TEST PROTOCOL FOR TRANSFORMER

Client : M/s. ENMAS GB, CHENNAI


Customer : M/s. SHRI JAGANNATH STEELS & POWER LTD, BARABIL
Test Location : TG BUILDING 0` METER
Feeder Description : DISTRIBUTION TRANSFORMER-1
Test Date : 26.03.2016

1. Transformer Name Plate Details:

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

Make VOLTAMP
Serial No 45293/2
Voltage HV- 11000V LV- 433V
Current HV- 131.21A LV- 3333.43A
Phase HV- 3 LV-3
Frequency 50Hz
Cooling ONAN
Vector group Dyn11

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

Impedance Voltage 7.27 Percentage


YOM 2015

2. IR Value:

Instrument Used Make Serial No. Calibration Due


Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

Date
Digital Insulation Tester KYORITSU W0418334 11.06.2016

Reference Megger DC Volts 60 Sec 600 Sec PI Value


HV To Earth 5000V 5.21GΩ 9.50GΩ 1.82
HV To LV 5000V 9.62GΩ 19.8GΩ 2.05
LV To Earth 500V >1GΩ -

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

3. Magnetic Balance test:

Calibration Due
Instrument Used Make Serial No.
Date
Digital Multimeter RISHABH 159889 11.06.2016

Applied Voltage HV
Reference Measured Voltage LV Side(V)
Side(V)

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

1U1V 1V1W 1W1U 2U2V 2V2W 2W2U 2U2N 2V2N 2W2N

W PHASE CUT 417 313 103 16.66 4.81 11.80 9.49 7.13 2.33

U PHASE CUT 210.1 422 212.3 14.25 14.35 0.128 04.67 9.46 4.78

V PHASE CUT 102.8 316 421 04.83 11.81 16.68 02.34 7.13 9.48

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

4. Magnetic Current Test:

Calibration Due
Instrument Used Make Serial No.
Date
Digital Multimeter RISHABH 159889 11.06.2016
Leakage Clamp meter KYORITSU 8167993 10.06.2016

Measured Current HV
Tap Position Applied Voltage HV side(V)
Side(A)
Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

1U1V 1V1W 1W1U UФ VФ WФ


1 421 415 421 13.3 9.6 9.5
2 419 420 423 13.5 9.9 9.9
3 415 416 417 14.3 10.3 10.3
4 417 420 420 14.8 10.7 10.8
5 419 420 419 15.7 11.3 11.3

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

5. Voltage Ratio Test:

Calibration Due
Instrument Used Make Serial No.
Date
Digital Multimeter RISHABH 159889 11.06.2016

Tap Position Applied Voltage HV Measured Voltage LV Side(V)


Side(V)

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

1U1V 1V1W 1W1U 2U2V 2V2W 2W2U 2U2N 2V2N 2W2N


1 421 415 421 15.70 15.89 15.75 9.08 9.11 9.13

2 419 420 423 16.0 16.14 15.96 9.18 9.28 9.30

3 415 416 417 16.36 16.47 16.53 9.48 9.45 9.51

4 417 420 420 16.73 16.97 16.90 9.67 9.72 9.78

5 419 420 419 17.27 17.43 17.36 10.0 10.02 10.05

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

6. Winding Resistance Test:

Instrument Used Make Serial No.


Micro ohm Meter METRAVI 028978

Tap Position HV Side Values in µΩ LV Side Values in mΩ

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

1U1V 1V1W 1W1U 2U2N 2V2N 2W2N


1 375 387 389

2 367 377 380


3 357 368 369 1.11 1.07 1.10

4 348 359 360


5 339 348 350

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

7. Vector Group Confirmation Test:

Calibration Due
Instrument Used Make Serial No.
Date
Digital Multimeter RISHABH 159889 11.06.2016

Dyn11

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

Satisfy the following conditions,

1) 1U1V=1U2N+1V2N
2) 1V2W=1V2V
3) 1W2W<1W2V

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign:


TEST PROTOCOL FOR TRANSFORMER

1. 418 = (09.4) + (407)


2. 402.8 = 403.4
3. 405 < 421

8. REMARKS:- Transformer Tested and Found Healthy.

Tested By: J.PREM KUMAR Witnessed By: M.ANTONY Witnessed By: SUMONTO DHAR
M/s. RESONANCE M/s. ENMAS M/s. SJSPL

Sign: Sign: Sign: