You are on page 1of 4

FREDON Project Notice

ABN 92 124 107 973


LCI Consultants
Level 4, 73 Walker Street, North Sydney NSW 2060

REVIEWED
This document has been reviewed by LCI Consultants with the intent
of the contract subject to the following notes and satisfactory
operation, for compliance with the project design general intent only.

PROJECT: Walsh Bay Arts Precinct This review does not relieve the Sub-Contractor of responsibility for all
specified requirements, correctness of quantities, dimensions,
calculations, fabrication techniques, compliance with statutory
PROJECT NO. : 30M067 regulations & relevant codes and standards, nor for the verification of
the site conditions, accessibility and co-ordination with other trades.

Project Notice No. : PN-17 (Rev 01) Reviewed:

Reviewed with Comments: X

Total Pages: 4
Revise and Resubmit:

19/07/19
Signed: .................................. Date: ....................

Type Of Notice
RFA INS RFI FIO

Request For Approval Instruction Request for Information For Information Only

Sent by
TO CC COMPANY ATTENTION
(email/fax/hand)
 Richard Crookes (RCC) Ian Barrat Aconex
 Richard Crookes (RCC) Steve Embleton Aconex
 Richard Crookes (RCC) Peter Fulton Aconex
 Richard Crookes (RCC) Michael Aquilina Aconex
 Richard Crookes (RCC) Katerina Oustambasidis Aconex

 Lehr Consultants International (LCI) Duncan Cooke Aconex

 Lehr Consultants International (LCI) Vishaal Deo Aconex

 Fredon Air (Fredon) Troy Fielding Aconex

 Fredon Air (Fredon) Paul Harrison Aconex

 Fredon Air (Fredon) Ben Eades Aconex

Details: Request for Approval: Sea Water Heat Exchanger Selection

Hi Ian & Steve,

Please find contained within this Project Notice our Sea Water Heat Exchangers for your review and approval.

We would request response on our selection by 12th of July, so as to progress procurement without impacting on
the programme.

Author: Ronda Masri Signed R.M. Date: 28/06/2019

Response/ Comments:
Confirm the sizing fits with the existing structure and provision has been made to adjust
the supports to suit
316 stainless steel frame is to be titanium for corrosion resistance.

Name: Signed Date:

Doc No. PMF-046


Rev1 (18/08/2015) Approved by: Alan Brown Page 1 of 1
Project Notice
FREDON AIR PTY LTD
Equipment Technical Data Schedule

SEA WATER HEAT EXCHANGER


Project : Walsh Bay

Project No. 30M067 Date: 28th June 2019


Rev.: 01
Status: For Approval
HX-01, HX-02, HX-03, HX-04 HX-01, HX-02, HX-03, HX-04
DESIGNATION UNITS HX-05, HX-06, HX-07, HX-08 HX-05, HX-06, HX-07, HX-08
Design Data Actual Selection Design Data Actual Selection
Number
System Condenser Water Condenser Water
Supplier AWEB SUPPLY
Model 9GLP090TICF316LAMHDPE4F4
Design Output kW 315
Type Plate Heat Exchanger Plate Heat Exchanger

PLATES
Model GLP-10T
Heat Rejection (Nominal) kw 35
Fluid Water Water
Density kg/m3 995 995
Specific Heat Capacity kJ/(kg*K) 4.186 4.186
Thermal Conductivity W/(m* K) 0.6 0.6
Water Flow Rate l/s 1.21
o
Inlet Temperature C 35
o
Outlet Temperature C 29.5
Pressure Drop kPa 45
Water volume Litres 26.5
Net Weight (Empty) kg 62.6
Length mm 4570
Width mm 9.5
Height mm 1200

HEAT EXCHANGER
Heat Rejection (Nominal) kW 315
No. of plates per Heat Exchanger 9
Water Flow Rate L/s 10.86 10.86
o
Inlet Temperature C 29.5 29.5
o
Outlet Temperature C 35 35
Pressure Drop kPa 45
Water volume Litres 278
Number of Passes x channel 1x9
Connection Diameter mm 110
Nozzle Orientation Vertical
Net Weight (Empty) kg 816
Overall Length mm 4835
Overall Width mm 2235
Overall Height mm 1660

