You are on page 1of 8

FIELD TAG DESCRIPTION SIGNAL TYPE

PIT-020 Seawater Inlet Pressure AI


PIT-020 Seawater Inlet Pressure AI
PIT-001 Seawater Booster pump P-1001 A Discharge Pressure AI
PIT-002 Seawater Booster pump P-1001 B Discharge Pressure AI
TIT-001 Seawater outlet temperature from S - 1001 A/B AI
DPIT- 001 Diff. Pressure across Strainer S - 1001 A AI
DPIT- 002 Diff. Pressure across Strainer S - 1001 B AI
FIT - 001 Electrolyzer E-1001 A inlet flow high detection AI
PIT-020 Seawater Inlet Pressure AI
PIT-020 Seawater Inlet Pressure AI
PIT-001 Seawater Booster pump P-1001 A Discharge Pressure AI
PIT-002 Seawater Booster pump P-1001 B Discharge Pressure AI
TIT-002 Seawater outlet temperature from S - 1001 A/B AI
DPIT- 003 Diff. Pressure across Strainer S - 1001 A AI
DPIT- 004 Diff. Pressure across Strainer S - 1001 B AI
FIT - 002 Electrolyzer E-1001 A inlet flow high detection AI
PIT-020 Seawater Inlet Pressure AI
PIT-020 Seawater Inlet Pressure AI
PIT-001 Seawater Booster pump P-1001 A Discharge Pressure AI
PIT-002 Seawater Booster pump P-1001 B Discharge Pressure AI
TIT-003 Seawater outlet temperature from S - 1001 A/B AI
DPIT- 005 Diff. Pressure across Strainer S - 1001 A AI
DPIT- 006 Diff. Pressure across Strainer S - 1001 B AI
FIT - 003 Electrolyzer E-1001 A inlet flow high detection AI
PIT-020 Seawater Inlet Pressure AI
PIT-020 Seawater Inlet Pressure AI
PIT-001 Seawater Booster pump P-1001 A Discharge Pressure AI
PIT-002 Seawater Booster pump P-1001 B Discharge Pressure AI
TIT-004 Seawater outlet temperature from S - 1001 A/B AI
DPIT- 007 Diff. Pressure across Strainer S - 1001 A AI
DPIT- 008 Diff. Pressure across Strainer S - 1001 B AI
FIT - 004 Electrolyzer E-1001 A inlet flow high detection AI
PIT-020 Seawater Inlet Pressure AI
PIT-020 Seawater Inlet Pressure AI
PIT-001 Seawater Booster pump P-1001 A Discharge Pressure AI
PIT-002 Seawater Booster pump P-1001 B Discharge Pressure AI
TIT-005 Seawater outlet temperature from S - 1001 A/B AI
DPIT- 009 Diff. Pressure across Strainer S - 1001 A AI
DPIT- 010 Diff. Pressure across Strainer S - 1001 B AI
FIT - 005 Electrolyzer E-1001 A inlet flow high detection AI
PIT-020 Seawater Inlet Pressure AI
PIT-020 Seawater Inlet Pressure AI
PIT-001 Seawater Booster pump P-1001 A Discharge Pressure AI
PIT-002 Seawater Booster pump P-1001 B Discharge Pressure AI
TIT-006 Seawater outlet temperature from S - 1001 A/B AI
DPIT- 011 Diff. Pressure across Strainer S - 1001 A AI
DPIT- 012 Diff. Pressure across Strainer S - 1001 B AI
FIT - 006 Electrolyzer E-1001 A inlet flow high detection AI
PIT-020 Seawater Inlet Pressure AI
PIT-020 Seawater Inlet Pressure AI
PIT-001 Seawater Booster pump P-1001 A Discharge Pressure AI
PIT-002 Seawater Booster pump P-1001 B Discharge Pressure AI
TIT-007 Seawater outlet temperature from S - 1001 A/B AI
DPIT- 013 Diff. Pressure across Strainer S - 1001 A AI
DPIT- 014 Diff. Pressure across Strainer S - 1001 B AI
FIT - 007 Electrolyzer E-1001 A inlet flow high detection AI
PIT-020 Seawater Inlet Pressure AI
PIT-020 Seawater Inlet Pressure AI
PIT-001 Seawater Booster pump P-1001 A Discharge Pressure AI
PIT-002 Seawater Booster pump P-1001 B Discharge Pressure AI
TIT-008 Seawater outlet temperature from S - 1001 A/B AI
DPIT- 015 Diff. Pressure across Strainer S - 1001 A AI
DPIT- 016 Diff. Pressure across Strainer S - 1001 B AI
FIT - 008 Electrolyzer E-1001 A inlet flow high detection AI
PIT-020 Seawater Inlet Pressure AI
PIT-020 Seawater Inlet Pressure AI
PIT-001 Seawater Booster pump P-1001 A Discharge Pressure AI
PIT-002 Seawater Booster pump P-1001 B Discharge Pressure AI
TIT-009 Seawater outlet temperature from S - 1001 A/B AI
DPIT- 017 Diff. Pressure across Strainer S - 1001 A AI
DPIT- 018 Diff. Pressure across Strainer S - 1001 B AI
FIT - 009 Electrolyzer E-1001 A inlet flow high detection AI
PIT-020 Seawater Inlet Pressure AI
PIT-020 Seawater Inlet Pressure AI
PIT-001 Seawater Booster pump P-1001 A Discharge Pressure AI
PIT-002 Seawater Booster pump P-1001 B Discharge Pressure AI
TIT-010 Seawater outlet temperature from S - 1001 A/B AI
DPIT- 019 Diff. Pressure across Strainer S - 1001 A AI

