MWFRS Wind Loads; ASCE 7-05 Enclosed & Partially Enclosed Buildings of All Heights
Building data
Table 28.3-1 ³
Building Width, B 10.46 m Height Exposure Normal to Ridge (q < 10°) and Parallel to Ridge for all q/Minimum Values Normal to Ridge (q < 10°) and Parallel to Ridge for all q/Minimum Values
Building Length, L 35.45 m Z [m] B C D 3 Horiz Distance From Windward Edge h/L: norm Horiz Distance From Windward Edge h/L: paral.
Ridge Height, hr (hr >= he) = 3.80 m 0 0.70 0.85 1.03 #NAME? h/L 0.0 m 1.5 m 3.0 m 5.9 m 0.28 h/L 0.0 m 0.0 m 0.0 m 0.0 m 0.08
hr=3.8m
Eave Height, he (he <= hr) = 2.95 m 4.6 0.70 0.85 1.03 0 -0.9 -0.9 -0.5 -0.3 0 -0.9 -0.9 -0.5 -0.3
he= 2.95m
Roof Slope Angle , θ 9.23° 6.1) 0.70 0.90 1.08 0.5 -0.9 -0.9 -0.5 -0.3 0.5 -0.9 -0.9 -0.5 -0.3
Median Roof Height, h 2.95 m 7.6) 0.70 0.94 1.12 1 #NAME? #NAME? -0.7 -0.7 1 #NAME? #NAME? -0.7 -0.7
Windward Roof Area 187.8 m² 9.1) 0.70 0.98 1.16 1000 #NAME? #NAME? -0.7 -0.7 1000 #NAME? #NAME? -0.7 -0.7
Roof Area Within 1.48 m of Edge 15.6 m² B= m 12.2) 0.76 1.04 1.22 Cp: #NAME? #NAME? #NAME? #NAME? Normal to redge Cp: #NAME? #NAME? #NAME? #NAME? Parallel to redge
10.4
Site Data 56 .454
m 35
Risk category 1 Table 1.1 L= Normal to Ridge (q < 10°) and Parallel to Ridge for all q/Maximum Values
The basic wind speed, V 240 Km/h 66.67 m/s 15.2) 0.81 1.09 1.27 Horiz Distance From Windward Edge h/L:
18) 0.85 1.13 1.31 h/L 0.0 m 1.5 m 3.0 m 5.9 m 0.28
wind load parameters: 20.0) 0.85 1.13 1.31 0 -0.18 -0.18 -0.18 -0.18 h/L: paral.
0.5 -0.18 -0.18 -0.18 -0.18 0.08
Wind directionality factor, Kd 0.85 Table 6.4 Leeward Walls 1 -0.18 -0.18 -0.18 -0.18
Exposure category C Sec. 6.5.6 L/B Cp L/B: Cp: 1000 -0.18 -0.18 -0.18 -0.18
Topographic factor, Kzt 1.00 Sec. 6.5.7 0 -0.5 3.39 #NAME? Cp: #NAME? #NAME? #NAME? #NAME? Normal to redge
Enclosure classifi cation Enclosed Sec. 6.2 1 -0.5 0.29 #NAME? Cp: #NAME? #NAME? #NAME? #NAME? Parallel to redge
2 -0.3
Velocity Pressure 4 -0.2
1000 -0.2
Terrain Exposure Constant, a 9.5 for exposoure C Table Table 6.2.
Terrain Exposure Constant, zg 274.32 m for exposoure C Table 6.2. Windward Roof: Normal to Ridge/Minimum Values (q ≥ 10°)
Median Roof Height, h 2.95 m (h = (hr+he)/2, for angle >10 deg.) Roof Pressure Coefficients, Cp Area Reduction Factors Area
Velocity pressure exposure Kz 0.85 Table 6.4 Angle, q (degrees) h/l: q: Cp: Area Factor 187.8 m²
Velocity pressure, 1.97 KN/m² Eq. 6-15 qz = 0.613 Kz.Kzt.Kd.V² h/L 10.0° 15.0° 20.0° 25.0° 30.0° 35.0° 45.0° 60.0° 80.0° 1000.0° 0.28 9.2° NA 0 1 15.6 m²
Gust Effect Factor, Gf 0.891 Eq. 6-8. 0 -0.7 -0.5 -0.3 -0.2 -0.2 0 0.4 0.6 0.8 0.8 h/L: paral. 30.5 1
0.25 -0.7 -0.5 -0.3 -0.2 -0.2 0 0.4 0.6 0.8 0.8 0.0° NA 76 0.9
Net Pressure Coefficients & Design Wind Pressure 0.5 -0.9 -0.7 -0.4 -0.3 -0.2 -0.2 0 0.6 0.8 0.8 305 0.8
Wind Direction Normal to ridge ( γ = 0 ) 1 #NAME? -1 -0.7 -0.5 -0.3 -0.2 0 0.6 0.8 0.8 10000 0.8
Internal pressure coeffi cient, (GCpi) +/- 0.18 Figure 6.5 1000 #NAME? -1 -0.7 -0.5 -0.3 -0.2 0 0.6 0.8 0.8
External Wall Pressure Coefficients
For Windward Wall Cp = 0.80 Figure 6-6 Windward Roof: Normal to Ridge/Maximum Values (q ≥ 10°)
For Leeward Wall Cp = #NAME? Figure 6-6 , with L/B = 3.39 Roof Pressure Coefficients, Cp
Side Wall -0.70 Figure 6-6 Angle, q (degrees) h/L: q: Cp:
External Roof Pressure Coefficients Figure 6-6 , Section 6.5.8, Eq. 6-17 h/L 10.0° 15.0° 20.0° 25.0° 30.0° 35.0° 45.0° 60.0° 80.0° 1000.0° 0.28 9.2° NA
Windward Roof Normal to Ridge, Cp 0 -0.18 0 0.2 0.3 0.3 0.4 0.4 0.6 0.8 0.8 h/L: paral.
Min Cp = #NAME? 0.25 -0.18 0 0.2 0.3 0.3 0.4 0.4 0.6 0.8 0.8 0.0° NA
Max Cp = #NAME? 0.5 -0.18 -0.18 0 0.2 0.2 0.3 0.4 0.6 0.8 0.8
Leeward Roof Normal to Ridge, Cp 1 -0.18 -0.18 -0.18 0 0.2 0.2 0.3 0.6 0.8 0.8
Min Cp = #NAME? 1000 -0.18 -0.18 -0.18 0 0.2 0.2 0.3 0.6 0.8 0.8
Max Cp = #NAME?
Height D. Pressure
#NAME? #NAME? 2.95 m 1.78 KN/m²
2.66 m 1.78 KN/m²
-0.87 KN/m² 2.36 m 1.78 KN/m²
2.07 m 1.78 KN/m²
. #NAME? 1.77 m 1.78 KN/m²
1.48 m 1.78 KN/m²
1.18 m 1.78 KN/m²
0.89 m 1.78 KN/m²
0.59 m 1.78 KN/m²
0.30 m 1.78 KN/m²
0.00 m 1.78 KN/m²
-0.87 KN/m²
Case B Design Loads: ( External - Internal Pressure)
7.52 m
7.52 m
Panel Area 30.08 m² 7.52 m
Site Data
Risk category 2 Table 1-2 4.00 m
The basic wind speed, V 47 m/s Building Ht Panel size