INSPECTION PROCEDURE
FOR
MEDIUM VOLTAGE ELECTRICAL EQUIPMENT
(ARH SITE INSPECTION)
D R A
IN4-OCT 19
2
- 2 0
INTED
EN PR
ONTR
OLLED WH 1 / 15
NC
HMD SOUTH SATELLITE REVAMPING PROJECT -
ALGERIA
JOB CODE DOC. NO. REV.
0-7382-20 S-200-1670-202 0
SONATRACH SHEET 2 OF 15
INDEX
1 INTRODUCTION............................................................................................................................................ 3
2 DEFINITIONS................................................................................................................................................. 3
3 SCOPE ........................................................................................................................................................... 3
4 ACCEPTANCE CRITERIA ............................................................................................................................ 4
5 RESPONSIBILITIES ...................................................................................................................................... 4
6 International standards ................................................................................................................................ 4
7 Project documents ....................................................................................................................................... 5
8 SAFETY REQUIREMENT.............................................................................................................................. 5
9 INSPECTION METHOD................................................................................................................................. 5
9.1 Insulation Resistance Test .................................................................................................................... 5
9.2 Di-electric Test (High pot Test) .............................................................................................................. 6
9.3 Di-electric Strength Test of Oil for Transformer..................................................................................... 7
10 AttachmEnts ............................................................................................................................................. 8
D R A
IN4-OCT 19
2
- 2 0
INTED
EN PR
ONTR
OLLED WH 2 / 15
NC
HMD SOUTH SATELLITE REVAMPING PROJECT -
ALGERIA
JOB CODE DOC. NO. REV.
0-7382-20 S-200-1670-202 0
SONATRACH SHEET 3 OF 15
1 INTRODUCTION
This document is issued in order to invite Algerian Regulation Authority for Hydrocarbons (ARH) to
witness the site electrical tests of Medium Voltage Equipment for the Revamping Project on South
Satellite Units in Hassi-Messaoud.
Algerian Regulatory Authority consists on the recommendations of Algerian Decree 90-245 for
pressure vessels, inter-ministrial decree of 02-Dec-1992 for pipeline transport, circular-2 of
21-Jul-1003 (electrical equipment) and procedure of Hydrocarbon Regulatory Authority (ARH).
2 DEFINITIONS
These definitions below refer to terms used in this document are used for convenience of reference in
this document only. Contractual terms shall be defined in the Project Terms and Conditions.
(1) ARH : Algerian Regulation Authority for Hydrocarbons
(2) CA : Sonatrach
(3) Contractor : The Consortium JGC CORPORATION / JGC Algeria
(4) Subcontractor : The person, firm or corporation to whom the Order is issued
(5) TR : Transformer
(6) IR : Insulation Resistance measurement
(7) N/A :Not applicable
3 SCOPE
This test procedure describes the necessary inspection and tests to ensure that the Medium Voltage
equipment are electrically ready to be energized in accordance with ARH requirement.
This document covers only the electrical tests for Medium Voltage equipment which need to be
witnessed or reviewed by ARH. The equipment and test methods witnessed by ARH shall be tested in
according to Table 1.
Scope of Field Test and Inspection shall be defined in Field Inspection and Test Plan for Electrical
Work (S-200-1670-181).
The detail scope of the equipment to be witnessed by ARH are shown the paragraph 10.
D R A
IN4-OCT 19
2
- 2 0
INTED
EN PR
ONTR
OLLED WH 3 / 15
NC
HMD SOUTH SATELLITE REVAMPING PROJECT -
ALGERIA
JOB CODE DOC. NO. REV.
0-7382-20 S-200-1670-202 0
SONATRACH SHEET 4 OF 15
4 ACCEPTANCE CRITERIA
Judgement shall be made in accordance with the acceptance criteria shown in the project
specifications, drawings and instructions. If the results of the inspection are not acceptable, changes
or repairs shall be made, and the work / material should be re-inspected.
5 RESPONSIBILITIES
The Subcontractor Supervisors and QC Inspectors are responsible to accomplish the activities
described in this procedure. Contractor Supervisor and QC Inspectors are responsible to ensure the
activities are accomplished in accordance with the requirements of the Engineering Design. The
Subcontractor’s and Contractor’s Supervisor and QC shall meet the inspection requirements as per
Field Inspection and Test Plan for Electrical Work (S-200-1670-181).