NOTE:
* Effect Column shows the cause of the patricular device and such causes are named as GROUPs. The GROUP details are as followings,
GROUP 1- SHUT DOWN THE ALL RECTIFIER UNIT (TR-1001A/B/C), STOP SEAWATER BOOSTER PUMPS (P-1001A/B), PNEUMATIC OPERATED
GROUP 2- SHUT DOWN THE RESPECTIVE RECTIFIER UNIT (TR-1001A/B/C) AND CLOSE CORRESPONDING PNEUMATIC OPERATED ON OFF V
GROUP 3- SHUT DOWN THE UNIT
GROUP 4- STOP THE HYPO DOSING PUMP (P-1002 , P-1003, P-1004)
GROUP 5- STOP THE ACID CLEANING PUMP
GROUP 6- STOP THE ACID TRANSFER PUMP
GROUP 7- STOP THE HYPOCHLORITE DOSING PUMP P-1005
GROUP 8- CLOSE RESPECTIVE PNEUMATIC OPERATED ON OFF VALVE (XSDV 002/003/004) WITH TIME DELAY.
ALARM / TRIP SET POINT IN PLC
INTERLOCK PLC TAG CALIBRATION RANGE
MIN MAX
I 01 LCP 001 0 6
I 02 LCP 001 0 6
- LCP 001 0 6
- LCP 001 0 6
I 03 LCP 001 0 100
- LCP 001 0 1
- LCP 001 0 1
- LCP 001 0 50
I 03 LCP 001 0 41
I 04 LCP 001 0 46
- LCP 001 0 50
- LCP 001 0 54
I 04 LCP 001 0 59
- LCP 001 0 63
- LCP 001 0 67
- LCP 001 0 72
I 05 LCP 001 0 76
I 06 LCP 001 0 80
- LCP 001 0 84
- LCP 001 0 89
I 05 LCP 001 0 93
- LCP 001 0 97
- LCP 001 0 102
- LCP 001 0 106
I 07 LCP 001 0 110
I 08 LCP 001 0 115
- LCP 001 0 119
- LCP 001 0 123
I 06 LCP 001 0 128
- LCP 001 0 132
- LCP 001 0 136
- LCP 001 0 141
I 09 LCP 001 0 145
I 10 LCP 001 0 149
- LCP 001 0 153
- LCP 001 0 158
I 07 LCP 001 0 162
- LCP 001 0 166
- LCP 001 0 171
- LCP 001 0 175
I 11 LCP 001 0 179
I 12 LCP 001 0 184
- LCP 001 0 188
- LCP 001 0 192
I 08 LCP 001 0 197
- LCP 001 0 201
- LCP 001 0 205
- LCP 001 0 209
I 13 LCP 001 0 214
I 14 LCP 001 0 218
- LCP 001 0 222
- LCP 001 0 227
I 09 LCP 001 0 231
- LCP 001 0 235
- LCP 001 0 240
- LCP 001 0 244
I 15 LCP 001 0 248
I 16 LCP 001 0 253
- LCP 001 0 257
- LCP 001 0 261
I 10 LCP 001 0 265
- LCP 001 0 270
- LCP 001 0 274
- LCP 001 0 278
I 17 LCP 001 0 283
I 18 LCP 001 0 287
- LCP 001 0 291
- LCP 001 0 296
I 11 LCP 001 0 300
- LCP 001 0 304
- LCP 001 0 309
- LCP 001 0 313
I 19 LCP 001 0 317
I 20 LCP 001 0 322
- LCP 001 0 326
- LCP 001 0 330
I 12 LCP 001 0 334
- LCP 001 0 339

The GROUP details are as followings,


PUMPS (P-1001A/B), PNEUMATIC OPERATED ON OFF VALVE XSDV 001 CLOSED.
PONDING PNEUMATIC OPERATED ON OFF VALVE (XSDV 002/003/004) WITH TIME DELAY.

