Regenerative IGBT Error (120-150m/min) : Run CPU Speed CPU DI120-150 DI180-420
Regenerative IGBT Error (120-150m/min) : Run CPU Speed CPU DI120-150 DI180-420
[Meaning]
[Actions to take]
When regenerative IGBT that uses regenerative power as resistance fails or IGBT driving 1. Check VA, GX, and GP connector in DPP-XXX(GDC) PCB with power
power is inferior.
OFF.
2. Verify if GP cable is well connected to FG PCB of regenerative IGBT.
[Diagram]
3. Verify if the voltage between GX9 to 17 in DPP-XXX PCB is AC29V.
(If power is not correct, replace the transformer.
DPP- 200
DPP-XXX
Yet, in permissible voltage dropping range.)
GET- E1
8 4. Check for regenerative resistance status.
HIC- 6
6 7 GX9 Power OFF and measure the resistance at both ends of
GP4
GX17 AC 29V
regenerative resistance connected serially. Normally it is
GP7
7.5 ohm at 30kw and 10 ohm at 22kW.
Regenerative
회생 IGBT
IGBT 6. Inspect IGBT.
GP1
VA19 VA20 7. Replace DPP-XXX(GDC) PCB.
VG19 VG20
Error Sign
Regenerative IGBT
DPC- 100
DPC-1XX [How to inspect IGBT]
driving power has
defect or short circuit. Be sure to open the resistance of FG PCB attached to IGBT before
inspection.
C2E1-E2 E2 G ∞ ∞
Short G E2 ∞ ∞
22kW System 2.5ohm 4Ea 30kW System 1.5ohm 5Ea G-E2 E2 C2E1 ∞ 10Ω or less
Short C2E1 E2 10Ω or less ∞
Structure of Regenerative resistance line