HEAT EXCHANGE MEDIUM


Fluid Sea Water Sea Water
o
Max. Temperature C 26.8
Density kg/m3 1029
Specific Heat Capacity kJ/(kg*K) 3.85
Thermal Conductivity W/(m* K) 0.6

CONSTRUCTION
Design Code ASME BPVC
Design Pressure MPa 0.4 0.4
Test Pressure MPa 1.0 1.0 316 stainless steel is not suitable
Design Temperature o
C 0 - 50 for this application. Provide
Plate Material Titanium titanium frame and support
Header material HDPE
Frame material 316 Stainless Steel
Support Hardware Material 316 Stainless Steel
Sealing Material Synthetic fiber sheet gasket

Project Number 30M067


Document Title 30M067 - WBAP - Sea Water Heat Exchangers Schedule
Document Number
Issue Issue Date Comments Prepared by Approved by
01 28/06/2019 For Approval P.H. H.D.

Doc No. PMF-280


Heat Exchanger Schedule Rev1 (20/08/2015) Approved by: Alan Brown Page 1 of 1
Slim Jim® Geo Lake Plate ® “Pond Loop in a Package”
 The Lake Loop of Choice for Fluid to Fluid Heat Transfer in Water Cooled Equipment -
A/C, Heat Pumps, Refrigeration, Etc. (Lakes, Ponds, Rivers, Oceans).
 304 Stainless Steel, 316L Stainless Steel or Titanium - Spot & Roll Welded
 Compact Footprint
 Easy to Install - Easy to Flush - Labor Friendly
 No Limit to Job Size - Single to Multiple*** Units

SPECIFICATIONS - US & SI Units


MODELS DIMENSIONS Pressure Drop (Approx.) Volume Weight Weight
DESCRIPTIONS (Approx.) (Approx.) (Approx.)

Water 304 & 316L SS Titanium

SJ = 304 SS US GPM @ ∆P psig Gallon Pounds Pounds


GLP = 316L or TITANIUM SI (l/s) @ ∆P FT HD (kPa) (BAR) Liter Kilogram Kilogram
2' X 6' X 3/8'' 6.0 GPM @ 3.8 psig 1.2 gal 51 lbs. 28 lbs.
SJ / GLP -02T
0.61 m X 1.83 m X 9.53 mm 0.38 l/s @ 8.77 FT HD (26.20 kPa) (0.26 BAR) 4.54 l 23.13 kg 12.70 kg
4' X 5' X 3/8'' 9.0 GPM @ 3.0 psig 2.0 gal 90 lbs. 46 lbs.
SJ / GLP -03T
1.22 m X 1.52 m X 9.53 mm 0.57 l/s @ 6.92 FT HD (20.68 kPa) (0.21 BAR) 7.57 l 40.82 kg 20.87 kg
4' X 6' X 3/8'' 12.0 GPM @ 4.5 psig 2.4 gal 110 lbs. 55 lbs.
SJ / GLP -04T
1.22 m X 1.83 m X 9.53 mm 0.76 l/s @ 10.38 FT HD (31.03 kPa) (0.31 BAR) 9.08 l 49.90 kg 24.95 kg
4' X 8' X 3/8'' 15.0 GPM @ 6.0 psig 3.2 gal 145 lbs. 74 lbs.
SJ / GLP -05T
1.22 m X 2.44 m X 9.53 mm 0.95 l/s @ 13.84 FT HD (41.37 kPa) (0.41 BAR) 12.11 l 65.77 kg 33.57 kg
2' X 15' X 3/8'' 15.0 GPM @ 4.5 psig 3.0 gal 138 lbs. 70 lbs.
SJ / GLP -05TC
0.61 m X 4.57 m X 9.53 mm 0.95 l/s @ 10.38 FT HD (31.03 kPa) (0.31 BAR) 11.36 l 62.60 kg 31.75 kg
4' X 12' X 3/8'' 24.0 GPM @ 5.5 psig 4.8 gal 220 lbs. 110 lbs.
SJ / GLP -08T
1.22 m X 3.66 m X 9.53 mm 1.51 l/s @ 12.69 FT HD (37.92 kPa) (0.38 BAR) 18.17 l 99.79 kg 49.90 kg
4' X 15' X 3/8'' 30.0 GPM @ 9.0 psig 7.0 gal 275 lbs. 138 lbs.
SJ / GLP -10T
1.22 m X 4.57 m X 9.53 mm 1.89 l/s @ 20.76 FT HD (62.05 kPa) (0.62 BAR) 26.50 l 124.74 kg 62.60 kg
Inlets/Outlets = NPS 1 1/4" MPT (Male Pipe Thread) (DN 32 mm) (Specifications Subject to Change without Notice)

