PROJECT # : 15.2.

06
DATE: 4-30-15
CHECKED BY: LM

REVISION:

GENERAL NOTES: DEMOLITION: (TO ALL SHEETS) GENERAL ELECTRICAL NOTES (TO ALL SHEETS)
A. THE EXTENT OF DEMOLITION WORK IS INDICATED ON THE ARCHITECTURAL A. CONTRACTOR TO VERIFY ALL EXISTING MAIN POWER SERVICES AND
DRAWINGS AND BY THE REQUIREMENTS OF THIS SECTION. A VISIT TO THE COORDINATE WITH POWER COMPANY FOR ALL NEW REQUIREMENTS AND ALL
SITE WILL BE REQUIRED TO PROPERLY BID THE DEMOLITION WORK. COST ASSOCIATED. CONTRACTOR SHALL INCLUDE ANY COST FOR THE NEW
B. PROVIDE ALL DEMOLITION WORK REQUIRED FOR THE REMOVAL AND/OR TRANSFORMER AND OTHER ASSOCIATED FEES IN BID. CONTRACTOR IS
TYP. RELOCATION OF ELECTRICAL EQUIPMENT AND ASSOCIATED RESPONSIBLE TO VERIFY ALL FEES WITH POWER COMPANY AND TO INCLUDE IN

TEXAS
BH-7,9,11 TYP. CONDUCTORS, CONDUIT, BOXES, ETC. TO PROVIDE A COMPLETE AND BID. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH POWER COMPANY AS
OPERABLE SYSTEM UPON COMPLETION OF THE PROJECT. SOON THE CONTRACT IS AWARDED TO ORDER TRANSFORMER AND THE RELATED
A2 ELECTRICAL SERVICE EQUIPMENT AS SOON AS POSSIBLE.
TYP. C. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO REVIEW THE
24" SPACE ARCHITECTURAL DOCUMENTS IN ADDITION TO THE DIVISION 15 AND 16 B. CONTRACTOR IS RESPONSIBLE FOR ALL EXCAVATION, TRENCHING AND
DOCUMENTS TO DETERMINE THE COMPLETE SCOPE OF WORK. BACKFILLING. COORDINATE WITH ALL UTILITIES PRIOR TO EXCAVATION.
BH-19,21,23 D. WHERE DEVICES OR EQUIPMENT ARE INDICATED OR REQUIRED TO BE
TYP.
REMOVED, THE ASSOCIATED BOXES, CONDUIT, AND CONDUCTORS C. CONTRACTOR TO VERIFY ALL EXISTING MAIN TELEPHONE SERVICES AND
B2 SHALL BE REMOVED BACK TO THEIR SOURCE. COORDINATE WITH TELEPHONE COMPANY FOR ALL REQUIREMENTS AND ALL
30" SPACE E. WHERE DEVICES OR EQUIPMENT ARE INDICATED OR REQUIRED TO BE
COST ASSOCIATED. INCLUDE ALL COST IN BID. CONDUIT FROM MAIN TELEPHONE
TYP. RISER SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR.
RELOCATED, THE ASSOCIATED BOXES, CONDUIT, AND CONDUCTORS
SHALL BE REMOVED BACK TO A CONCEALED JUNCTION BOX AND NEW
PRODUCTS SHALL BE USED TO EXTEND THE SERVICE TO THE NEW D. ALL ELECTRICAL EQUIPMENT OUTDOORS SHALL BE RATED TYPE NEMA 3R UNLESS
LOCATION. OTHERWISE NOTED.

