You are on page 1of 7

DISTRICT COOLING SCHEME FOR KFUPM BUSINESS PARK

REVIEW COMMENTS SHEET

SLA Submittal Title: Technical Document for Chiller (DAIKIN) 6301 Project Name: District Cooling Scheme for KFUPM Business Park

SLA Transmittal No: 667084-CA-0001 Client: Dhahran Valley Cooling Company (DVCC)

SLA Transmittal Date: 29-Mar-2020

DVCC COMMENTS SLA REPLY DVCC COMMENTS SLA REPLY STATUS


ITEM Rev.-- date by 20th Apr 2020 Rev.---- date by ----- 2020
Rev.00 date by 15th Mar-2020 Rev.01 date by 29th Mar- 2020 (Open /
No. Letter No.: DVCC-SLA-016 Letter No.: 667084-CA-------
Letter No.: DVCC-SLA-009 Letter No.: 667084-CA-1000 Closed)

Such a request cannot be fulfilled as the


Purchase Order is not placed yet. Detailed
components documents are normally produced
by the manufacturer after award and shall be
shared with DVCC with the closeout documents
at the end of the Project.
Meanwhile, and as per standard practice in all Agreed
projects, the important documents as listed below
which are required to approve the chillers are
already part of chiller submittal.
All items indicated in specification
1. section 15620, Part 1, Item 1.4 shall  Chiller datasheet
be submitted
 Motor datasheet
 Statement of Country of origin
 Chiller selection sheet
 Project compliance statement
 GA drawings
 RRU Details
 IOM manual etc. are already provided

It is presumed that all items referred


2. Confirmed. Agreed
to be done by others or by contractor
shall be done by SNC Lavalin
Only technical documents are normally submitted
3. Warranty shall be indicated in the for equipment approval. Warranty shall be as per 5-years warranty to be provided
submittal. the EPC Contract. from the startup date

Seismic type spring vibration isolator Spring isolators shall be provided. Seismic type
4. spring isolators are not required in the contract Agreed
is recommended instead of the
offered rubber type. specifications.

Form No.: 67084-A-40SN-0000-0001 KFUPM District Cooling


Rev. No.: 00 Plant
Date: 06/02/2020 Page 1 of 7
DISTRICT COOLING SCHEME FOR KFUPM BUSINESS PARK

REVIEW COMMENTS SHEET

DVCC COMMENTS SLA REPLY DVCC COMMENTS SLA REPLY STATUS


ITEM Rev.-- date by 20th Apr 2020 Rev.---- date by ----- 2020
Rev.00 date by 15th Mar-2020 Rev.01 date by 29th Mar- 2020 (Open /
No. Letter No.: DVCC-SLA-016 Letter No.: 667084-CA-------
Letter No.: DVCC-SLA-009 Letter No.: 667084-CA-1000 Closed)

Evaporator and condenser marine Please note that the marine box is provided with
box shall be provided with 1" ½"as per standard manufacturer design
5. Not Acceptable; 1” shall be provided
minimum air vent as per Please note that there are additional air vents
specifications instead of the offered provided on the connected CHW and CW
½" air vent. lines
Not applicable, Rupture disc are used only with
negative pressure chillers.
Daikin chillers are Positive pressure Design
6. Rupture disc shall be provided as per which is having the benefit to avoid any air, Acceptable; subject to providing dual
specifications. moisture, or any other contaminants to seep into pressure relief valve.
the system

Please note that there is no technical justification


Factory installed insulation is not for this comment. Normally work performed by
7. accepted. All insulation to be the OEM is recommended since the chiller Aluminum Cladding shall be done at
furnished and installed at site as per parameters are considered accordingly. site
specifications.

Sound pressure level at 1 m (dB) = 87


Please note that this item is already appearing in
8. The sound pressure level at one the Material submittal. Please refer to Technical Shall be as per project specs
meter at full load shall be indicated. bid evaluation, and Page no 4 of 5, line no 109.

Performance testing shall be done by SNC Agreed


9. Field performance test shall be Lavalin as per Appendix 3 of the contract
provided as per specifications. documents
Comply.
Refrigerant recovery unit shall be
sized to handle one chiller complete Please note that compliance to these items was
10. already provided in the compliance statement, Agreed
charge and to be 80% full at 50°C.
please refer to section 2.11, RRU Item no B.

