:
Red I
Vp, Ip R
Ep s
n V n’
Yellow
Blue
Rs = Vphase/Iphase =(V/3)/I
=(380/3)/27.3 =8.07
18
Example 1 – Answer (ii)
(ii) For delta connected resistors without using
star/delta transformation:
Red I
Ep Rd Vp Rd
n
V Rd Ip
Yellow
Blue
Rd = Vphase/Iphase =V/(I/3)
=380/(27.3/3) =24.2 =3Rs
19
Example 1 – Answer (iii)
(iii) For delta connected resistors, using star/delta
transformation:
I I
Ibr
Rr Ir V R Iry V
Iy Rbr ry
Rb Ryb
Ry
Ib Iyb
Rry = Rr+Ry+Rr*Ry/Rb
Since Rr=Ry=Rb=Rs
Rd = Rry = Rs + Rs + Rs * Rs /Rs
=3Rs =24.21
20
Example 2
Q.A star connected three-phase supply with voltage 346 V is
supplying three single-phase loads each rated at 200V. A
820W toaster is connected to red phase, an hair dryer of
1200W is connected to the yellow phase and lastly a 100W
tungsten filament lamp connected to blue phase. The neutral
conductor at the source-end is disconnected accidentally.
Find the line currents. State all the assumptions clearly.
(Hint: Try to use Mesh Equations to calculate and then change the
loads to delta-connected equivalent by star/delta transformation
and calculate again. Compare the two methods, you will find
the usefulness of star/delta or delta/star transformation.)
21
Example 2-Answer
Red Ir
Eb
n Er=200V Vry=346V n’ Rr
Ry
Yellow Iy Rb
Ey
Blue Ib
24
Example 3 - Answer
A.Since the source is 346V delta-connected, and the loads
are in balance, this circuit can be analyzed by using
single-phase equivalent circuit.
Assume both load and capacitor are star-connected.
load per phase ZL = 346V2/300kVA = 0.4
pf = 200kW/300kVA = 0.667= cos
ZL = 0.448.16 =0.27+j0.3
Capacitor, ZC = 346V2/60kVAr=2-90= -j2
For each phase, ZL and ZC are in parallel, the single-phase
equivalent circuit is as following:
25
Example 3 – Answer (continue)
Iphase 0.01 70
IC IL
200V ZC ZL
The end
27