F. WHERE CONDUITS RUN ABOVE INACCESSIBLE CEILINGS OR IN WALLS E. CONTRACTOR SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND
WHICH ARE NOT PART OF DEMOLITION ARE TO REMAIN UNDISTURBED, ORDINANCES. ALL WORK SHALL CONFORM TO NATIONAL ELECTRICAL CODES
CONDUCTORS SHALL BE REMOVED AND THE CONDUITS CAPPED AND AND ALL OTHER AUTHORITY HAVING JURISDICTION. OBTAIN PERMITS AND PAY
TYP. ABANDONED. ALL FEES. PERFORM MODIFICATIONS TO MEET CODE AND ORDINANCE
REQUIREMENTS AT NO ADDITIONAL COST TO OWNER, ARCHITECT OR ENGINEER.
G. WHERE THE REMOVAL OF DEVICES OR EQUIPMENT RENDERS EQUIPMENT
TYP. VERIFY PRIOR TO BID DATE.
DOWNSTREAM INOPERABLE, SERVICE SHALL BE EXTENDED TO THE
DOWNSTREAM DEVICE OR EQUIPMENT SO THAT THE DEVICE OR

BASEBALL FIELD LIGHTING


F. VERIFY AT JOB SITE THE EXACT LOCATIONS OF STRUCTURAL MEMBERS SUCH AS

WESLACO HIGH SCHOOL


EQUIPMENT IS LEFT IN OPERATING CONDITION. BEAMS, COLUMNS, ETC. TO LOCATE EQUIPMENT CONDUIT, PANELS AND DEVICES.
TYP. IF DEVIATIONS FROM THE DRAWING ARE NECESSARY TO MEET STRUCTURAL
H. COORDINATE DEMOLITION OF DIVISION 16 SYSTEMS AS REQUIRED WITH CONDITIONS MAKE DEVIATIONS WITHOUT ADDITIONAL COST, TO OWNER,
ALL OTHER TRADES. ARCHITECT, OR ENGINEER.
I. ALL EXISTING ELECTRICAL EQUIPMENT, CONDUIT AND WIRING REMOVED
DURING CONSTRUCTION NO LONGER REQUIRED AS PART OF AN ACTIVE G. IN COOPERATION WITH OTHER CONTRACTORS, DETERMINE THE EXACT LOCATION
BH-1,3,5
SYSTEM AND NOT TO BE REUSED SHALL BE REMOVED FROM THE JOB SITE OF EQUIPMENT AND DEVICES AND CONNECTIONS THERETO BY REFERENCE TO THE
BH-8,10,12 AND PROPERLY RETURNED TO THE OWNER, IF DESIRED BY OWNER. SUBMITTALS AND ROUGH-IN DRAWINGS, AND BY MEASUREMENTS AT THE SITE.
30" SPACE REFER TO ALL OTHER TRADES SUBMITTAL FOR ELECTRICAL INFORMATION.
J. WHERE EXISTING EQUIPMENT IS TO BE RELOCATED, EXTREME CARE SHALL
BE TAKEN TO PREVENT DAMAGE DURING THE REMOVAL AND H. GROUND ENTIRE ELECTRICAL SYSTEM IN STRICT ACCORDANCE WITH THE
A1 NATIONAL ELECTRICAL CODE.
REINSTALLATION. WHERE DAMAGE OCCURS, THE EQUIPMENT SHALL BE
C2 12" SPACE REPLACED OR REPAIRED TO THE SATISFACTION AND APPROVAL OF THE
ARCHITECT AT NO ADDITIONAL COST TO THE OWNER. I. VERIFY AT JOB SITE GENERAL WORK TO BE DONE AS SPECIFIED, AS NOTED, OR AS
REQUIRED FOR INSTALLATION ELECTRICAL SYSTEMS PRIOR TO SUBMISSION OF BIDS.
K. EXISTING DEVICES AND/OR EQUIPMENT TO BE REUSED SHALL BE
CLEANED AND REPAIRED AT THE DISCRETION OF THE ARCHITECT
WHERE APPLICABLE. J. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND EQUIPMENT TO BE
L. ALL DEVICES WITH AN "EX" SYMBOL ARE EXISTING TO REMAIN. REMOVED AND REPLACED BEFORE SUBMITTING HIS BID.