H TIME DELAY.
LARM / TRIP SET POINT IN PLC
CALIBRATION UNIT TRIP EFFECT LOW LOW LOW HIGH HIGH HIGH
PLC PLC PLC PLC
kg/cm2 g HIGH HIGH Group - 1 - - - 5
kg/cm2 g HIGH - - - 3.5 -
kg/cm2 g LOW - 3.5 - - -
kg/cm2 g LOW - 3.5 - - -
Deg.C HIGH Group - 1 - - 40 -
kg/cm2 HIGH HIGH - - - - 0.75
kg/cm2 HIGH HIGH - - - - 0.75
m3/hr HIGH - - - 36 -
kg/cm2 g HIGH HIGH Group - 2 - - - 6
kg/cm2 g HIGH - - - 4.5 -
kg/cm2 g LOW - 3.5 - - -
kg/cm2 g LOW - 3.5 - - -
Deg.C HIGH Group - 2 - - 41 -
kg/cm2 HIGH HIGH - - - - 0.75
kg/cm2 HIGH HIGH - - - - 0.75
m3/hr HIGH - - - 37 -
kg/cm2 g HIGH HIGH Group - 3 - - - 7
kg/cm2 g HIGH - - - 5.5 -
kg/cm2 g LOW - 3.5 - - -
kg/cm2 g LOW - 3.5 - - -
Deg.C HIGH Group - 3 - - 42 -
kg/cm2 HIGH HIGH - - - - 0.75
kg/cm2 HIGH HIGH - - - - 0.75
m3/hr HIGH - - - 38 -
kg/cm2 g HIGH HIGH Group - 4 - - - 8
kg/cm2 g HIGH - - - 6.5 -
kg/cm2 g LOW - 3.5 - - -
kg/cm2 g LOW - 3.5 - - -
Deg.C HIGH Group - 4 - - 43 -
kg/cm2 HIGH HIGH - - - - 0.75
kg/cm2 HIGH HIGH - - - - 0.75
m3/hr HIGH - - - 39 -
kg/cm2 g HIGH HIGH Group - 5 - - - 9
kg/cm2 g HIGH - - - 7.5 -
kg/cm2 g LOW - 3.5 - - -
kg/cm2 g LOW - 3.5 - - -
Deg.C HIGH Group - 5 - - 44 -
kg/cm2 HIGH HIGH - - - - 0.75
kg/cm2 HIGH HIGH - - - - 0.75
m3/hr HIGH - - - 40 -
kg/cm2 g HIGH HIGH Group - 6 - - - 10
kg/cm2 g HIGH - - - 8.5 -
kg/cm2 g LOW - 3.5 - - -
kg/cm2 g LOW - 3.5 - - -
Deg.C HIGH Group - 6 - - 45 -
kg/cm2 HIGH HIGH - - - - 0.75
kg/cm2 HIGH HIGH - - - - 0.75
m3/hr HIGH - - - 41 -
kg/cm2 g HIGH HIGH Group - 7 - - - 11
kg/cm2 g HIGH - - - 9.5 -
kg/cm2 g LOW - 3.5 - - -
kg/cm2 g LOW - 3.5 - - -
Deg.C HIGH Group - 7 - - 46 -
kg/cm2 HIGH HIGH - - - - 0.75
kg/cm2 HIGH HIGH - - - - 0.75
m3/hr HIGH - - - 42 -
kg/cm2 g HIGH HIGH Group - 8 - - - 12
kg/cm2 g HIGH - - - 10.5 -
kg/cm2 g LOW - 3.5 - - -
kg/cm2 g LOW - 3.5 - - -
Deg.C HIGH Group - 8 - - 47 -
kg/cm2 HIGH HIGH - - - - 0.75
kg/cm2 HIGH HIGH - - - - 0.75
m3/hr HIGH - - - 43 -
kg/cm2 g HIGH HIGH Group - 9 - - - 13
kg/cm2 g HIGH - - - 11.5 -
kg/cm2 g LOW - 3.5 - - -
kg/cm2 g LOW - 3.5 - - -
Deg.C HIGH Group - 9 - - 48 -
kg/cm2 HIGH HIGH - - - - 0.75
kg/cm2 HIGH HIGH - - - - 0.75
m3/hr HIGH - - - 44 -
kg/cm2 g HIGH HIGH Group - 10 - - - 14
kg/cm2 g HIGH - - - 12.5 -
kg/cm2 g LOW - 3.5 - - -
kg/cm2 g LOW - 3.5 - - -
Deg.C HIGH Group - 10 - - 49 -
kg/cm2 HIGH HIGH - - - - 0.75
TRIP ALARM UNIT SHUTDOWN ALARM DESCRIPTION
PLC PLC
YES - Sea water inlet pressure high high alarm
YES - Sea water inlet pressure high alarm
- - Seawater Booster pump P-1001 A Discharge Pressure low alarm
- - Seawater Booster pump P-1001 B Discharge Pressure low alarm
YES - Seawater Outlet temperature from S-1001 A/B high alarm
- - Differential pressure across Strainer S -1001 A high high alarm
- - Differential pressure across Strainer S -1001 B high high alarm
- - Electrolyzer E-1001A inlet low Flow Alarm
YES - Sea water inlet pressure high high alarm
YES - Sea water inlet pressure high alarm
- - Seawater Booster pump P-1001 A Discharge Pressure low alarm
- - Seawater Booster pump P-1001 B Discharge Pressure low alarm
YES - Seawater Outlet temperature from S-1001 A/B high alarm
- - Differential pressure across Strainer S -1001 A high high alarm
- - Differential pressure across Strainer S -1001 B high high alarm
- - Electrolyzer E-1001A inlet low Flow Alarm
YES - Sea water inlet pressure high high alarm
YES - Sea water inlet pressure high alarm
- - Seawater Booster pump P-1001 A Discharge Pressure low alarm
