Professional Documents
Culture Documents
MODEC, Inc. and affiliates ("MODEC Group") and is furnished on a confidential basis with the express
agreement that it shall neither be used, sold, transferred, copied, traced, photographed, nor reproduced in
any manner whatsoever, in whole or in part, nor any item herein be sold, manufactured, or assembled
without the written agreement of MODEC, Group. The recipient of this document agrees not to disclose to
any other party information contained herein, nor use such information, except for the specific purpose
intended at the time of release of this document.
Client
Client Client Validity
Doc. No. 600301DTPT74006 Rev. 00 Status EX-CO
No.
TBJN0144-S-PI-PRD-0002
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27
Eni Mexico Area 1 FPSO Project Flushing, Hydrostatic and Pneumatic Test Procedure
0568-BOM20-92P1-0001-001, Rev. 0
RECORD OF AMENDMENT
REVISION SECTION PARAGRAPH DESCRIPTION OF CHANGE
B ISSUED FOR REVIEW
0 ISSUED FOR CONSTRUCTION
0568-BOM20-92P1-0001-001 2 OF 12
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27
Eni Mexico Area 1 FPSO Project Flushing, Hydrostatic and Pneumatic Test Procedure
0568-BOM20-92P1-0001-001, Rev. 0
TABLE OF CONTENTS
1. SCOPE.............................................................................................................................. 4
2. APPLICABLE CODES AND STANDARDS ..................................................................... 4
3. FLUSHING ........................................................................................................................ 4
4. PRESSURE TESTING ...................................................................................................... 5
5. POST TEST PROCEDURES ............................................................................................ 9
6. TESTING MATERIALS AND EQUIPMENTS ................................................................. 10
7. TEST RECORD .............................................................................................................. 10
8. SAFETY .......................................................................................................................... 10
0568-BOM20-92P1-0001-001 3 OF 12
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27
Eni Mexico Area 1 FPSO Project Flushing, Hydrostatic and Pneumatic Test Procedure
0568-BOM20-92P1-0001-001, Rev. 0
1. SCOPE
This procedure requires the minimum requirements for flushing, pneumatic, hydrostatic and
leaking test to piping systems for MV34 Eni Mexico Area 1 Development Project M4S, M5 and
M6P. This procedure include flushing & borescope requirements to be incorporated according
to MODEC Fabrication of Piping Specification 0568-MI20-00S1-0070-001.
3. FLUSHING
3.1 GENERAL
3.1.1 Carbon steel pipes
In most cases, the water used shall be good quality inhibited fresh water. However, in
extraordinary circumstances, when the quantities involved are very large, it is allowed to carry
out the first flushing operations on a given network with raw water not containing more than
50ppm of chlorides and then final rinsing of the same network has to be carried out with
inhibited fresh water.
3.1.2 CRA Pipes / Tubing
As a rule, water containing chloride (more than 50 ppm) should not be used. However, in
some cases it may be used following agreement with the Company. In such case the final
rinsing must be carried out with inhibited water. NaNO3 will be added to the water three times
the chloride ion content.
In specific cases, where system flushing requirements are dictated by specialist suppliers or
criticality of system operation, water mixed with special chemicals / additives shall be used for
system flushing.
For liquid process lines, the flushing velocity shall be lower of 3 m/s and the velocity obtained
with 1.3 times the maximum process flow. For gas process lines, use 3 m/s flushing velocity
(ensure that water-filled lines are adequately supported / no excessive load on support,
hangers, pads, spring supports, or equipment nozzle itself). The flushing velocity shall be
demonstrated, and Photo’s evidence of cleaning shall be included in the inspection records.
Alternately retro jetting equipment and centralizers at various operating pressure with spinning
0568-BOM20-92P1-0001-001 4 OF 12
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27
Eni Mexico Area 1 FPSO Project Flushing, Hydrostatic and Pneumatic Test Procedure
0568-BOM20-92P1-0001-001, Rev. 0
nozzle shall be used for pipes ≥ 6” NPS to scour the lines to remove foreign particles and
flush dirt/debris from the system. The supply water pressure should be sufficient to dislodge
particles from the pipe internal walls and the water flow adequate to carry debris from the
system to a safe, contained exit point.
4. PRESSURE TESTING
4.1 GENERAL
Inspect related drawing and document shall include the following information as minimum:
1) Test method and medium
2) Test equipment and instruments
3) Calibration certificate
4) Marked P&ID showing all the installed blinds, vent and drain valves, and isolation of each
segment to be tested.
All welding, heat treatment and nondestructive testing shall be completed prior to pressure
testing.
Unless noted otherwise, all in-line valves are in normal open, to avoid the corrosion and
damage.
The pressure test includes hydrostatic pressure and pneumatic test. The value of hydrostatic
pressure test shall be no less than 1.5 times of the design pressure. Test pressure shown in
MODEC’S fabrication line list shall be followed. The pressure test is the one that is performed
to confirm the piping systems have the sufficient strength safety against static pressure test.
The pipeline checking in the pressure test is particularly performed to check the condition of
piping work including leakage.
Nondestructive inspection and hydro testing of carbon steel lined piping shall be performed
prior to lining or external coating is applied.
If the valve is to be tested in the closed position, manufacturer's written approval of the
maximum test pressure that may be applied to the valve in the closed position shall be
obtained if the test pressure will exceed published seat pressure rating of the valve.