M. ALL DEVICES ATTACHED TO WALLS OR CEILINGS SHALL BE REMOVED K. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SMALL SCALE ONLY. THEY
PER DEMOLITION NOTE A - L WHETHER SHOWN ON DRAWINGS OR NOT. CONVEY THE INTENT OF THE WORK BUT DO NOT SHOW DETAIL SUCH AS
TYP. JUNCTION AND PULL BOXES REQUIRED BY THE SPECIFICATIONS AND THE
NATIONAL ELECTRICAL CODE(NEC). PROVIDE ALL MATERIALS AND METHODS
CALLED FOR IN THE SPECIFICATIONS AND AS REQUIRED IN THE NEC TO PROVIDE
TYP. A COMPLETE INSTALLATION OF ALL WORK.

L. ALL WIRING SHALL BE COPPER.

M. ALL SLEEVES, PENETRATIONS, ETC. SHALL BE SEALED SOLID NON-SHRINKING


MATERIAL IMMEDIATELY UPON FILLING OF THE OPENING WITH PIPE OR CONDUIT.
12" SPACE TYP.
TYP. N. ARRANGE FOR SOURCES OF TEMPORARY CONSTRUCTION SERVICES. SUCH
SERVICES SHALL BE NOMINALLY 120/240V, 1-PHASE, 3-WIRE FROM WHICH A
COMPLETE SYSTEM OF TEMPORARY POWER AND LIGHTING SHALL BE PROVIDED
FOR ALL CONSTRUCTION NEEDS.

BH-13,15,17
BH-20,22,24 W Expy 83
KEYED NOTES: ELECTRICAL

S Westgate Dr.
B1 EXISTING POWER COMPANY PAD MOUNTED TRANSFORMER. FIELD VERIFY
D2 EXISTING LOCATION AND CONDITIONS.
12" SPACE

EXISTING BASEBALL ELECTRICAL PANEL BOARD TO BE REMOVED. REFER TO


REMODEL ELECTRICAL RISER DIAGRAM. CONTRACTOR SHALL FIELD VERIFY
EXISTING LOCATION AND EXISTING CONDITIONS.
TYP.
W Pike Blvd EXISTING LIGHT FIXTURES AND POLE TO BE REMOVED. EXISTING LIGHT FIXTURES
TO RETURN TO OWNER. POLE TO BE DEMO. CONCRETE FOOTING TO BE DEMO,
REMOVED FROM GROUND. CONTRACTOR SHALL PROVIDE ALL COST TO FILL
EXISTING VOID WITH DIRT.

Mile 5 1/2 Rd
EXISTING BASEBALL DISCONNECT TO BE REPLACE, REFER TO REMODEL ELECTRICAL
RISER DIAGRAM.

LINE REPRESENTS PROPOSED CONDUIT PATH. FIELD VERIFY EXACT ROUTE. PROVIDE
ALL TRENCHING AND BACK FILLING FOR NEW CONDUITS.

TYP. EXISTING ELECTRICAL DISCONNECT, BREAKERS NOT RELATED TO BASEBALL FIELD


TO RE-INSTALL TO NEW SUPPORT STRUCTURAL.
Panther Dr
EXISTING STRUCTUAL SUPPORT TO BE REPLACED WITH NEW AT SAME LOCATION.
PROVIDE TEMPORARY SUPPORT FOR EXISTING ELECTRICAL EQUIPMENT TO
REMAIN.
CONTRACTOR IS RESPONSIBLE TO IDENTIFY ALL EXISTING UNDERGROUND UTILITIES
TYP.
PRIOR TO ANY WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGES
TO EXISTING UNDERGROUND UTILITIES. CONTRACTOR SHALL REPAIR DAMAGES AT

12" SPACE 12" SPACE


PROJECT LOCATION NO COST TO CONTRACT.
EXISTING CONCRETE FOOTING WITH NO POLE TO BE PARTIALLY DEMO. FIELD
VERIFY EXISTING CONDITIONS. REFER TO DETAIL.

WESLACO
D1 C1 EXISTING AEP PULLBOX STATION LOCATION. CONTRACTOR SHALL FIELD VERIFY
EXACT LOCATION AND IDENTIFY EXISTING CONDUIT PATH PRIOR TO ANY WORK.