- - Seawater Booster pump P-1001 B Discharge Pressure low alarm
YES - Seawater Outlet temperature from S-1001 A/B high alarm
- - Differential pressure across Strainer S -1001 A high high alarm
- - Differential pressure across Strainer S -1001 B high high alarm
- - Electrolyzer E-1001A inlet low Flow Alarm
YES - Sea water inlet pressure high high alarm
YES - Sea water inlet pressure high alarm
- - Seawater Booster pump P-1001 A Discharge Pressure low alarm
- - Seawater Booster pump P-1001 B Discharge Pressure low alarm
YES - Seawater Outlet temperature from S-1001 A/B high alarm
- - Differential pressure across Strainer S -1001 A high high alarm
- - Differential pressure across Strainer S -1001 B high high alarm
- - Electrolyzer E-1001A inlet low Flow Alarm
YES - Sea water inlet pressure high high alarm
YES - Sea water inlet pressure high alarm
- - Seawater Booster pump P-1001 A Discharge Pressure low alarm
- - Seawater Booster pump P-1001 B Discharge Pressure low alarm
YES - Seawater Outlet temperature from S-1001 A/B high alarm
- - Differential pressure across Strainer S -1001 A high high alarm
- - Differential pressure across Strainer S -1001 B high high alarm
- - Electrolyzer E-1001A inlet low Flow Alarm
YES - Sea water inlet pressure high high alarm
YES - Sea water inlet pressure high alarm
- - Seawater Booster pump P-1001 A Discharge Pressure low alarm
- - Seawater Booster pump P-1001 B Discharge Pressure low alarm
YES - Seawater Outlet temperature from S-1001 A/B high alarm
- - Differential pressure across Strainer S -1001 A high high alarm
- - Differential pressure across Strainer S -1001 B high high alarm
- - Electrolyzer E-1001A inlet low Flow Alarm
YES - Sea water inlet pressure high high alarm
YES - Sea water inlet pressure high alarm
- - Seawater Booster pump P-1001 A Discharge Pressure low alarm
- - Seawater Booster pump P-1001 B Discharge Pressure low alarm
YES - Seawater Outlet temperature from S-1001 A/B high alarm
- - Differential pressure across Strainer S -1001 A high high alarm
- - Differential pressure across Strainer S -1001 B high high alarm
- - Electrolyzer E-1001A inlet low Flow Alarm
YES - Sea water inlet pressure high high alarm
YES - Sea water inlet pressure high alarm
- - Seawater Booster pump P-1001 A Discharge Pressure low alarm
- - Seawater Booster pump P-1001 B Discharge Pressure low alarm
YES - Seawater Outlet temperature from S-1001 A/B high alarm
- - Differential pressure across Strainer S -1001 A high high alarm
- - Differential pressure across Strainer S -1001 B high high alarm
- - Electrolyzer E-1001A inlet low Flow Alarm
YES - Sea water inlet pressure high high alarm
YES - Sea water inlet pressure high alarm
- - Seawater Booster pump P-1001 A Discharge Pressure low alarm
- - Seawater Booster pump P-1001 B Discharge Pressure low alarm
YES - Seawater Outlet temperature from S-1001 A/B high alarm
- - Differential pressure across Strainer S -1001 A high high alarm
- - Differential pressure across Strainer S -1001 B high high alarm
- - Electrolyzer E-1001A inlet low Flow Alarm
YES - Sea water inlet pressure high high alarm
YES - Sea water inlet pressure high alarm
- - Seawater Booster pump P-1001 A Discharge Pressure low alarm
- - Seawater Booster pump P-1001 B Discharge Pressure low alarm
YES - Seawater Outlet temperature from S-1001 A/B high alarm
- - Differential pressure across Strainer S -1001 A high high alarm