You are on page 1of 7

REFEREN CALCULATION OUTPUT

CE
Design,
Constructio POPULATION FORECASTING
n
Supervision
, Operation
And
Maintenanc
e (DCOM)
Manual

DOMESTIC CONSUMPTION

DOMESTIC DEMAND
PRESENT
POPULATI FUTURE CATEGORY
DESCRIPTI ON ( POPULATION(12 CONSUMPTI
ON 10568) 883 ON (l/ca/d) DEMAND
Low
income
using
kiosks or 489,554.0
public taps 154,596. 0
60% 60% 7,730 20 00
low income
multiple
household
with yard 115,947.
tap 20% 20% 2,577 45 00
low
income,sin
gle
household
with yard 77,298.0
tap 10% 10% 1,288 60 0
medium
income
house hold 141,713.
10% 10% 1,288 110 00
489,554.
TOTAL DOMESTIC DEMAND 00
Modified
from INSTITUTE DEMAND
MoW3rd
Edition
Design
Manual
2009)

INSTITUTE DEMAND
PRESENT
POPULATI FUTURE CATEGORY
DESCRIPTI ON ( POPULATION(12 CONSUMPTI
ON 10568) 883 ON (l/ca/d) DEMAND

MWAUKOLI DAY SECONDARY SCHOOL


29,825.0
STUDENTS 978 1,193 25 0
STAFFS 16 20 70 1,400.00
31,225.0
0

MWAUKOLI DISPENSARY

STAFF 10 13 70 910.00
35,875.00
OUTPATIE
NT 200 244 10 2,440.00

BEDS 10 13 100 1,300.00

4,650.00
35,875.
TOTAL INSTITUTION DEMAND 00
Modified INDUSTRIAL DEMAND
from
MoW3rd
Edition
Design
Manual
2009)
Industrial DEMAND
PRESENT FUTURE CATEGORY
DESCRIPTIO POPULATIO POPULATIO CONSUMPTIO
N N N N (l/ca/d) DEMAND
CHIPBOARD 300,000.0
S FACTORY 1 2 150000 0
300,000.0
300,000.0 0
TOTAL INDUSRIAL DEMAND 0
Modified LIVESTOCK DEMAND
from
MoW3rd
Edition
Design
Manual
2009)
Livestock DEMAND
PRESENT
POPULATI FUTURE CATEGORY
DESCRIPTIO ON ( POPULATION(12 CONSUMPTI DEMAN
N 10568) 883 ON (l/ca/d) D
MWAUKOLI DAY SECONDARY SCHOOL
5,875.0
GOATS 940 1,175 5 0
2,535.0
SHEEP 405 507 5 0 24,290.00
15,880.
COWS 1270 1,588 10 00
24,290.
TOTAL LIVESTOCK CONSUMPTION 00
Modified NET WATER DEMAND
from Net water demand =Domestic consumption+ Institutional
MoW3rd consumption +Industrial consumption+ Commercial consumption +
Edition Livestock consumption + Energy cooling.
Design 849,719.0
Manual NET WATER DEMAND REVENUE WATER 0
2009)
Fire Fighting Water
consumption 2% 16,994.38

Operational water
consumption 7% 59,480.33

212,429.7
WATER LOSES 25% 5

288,904.4
NET Non-Revenue Water 6

1,138,623
1,525.755
TOTAL CONSUMPTION .46
.44
PERCENTAGE OF NRW 0.25

1,525,755
WATER DEMAND .44

Modified STORAGE CAPACITY


from Storage capacity= Balancing storage + Break down storage +Fire
MoW3rd reserve
Edition
Design
Manual
2009)
CUMULATIVE CUMULATIVE
HOURS PERCENTAGE DEMAND RATE SURPLUS DEFICIT SURPLUS DEFICT
6 TO 9 14.59 0.15 222,608 311,651 306000 5,651 5651
9 TO 12 16.99 0.17 259,226 362,916 306000 56,916 62,567
12 TO 15 16.12 0.16 245,952 344,332 306000 38,332 100,900
15 TO 18 18.67 0.19 284,859 398,802 306000 92,802 193,702
18 TO 21 15.19 0.15 231,762 324,467 306000 18,467 212,169
21 TO 24 8.58 0.09 130,910 183,274 306000 122,726 89,443
00 TO 03 4.93 0.05 75,220 105,308 306000 200,692 111,250
03 TO 06 4.93 0.05 75,220 105,308 306000 200,692 311,942

Balancing storage=Maximum cumulative surplus+Maximum


cumulative deficit
=311942+212169=524,111litres

Breakdown storage=3×Pumping rate


=3×102000
=30600litres

Fire reserve =2%×1525755.44


=30515.1088litres 860626.109
Total storage
=524111+306000+30515.1088=860626.109litres

AVERAGE DAILY DEMAND=


1,525,755.44Litre/day
1,525,755.44litre/day

Maximum daily demand=1.4×1,525,755.44Litre/day 2,136,057.616litre/day


=2,136,057.616litre/day

PEAK HOUR DEMAND=peak hour factor×average hour 89,002.40litr/hour


demand =1.4×63573.1433
=89,002.40litr/hour

LOCATION = 8m above the ground

SURFACE LEVEL
1363m
MoW 3 SELECTION OF PUMP VORTEX PUMP
rd According to table 6.2 of the design manual the pump
Edition selected was between 10 to 100m3/h which is VORTEX
Design PUMP
Manual,
2009

You might also like