TYP. TYP. EXISTING 20'POLE AND FIXTURE TO BE REMOVED BY OWNER.


BH-2,4,6
BH-2,4,6 N

LOCATION MAP

04/30/15

ELECTRICAL SITE PLAN


1
SCALE:1"=30'
3533 Moreland Dr. Ste A l Weslaco, Tx 78596
p:956.973.0500 l f:956-351-5750
www.trinitymep.com I Copyright 2015
ES1.1
Texas Registered Engineering Firm - F10362
Project number: 15.2.06
PROJECT # : 15.2.06
ELECTRICAL ABBREVIATIONS: SPORTS FIELD LIGHTING SCHEDULE DATE: 4-30-15
ELECTRICAL LEGEND - GENERAL MARK VOLTAGE LAMP MOUNTING DESCRIPTION MODEL NO. CHECKED BY: LM
ABBV: DESCRIPTION ABBV: DESCRIPTION
---ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.
SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE. 480V MUSCO
AFF ABOVE FINISHED FLOOR MFR. MANUFACTURER A1-A2 8-1500W MZ 80' POLE SPORTS LIGHTING SYSTEM
2-LED MPI LSG
(S.C.) SHARE CIRCUIT
BFC BELOW FINISHED CEILING
QRCPT(S) QUAD RECEPTACLE(S)
C CONDUIT
RCPT(S) DUPLEX RECEPTACLE(S) 480V MUSCO
SYMBOL DESCRIPTION B1,B2 10-1500W MZ 90' POLE SPORTS LIGHTING SYSTEM
LSG
CB CIRCUIT BREAKER
CRCPT(S) I.G. RECEPTACLE(S)
1-1500W MZ REVISION:
EC EMPTY CONDUIT QCRCPT(S) QUAD I.G. RECEPTACLE(S)
EX 480V MUSCO
HID FIXTURE - SPORT LIGHTING - REFER TO SCHEDULE EXISTING PNL PANEL C1-C2 4-1500W MZ 70' POLE SPORTS LIGHTING SYSTEM
LSG
F FUSE SO (S.O.) SPACE ONLY
WALL SWITCH SPST, 20A,120/277V
G GROUND (EQUIPMENT) SP SPARE
480V MUSCO
SINGLE RECEPTACLE - 20A/125V/2P/3W/G NEMA 5-20R D1-D2 5-1500W MZ 70' POLE SPORTS LIGHTING SYSTEM
GFI GROUND FAULT INTERRUPTER ST (S.T.) SHUNT TRIP LSG

TEXAS
DUPLEX RECEPTACLE - 20A/125V/2P/3W/G NEMA 5-20R MTD MOUNT OR MOUNTED SW SWITCH
NOTE:
NF NONFUSED
UF UNDERFLOOR 1. REFER TO SPECIFICATION 16526.
DUPLEX RCPT. GFI - 20A/125V/2P/3W/G NEMA 5-20R NIC NOT IN CONTRACT 2. SPORTS LIGHTING MANUFACTURER SHALL PROVIDE COMPLETE SET OF STRUCTURAL POLE
H.D HEAVY DUTY UG UNDERGROUND FOUNDATION DRAWINGS DESIGN BY A LICIENSED STRUCTURAL ENGINEER. CONTACT MFR.
WP/ DUPLEX RCPT. GFI INSTALLED IN A "IN-USE" WEATHER PROOF MUSCO LIGHTING; TIM OORDT CELL:1-512-658-6884 FOR POLE FOUNDATION INFORMATION
"IN-USE" STEEL ENCLOSURE- 20A/125V/2P/3W/G NEMA 5-20R NL NIGHT LIGHT UNO(U.N.O.) UNLESS NOTED OTHERWISE FOR MUSCO SYSTEMS.
AC ABOVE COUNTER
WG WIRE GUARD
QUADRAPLEX RECEPTACLE HT. HEIGHT
WP WEATHERPROOF
MTD. MOUNTING
208V RECEPTACLE, VERIFY NEMA NO. WITH EQUIPMENT SUPPLIER
FDR. FEEDER XFMR TRANSFORMER

