Protection Condition of Individual Drives

S.No Trip Conditions Instrument no Status Remarks


Rectifier-TR001A
1 Sea Water Inlet Pressure Very High >5 Kg/cm2 PIT020 OK
2 Filter Outlet Temp High > 40 DegC TIT001 OK
3 Hydrogen Conc Very High HE001 OK
4 Hydrogen Conc Very High HE002 OK
5 Hydrogen Conc Very High HE003 OK
6 Level in Hypochlorite Tank-1 Very High > 6500mmwc LT001 OK
7 Level in Hypochlorite Tank-2 Very High > 6500mmwc LT002 OK
8 Both Dilution Blower Set not running. B1001A/B/2A/B OK
9 Air Flow from Blower 1001A/B Low < 1500 m3/hr FT008 OK
10 Air Flow from Blower 1002A/B Low < 1500 m3/hr FT009 OK
11 Emergency Shutdown PB pressed ESD OK
12 Electrolyzer Flow Low from Switch FS001 OK
13 Electrolyzer Flow < 20 m3/hr from transmitter FIT001 OK Added as per site conditions
14 Electrolyzer Outlet Temp High > 45 DegC TIT002 OK
15 DP Across Electrolyzer High > 1 mmwc DPIT003 OK
OK
Rectifier-TR001B
1 Sea Water Inlet Pressure Very High >5 Kg/cm2 PIT020 OK
2 Filter Outlet Temp High > 40 DegC TIT001 OK
3 Hydrogen Conc Very High HE001 OK
4 Hydrogen Conc Very High HE002 OK
5 Hydrogen Conc Very High HE003 OK
6 Level in Hypochlorite Tank-1 Very High > 6500mmwc LT001 OK
7 Level in Hypochlorite Tank-2 Very High > 6500mmwc LT002 OK
8 Both Dilution Blower Set not running. B1001A/B/2A/B OK
9 Air Flow from Blower 1001A/B Low < 1500 m3/hr FT008 OK
10 Air Flow from Blower 1002A/B Low < 1500 m3/hr FT009 OK
11 Emergency Shutdown PB pressed ESD OK
12 Electrolyzer Flow Low FS002 OK
13 Electrolyzer Flow < 20 m3/hr from transmitter FIT002 OK Added as per site conditions
14 Electrolyzer Outlet Temp High > 45 DegC TIT003 OK
15 DP Across Electrolyzer High > 1 mmwc DPIT004 OK

Rectifier-TR001C
1 Sea Water Inlet Pressure Very High >5 Kg/cm2 PIT020 OK
2 Filter Outlet Temp High > 40 DegC TIT001 OK
3 Hydrogen Conc Very High HE001 OK
4 Hydrogen Conc Very High HE002 OK
5 Hydrogen Conc Very High HE003 OK
6 Level in Hypochlorite Tank-1 Very High > 6500mmwc LT001 OK
7 Level in Hypochlorite Tank-2 Very High > 6500mmwc LT002 OK
8 Both Dilution Blower Set not running. B1001A/B/2A/B OK
9 Air Flow from Blower 1001A/B Low < 1500 m3/hr FT008 OK
10 Air Flow from Blower 1002A/B Low < 1500 m3/hr FT009 OK
11 Emergency Shutdown PB pressed ESD OK
12 Electrolyzer Flow Low FS003 OK
13 Electrolyzer Flow < 20 m3/hr from transmitter FIT003 OK Added as per site conditions
14 Electrolyzer Outlet Temp High > 45 DegC TIT003 OK
15 DP Across Electrolyzer High > 1 mmwc DPIT005 OK

Sea Water Booster Pump-A - P1001A


1 Sea Water Inlet Pressure High > 3.5 Kg/cm2 PIT020 OK
2 Filter Outlet Temp High > 40 DegC TIT001 OK
3 Hydrogen Conc Very High HE001 OK
4 Hydrogen Conc Very High HE002 OK
5 Hydrogen Conc Very High HE003 OK
6 Level in Hypochlorite Tank-1 Very High > 6500mmwc LT001 OK
7 Level in Hypochlorite Tank-2 Very High > 6500mmwc LT002 OK
8 Both Dilution Blower Set not running. B1001A/B/2A/B OK
9 Air Flow from Blower 1001A/B Low < 1500 m3/hr FT008 OK
10 Air Flow from Blower 1002A/B Low < 1500 m3/hr FT009 OK
11 Emergency Shutdown PB pressed ESD OK
12 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement
13 Sea Water Inlet Pressure < 1.5 Kg/cm2 PIT020 OK Added as per site requirement

Sea Water Booster Pump-B - P1001B


1 Sea Water Inlet Pressure High > 3.5 Kg/cm2 PIT020 OK
2 Filter Outlet Temp High > 40 DegC TIT001 OK
3 Hydrogen Conc Very High HE001 OK
4 Hydrogen Conc Very High HE002 OK
5 Hydrogen Conc Very High HE003 OK
6 Level in Hypochlorite Tank-1 Very High > 6500mmwc LT001 OK
7 Level in Hypochlorite Tank-2 Very High > 6500mmwc LT002 OK
8 Both Dilution Blower Set not running. B1001A/B/2A/B OK
9 Air Flow from Blower 1001A/B Low < 1500 m3/hr FT008 OK
10 Air Flow from Blower 1002A/B Low < 1500 m3/hr FT009 OK
11 Emergency Shutdown PB pressed ESD OK
12 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement
13 Sea Water Inlet Pressure < 1.5 Kg/cm2 PIT020 OK Added as per site requirement

