IS 7098 (Part 2) : 2011

Table 3 Properties of Thermoplastic 12.5 Application of Insulation


Polyethylene Sheath
The insulation shall be so applied that it fits closely
(Clause 9)
on the conductor (or conductor screening or barrier if
Sl No. Property Requirements any) and it shall be possible to remove it without
(1) (2) (3) damaging the conductor.
i) Without aging
a) Tensile strength (N/mm²) 12.5 N/mm², Min 13 INSULATION SCREENING
b) Elongation at break 300 percent, Min
ii) Ageing in air oven: 13.1 All cables rated above 1.9/3.3 kV shall be provided
a) Treatment Temperature 110 ± 2 °C with insulation screening.
Duration 7 days
b) Elongation at break 300 percent, Min 13.2 The insulation screening shall consist of two parts;
iii) Carbon black content 2.5 ± 0.5 percent namely, metallic and non-metallic.
iv) Hot deformation test
110 ± 2 °C for 6 h 13.3 Non-metallic part shall be applied directly over
Maximum depth of indentation 50 percent the insulation of each core and shall consist of either
extruded semi-conducting compound or a
12.2 Thickness of Insulation combination of semi-conducting tape and extruded
The average thickness of insulation shall be not less semi-conducting compound. The test method for
than the nominal value (ti) specified in Table 4 strippability test for strippable semi-conducting
insulation screen is given in Annex B. Semi-
12.3 Tolerance on Thickness of Insulation conducting water swell-able tapes if used shall be as
The smallest of measured values of thickness of agreed between the purchaser and the supplier.
insulation shall not fall below the nominal value (ti) 13.4 Metallic part shall consist of either tape, or braid,
specified in Table 4 by more than 0.1 mm + 0.1 ti. or concentric serving of wires or a combination of wires
12.4 Eccentricity and Ovality and tapes or a sheath shall be non-magnetic and shall
be applied over the non-metallic part. For single-core
Eccentricity of insulation shall not exceed 15 percent armoured cables, the armouring may constitute the
when tested as per Annex A. metallic part of the screening.

Table 4 Nominal Thickness of Insulation


(Clauses 12.2 and 12.3)
Sl No. Nominal Area of Nominal Thickness of Insulation (tI)
Conductor
1.9/3.3 kV and 3.3/3.3 kV 3.8/6.6 kV 6.35/11 kV 11/11 kV 12.7/22 kV 19/33kV

Single Core Single Core


Armoured Unarmoured and
Cables Three Core Cables
mm2 mm mm mm mm mm mm mm
(1) (2) (3) (4) (5) (6) (7) (8) (9)

i) 25 2.5 2.2 2.8 3.6 5.5 6.0 8.8


ii) 35 2.5 2.2 2.8 3.6 5.5 6.0 8.8
iii) 50 2.5 2.2 2.8 3.6 5.5 6.0 8.8
iv) 70 2.5 2.2 2.8 3.6 5.5 6.0 8.8
v) 95 2.5 2.2 2.8 3.6 5.5 6.0 8.8

vi) 120 2.5 2.2 2.8 3.6 5.5 6.0 8.8


vii) 150 2.5 2.2 2.8 3.6 5.5 6.0 8.8
viii) 185 2.5 2.2 2.8 3.6 5.5 6.0 8.8
ix) 240 2.5 2.2 2.8 3.6 5.5 6.0 8.8
x) 300 2.5 2.2 3.0 3.6 5.5 6.0 8.8

xi) 400 2.6 2.2 3.3 3.6 5.5 6.0 8.8


xii) 500 2.8 2.4 3.5 3.6 5.5 6.0 8.8
xiii) 630 3.0 2.6 3.5 3.6 5.5 6.0 8.8
xiv) 800 3.3 2.8 3.5 3.6 5.5 6.0 8.8
xv) 10000. 3.5 3.0 3.6 3.6 5.5 6.0 8.8