SPECIAL PURPOSE RECEPTACLE (NEMA NO. AS INDICATED) CKT. CIRCUIT MB MAIN BREAKER
LTG. LIGHTING MLO MAIN LUGS ONLY
JUNCTION BOX - SIZE & MOUNTING AS REQUIRED LC LIGHTING CONTACTOR RMC RIGID METAL CONDUIT
MINIMUM OF 4" SQUARE
IG ISOLATED GROUND RNC RIGID NONMETALLIC CONDUIT DRY-TYPE TRANSFORMER SCHEDULE
EA. EACH EMT ELECTRICAL METALLIC
WALL MOUNTED TELEPHONE/DATA OUTLET. FURNISH AND INSTALL TX-B
TUBING CONDUIT
1"C., WITH PULLSTRING AND INSULATED BUSHING, STUBBED ABOVE CEILING.
S/N SOLID NEUTRAL

BASEBALL FIELD LIGHTING


WESLACO HIGH SCHOOL
+24" UNLESS OTHERWISE NOTE. BOX TO BE MINIMUM 2 1/8" DEEP.
AC ABOVE COUNTER NOTE: 1. ALL DRY-TYPE TRANSFORMERS SHALL BE ENERGY EFFICENT MODEL.
WALL MOUNTED TELEPHONE OUTLET. FURNISH AND INSTALL 3/4"C
, WITH PULLSTRING AND INSULATED BUSHING, STUBBED ABOVE CEILING.
+24" UNLESS OTHERWISE NOTE. BOX TO BE MINIMUM 2 1/8" DEEP.

WALL MOUNTED DATA OUTLET. FURNISH AND INSTALL 1"C


, WITH PULLSTRING AND INSULATED BUSHING, STUBBED ABOVE CEILING.
+24" UNLESS OTHERWISE NOTE. BOX TO BE MINIMUM 2 1/8" DEEP. NOTES:
01 CLEAR TRENCH OF ALL ROCKS AND DEBRIS BEFORE ADDING SAND CUSHION.
03
COMPACT TRENCH FILL TO 95% PROCTOR DENSITY.
1.) 48" AFF INDICATES TO TOP OF DEVICE;
PHOTO CELL 15" AFF INDICATES TO BOTTOM OF DEVICE; MAINTAIN A MINIMUM OF 60 INCHES UNDISTURBED EARTH BETWEEN PARALLEL
ALL OTHER MOUNTING HEIGHTS REFER TO CENTERLINE OF DEVICE. WATER AND SEWER LINES OR SUPPORT WATER LINE ON SEPARATE SHELF A
LIGHTING CONTACTOR, NEMA-1, W/H.O.A. SWITCH AC INDICATES 6" ABOVE COUNTER TO BOTTOM OF DEVICE. MINIMUM OF 12" ABOVE SEWER LINE.

TIME CLOCK (TORK#7202Z) MAINTAIN A MINIMUM OF 24" HORIZONTALLY BETWEEN ELECTRICAL PRIMARY AND
SEWER. MAINTAIN A MINIM OF 12" VERTICALLY OR 24" HORIZONTALLY BETWEEN
HEAVY DUTY DISCONNECT SWITCH FUSED ELECTRICAL PRIMARY AND WATER LINES, GAS LINES, TELEPHONE RACEWAYS AND
CABLE RACEWAYS.
HEAVY DUTY DISCONNECT SWITCH NONFUSED
MIN. 24" WATER
HEAVY DUTY COMBINATION DISCONNECT/MOTOR STARTER

HEAVY DUTY MOTOR STARTER MIN. 36" MIN. 8" GAS


MIN. 12"
ENCLOSED BREAKER, RE: TO SCH. FOR MORE INFO. SEWER
MIN. 8"
MOTOR
SAND
ELECTRICAL MIN. 24"
PANELBOARD, CLEARANCE AS PER LATEST NEC SECONDARY
MIN. 60"