Dosing Pump to Sea Water Intake and Sump-A - P1002A


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in Hypochlorite Tank-1 Very Low < 700 mmwc LT001 OK Setpoint revised as per site condition
5 Level in Hypochlorite Tank-2 Very Low < 700 mmwc LT002 OK Setpoint revised as per site condition
6 Emergency Shutdown PB pressed ESD OK
7 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Dosing Pump to Sea Water Intake and Sump-B - P1002B


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in Hypochlorite Tank-1 Very Low < 450 mmwc LT001 OK Setpoint revised as per site condition
5 Level in Hypochlorite Tank-2 Very Low < 450 mmwc LT002 OK Setpoint revised as per site condition
6 Emergency Shutdown PB pressed ESD OK
7 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Dosing Pump to Sea Water Intake and Sump-C - P1002C


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in Hypochlorite Tank-1 Very Low < 700 mmwc LT001 OK Setpoint revised as per site condition
5 Level in Hypochlorite Tank-2 Very Low < 700 mmwc LT002 OK Setpoint revised as per site condition
6 Emergency Shutdown PB pressed ESD OK
7 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Dosing Pump to PT Plant-A - P1003A


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in Hypochlorite Tank-1 Very Low < 700 mmwc LT001 OK Setpoint revised as per site condition
5 Level in Hypochlorite Tank-2 Very Low < 700 mmwc LT002 OK Setpoint revised as per site condition
6 Emergency Shutdown PB pressed ESD OK
7 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Dosing Pump to PT Plant-B - P1003B


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in Hypochlorite Tank-1 Very Low < 700 mmwc LT001 OK Setpoint revised as per site condition
5 Level in Hypochlorite Tank-2 Very Low < 700 mmwc LT002 OK Setpoint revised as per site condition
6 Emergency Shutdown PB pressed ESD OK
7 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Dosing Pump to Cooling Tower-A - P1004A


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in Hypochlorite Tank-1 Very Low < 700 mmwc LT001 OK Setpoint revised as per site condition
5 Level in Hypochlorite Tank-2 Very Low < 700 mmwc LT002 OK Setpoint revised as per site condition
6 Emergency Shutdown PB pressed ESD OK
7 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Dosing Pump to Cooling Tower-B - P1004B


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in Hypochlorite Tank-1 Very Low < 700 mmwc LT001 OK Setpoint revised as per site condition
5 Level in Hypochlorite Tank-2 Very Low < 700 mmwc LT002 OK Setpoint revised as per site condition
6 Emergency Shutdown PB pressed ESD OK
7 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Dosing Pump to Cooling Tower-C - P1004C


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in Hypochlorite Tank-1 Very Low < 700 mmwc LT001 OK Setpoint revised as per site condition
5 Level in Hypochlorite Tank-2 Very Low < 700 mmwc LT002 OK Setpoint revised as per site condition
6 Emergency Shutdown PB pressed ESD OK
7 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Dosing Pump - P1005A


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in 7% Comm HCL Storage Tank Very Low-T1004 < 300 mmwc LT005 OK
5 Emergency Shutdown PB pressed ESD OK
6 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Dosing Pump - P1005B


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in 7% Comm HCL Storage Tank Very Low-T1004 < 300 mmwc LT005 OK
5 Emergency Shutdown PB pressed ESD OK
6 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Acid Cleaning Pump - P1006A


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in 6% Dil HCL Storage Tank Very Low-T1002 < 300 mmwc LT004 OK
5 Emergency Shutdown PB pressed ESD OK
6 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement
Acid Cleaning Pump - P1006B
1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in 6% Dil HCL Storage Tank Very Low-T1002 < 300 mmwc LT004 OK
5 Emergency Shutdown PB pressed ESD OK
6 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Acid Transfer Pump - P1007A


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in Comm HCL Storage Tank Very Low-T1003 < 300 mmwc LT003 OK
5 Emergency Shutdown PB pressed ESD OK
6 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Acid Transfer Pump - P1007B


1 Hydrogen Conc Very High HE001 OK
2 Hydrogen Conc Very High HE002 OK
3 Hydrogen Conc Very High HE003 OK
4 Level in Comm HCL Storage Tank Very Low-T1003 < 300 mmwc LT003 OK
5 Emergency Shutdown PB pressed ESD OK
6 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Pump - P1008A
1 Emergency Shutdown PB pressed ESD
2 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Pump - P1008B
1 Emergency Shutdown PB pressed ESD
2 Service Water Pressure Low < 2.25 Kg/Cm2 PIT-X001 OK Added as per site requirement

Air Dilution Blower-1001A


1 Hydrogen Conc Very High HE001
2 Hydrogen Conc Very High HE002
3 Hydrogen Conc Very High HE003
4 Emergency Shutdown PB pressed ESD
5 Discharge Gate Closed Added as per site requirement

Air Dilution Blower-1001B


1 Hydrogen Conc Very High HE001
2 Hydrogen Conc Very High HE002
3 Hydrogen Conc Very High HE003
4 Emergency Shutdown PB pressed ESD
5 Discharge Gate Closed Added as per site requirement

Air Dilution Blower-1002A


1 Hydrogen Conc Very High HE001
2 Hydrogen Conc Very High HE002
3 Hydrogen Conc Very High HE003
4 Emergency Shutdown PB pressed ESD
5 Discharge Gate Closed Added as per site requirement

Air Dilution Blower-1002B


1 Hydrogen Conc Very High HE001
2 Hydrogen Conc Very High HE002
3 Hydrogen Conc Very High HE003
4 Emergency Shutdown PB pressed ESD
5 Discharge Gate Closed Added as per site requirement