CALIBRATION REPORT

DATE 15 Juli 2021


KKS 42LAE12AA700
DESCRIPTION HRSG 4-2 RH SPRAY BLOCK VALVE
AIR SET VALUE 3,03 Bar
AIR FALL TO CLOSE
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON GOOD CLOSE TO OPEN 1.72
OFF GOOD OPEN TO CLOSE 4.91
CLOSE ON GOOD
OFF GOOD JUDGEMENT GOOD
CALIBRATION REPORT

DATE 13 JULI 2021


KKS 42LAE13AA700
DESCRIPTION HRSG 4-2 HP SH SPRAY BLOCK VALVE
AIR SET VALUE 4.2 BAR
AIR FALL TO
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON GOOD CLOSE TO OPEN 6.35
OFF GOOD OPEN TO CLOSE 2.86
CLOSE ON GOOD
OFF GOOD JUDGEMENT GOOD
CALIBRATION REPORT

DATE 15 Juli 2021


KKS 42LAE12AA701
DESCRIPTION HRSG 4-2 RH SPRAY CONTROL VALVE
AIR SET VALUE 2,62 Bar
AIR FALL TO CLOSE
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
100 95.6 95.6 96 96
75 74.4 74.3 75 75
50 49.5 49.6 50 50
25 24.5 24.5 25 25
0 -1.3 -1.3 0 0
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 3.73
OFF - OPEN TO CLOSE 3.82
CLOSE ON -
OFF - JUDGEMENT GOOD
CALIBRATION REPORT

DATE 14 Juli 2021


KKS 42LAB73AA700
DESCRIPTION HRSG 4-2 LP FEEDWATER CONTROL VALVE
AIR SET VALUE 5,5 bar
AIR FALL TO
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
100 98.8 98.8 100 100
75 74.8 74.3 75 75
50 49.8 49.4 50 50
25 24.7 24.5 25 25
0 -0.3 -0.3 0 -
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 5.51
OFF - OPEN TO CLOSE 4.68
CLOSE ON -
OFF - JUDGEMENT GOOD
CALIBRATION REPORT

DATE 13 JULI 2021


KKS 42LAB63AA700
DESCRIPTION HRSG 4-2 ECO INLET FEEDWATER TEMPERATURE CV
AIR SET VALUE 6.9 bar
AIR FALL TO
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
100 -0.1 0 0% 0
75 25.3 27.7 25 28
50 50.3 52.2 50 52
25 75.1 77.1 75 77
AS FOUND
0 99.6 100 -
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 2.45
OFF - OPEN TO CLOSE 13.04
CLOSE ON -
OFF - JUDGEMENT NEED CALIBRATION
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
100 -0.1 0 0% 0
75 25.3 27.7 25 28
50 50.3 52.2 50 52
AFTER 25 75.1 77.1 75 77
RECALIBRATED 0 99.6 100 -
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 2.45
OFF - OPEN TO CLOSE 13.04
CLOSE ON -
OFF - JUDGEMENT GOOD
CALIBRATION REPORT

DATE 17 Juli 2021


KKS 42LAB91AA703
DESCRIPTION HRSG 4-2 HP ECO MOD CV
AIR SET VALUE 6.2 bar
AIR FALL TO
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
0 0.9 0.8 0 0
25 25.6 24.3 26 25
50 50.7 49.6 50 49
75 76 74.3 77 75
100 99.9 - 100 -
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 5.97
OFF - OPEN TO CLOSE 6.67
CLOSE ON -
OFF - JUDGEMENT GOOD
CALIBRATION REPORT

DATE 16 Juli 2021


KKS 42LAB91AA702
DESCRIPTION HRSG 4-2 HP/IP FWP B MIN FLOW CV
AIR SET VALUE 6.5 bar
AIR FALL TO
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
0 -0.5 -0.5 0 0
25 25.8 24.7 27 25
50 50.7 49.9 50 50
75 76.3 74.5 76 75
100 98.6 - 100 -
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 2.29
OFF - OPEN TO CLOSE 1.84
CLOSE ON -
OFF - JUDGEMENT GOOD
CALIBRATION REPORT