SWITCH LEG CONTRACTOR SHALL


TRENCH DETAIL DEMO EXISTING
CONCRETE PARTIAL
NO SCALE
ELECTRICAL CONDUIT ONLY, 12" BELOW
GROUND. PROVIDE FILL

2'-6"
DIRT TO COVER
UNDERGROUND ELECTRICAL CONDUIT
02 NOTE: DESIGN BASES ON
OPENING ENOUGH TO
BE FLUSH WITH EXISTING
MUSCO SYSTEM. GROUND.
X, X, X MULTI-POLE DEVICE CIRCUIT NUMBERS
EARTH GROUND
TRANSFORMER DIGITAL

1'-0"
X/X/X THREE SINGLE POLE DEVICE CIRCUIT NUMBERS REFER TO RISER DIAGRAM OFF-ON-AUTO KEYED CELLULAR
SWITCHES ANTENNA
CONDUIT AND WIRE HOMERUN TO PANEL. SHORT HATCH
A-1 INDICATES NEUTRAL CONDUCTOR, LONG HATCHES INDICATE PHASE EXISTING CONCRETE
ELECTRICAL
CONDUCTORS, AND LONG HATCH WITH CIRCLE INDICATES ISOLATES DISTRIBUTION PANEL FOOTING TO BE DEMO
OR INSULATED GROUND. ALPHANUMERIC DESCRIPTION INDICATES
PANEL AND BREAKER. WEATHER PROOF
ENCLOSURE WITH , REMOTE
A-1 UNDERGROUND CONDUIT AND WIRE HOMERUN TO PANEL. SHORT BALLAST, FUSE PROTECTION,
HATCH INDICATES NEUTRAL CONDUCTOR, LONG HATCHES INDICATE WIRE HARNESS, RE:
PHASE CONDUCTORS, AND LONG HATCH WITH CIRCLE INDICATES SPECIFICATION#16526.
ISOLATED OR INSULATED GROUND. ALPHANUMERIC DESCRIPTION CONTROL AND
SURGE PARTIAL TO REMAIN EXISTING
INDICATES PANEL AND BREAKER. MONITORING
PROTECTION
CABINET EXISTING CONCRETE
DEVICE
DETAIL NUMBER FOOTING NOT BEEN USE.

SHEET NUMBER

Equipment
CONDUIT
DEPTH MIN.24"
EXISTING CONCRETE FOOTING
ground
TO LIGHTING
REFER TO SPECIFICATION
#16526 FOR FOUNDATION
(NOT BEEN USED) DEMO DETAIL
LOAD NO SCALE
INFORMATION

KEYED NOTE DESCRIPTION # OF TYP. WIRE MAX. WIRE WIRE FROM


WIRES SIZE (AWG) LENGTH (FT) MUSCO
1 LINE POWER & GROUND TO CONTACTORS NOTE A NOTE B 27 NO

WESLACO
2 LOAD POWER TO LIGHTING CIRCUITS NOTE A NOTE B N/A NO

3 CONTROL POWER (DEDICATED, 20A) 3 12 N/A NO

4 SURGE PROTECTION DEVICE TO DISTRIBUTION PANEL -- -- N/A YES

5 SURGE PROTECTION DEVICE MONITORING 2 14 N/A NO

Notes
A. Voltage and phasing per the notes on cover page
B. Calculate per load and voltage drop
C. All conduit diameters per code.
D. Refer to Control and Monitoring System installation Instructions for more
details on equipment information and the installation requirements.
E. Contact (3) and monitoring (5) wiring must be in seperate conduits from line and
load power wiring (1,2).
04/30/15

