You are on page 1of 1

Customer :

SPP Pumps Limited


Theale Cross, Pincents Lane, Calcot, Reading,
Berks, RG31 7SP, United Kingdom
Phone +44 (0) 118 9323123
Fax +44 (0) 118 9323302
Contact :
Project : Phone : Fax :
Quote Ref. : UK-4005-2 Page No : 1 Date : Wednesday, 25 de June de 2014

Type: Horizontal Thru-Stream (FM and/or UL) - Axial Split Case Item : 1
Pump Model: SPP - TD20E Impeller No.:
Pump Op. Speed: 2950 RPM, 50 Hz Electric Liquid: Water
Impeller Dia.: 13,35 inch Temperature: 59 °F
Curve No.: TD20E-C2950/2G-A1 Viscosity: 1,14 cSt
Market : FM/UL/ULC Listed Fire Pump Sp. Gravity: 1,00
Your Ref. :

Rated Flow 2000 US gpm


Rated Head 170 psi
Imp. Dia. 13,35 inch
250 Rated Power Required 275,4 hp
Rated NPSH Required 13,9 ft
Rated Efficiency 72,2 %
200 NFPA Limits:
140% Head at shutoff 238 psi
Head - psi

65% Head at 150% 110,5 psi


150 flow
Flow at 150% 3000 US gpm
Head at 150 146,5 psi
100 Power Req. at 150% 317 hp
NPSH Req. at 150% 16,5 ft
Efficiency at 150% 81,1 %
50 Peak Power 322,9 hp
Closed Valve Pressure 202,3 psi
Approval FM/UL/ULC
Power - hp

300 Comments
NPSH REQUIRED at centreline of
200 impeller. Add 0.5m to Laboratory
100 NPSH curve for field applications

1.000 2.000 3.000 4.000 5.000


Flow - US gpm
Flow Head Pump Efficiency Power Required NPSH Required
(US gpm) (psi) (%) (hp) (ft)
0,0 202,3 0,0 177,7
574,0 193,1 33,2 195,3
1148,0 184,3 54,9 225,2 12,0
1722,1 175,0 67,9 259,4 13,2
2296,1 164,1 75,8 290,9 14,7
2870,1 150,2 80,4 313,6 16,2
3444,1 131,6 82,1 322,9 17,6
4018,2 106,4 79,3 315,0 21,4
4592,2 72,1 67,4 287,6

SPP Pumps Limited - RAPID v8.06 - 1st August 2007.