4
IS 7098 (Part 2) : 2011

14 CORE IDENTIFICATION Table 5 Thickness of Inner Sheath


(Clause 16.3)
14.1 Core identification for three core cables shall be
as follows: All dimensions in millimetres.
Sl No. Calculated Diameter Over Thickness of Inner
Voltage Grade kV Method of Identification Laid Up Cores, Sheath
1.9/3.3 and 3.3/3.3 a) Different colouring of Ref to IS 10462 (Part 1) Min
XLPE insulation, or
b) Coloured strips applied on Over Up to and
the cores, or Including
(1) (2) (3) (4)
c) By numerals (1, 2, 3,)
either by applying i) — 25 0.3
numbered strips or by ii) 25 35 0.4
iii) 35 45 0.5
printing on the cores. iv) 45 55 0.6
NOTE — It is permissible to apply v) 55 — 0.7
the strips above the insulation
screen
3.8/6.6, 6.35/11, a) Coloured strips applied on protective barrier or non-metallic part of insulation
11/11, 12.7/22 and the cores, or screening, if any in case of single core cables or over
19/33 kV b) By numerals (1, 2, 3…) inner sheath in case of screened and armoured single
either by applying numbered core cables and over inner sheath in case of three cores
strips or by printing on the cables.
cores
17.1.1 The armour wires/formed wires shall be applied
14.1.1 For identification by using coloured strips, red, as closely as practicable.
yellow and blue colours respectively shall be used to
17.1.2 The direction of lay of armour shall be left hand
identify phase conductors.
for double wires/formed wires armoured cable this
15 LAYING UP OF CORES requirement shall apply to the inner layer of wires/
formed wires the outer layer shall, except in special
15.1 In three core cables, the cores shall be laid together
cases be applied in the reverse direction to the inner
with a suitable right hand lay. Where necessary the
layer, and there shall be a separator of suitable non-
interstices shall be filled with non-hygroscopic
hygroscopic material: such as plastic tape bituminized
material.
Hessian cotton tape, rubber proofed tape between the
16 INNER SHEATH (COMMON COVERING) inner and outer layers of armoured wires/formed
wires.
16.1 The laid up cores shall be provided with inner
sheath applied either by extrusion or by wrapping. It 17.1.3 A binder tape may be applied over the armour.
shall be ensured that the shape is as circular as possible.
17.2 Types of Armour
16.2 The inner sheath shall be so applied that it fits
closely on the laid up cores and it shall be possible to Where the calculated diameter below armouring does
remove it without damage to the insulation. not exceed 13 mm, the armour shall consist of
galvanized round steel wires. The armour of cables
16.2.1 In case of single core cables where there are having calculated diameter below armouring greater
both metallic screening and armouring there shall be than 13 mm shall consist of either galvanized round
extruded inner sheath between them. steel wires or galvanized formed wires.
16.3 Thickness of Inner Sheath 17.2.1 In case of single-core cables for ac system, the
The thickness of inner sheath (common covering) shall armouring shall be of non-magnetic material.
be as given in Table 5 single core cables except those
17.3 Dimensions
specified on 15.2.1 shall have no inner sheath.
The dimension of galvanized steel wire or formed wires
16.3.1 When one or more layers of binder tapes are
shall be as specified in Table 6.
applied over the laid up cores, the thickness of the tapes
shall not be construed as a part of the inner sheath. 17.4 Joints
17 ARMOURING The joints in armour wires or formed wires shall be
made by brazing or welding and the surface
17.1 Application
irregularities shall be removed. A joint in any wires/
Armouring shall be applied over the insulation or formed wires shall be at least 300 mm from the nearest

