You are on page 1of 88

FEU Institute of Technology

College of Engineering
Civil Engineering Department

Compilation of Plate

Designed by:

FESTEJO, Marcus Julian V.


201520129
MONDAL, Mary Jane G.
201512835

Approved by:
Engr. Orlando Lopez
Introduction

The plates are a partial requirement of CEGEOTECH2 for school 3rd term school year
2020-2021. The plates are composed of a foundation design of a 4-storey school building.
The foundation has been designed from several topic from this term such as design of wall
footing, design of isolated footing, design of isolated footing subject to eccentric load, design
of combined footing and deep foundation. The inner columns will be labeled as F1, the outer
but not the corner column, will be labeled as F2, and the outer corner column will be labeled
as F3.

Plate number one is about the architectural and framing plan of a 4-storey school building
which is based on our plan in our previous course, reinforce concrete design.

Plate number two is about the design of the wall footing of the 4-storey school building. Wall
footing is designed to safely support structural or nonstructural walls and transmit and
distribute loads to the soil in such a manner that the load-bearing capacity of soil is not
surpassed.

Plate number three is about the design of isolated footing of the 4-storey school building. In
the design of isolated footing no boundary condition is set. The isolated footing was designed
to avoid exceeding its bearing capacity to provide safety against overturning or sliding while
preventing the ground from settling.

Plate number four is about the design of isolated footing of the 4-storey school building that
is subjected to eccentric load. The plate is designed in such a way that the center of gravity of
the superimposed load coincides with the center of gravity of the base area so, resulting in
uniform bearing pressure this footing is subjected to concentric loading.

Plate number five is about the design of combined footing of the 4-storey school building.
The design of combined footings is constructed for two or more columns when they are close
to each other and their foundation overlap. The footing that was chosen to be designed was
the critical columns.

Plate number six is about the design of deep foundation of the 4-storey school building. Deep
foundation is a type of foundation which is placed at a greater depth below the ground surface
and transfers structure loads to the earth at depth.
Acknowledgment

I would like to express my special thanks of gratitude to our CEGEOTECH2

professor, Engr. Orlando Lopez, in his persistent in teaching and helping me accomplish my

goal during these hard times.

I would also like to give thanks to my partner for being always available and approachable

during the process of accomplishing task given to us.

And lastly, thank you to our parents for being the best support system that we could ever had.

Thank you for you undying love and support that you give unconditionally.
Summary of Plates

Plate number Title of the Plate Grade

1 Architectural and Framing 84


Plan
2 Design of Wall Footing 92

3 Design of Isolated Footing 92

4 Design of Isolated Footing 92


Subjected to Eccentric Load
5 Design of Combined 92
Footing
6 Deep Foundation 92

Average 90.67
FEU Institute of Technology
College of Engineering
Civil Engineering Department

Architectural and Framing Plan

Designed by:

FESTEJO, Marcus Julian V.


201520129
MONDAL, Mary Jane G.
201512835

Approved by:

Engr. Orlando Lopez


FEU Institute of Technology
College of Engineering
Civil Engineering Department

Design of Wall Footing

Designed by:

FESTEJO, Marcus Julian V.


201520129
MONDAL, Mary Jane G.
201512835

Approved by:

Engr. Orlando Lopez


Material Properties:
• Concrete = 28 MPa
• Steel = 415 MPa
Section Properties:
• C1 (1st floor to Roofdeck) = 450 mm x 450 mm
• C2 (1st floor to Roofdeck) = 450 mm x 450 mm
• C3 (1st floor to Roofdeck) = 450 mm x 450 mm
• G1 = 450 mm x 450 mm
• Slab Thickness = 120 mm
Dead Load:
• Floor Load = 4.5 KPa (including Slab Weight)
• Hollow Concrete Masorny = 3.02 KPa
Live Load:
• Floor Load = 1.9 KPa
Seismic Parameter:
• Seismic Load Code
• Soil Profile Type
• Closest Distance to Source
• Importance Factor
• Ductility Coefficient
Geotechnical Condition:
• Allowable Soil Bearing Capacity = 200 KPa
• Weight of Soil = 16 KNm3
Boundary Condition:
• Support = Pinned Support
Load Combination:
• Load Combination = ACI 318-14
FEU Institute of Technology
College of Engineering
Civil Engineering Department

Design of Isolated Footing

Designed by:

FESTEJO, Marcus Julian V.


201520129
MONDAL, Mary Jane
201512835

Approved by:

Engr. Orlando Lopez


FEU Institute of Technology
College of Engineering
Civil Engineering Department

Design of Isolated Footing Subject to


Eccentric Loading

Designed by:

FESTEJO, Marcus Julian V.


201520129
MONDAL, Mary Jane
201512835

Approved by:
Engr. Orlando Lopez
FEU Institute of Technology
College of Engineering
Civil Engineering Department

Design of Combined Footing

Designed by:

FESTEJO, Marcus Julian V.


201520129
MONDAL, Mary Jane
201512835

Approved by:
Engr. Orlando Lopez
FEU Institute of Technology
College of Engineering
Civil Engineering Department

Deep Foundations

Designed by:

FESTEJO, Marcus Julian V.


201520129
MONDAL, Mary Jane
201512835

Approved by:

Engr. Orlando Lopez