SPORTS LIGHTING ELECTRICAL DETAIL

E1.1
NO SCALE

3533 Moreland Dr. Ste A l Weslaco, Tx 78596


p:956.973.0500 l f:956-351-5750
www.trinitymep.com I Copyright 2015
Texas Registered Engineering Firm - F10362
Project number: 15.2.06
PROJECT # : 15.2.06
DATE: 4-30-15
CHECKED BY: LM
PANEL: BH AMP LUGS NEMA V(LL) (P) (W) V(LN) MNT KAIC FDR PANEL: BL AMP LUGS NEMA V(LL) (P) (W) V(LN) MNT KAIC FDR
LOCATION: 225 MB 3R 480 3 4 277 SUR. 22 1-RUN 4#4/0, 1#4G, 3"C LOCATION: 100 MB 3R 240 1 3 120 S 10 1-RUN 3#3, 1#8G, 1 1/2"C
LOAD CKT LOAD BKR POLE FEEDER/BRANCH CIRCUIT FEEDER/BRANCH CIRCUIT POLE BKR LOAD CKT LOAD LOAD CKT LOAD BKR POLE FEEDER/BRANCH CIRCUIT FEEDER/BRANCH CIRCUIT POLE BKR LOAD CKT LOAD
SERVED # KVA SIZE SIZE A B C SIZE SIZE KVA # SERVED SERVED # KVA SIZE SIZE A B SIZE SIZE KVA # SERVED
2) POLE-A1 1 7.1 40 3 4#6, 1#8G,1"C * 4#4, 1#8G,1.25"C 3 20 3.1 2 2) POLE-C1 1 RCPT 1 1.5 20 1 2#12, 1#12G,1/2"C * - 2 SPACE
" 3 7.1 - * - 3.1 4 " MUSCO CONTROLS 3 1 20 1 2#12, 1#12G,1/2"C * - 4 SPACE
REVISION:
" 5 7.1 - * - 3.1 6 " SPACE 5 - * - 6 SPACE
2) POLE-A2 7 7.1 40 3 4#8, 1#8G,1"C * 4#10, 1#10G,3/4"C 3 20 3.1 8 2) POLE-C2 SPACE 7 - * - 8 SPACE
" 9 7.1 - * - 3.1 10 " SPACE 9 - * - 10 SPACE
" 11 7.1 - * - 3.1 12 " SPACE 11 - * - 12 SPACE
2) POLE-B1 13 8.3 45 3 4#4, 1#8G,1.25"C * 4#6, 1#8G,1"C 3 25 4.2 14 2) POLE-D1 SPACE 13 - * - 14 SPACE
" 15 8.3 - * - 4.2 16 " SPACE 15 - * - 16 SPACE

TEXAS
" 17 8.3 - * - 4.2 18 " SPACE 17 - * - 18 SPACE
2) POLE-B2 19 8.3 45 3 4#4, 1#8G,1.25"C * 4#8, 1#8G,1"C 3 25 4.2 20 2) POLE-D2 SPACE 19 - * - 20 SPACE
" 21 8.3 - * - 4.2 22 " SPACE 21 - * - 22 SPACE
" 23 8.3 - * - 4.2 24 " SPACE 23 - * - 24 SPACE
SPACE 25 - * 3#10, 1#10G,3/4"C 2 30 2 26 PANEL-BL LOADS - (KVA) 2 1 (KVA) - DESCRIPTIVE LOADS
SPACE 27 - * - 1 28 VIA TX-B CONNECTED LOAD - 3 KVA/PHASE 0 - LIGHTING
SPACE 29 - * - 30 SPACE RESERVE 0 0 3 - RECEPTACLES
SPACE 31 - * - 32 SPACE TOTAL LOAD - 0 - COOLING

SPACE 33 - * - 34 SPACE 0 - HEATING


TOTAL AMPS - 0 - OTHER
SPACE 35 - * - 36 SPACE
NOTES:
SPACE 37 - * - 38 SPACE
1) PROVIDE 40AMP MAIN BREAKER
SPACE 39 - * - 40 SPACE 2)
SPACE 41 - * - 42 SPACE 3)
LOADS - (KVA) 46 45 44 (KVA) - DESCRIPTIVE LOADS
CONNECTED LOAD - 139 KVA/PHASE 136 - LIGHTING
RESERVE 25 35 3 - RECEPTACLES

BASEBALL FIELD LIGHTING


WESLACO HIGH SCHOOL
TOTAL LOAD - 0 - COOLING
0 - HEATING
TOTAL AMPS - 0 - OTHER
NOTES:
1) PROVIDE INTEGRAL TVSS, 120K
2) PROVIDE BREAKER FRAME WITH INDICATED TRIP UNIT AND LUGS TO BE SIZE FOR THE INDICATED WIRING.
3) MAIN BREAKER SHALL BE SERVICE RATED.