5
IS 7098 (Part 2) : 2011

Table 6 Dimensions of Armour — Round Wires formed wires in armour by required number of tinned
and Formed Wires copper wires/formed wires is permissible.
(Clause 17.3)
18 OUTER SHEATH
All dimensions in millimetres.
18.1 The outer sheath shall be applied by extrusion. It
Sl Calculated Diameter Nominal Nominal Diameter shall be applied:
No. Under Armour Thickness of of Round Wire
[IS 10462 (Part 1)] Steel Strip a) Over the non-magnetic metallic tape
covering. The insulation or over The non-
Over Up to and magnetic metallic part of insulation
Including
(1) (2) (3) (4) (5) screening in case of un-armoured single core
cables, and
i) For all diameter in 0.8 —
excess of 13 or b) Over the armouring in case of armoured cables.
ii) 13 — 1.4
b) 13 25 0.8 1.6 18.2 Colour of outer sheath shall be black or any
c) 25 40 0.8 2.0 other colour as agreed to between the purchaser and
d) 40 55 1.4 2.5 the supplier.
e) 55 70 1.4 3.15
f) 70 — 1.4 4.0 18.3 Thickness of Outer Sheath
NOTE — (i) and (ii) indicate two methods of practice in the
application of armouring. 18.3.1 Unarmoured Cables
The thickness of outer sheath of unarmoured cables
determined by taking the average of a number of
joint in any other armoured wire/formed wires in the measurements shall be not less than the nominal value
completed cable. specified in col 3 of Table 7 and the smallest of the
measured values shall not fall below the nominal value
17.5 Resistance
specified in col 4 of Table 7.
In case of cable for use in mines the resistance of
18.3.2 Armoured Cables
armoured shall be not exceed that of conductor as
specified in IS 8130 by more than 33 percent. To The thickness of outer sheath shall not be less than
satisfy this, substitution of the galvanized steel wires/ the minimum value specified in col 5 of Table 7.

Table 7 Thickness of Outer Sheath


(Clauses 18.3.1 and 18.3.2)
All dimensions in millimetres.

Sl No. Calculated Diameter Under the Thickness of Outer Sheath for Minimum Thickness of Outer
Outer Sheath [IS 1S462 (Part 1)] Unarmoured Cables Sheath for Armoured Cables

Over Up to and Nominal Minimum


Including (ts)
(1) (2) (3) (4) (5) (6)

i) — 15 1.8 1.24 1.24


ii) 15 25 2.0 1.4 1.4
iii) 25 35 2.2 1.56 1.56
iv) 35 40 2.4 1.72 1.72
v) 40 45 2.6 1.88 1.88
vi) 45 50 2.8 2.04 2.04
vii) 50 55 3.0 2.2 2.2
viii) 55 60 3.2 2.36 2.36
ix) 60 65 3.4 2.52 2.52
x) 65 70 3.6 2.68 2.68
xi) 70 75 3.8 2.84 2.84
xii) 75 — 4.0 3.0 3.0

6
IS 7098 (Part 2) : 2011

19 CLASSIFICATION OF TESTS 19.1.1 Test (viii), (x), (xii) and (xiii), are applicable
only to screened cables.
19.1 Type Tests
19.1.2 With the exception and provision of 19.1.1 the
The following shall constitute type tests: following tests on screened cable shall be performed

Sl No. Test For Requirements, Ref to Method of Test, Ref to


IS 10810
(1) (2) (3) (4)
i) Test on conductor:
a) Annealing test (for copper) IS 8130 1
b) Tensile test (for aluminium) IS 8130 2
c) Wrapping test (for aluminium) IS 8130 3
d) Resistance test IS 8130 5
ii) Test for armouring wires/formed wires Clause 7, Table 6 and 36-42
IS 3975
iii) Physical test for insulation:
a) Tensile strength and elongation at break Table 1 7
b) Ageing in air oven Table 1 11
c) Degree of cross linking
d) Hot set test Table 1 30
e) Shrinkage test Table 1 12
f) Water absorption test (gravimetric) Table 1 33
iv) Test for thickness of insulation Clause 11, Tables 4, 5 and 6
(eccentricity) and sheath 7 and Annex A
v) Test on extruded semi conducting screens

a) Test for strippability of semicon- Table 2 and Annex B


ducting strippable insulation screen
(when applicable)

b) Volume resistivity Table 2 and Annex E


vi) Physical test for outer sheath:
a) Tensile strength and elongation at IS 5831 or Table 3 7
break
b) Ageing in air oven IS 5831 or Table 3 11
c) Shrinkage test IS 5831 12
d) Hot deformation IS 5831 or Table 3 15
e) Loss of mass in air oven IS 5831 10
f) Heat shock IS 5831 14
g) Thermal stability IS 5831 60
h) Carbon black content of polythene Table 3 32 or any other thermo
sheath analytic method (by thermo
gravimetric analysis)
vii) Thermal ageing test for complete cable 19.9 see 19.9
viii) Partial discharge test 19.2 46
ix) Bending test 19.3 50
x) Dielectric power factor test: 19.4 48
a) As a function of voltage
b) As a function of temperature
xi) Insulation resistance (volume resistivity) test Table 1 43
xii) Heat cycle test 19.5 49
xiii) Impulse withstand test 19.6 47
xiv) High voltage test 19.7 45
xv) Flammability test for PVC sheathed cables 19.8 53

