You are on page 1of 41

Lecture 4

Unbalanced Three-Phase
Systems
LEARNING OUTCOMES

After completing this lesson you will be able to:


Introduction
So far, we have considered balanced loads connected to balanced
systems. It is enough to solve problems, considering one phase only
on balanced loads; the conditions on other two phases being similar.
Problems on unbalanced three-phase loads are difficult to handle
because conditions in the three phases are different. However, the
source voltages are assumed to be balanced. If the system is a
three-wire system, the currents flowing towards the load in the three
lines must add to zero at any given instant. If the system is a four-
wire system, the sum of the three outgoing line currents is equal to
the return current in the neutral wire. We will now consider different
methods to handle unbalanced star-connected and delta-connected
loads.
Definition

An unbalance exists in a circuit when the impedances in


one or more phases differ from the impedances of the other
phases. In such a case, line or phase currents are different
and displaced from one another by unequal angles.

In practice, we may come across the following unbalanced loads:

1. Unbalanced four-wire star-connected load


2. Unbalanced three-wire star-connected load, and
3. Unbalanced delta-connected load
In practice, we may come across the following unbalanced loads:

1. Unbalanced four-wire star-connected load


2. Unbalanced three-wire star-connected load, and
3. Unbalanced delta-connected load
Unbalanced Four Wire Star-Connected Load

Figure below shows an unbalanced star load connected to a


balanced 3-phase 4-wire supply.

• The star point, NL, of the load is connected to the star point, NS of
the supply.
• It is the simplest case of an unbalanced load because of the
presence of the neutral wire; the star points of the supply NS
(generator) and the load NL are at the same potential.
Unbalanced Four Wire Star-Connected Load (continued)

• It means that the voltage across each load impedance is equal


to the phase voltage of the supply (generator), i.e. the voltages
across the three load impedances are equalised even though
load impedances are unequal.
Unbalanced Four Wire Star-Connected Load (continued)

Taking the phase voltage

V RN  V 0 V
as reference, and assuming RYB phase sequences, we have the
three phase voltages as follows:

V RN  V 0 V; V YN  V   120 V

V BN  V 120 V
Unbalanced Four Wire Star-Connected Load (continued)

The phase currents can therefore be determined by Ohm’s law;

V RN V0 V
IR      1 A
Z1 Z 11 Z 1

VYN V  120 V
IY      120   2 A
Z2 Z 2 1 Z2
Unbalanced Four Wire Star-Connected Load (continued)

V B V120 V
IB    120  3 A
Z3 Z 3 3 Z3
Unbalanced Four Wire Star-Connected Load (continued)

Obviously, the current in each phase (or line) will be different. Hence,
the vector sum of the currents in the three lines is not zero, but is
equal to neutral current, i.e.

I N  I R  IY  I B  0
Worked Example 1

For the system below:


i. Calculate the magnitude of the voltage across each phase
of the load.
ii. Find the magnitude of the current through each phase of
the load.
iii. Determine the neutral current.
iv. Find the total watts, volt-amperes reactive, and volt-amperes.
Assume RYB phase sequence.
IR
R

ZR = (10 + j10)
208 V
208 V IN
N
ZB = (12 + j12) 

IY ZY = (2 + j2) 
Y
208 V
IB
B
Solution

Let V RN be the reference phasor; that is let


208
V RN  0  1200 V
3
Then
208
V YN    120  120 - 120 V
3
and
208
V BN  120  120120 V
3
The phase currents are

VRN 1200
IR    6  j 6  8.485  45 A
Z R 10  j10

VYN 120  120


IY    40.98  j10.98  47.426  165 A
ZY 2  j2

VBN 120120
IB    1.83  j 6.83  7.0775 A
Z3 12  j12

and the neutral current is

I N  I R  I Y  I B  8.485  45  47.426  165  7.0775

 39.654  163.23 A
Worked Example 2

An unbalanced four-wire, star-connected load has a balanced


voltage of 400 V, the loads are

Z R  4  j8  ; Z Y  3  j 4   ; Z B  15  j 20 

Calculate (i) line currents


(ii) current in the neutral wire and
(iii) total power
Solution

Z 1  4  j8  8.9463.40 

Z 2  3  j 4   553.1 

Z 3  15  j 20  2553.13


Solution

Let us assume RYB phase sequence.

The phase voltage


400
V RN   230.94 V
3

Taking V RN as the reference phasor, we have

VRN  230.940 V
.
VYN  230.94  120 V

VBN  230.94120 V
Solution

The three line currents are


VRN 230.940
IR    25.83  63.4 A
Z1 8.9463.4

VYN 230  120


IY    46.188  173.1 A
Z2 553.1

VB 230120
IB    9.23  293.13 A
Z 3 2553.13
Solution
(i) To find the neutral current, we must add the three line currents.
The neutral current must then be equal and opposite to this sum.
Thus

I N  I R  I Y  I B 

 25.83  63.4  46.188 - 173.1  9.23 - 293.13 A

 11 .56  j 23.09   45.85  j 5.54  3.62  j8.48 A

 30.67  j 20.15 A
In polar form,
I R  36.6933.30 A
Solution

It’s phase with respect to is 33.3, the disposition of all the currents
is shown in the figure below.
Power in R phase,
PR  I R2  25.83  4  2668.75 W
2

Power in Y phase,

PY  I Y2  46.18  3  6397.77 W
2

Power in B phase,

PB  I B2  9.23  15  1277.89 W
2

Total power absorbed by the load

PT  PR  PY  PB
 2668.75  6397.77  1277.89 W
 10344.41 W
Unbalanced Three Wire Star-Connected Load