0568-BOM20-92P1-0001-001 5 OF 12
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27
Eni Mexico Area 1 FPSO Project Flushing, Hydrostatic and Pneumatic Test Procedure
0568-BOM20-92P1-0001-001, Rev. 0
All test systems shall be reviewed to ensure that vents, drains, blind flanges, etc., are installed
as necessary whether shown on drawings or not.
Temporary supports shall be provided where required due to additional weights of testing
medium.
Closed valves shall not be used to separate test systems, instead blind to be used for
isolation.
Positive provisions shall be made to protect pressure-sensitive equipment and instruments
such as gauges, level controllers, pressure controllers, relief valves, etc.
Any instruments, which are suspected to have been hydrotested, shall be inspected and
recalibrated.
Open ends of a system shall be fitted with flanges, blinds, or plugs prior to pressure test.
0568-BOM20-92P1-0001-001 6 OF 12
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27
Eni Mexico Area 1 FPSO Project Flushing, Hydrostatic and Pneumatic Test Procedure
0568-BOM20-92P1-0001-001, Rev. 0
0568-BOM20-92P1-0001-001 7 OF 12
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27
Eni Mexico Area 1 FPSO Project Flushing, Hydrostatic and Pneumatic Test Procedure
0568-BOM20-92P1-0001-001, Rev. 0
pressure at each step long enough to equalize piping strain, the pressure shall then be
reduced to the design pressure before examining for leakage.
All joints, welds, and connections shall be swabbed with a soap solution to facilitate the
detection of leaks. Test pressure shall be maintained for at least 30 min.
Replace packing seals in items such as valves when leaks cannot be stopped by normal
tightening of packing glands.
Record each test including date, time, system being tested, test fluid, test pressure, and
atmospheric temperature, Obtain signature of Company's Authorized Inspector.
Release pressure slowly and take preservative measures as agreed with the Company.
Replace material such as gaskets, bolting, damaged during testing.
0568-BOM20-92P1-0001-001 8 OF 12
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27
Eni Mexico Area 1 FPSO Project Flushing, Hydrostatic and Pneumatic Test Procedure
0568-BOM20-92P1-0001-001, Rev. 0
0568-BOM20-92P1-0001-001 9 OF 12
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27
Eni Mexico Area 1 FPSO Project Flushing, Hydrostatic and Pneumatic Test Procedure
0568-BOM20-92P1-0001-001, Rev. 0
and gaskets.
15) Instruments, which were removed or blocked out for tests shall be reinstalled and blocks
placed in the normal operating position.
16) Vessels and piping shall be treated with an industrial corrosion inhibitor solution to
minimize internal corrosion.
17) Lubricating, seals, and control oil systems shall receive a hot oil flush in lieu of water.
After final assembly at the site, the filter casings, cooler MODEC’s, and other system
components shall be opened and wiped clean. Heated flushing oil (150ºF to 180ºF) shall then
be circulated until it runs clean, but for not less than eight hours. The equipment
manufacturer’s representative shall determine the method of checking the cleanliness of the
system. Bearings shall be by-passed during flushing.
7. TEST RECORD
The records shall include the following information:
1) Verification that the system has been returned to operational condition
2) Pressure and temperature recorder charts
3) A pressure test system chart for each piping system or spool
The chart shall indicate:
- Test medium
- Test pressure
- Test duration
8. SAFETY
1) Barrier tapes shall be provided around test areas appropriately with waning notices
displayed 10m distance is needed to place boundary.
2) Caution testing in progress Eye protection PPE should be worn by all personnel involved in
testing.
3) Only authorized personnel (test worker, test engineer and inspector, etc.) should be
0568-BOM20-92P1-0001-001 10 OF 12
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27
Eni Mexico Area 1 FPSO Project Flushing, Hydrostatic and Pneumatic Test Procedure
0568-BOM20-92P1-0001-001, Rev. 0
allowed in vicinity of testing, i.e. inside barriers. All personal stay out of barrier tapes in the
case of a hydrotest failure.
4) Take-all necessary precaution in cleaning, hydrostatic test work to protect personals and
environment, conditions considered unsafe shall be corrected before work is started or
continued.
0568-BOM20-92P1-0001-001 11 OF 12
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27
Eni Mexico Area 1 FPSO Project Flushing, Hydrostatic and Pneumatic Test Procedure
0568-BOM20-92P1-0001-001, Rev. 0
APPENDIX A
Schedule of Maximum Allowable Hydrostatic Test Pressure (kPa) for the Listed Test Blind Thicknesses (mm).
6.35 14668 6754 4086 1885 1112 716 509 422 323 255 207 144
9.53 33038 15213 9203 4246 2505 1613 1146 951 728 575 466 324
12.7 58672 58672 16343 7540 4449 2864 2036 1689 1293 1021 827 575
15.88 91733 42239 25552 11789 6956 4478 3183 2640 2021 1597 1294 898
NOTES:
1) The tabulated pressures above are based on the formula stated in ASME B31.3, Para. 104.5.3 (b)
using the following:
a. Flat non-asbestos gaskets conforming to ASME B16.21.
b. Structural grade, carbon steel plate, ASTM A36 having a minimum specified yield strength of 36,000
psi.
2) For plate that is identified as having a lower minimum yield strength, the allowable hydrostatic
pressure must be reduced by the factor listed below. The factor shall then be applied to the
pressures listed in Attachment 03 pressure table:
P ma = Y x / Y
Where:
3) Pneumatic test pressures shall not exceed 50 percent of the values indicated.
0568-BOM20-92P1-0001-001 12 OF 12
Lead Reviewer: Senthil Rajendra Acceptance Code: 1 - APPROVED Review Date: 02-Nov-2019 06:44:27