7
IS 7098 (Part 2) : 2011

successively on the same test sample of completed power factor as a function of voltage and
cable not less than 10 m in length between the test partial discharge tests,
accessories: f) Impulse withstand test, and
a) Partial discharge test, g) High voltage test.
b) Bending test followed by partial discharge test, 19.1.2.1 If a sample fails in test (vii) one more sample
c) Dielectric power factor as a function of voltage, shall be taken for this test preceded by tests (ii) and (v).
d) Dielectric power factor as a function of 19.1.3 The following shall constitute additional type
temperature, test for the cables with improved fire performance as
e) Heating cycle test followed by dielectric per the Categories given in Annex C.

Category Test For Requirement, Methods of Test,


Ref to Clause Ref to IS 10810
(1) (2) (3) (4)
01 No additional test — —
C1 a) Oxygen index 20.10 58
b) Flame retardance test on single cables 20.11 61
c) Flame retardance test on bunched cables 20.12 62
d) Temperature index 20.15 64
C2 a) Oxygen index 20.10 58
b) Flame retardance test on single cables 20.11 61
c) Flame retardance test on bunched cables 20.12 62
d) Smoke density test (on sheathing material) 20.14 under preparation
e) Test for halogen acid gas evolution 20.13 59
f) Temperature index 20.15 64

NOTES
1 For Category C1 tests (a) and (d) are to be performed on sample taken from the outer sheath, as applicable and prepared in
the manner given in the relevant test methods .
2 For Category C2 test (a) , (e), and (f) are to be performed on samples taken from outer sheath , as applicable and prepared
in the manner given in relevant test methods .

19.2 Acceptance Tests 19.2.1 A recommended sampling plan for acceptance


test is given in Annex D.
The following shall constitute acceptance tests:
19.2.2 The following shall constitute additional
a) Annealing tests (for copper),
acceptance tests for cables with improved fire
b) Tensile test (for aluminium),
performance as per the categories given in Annex C.
c) Wrapping test (for aluminium),
d) Conductor resistance tests, Category Test
e) Test for thickness of insulation (eccentricity) 01 No additional test
and sheath, C1 a) Oxygen index
f) Hot set test for insulation, b) Flame retardance test on single cable
g) Tensile strength and elongation at break test c) Flame retardance on bunched cables
for insulation and outer sheath, C2 a) Oxygen index
h) Partial discharge test (for screened cables b) Flame retardance test on single cable
only), c) Flame retardance test on bunched
j) High voltage test, cables
d) Test for halogen acid gas evolution
k) Insulation resistance (volume resistivity) test,
and e) Test for smoke density
m) Test for cross linking for extruded semi- 19.3 Routine Tests
conducting screen.
The following shall constitute routine tests:
NOTE — Partial discharge test shall be carried out on full
drum length. a) Conductor resistance test,

8
IS 7098 (Part 2) : 2011

b) Partial discharge test (for screened cables The heating cycle shall be of atleast 8 h duration. The
only), conductor temperature shall be maintained within the
c) High voltage test, and stated temperature limits for atleast 2 h of each heating
d) Resistance test for armour (for mining cables) period. This shall be followed by atleast 3 h of natural
in accordance with IS 10810 (Part 42) cooling in air to a conductor temperature within 10 K
and 17.5. of ambient temperature.
NOTES
NOTE — Partial discharge test shall be carried out on full
drum length. 1 The cycle shall be carried out 20 times.
2 After twentieth cycle, the sample shall be subjected to
19.4 Optional Test dielectric power factor as a function of voltage (20.4.1) and
partial discharge test (see 20.2).
Cold impact test for outer sheath (see IS 5831).
20.6 Impulse Withstand Test
20 DETAILS OF TESTS
Impulse voltage level shall be as given below:
20.1 General
Rated voltage, 3.8/6.6 6.35/11 11/11 12.7/22 19/33
Unless otherwise stated in this standard, the test shall kV
be carried out in accordance with appropriate part of Impulse volt- 60 75 95 125 170
IS 10810, taking into account additional information age, kV
given in this standard.
No breakdown of insulation shall occur during the
20.2 Partial Discharge Test test. The temperature of the conductor shall be at 5 °C
The partial discharge magnitude at test voltage equal to 10 °C above the maximum conductor temperature
to 1.73 Uo shall not exceed 10 pC for routine tests/ in normal operation.
acceptance tests and 5pC for Type Tests.
20.7 High Voltage Test
20.3 Bending Test 20.7.1 Type/Acceptance Test
The diameter of the test cylinder shall be 20D ± 5 The cable shall withstand without breakdown an ac
percent where D is the overall diameter of the voltage equal to 4 Uo when applied to the sample
completed cable. After completing the bending between conductor and screen/metallic tape/armour
operations, the test sample shall be subjected to partial (and between conductors in case of unscreened cable).
discharge measurement and shall comply with the the voltage shall be gradually increased to the specified
requirements given in 20.2. value and maintained for a period of 4 h.
20.4 Dielectric Power Factor Test If while testing, interruption occurs during the 4 h
20.4.1 tan δ as a Function of Voltage period the test shall be prolonged to the same extent.
If the interruption period exceeds 30 min, the tests shall
The measured value of tan δ at U o shall not be repeated.
exceed 0.004 and the increment of tan δ between 0.5 Uo
and 2 Uo shall not be more than 0.002. 20.7.2 Routine Test

20.4.2 tan δ as a Function of Temperature The cables shall withstand without any failure, the
test voltages given below, when applied for a period
The measured value of tan δ shall not exceed 0.004 at of five minutes for each test connection:
ambient temperature and 0.008 at 5 °C to 10 °C above
the maximum conductor temperature in normal Voltage Test Voltage
operation. Grade kV
Between Conductor Between
20.5 Heating Cycle Test and Screen/Armour Conductor
The sample, which has been subjected to previous tests kV (rms) kV (rms)
shall be laid out on the floor of the test room and heated
by passing a current through the conductor, until the 1.9/3.3 10 10
conductor reaches a steady temperature of 5°C to 10 °C 3.8/6.6 13
above the maximum conductor temperature in normal 6.35/11 21
operation. 11/11 35
12.7/22 42
For three core cables, the heating current shall be 19/33 63
passed through all conductors.

9
IS 7098 (Part 2) : 2011

20.8 Flammability Test for PVC Sheathed Cables reached a height exceeding 2.5 m above the bottom
edge of the burner, measured at the front and rear of
Period of burning after removal of the flame shall not
the cable assembly.
exceed 60 s and the unaffected (uncharred) portion from
the lower edge of the top clamp shall be at least 50 mm. NOTE — Requirements for this test are split in 3 categories
that is A, B and C as described in IS 10810 (Part 62). For
20.9 Thermal Ageing Test for Complete Cable the purpose of this standard, category B and C test method
shall be used. In the absence of any special requirements
This test shall be carried out to check that the for method B, method C shall be used for both categories
C1 and C2.
insulation, non-metallic sheath and extruded semi-
conducting layer over the conductor and insulation 20.13 Test for Halogen Acid Gas Evolution
are not liable to deteriorate in operation due to contact
with other components in the cable. The level of HCl evolved shall not exceed 20 percent
by weight.
Three pieces of complete cable about 200 mm long
shall be suspended vertically and substantially in the 20.14 Test for Smoke Density
center of the oven at least 20 mm away from each
Smoke density rating shall be 60 maximum.
other and shall not occupy more than 2 percent of the
volume of the oven. The pieces of cables shall be kept 20.15 Test for Temperature Index
in the oven at the temperature of 10 ± 2°C above the
rated maximum normal operating conductor The extrapolated values of temperature at which
temperature of the cable for duration of 168 h. oxygen index is 21 shall be minimum 250°C.