Contractor and Subcontractor will perform quality control, by means of check, tests and inspections, at
scheduled required stage of construction in accordance with Contractor’s construction specifications
and drawings
6 INTERNATIONAL STANDARDS
IEC 60060-1 High-voltage test techniques – Part 1: General definitions and test
requirements
D R A
IN4-OCT 19
2
- 2 0
INTED
EN PR
ONTR
OLLED WH 4 / 15
NC
HMD SOUTH SATELLITE REVAMPING PROJECT -
ALGERIA
JOB CODE DOC. NO. REV.
0-7382-20 S-200-1670-202 0
SONATRACH SHEET 5 OF 15
IEC 60502-2 Power cables with extruded insulation and their accessories for rated
voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 2:
Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36
kV)
7 PROJECT DOCUMENTS
S-200-1670-181 : FIELD INSPECTION AND TEST PLAN FOR ELECTRICAL WORK
8 SAFETY REQUIREMENT
The High pot test generates voltages and currents that can cause harmful or even fatal electric shock,
for these reasons the following precautions should be considered:
(1) High pot generator should be installed in a manner that provides a safe test environment.
(2) Untrained people should not be able to have access to the testing area during tests performed
especially.
9 INSPECTION METHOD
The following Electrical tests shall be carried out with witness of ARH.
For transformer 11/5.7kV, 5000V test voltage and the result must exceed the following criteria.
Measuring points (Winding) Measured values (Usual values for mineral oil)
IN DR20A
CT-
19
24-O INTED
EN PR
ONTR
OLLED WH 5 / 15
NC
HMD SOUTH SATELLITE REVAMPING PROJECT -
ALGERIA
JOB CODE DOC. NO. REV.
0-7382-20 S-200-1670-202 0
SONATRACH SHEET 6 OF 15
9.1.2 Cable
Test voltage value for insulation resistance test shall be 5000V DC for the equipment which voltage
rating is above 5000 volts. Duration is 1 min. and the acceptance criteria are no less than 10 x Rating
Voltage [kV] / Length [km] in Mega ohms.
9.1.4 Motor
For electrical motor, test voltage value for insulation resistance test shall be 5000V DC for the
equipment which voltage rating is above 5000 volts. Duration is 1 min. and the acceptance criteria are
no less than 100 Mega ohms according to IEEE-43-2000.
D R A
IN4-OCT 19
2
- 2 0
INTED
EN PR
ONTR
OLLED WH 6 / 15
NC
HMD SOUTH SATELLITE REVAMPING PROJECT -
ALGERIA
JOB CODE DOC. NO. REV.
0-7382-20 S-200-1670-202 0
SONATRACH SHEET 7 OF 15
Cable Specification
Service Voltage Test Voltage (DC)
Uo/U (Um)
a) 18/30 kV 30 kV 4 x 18 = 72 kV
b) 3.6/6 kV 5.5kV 4 x 3.6 = 14.4 kV
The criteria of High pot test are according to Appendix DD of IEC 62271-200. Applied voltage shall be
AC during 1 min.
Finally, the valve should be flushed by draining off a sufficient quantity of oil to ensure that the sample
obtained is representative of the oil at the bottom of the tank.
Sealed glass sampling bottles are recommended. They must be absolutely clean and dry and should
be rinsed with the first sample drawn.
A green color may indicate the presence of copper soaps, and it may be expected that rapid
deterioration of the oil will occur.
D R A
IN4-OCT 19
2
- 2 0
INTED
EN PR
ONTR
OLLED WH 7 / 15
NC
HMD SOUTH SATELLITE REVAMPING PROJECT -
ALGERIA
JOB CODE DOC. NO. REV.
0-7382-20 S-200-1670-202 0
SONATRACH SHEET 8 OF 15
A strong acid smell is indicative of the presence of volatile acids which can cause tank corrosion
above oil level.
If the oil sample looks pure and clean, then Electrical Break Down tests can be carried out.
The electric strength of the oil will be the arithmetic mean of the six (06) tests and shall not be lower
than 50kV.
