Professional Documents
Culture Documents
1. Power transformers
2. Electric motors
3. Electric power generators
Additional content
1. Other electrical actuators
2. Transducers
Practical or Real Power Transformer
• In the Engineering Science lecture in Semester-1, we considered
ideal transformers.
• Practically, transformers are not ideal. However, sometimes, it
may be okay to assume practical transformers to be ideal to
obtain approximate results.
• Practically, or in practical transformers, the magnetic core and the
windings are not perfect. Windings have resistances. Core heats
up. Further, the magnetic coupling between the primary winding
and the secondary winding is not perfect due to flux leakages. This
results in a voltage drop. Also, the primary side draws a small
current called magnetizing current to establish the magnetic flux.
Hence, the transformer draws a small current even when there is
no electric load connected to the secondary side.
T/F B:
415−398
Voltage regulation = × 100% = 4.27%
398
Power Efficiency
Because of the internal heat losses due to 𝑅1 , 𝑅2 , 𝑅𝑐 , not all the power
delivered to the transformer is delivered to the load. Better
transformer have lower losses and hence higher power efficiencies.
Power efficiency is defined as:
output power to the load
Power efficiency = × 100%
input power from the source
Assume that the transformer operating at rated capacity (full-load) at rated output
voltage. The load has 0.8 lagging power factor.
Find
a. The voltage regulation
b. Full-load power efficiency
Ans:
𝐼1′
′
𝐼1 𝐼𝑚 𝐼2
𝐼𝑚 𝐼𝑐 𝐸1 𝐸2 𝑉2
𝑉1
𝑉2 = 240∠0°40∠0°
𝜃
𝐼2 = 88.33∠ − 𝜃°
In no-load condition,
𝐼2 = 0 and 𝐼1′ = 0
And, the no-load voltage is
𝑁2
𝑉2 = 𝐸2 = ( ) × 𝐸1
𝑁1
′
In no-load, 𝐼1 = 𝐼𝑚 . This is a very small current. Hence, it is okay to ignore the
voltage drop across 𝑅1 + 𝑗𝜔𝐿1 . Then,
𝐸1 ≈ 𝑉1
And, hence the no-load voltage is
𝑁2 240
𝑉2 = ( ) × 𝑉1 = ( ) × 2512 = 251.2 𝑉
𝑁1 2400
This is the no-load voltage at the load terminal.
251.2−240
Voltage regulation = X100% = 4.67%
240
Note: However, in practice in the industry, you make the measurements of full and
no-load voltages to calculate the voltage regulation.
Ex:
Equivalent circuit parameters of 50 Hz, 60 kVA, 11000 V/415 V, 3-phase transformer are given
bellow.
Parameters
Symbol Value
(Per-phase circuit parameter)
Primary resistance 𝑅1 6.0 Ω
Secondary resistance 𝑅2 0.03 Ω
Primary leakage resistance 𝑋1 = 𝜔𝐿1 12.0 Ω
Secondary leakage resistance 𝑋2 = 𝜔𝐿2 0.07 Ω
Magnetizing resistance 𝑋𝑚 = 𝜔𝐿𝑚 30 kΩ
Core-loss resistance 𝑅𝐶 300 kΩ
Assume that the transformer operating at rated capacity (full load) at rated output voltage. The
load is balanced and has 0.8 lagging power factor.
Ans:
Because the load is balanced, each phase of the transformer is equally loaded. As a result, we can
solve this problem using the single-phase equivalent circuit of the transformer.
𝐼1′
′
𝐼1 𝐼𝑚 𝐼2
𝐼𝑚 𝐼𝑐 𝐸1 𝐸2 𝑉2
𝑉1
𝑉2
𝜃
𝐼2
cos 𝜃 = 0.8 𝜃 = 36.87°
Just follow the same steps as in the case of analysis of the 1-phase
𝑁 11000
transformer. Here, the turns ratio; 1 =
𝑁2 415
Remark:
However, if the load is unbalanced, the power, power factors, currents in
each phase will be different. You have to consider each phase separately.
Hence, the above steps have to be followed 3 times.
Let is find the current drawn by the electrical load (3-phase motor) from
the transformer as follows.
27×103
Load power = = √3 × 400 × 𝐼 × 0.84 → 𝐼 = 58.0 𝐴
0.8
𝑹 𝐼𝑅 𝐼𝑅ℎ 𝐼𝑅𝑚
𝑉𝑅𝑁
𝑍ℎ 𝑍𝑚
𝐼𝑁 = 𝐼𝑅ℎ + 𝐼𝑅𝑚 + 𝐼𝑌 + 𝐼𝐵
𝑉𝐵𝑁
𝑍𝑚 𝑍𝑚
𝑵
𝑩 𝒀
𝑉𝑌𝑁
𝐼𝐵
𝐼𝑌
𝜃 = cos −1 0.84
𝐼𝑅𝑚
= 32.86°