Professional Documents
Culture Documents
PEGS
Revision History
TABLE OF CONTENTS
1.0 Purpose................................................................................................................... 1
2.0 Scope ...................................................................................................................... 1
3.0 Definitions .............................................................................................................. 2
3.1 Language .............................................................................................................................2
3.2 Terminology .........................................................................................................................2
3.3 Common Acronyms ..............................................................................................................2
4.0 References.............................................................................................................. 3
4.1 PTTEP Internal References ..................................................................................................4
4.2 International Standards ........................................................................................................4
4.3 Industry Codes and Standards .............................................................................................4
5.0 Design Philosophy and Requirements for Boiler Water Treatment .................... 5
5.1 Water treatment....................................................................................................................5
5.2 Chemistry of boiler water ......................................................................................................5
5.3 Steam quality .......................................................................................................................5
5.4 Water chemistry ...................................................................................................................5
5.5 Condensates ........................................................................................................................7
5.6 Analytical control ..................................................................................................................7
5.7 Hot water loop ......................................................................................................................8
6.0 Appendices ............................................................................................................. 9
Appendix 1..........................................................................................................................................9
1.0 PURPOSE
2.0 SCOPE
This Specification defines minimal requirements relative to boiler water treatment to minimize
the risks of corrosion and fouling, reduce cleaning, and thus increase the efficiency of boilers
and steam-using equipment.
• Water-tube boilers
• Fire-tube boilers.
Steam generation water treatment is a sophisticated water chemistry area and requires an
understanding of the fundamentals of boiler water chemistry.
The requirements given in this document apply to boilers operating continuously. This
specification does not cover conditions relative to particular operations such as start-up,
shutdown or fast fluctuation steam production.
• Electric boilers
The particular case of pressurized hot water loop is also considered in this document.
In any cases, Boiler Manufacturer shall be consulted either for approval or advices.
3.0 DEFINITIONS
A number of different terms are commonly used to describe the work stages, processes, and
approvals which take place during the early stages of a development. This can often be a
source of confusion so the following section is intended to show the PTTEP preferred
terminology as used in this document.
3.1 LANGUAGE
In this document, the words should and shall have the following meanings:
3.2 TERMINOLOGY
Terminology Description
Set out below in alphabetical order are common acronyms as found within this document:
4.0 REFERENCES
The reference documents listed below, including Industry Codes and Standards and
COMPANY specifications, form an integral part of this Engineering General Specification.
Unless otherwise stipulated, the applicable version of these documents, including relevant
appendices and supplements, is the latest revision published on the effective date of a
contract.
1. Applicable Laws, Rules and Regulations of the country in which the system/equipment
will be operated (if any);
2. Purchase Order/ Service Order/ Contract Documents (Only applicable for direct
purchase by COMPANY)
Any conflict between any of the Contract Documents, or between this specification and any
other Contract Document, shall be reported to COMPANY for decision. In such a case, and
unless otherwise agreed or decided by COMPANY, it is understood that the more stringent
requirement shall apply. Exceptions to, or deviations from this specification are not permitted
unless previously accepted in writing by COMPANY. For this purpose, requests for
substitutions or changes of any kind shall be complete with all pertinent information required
for COMPANY assessment. COMPANY’s approval, nevertheless, will not, in any way, relieve
the responsibility of the CONTRACTOR to meet the requirements of the industry Codes and
Standards referred to and amended herein, in the event of conflict.
Internal documents applicable to this document are indicated in the table below.
International standards applicable to this document are indicated in the table below.
Industry codes, standards and regional legislation applicable to this document are indicated in
the table below.
- -
An appropriate on-site treatment of the water is always needed. This treatment has two
main objectives:
• The prevention of corrosion and fouling of the various elements of the boiler
(economizer, vaporization tubes, superheater)
• The production of vapor of suitable quality following the main criteria below:
Whenever possible, a pretreatment of the water external to the circuit must be privileged.
• “Low or very low phosphate” treatment for 40 < operating pressures < 110 bars
For any boiler, the quality of the steam to be produced is directly dictated by the users. The
criteria of purity of the vapor reflect the ultimate usage that is made: production of electricity
(turbines), superheated steam, etc.
The quality of the vapor is directly related to the quality of the water and to the design of the
boiler (drum, deheater, etc.).
Particular case of closed circuit hot water heating loops: Hot water loops are generally treated
using an oxygen scavenger (sulfite) only.
Specific circuit treatments (based on dispersing or chelating agents) can tolerate a higher
concentration of iron, copper and hardness in boilers. In normal conditions, water treatment
does not need dispersing agents. In certain cases however, the addition of dispersing or
chelating agents may be necessary. In that case, a dedicated study shall be carried out and
these specific treatments shall be qualified prior to their use.
Verification of the treatment efficiency may include (when fuel is used as combustible) the
extraction of a sample of tube in the zone with high thermal transfer during inspection of the
equipment to determine the on-surface mass of deposit. When the extraction of tubes is
inappropriate, specific non-destructive methods of inspection can be used.
5.4.3 PH
A pH > 8.5 is recommended for the feedwater to protect preheaters against corrosion. This
value is consistent with the water treatment of boiler. At high pressures, pH adjustment shall
be made by means of alkaline volatile agents only. (Note that to high pH can be detrimental to
steam and condensate piping)
Organic compounds could cause severe damages in generators as well as in turbines and
facilitate foaming.
5.4.5 SILICA
The limits for silica contents in boiler waters are given in appendix (Figures 3 and 4).
5.4.6 ALCALINITY
The P- and M- alkalinity are selected as basic control criteria because they correlate well to
the pH, corrosion inhibition, and foaming tendency.
5.4.7 CONDUCTIVITY
The recommended values are presented in appendix (Figures 1 and 2).
5.5 CONDENSATES
At least three parameters shall be controlled: pH, cationic conductivity and a specific
parameter related to the process (e.g. visual control if risk of pollution by hydrocarbons,
evaluation of the quantity of Cl-, etc.).
The contents and frequencies of water analyses relative to boilers is presented in tables 1 to
3. Water samples shall be taken at representative locations of the circuit.
Parameter Feedwater
Pressure (bar) 5 - 20 20 - 40 40 - 100
(1) (1)
pH Continuous Continuous Continuous(1)
Direct conduct. at 25oC Continuous(1) Continuous(1) Continuous(1)
H (Ca + Mg) once/shift once/shift once/shift
HCa once/month once/month once/month
SiO2 once/week once/week Continuous
O2 once/quarter once/quarter once/quarter
(1) For P > 100 bars, analytical control program to be defined specifically
A typical water treatment for closed pressurized hot water loops (< 20 bars) is presented in
appendix (Table 5). In order to be efficient, the loop shall be closed (monthly makeup water <
5% the total volume).
6.0 APPENDICES
Appendix 1.
Table 4 - Feedwater and boiler water quality for natural circulation steam
(1) For high heat flux (> 230 kW/m2), values of the upper pressure zone shall be used.
Pressure
(MPa)
Figure 1 - Direct conductivity limit in boiler water; direct conductivity of feed
water of feed > 30 μS/cm
Direct conductivity (µS/cm)
Pressure
(MPa)
Figure 2 - Direct conductivity limit in the boiler water; direct conductivity of feed
water of feed ≤ 30 μS/cm
Max SI O2 (mg/l)
Pressure
(MPa)
Figure 3 - Maximal (SiO2) concentration in boiler water (between 0.05 and 6 MPa)
Max SI O2 (mg/l)
Operating pressure
(MPa)
Figure 4 - Maximal (SiO2) concentration in boiler water (between 6 and 18 MPa)
Closed loop
Typical Target
conditioning Role Injection mode Typical dosage Periodicity monitoring Comments
product values
2-
Sulfite O2 Initial + top up Calculated to reach an in Batch [SO3 ] >10
scavenger in case of situ excess sulfite mg/l
2-
[SO3 ] concentration> 10 mg/l
decrease
Area of Concern: PEGS Content PEGS Relevance ISO standard Other standards
Document Title: Click here to enter text. Document I/D: Click here
Feedback details (when referring to documents, please state chapter and page number where appropriate.)
Received by: Enter text Feedback register updated by: Click here
Action taken
Click here to enter text. Date By Whom
Click date name
Further Action
By: Click here Title: Click here Dept.: Click Date: Click