If the test is not satisfactory, then the oil analysis (Dissolved Gas Analysis / DSA) shall be carried out
by the approved laboratory.
As per the analysis results, it will be indicated if an oil regeneration (re-conditioning) is required or not.
The oil regeneration can be carried out on site (use of appropriate equipment, truck mounted)
The results of testing record shall be signed by all parties. The results of testing shall be recorded and
will be reviewed by ARH.
10 ATTACHMENTS
Regarding the detail scope of the equipment to be witnessed by ARH shall be confirmed the following
attachments.
D R A
IN4-OCT 19
2
- 2 0
INTED
EN PR
ONTR
OLLED WH 8 / 15
NC
HMD SOUTH SATELLITE REVAMPING PROJECT-ALGERIA JGC DOC. NO. S-200-1670-202 REV. 0
JGC JOB CODE: 0-7382-20 SHEET 9 OF 15
Note :
:Meggar Test ( Insulation test )
ATTACHMENT-1
S1A
For Inf For Review For Const As Built
TITLE: TITRE:
INDTR
-2019
24-O
C
PRINT
ED
A310 E/029/HMD/2015 NONE
WHEN 9 / 15
LLED
NCONTRO
HMD SOUTH SATELLITE REVAMPING PROJECT-ALGERIA JGC DOC. NO. S-200-1670-202 REV. 0
JGC JOB CODE: 0-7382-20 SHEET 10 OF 15
Note :
:Meggar Test ( Insulation test )
ATTACHMENT-2
W1A
For Inf For Review For Const As Built
TITLE: TITRE:
INDTR
-2019
24-O
C
PRINT
ED
C310 E/029/HMD/2015 NONE
WHEN 10 / 15
LLED
NCONTRO
HMD SOUTH SATELLITE REVAMPING PROJECT-ALGERIA JGC DOC. NO. S-200-1670-202 REV. 0
JGC JOB CODE: 0-7382-20 SHEET 11 OF 15
Note :
:Meggar Test ( Insulation test )
ATTACHMENT-3
W1C
For Inf For Review For Const As Built
TITLE: TITRE:
INDTR
-2019
24-O
C
PRINT
ED
C410 E/029/HMD/2015 NONE
WHEN 11 / 15
LLED
NCONTRO
HMD SOUTH SATELLITE REVAMPING PROJECT-ALGERIA JGC DOC. NO. S-200-1670-202 REV. 0
JGC JOB CODE: 0-7382-20 SHEET 12 OF 15
Note :
:Meggar Test ( Insulation test )
ATTACHMENT-4
W2A
For Inf For Review For Const As Built
TITLE: TITRE:
INDTR
-2019
24-O
C
PRINT
ED
C110 E/029/HMD/2015 NONE
WHEN 12 / 15
LLED
NCONTRO
HMD SOUTH SATELLITE REVAMPING PROJECT-ALGERIA JGC DOC. NO. S-200-1670-202 REV. 0
JGC JOB CODE: 0-7382-20 SHEET 13 OF 15
Note :
:Meggar Test ( Insulation test )
ATTACHMENT-5
E1C
For Inf For Review For Const As Built
TITLE: TITRE:
INDTR
-2019
24-O
C
PRINT
ED
A110 E/029/HMD/2015 NONE
WHEN 13 / 15
LLED
NCONTRO
HMD SOUTH SATELLITE REVAMPING PROJECT-ALGERIA JGC DOC. NO. S-200-1670-202 REV. 0
JGC JOB CODE: 0-7382-20 SHEET 14 OF 15
Note :
:Meggar Test ( Insulation test )
ATTACHMENT-6
E2A
For Inf For Review For Const As Built
TITLE: TITRE:
INDTR
-2019
24-O
C
PRINT
ED
A210 E/029/HMD/2019 NONE
WHEN 14 / 15
LLED
NCONTRO
HMD SOUTH SATELLITE REVAMPING PROJECT-ALGERIA JGC DOC. NO. S-200-1670-202 REV. 0
JGC JOB CODE: 0-7382-20 SHEET 15 OF 15
Note :
:Meggar Test ( Insulation test )
ATTACHMENT-7