DATE 15 Juli 2021


KKS 42LAB91AA701
DESCRIPTION HRSG 4-2 HP/IP FWP A MIN FLOW CV
AIR SET VALUE 6.2 bar
AIR FALL TO
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
0 -1.2 -1.2 0 0
25 24.8 23.6 25 24
50 49.8 48.3 50 49
75 74.6 73.3 75 74
AS FOUND
100 98.4 - 100 -
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 2.25
OFF - OPEN TO CLOSE 1.57
CLOSE ON -
OFF - JUDGEMENT NEED CALIBRATION
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
0 0 0.1 0 0
25 25.5 24.1 25 24
50 50.4 49.2 50 50
AFTER 75 75.4 74.5 75 75
RECALIBRATED 100 100.3 - 100 -
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 2.25
OFF - OPEN TO CLOSE 1.57
CLOSE ON -
OFF - JUDGEMENT GOOD
CALIBRATION REPORT

DATE 15 Juli 2021


KKS 42LAC14AA711
DESCRIPTION HRSG 4-2 LP DRUM BYPASS CV
AIR SET VALUE 2,2 bar
AIR FALL TO OPEN
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
100 98.4 98.4 99 99
75 74.4 74.1 75 75
50 49.4 49.2 50 50
25 24.5 24.1 25 25
0 -1 -1 0 -
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 12.75
OFF - OPEN TO CLOSE 6.49
CLOSE ON -
OFF - JUDGEMENT GOOD
CALIBRATION REPORT

DATE 14 Juli 2021


KKS 42LAB83AA700
DESCRIPTION HRSG 4-2 IP FEEDWATER CONTROL VALVE
AIR SET VALUE 5,5 Bar
AIR FALL TO CLOSE
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
100 98.4 98.4 99 98.9
75 74.4 74.3 75 75
50 49.3 49.3 50 50
25 24.4 24.3 25 25
0 -0.1 0 0 -
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 2.37
OFF - OPEN TO CLOSE 1.93
CLOSE ON -
OFF - JUDGEMENT GOOD
CALIBRATION REPORT

DATE 14 Juli 2021


KKS 42LAB93AA701
DESCRIPTION HRSG 4-2 HP FEEDWATER CONTROL VALVE-2
AIR SET VALUE 5,5 Bar
AIR FALL TO CLOSE
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
100 98.3 98.3 100 100
75 74.6 74.4 74.5 74.5
50 49.6 49.3 49.5 49.5
25 24.5 24.2 25 25
0 1.4 1.4 >0 >0
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 9.05
OFF - OPEN TO CLOSE 5.28
CLOSE ON -
OFF - JUDGEMENT GOOD
CALIBRATION REPORT

DATE 14 Juli 2021


KKS 42LAB93AA700
DESCRIPTION HRSG 4-2 HP FEEDWATER CONTROL VALVE-1
AIR SET VALUE 5,5 bar
AIR FALL TO CLOSE
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
100 99.3 99.3 100 100
75 74.2 74.1 75 75
50 49.3 49.2 50 50
25 24.3 24.2 25 25
0 -0.6 -0.6 0 -
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 9.87
OFF - OPEN TO CLOSE 5.37
CLOSE ON -
OFF - JUDGEMENT GOOD
CALIBRATION REPORT

DATE 13 JULI 2021


KKS 42LAE13AA701
DESCRIPTION HRSG 4-2 HP SH SPRAY CONTROL VALVE
AIR SET VALUE 5.5 BAR
AIR FALL TO
COMMAND TRAVEL (OPS) LOCAL
% UP DOWN UP DOWN
0 -1.2 -0.9 0 0
25 24.2 24.4 25 25
50 49.2 49.5 50 50
75 74.4 74.4 75 75
100 98.3 100 -
LIMIT SWITCH TRAVEL TIME (s)
OPEN ON - CLOSE TO OPEN 3.03
OFF - OPEN TO CLOSE 1.36
CLOSE ON -
OFF - JUDGEMENT GOOD