• In three-phase, four-wire system if the connection between


supply neutral and load neutral is broken, it would result in an
unbalanced three-wire star load.
• This type of load is rarely found in practice, because all the three
wire star loads are balanced. Such a system is shown in the
figure below. Note that the supply star point NS is different from
that of the load star point NL.
Unbalanced Three Wire Star-Connected Load

• The potential of the load star point is different from that of the
supply star point. The result is that the load phase voltage is not
equal to the supply phase voltage; and they are only unequal in
magnitude, but also subtend angles other than 120 with each
other.
• The magnitude of each phase voltage depends upon the
individual phase loads.
Unbalanced Three Wire Star-Connected Load

• The potential of the load neutral point changes according to


changes in the impedances of the phases, that is why sometimes
the load neutral is also called a floating neutral point.
• All star-connected, unbalanced loads supplied from polyphase
systems without a neutral wire have floating neutral point.
• The phasor sum of the three unbalanced line currents is zero.
The phase voltage of the load is not of the line voltage.
• The unbalanced three-wire star load is difficult to deal with. It is
because load phase voltages cannot be determined directly from
the given supply line voltages.
Solving Unbalanced Three Wire Star-Connected Loads

There are many methods to solve unbalanced Y-connected loads.


Two frequently used methods are presented here. They are:
1. Star-delta conversion method, and

2. The application of Millman’s theorem


Star-Delta Method to solve unbalanced load
Figure below shows an unbalanced star-connected load. It has
already been shown earlier that a three-phase star-connected load
can be replaced by an equivalent delta-connected load. Thus the
star-connected load can be replaced by an equivalent delta as
shown in the below, where the impedances in each phase is given
by
Z R ZY  ZY Z B  Z B Z R
Z RY 
ZB

Z R ZY  ZY Z B  Z B Z R
Z YB 
ZY
Z RZY  ZY Z B  Z BZ R
Z BR 
ZY

The problem is then solved as an unbalanced delta-connected


system. The currents so calculated are equal in magnitude and phase
to those taken by the original unbalanced wye (Y) connected load.
Example

A 400 V, three-phase supply feeds an unbalanced three-wire, star-


connected load. The branch impedances of the load are

Z R  4  j8  ; Z Y  3  j 4   ; Z B  15  j 20 

Find the line currents and voltage across each phase impedance.
Assume RYB sequence.
Solution

The unbalanced star load and its equivalent delta () is shown in the
figures below.

Z R  4  j8  8.9463.40 

Z Y  3  j 4   553.1 
Z B  15  j 20  2553.13
Solution

Calculate Z RY , Z YB and Z BR .

Z R Z Y  Z Y Z B  Z B Z R  8.9463.40553.1  55.312553.1
 2553.18.9463.4

 391.80113.23
Therefore,

Z R ZY  ZY Z B  Z B Z R
Z RY 
ZB

391.80113 .23

2553.1

 15.6760.13 
Solution

Z R Z Y  Z Y Z B  Z B Z R 391.80113 .23
ZYB  
ZY 8.9463.4

 43.8349.83

Z R Z Y  Z Y Z B  Z B Z R 391.80113.23
Z BR  
ZY 553.1

 78.3660.13
Solution

Taking V RY as reference, we can write

V RY  4000 V ; V YB  400  120 V

V BR  400120 V

Therefore,
VRY 4000
IR    25.52  60.13 A
Z RY 15.6760.13

VRY 400  120


I YB    9.12  169.83 A
Z RY 43.8349.83

VBR 400120
I BR    5.10  300.13 A
Z BR 78.3660.13
Solution

The various line currents in the delta load are

I 1  I R  I B  25.52  60.13 - 5.1 - 300.13

 28.41 - 69.07 A

I 2  I Y  I R  9.12  169.83  25.52  60.13

 29.85136.83 A

I 3  I B  I R  5.1  300.13 - 9.12 - 169.83

 1327.60 A
These line currents are also equal to the line (phase) currents of the
original star-connected load.
Solution

The voltage drop across each star-connected load will be as follows:

Voltage drop across Z R,


V Z R  I 1 Z R  28.41  69.078.9463.4
 253.89  5.67 V

Voltage drop across ZY ,


V ZY  I 2 Z Y  29.85136.58553.1

 149.2189.68 V
Voltage drop across Z B ,

V Z B  I 3 Z B  1327.602553.1  32580.7 V
END OF FIRST PART
MILLMAN’S METHOD OF SOLVING UNBALANCED LOAD

The star-delta conversion method of solving an unbalanced three-


wire star-connected load shown earlier is laborious and involved
lengthy calculations. By using Millman’s theorem, we can solve this
type of problem in a much easier way.

Generalised Form of Millman’s Theorem


Millman’s theorem is particularly useful for solving many circuits
which are encountered in both electronics and power applications. In
three-phase circuit analysis, for example, this theorem can be used
to find the potential difference between the star point of a wye-
connected source and the star-point of a star-connected load in an
unbalanced three-wire three-phase circuit.
Consider a number of impedances Z 1 , Z 2 , Z 3 , …, Z n which
terminate at common point N’ (see figure below). The other ends
of the impedances are connected to voltage sources numbered
as , , V 1, …V 2 V.3Let N V
ben any other point in the
network.
N’

I1 I2 I3 I4 In

Z1 Z2 Z3  Zi  Zn

V1 V2 V3 Vi Vn

N
Application of Ohm’s law to the circuit leads to the following
equations:

V 1  V N 'N
I !Z 1 
Z1 N’

I1 I2 I3 I4 In
V 2  V N 'N
I Z2 
Z2 Z1 Z2 Z3  Zi  Zn

V 3  V N 'N V1 V2 V3 Vi Vn
I Z3 
Z3 N

V n  V N 'N
I Zn 
Zn

You might also like