The test piece of insulation and sheath from the aged 21 IDENTIFICATION
piece of the cable shall be prepared and subjected to
21.1 Manufacturer’s Identification
tensile strength and elongation at break.
The manufacturer shall be identified throughout the
The resistivity of the extruded semi-conducting layers length of cable by manufacturers name or trade-mark
shall be determined on the test piece from the aged and the voltage grade and year of manufacture
cable sample in accordance with Annex E. indented, printed or embossed or by means of a tape
The resistivity of semi conducting screen layers measured bearing this information. the indentation, printing
as per Annex E shall not exceed the following values: or embossing shall be done only on the outer sheath.

a) Conductor screen : 1 000 Ω. m For manufacturers’ name, if none of these methods is


employed or if the purchaser so desires, colour
b) Insulation screen : 500 Ω. m
identification threads in accordance with a scheme to
20.9.1 The test results for the tensile strength and be approved by the Indian Standard insulation shall
elongation at break shall comply with the values be employed.
of insulation and sheath after ageing as given in
Table 1 for insulation and IS 5831 for PVC outer 21.2 Cable Identification
sheath and Table 3 for thermoplastic polyethylene 21.2.1 In case of cables intended for use in mines, the
outer sheath. word ‘Mining’ shall be indented, printed or embossed
on the outer sheath throughout the length of the cable.
20.10 Oxygen Index Test
21.2.2 The special cables with improved fire
The test on samples of outer sheath shall be done
performance for Category C1 and C2 shall be identified
at 27 ± 2°C or ambient. The oxygen index shall not
by indenting, embossing or printing the appropriate
be less than 29.
legend on the outer sheath throughout the cable length
20.11 Flame Retardance Test on Single Cables (for in addition to the existing marking requirements.
overall diameter ≤ 35 mm) Type of Cable Legend
After the test, there should be no visible damages on a) Improved fire performance or FR
the test specimen within 300 mm from its upper end. Category C1
Mark from fixing devices, soot or changing of the b) Improved fire performance or FR-LSH
colour are not considered damages. Category C2
20.12 Flame Retardance Test on Bunched Cables 21.3 Cable Code
After burning has ceased, the cables should be wiped The following code shall be used for designating the
clean and charred or affected portion should not have cable:

10
IS 7098 (Part 2) : 2011

Sl No. Constitute Code Letter b) Manufacturer’s name or trade-mark;


i) Aluminium conductor A c) Type of cable and voltage grade;
ii) XLPE insulation 2X d) Number of cores;
iii) Steel round wire armour W e) Nominal cross-sectional area of conductor;
iv) Non-magnetic round wire armour Wa f) Cable code;
v) Steel strip armour F g) Length of cable on the drum;
vi) Non-magnetic strip armour Fa h) Number of lengths on the drum (if more than
vii) Double steel round wire armour WW one);
viii) Double steel strip armour FF j) Direction of rotation of drum (by means of
ix) PVC outer sheath Y an arrow);
x) Polyethylene outer sheath 2Y k) Gross mass;
NOTE — No code letter for conductor is required when
m) Country of manufacture; and
the conductor material is copper. n) Year of manufacture.
22 PACKING AND MARKING 22.2.1 BIS Certification Marking
22.1 The cable shall be wound on a drum either wooden The cable (drum or label) may also be marked with the
(see IS 10418) or steel and packed. The ends of the cable Standard Mark.
shall be sealed by of non-hygroscopic sealing material. 22.2.1.1 The use of the Standard Mark is governed by
the provisions of the Bureau of Indian Standards Act,
22.2 The cable shall carry the following information
1986 and the Rules and Regulations made there under.
either stenciled on the drum or contained in a label
The details of conditions under which the Iicence for
attached to it:
the use of the Standard Mark may be granted to
a) Reference to this Indian Standard, for manufacturers or producers maybe obtained from the
example, see IS 7098 (Part 2); Bureau of Indian Standards.

ANNEX A
(Clauses 1.4 and 12.4)
TEST METHODS FOR ECCENTRICITY AND OVALITY

A-1 TEST METHOD FOR ECCENTRICITY A-2 TEST METHOD FOR OVALITY
The eccentricity of the insulation shall be checked as The ovality of the core shall be checked as follows:
follows:
dcore Max – dcore Min
t Max – t Min Percent ovality = ×100
Percent eccentricity = ×100 dcore Max
t Max

where t stands for the thickness of insulation. where d stands for the diameter of the core.