DISCRIPTION TOTAL KVA

LIGHTING 136

GENERAL POWER 3

TOTAL WATTS: 139 KVA


TOTAL AMPS: 167 AMPS
TOTAL AMPS+25%: 209 AMPS
WIRE SIZE AMPS: 225 AMPS
ELECTRICAL RISER
GENERAL NOTES: DIAGRAM KEYED NOTES:
A. PROVIDE GROUND /BONDING AS INDICATED ON THE NATIONAL ELECTRICAL CODE.
REMAIN. COORDINATE WITH AEP FOR NEW SECONDARY WIRING.
B. NAME PLATES SHALL BE PROVIDED FOR ALL ELECTRICAL SWITCH GEAR, PANEL BOARDS,
CONTRACTOR SHALL INCLUDE ALL COST FROM AEP FOR THE NEW
LIGHTING CONTACTORS, LIGHTING CONTROL PANELS, ETC.. BY ELECTRICAL CONTRACTOR. WORK ON THE SECONDARY SIDE.
C. NEW ELECTRICAL METERING AND SERVICE EQUIPMENT SHALL BE PROVIDED AND INSTALLED WP/"IN-USE GENERAL RECEPTACLE CIRCUIT. CIRCUIT SHALL BE
ACCORDING TO THE LOCAL POWER UTILITY CO. AND CITY REQUIREMENTS. VERIFY AND "BL-1" OF PANEL-BL.
COORDINATE WITH POWER UTILITY CO. AND AHJ BEFORE BID AND INSTALLATION.
LIGHTING CIRCUIT VIA LIGHTING CONTROL CABINET. WIRE SIZE
D. COMPLY WITH NFPA 70E SAFETY REQUIREMENTS. SHALL REMAIN THE SAME AS SCHEDULED.

E. PROVIDE ARC FLASH WARNING LABELS. NEW 1-RUN 4#4/0, 1#4G, 2.5"C. PROVIDE WARNING RIBBONS 12"
ABOVE CONDUIT.
F. PROVIDE 4"CONCRETE PAD FOR ALL DRY-TYPE TRANSFORMERS.
G. COMPLY WITH SEPARATE BUILDINGS OR STRUCTURES GROUNDING BONDING PER NEC. ALL OTHER DISCONNECT NOT RELATED TO BASEBAL SHALL BE
INSTALL BACK. FIELD VERIFY EXISTING CONDITIONS.
H. CONTRACTOR SHALL BE RESPONSIBLE FOR DELIVERY OF ELECTRICAL SERVICE TO THE NEW
GALVANIZED 3" PIPE AND GALVANIZED UNISTRUT STAND, SIZE AS
PROJECT WITHIN PROJECT SCHEDULE.
NEED FOR NEW AND EXISTING EQUIPMENT. PLACE IN THE
EXISTING LOCATION OF EXISTING SUPPORTS.

TYP.
LIGHTING CONTROL TYP.
CONTROL CIRCUIT CABINET

PNL
PNL
'BR'
'BH'
EXISTING
POWER
COMPANY
3#10, 1#10G,1"C TVSS TRANSFORMER
TX-B-SUPPORT TO STAND 1#2G
1#8G
P S
CONCRETE
GND ROD DEPTH MIN.36"

WESLACO
EXISTING EXISTING
GND ROD
3#8, 1#10G,1"C

MIN.DEPTH 24"
TO LIGHT POLES
REFER TO PANEL SCHEDULES

04/30/15

3533 Moreland Dr. Ste A l Weslaco, Tx 78596


p:956.973.0500 l f:956-351-5750
www.trinitymep.com I Copyright 2015
E2.1
Texas Registered Engineering Firm - F10362
Project number: 15.2.06