SJ / GLP Legs - (SHORT) - 3' (0.91 m) in Length, Provides 12" (304.80 mm) Clearance from Bottom. Use with 02T and 05TC Models
SJ / GLP Legs - (TALL) - 5' (1.52 m) in Length, Provides 12" (304.80 mm) Clearance from Bottom. Use with 03T, 04T, 05T, 08T and 10T Models
***Multiple plates of like capacity can be manifold in field with polyethylene pipe to accommodated larger loads. Or, we can custom build (pre-manifold multiple plates)
with headers equipped with flange connections (single point hookups), reinforced frame with legs on skids to stand off bottom (special quote required).

IMPORTANT: SJ / GLP Plates are Rated in HEAT OF REJECTION (HR) - COOLING

Example: 4 Ton (14.07 kW) Heat Pump would Require SJ/GPL-05T plate in Cooling Dominate Application
Each 12,000 Btu (3.52 kW) of Cooling Rejects Approximately 15,000 Btu (4.39 kW) Heat

HEATING DOMINATE APPLICATIONS (HE) REQUIRE MORE PLATE SURFACE AREA


CAUTION - For Final Sizing Selection Assistance, contact AWEB Supply or Authorized Distributor

Flow Rate: 3 gpm (0.189 l/s) per ton (3.52 kW) equipment.
Approx. (HR) Heat Transfer Rate**: 100 BTu/Ft2 (567.83 W /(m².°C) transfer surface of plate per degree DeltaT in still body of water.
Both sides of plate are exchanger surface. (Note, any current accentuates performance greatly and allows for closer grouping of multiple plate AWEB SUPPLY
assembly – such as river applications). **Shallow bodies of water AND colder climates will require additional plate capacity for heating. 7350 Tom Drive, Baton Rouge, LA 70806
225-928-2630 * 888-277-2932 - Fax 225-928-
Example: SJ-05T Plate SJ-05T Plate 2087
4' X 8' X 2 = 64 ft2 1.22 m x 2.44 m x 2 = 5.95 m2 email: info@awebgeo.com
64 X 100 = 6,400 5.95 m2 x 567.83 W/(m².°C) = 3,380.633 Website: www.awebgeo.com
6,400 X 10 ∆T/ᵒF = 64,000 BTU approx. HR 3,380.633 x 5.5556 ∆T/ᵒC = 18.7814 kW approx. HR Rev. 4/12
Is the pile size correct? Confirm allowance has been made to
provide for modification to suit exact pile sizes found on site.`

TYPICAL PILE SPACING


What is this material?
PILE ALIGNMENT AND SPACING VARIES How are heat exchangers fastened to the cross bracing?
MOUNT CROSS BRACING TO SUIT 3080

CROSS BRACING TYPICAL

400DIA TIMBER/ STEEL PILE ø 42


1
TYPICAL ASSEMBLY PHYSICAL PROPERTIES
DRY WEIGHT 816 kg
VOLUME 278 Litres
TWO PIECE MOUNTING BRACKET
WRAP TIMER PILE WITH
PROTECTIVE MEMBRANE AND PLACE
BARCKET OVER

2592
ISOMETRIC

TOP VIEW

ELEVATION

AIR CONDITIONS & MECHANICAL SERVICES


ABN: 86 122 132 281

123 WETHERILL STREET, SILVERWATER NSW 2128


PHONE NO. 02 9475 9400 FAX NO. 02 9748 0040 www.fredon.com.au

You might also like