11. The proposed details of Refrigerant monitor


Refrigerant monitor system has no
system are attached.
specific model or number of sensors
The specific details like datasheet shall be ready Agreed
or layout showing the locations. It is
not clear the system is dedicated type only after award to chiller supplier during detail

Form No.: 67084-A-40SN-0000-0001 KFUPM District Cooling


Rev. No.: 00 Plant
Date: 06/02/2020 Page 2 of 7
DISTRICT COOLING SCHEME FOR KFUPM BUSINESS PARK

REVIEW COMMENTS SHEET

DVCC COMMENTS SLA REPLY DVCC COMMENTS SLA REPLY STATUS


ITEM Rev.-- date by 20th Apr 2020 Rev.---- date by ----- 2020
Rev.00 date by 15th Mar-2020 Rev.01 date by 29th Mar- 2020 (Open /
No. Letter No.: DVCC-SLA-016 Letter No.: 667084-CA-------
Letter No.: DVCC-SLA-009 Letter No.: 667084-CA-1000 Closed)
design.
or not (to display specific sensing
element near the leakage point). Please note that the layout and the location of the
part is a part of detail design which is
not required at the approval stage of the chiller.

Please check "Annexure 3" for revised technical


Some of the motor curves/graphs
selection sheet. Also, it shall be noted that
don't match the indicated electrical
906.1kW mentioned in the motor data sheet is
12. parameters in the motor data sheet
the input power and 870kW mentioned in the Noted
and chiller technical data sheet, to be
motor curves is the motor output power.
revised.

The chiller vendor only provides the motor along


Soft starter data sheet and technical
with details like motor datasheet and curves
submittal are to be reviewed with the
based on the input of the motor vendor. Soft
motor data sheet.
starter is provided by others.
13. The soft starter was already submitted as a part Agreed
of different material submittal and technically it
should not hold the approval of the chiller
material submittal.

Preliminary motor performance curves have been


Motor performance curves and start-
attached. Further, motor starting analysis and
up calculation using soft starter are to
Torque-current-speed characteristics for reduced Agreed
14. be provided.
voltage starting will be prepared during detailed
engineering. Based on the present data, we do
not see any concerns in motor starting.
Reduced voltage and starting current curves (up
The reduced starting current and
to 65% of rated voltage) and its acceleration time
torque that will be achieved by soft
with respect to motor thermal limit curves are
starter are to be coordinated and
provided, which shows that the motor is not
revised with motor thermal limits
15. exceeding its thermal limits. Please refer to curve Agreed
curves (Acceleration time, etc.)
titled “% of FLA Curve”.
Further, Torque-current-speed characteristics for
reduced voltage starting will be prepared during
detailed engineering.
16. Noted and will be verified as part of detailed
The heat generated from the chiller’s
engineering. Agreed
specified number of starts per hour
is to be coordinated with motor & Start to start timer by default for chiller is 40
soft starter stack thermal cooling minutes (1 start an hour, but it can be adjusted

Form No.: 67084-A-40SN-0000-0001 KFUPM District Cooling


Rev. No.: 00 Plant
Date: 06/02/2020 Page 3 of 7
DISTRICT COOLING SCHEME FOR KFUPM BUSINESS PARK

REVIEW COMMENTS SHEET

DVCC COMMENTS SLA REPLY DVCC COMMENTS SLA REPLY STATUS


ITEM Rev.-- date by 20th Apr 2020 Rev.---- date by ----- 2020
Rev.00 date by 15th Mar-2020 Rev.01 date by 29th Mar- 2020 (Open /
No. Letter No.: DVCC-SLA-016 Letter No.: 667084-CA-------
Letter No.: DVCC-SLA-009 Letter No.: 667084-CA-1000 Closed)

down curve. down to 15 minutes‐ 4 starts an hour).


Interconnection wiring diagram will be prepared
Interconnection cabling between soft
during detailed engineering. Agreed
starter and chiller is to be provided to
revise the chiller's auxiliary loads As far as the chiller auxiliary loads are
power feeding sources (from soft concerned, each chiller will be provided with 1
17. starter or from building services). No. 3 phase 400V power supply from Chiller
Auxiliary DB (DB-CHOP-XXX). From this power
supply, all auxiliaries of chiller will be powered.
Step-down transformers will be used where
required.
Noted. This shall be part of the detail design.
Motor termination box size is to be
18. Agreed
coordinated with 13.8KV design
cables cross-sectional areas.
This is an example only to demonstrate that the
Some of the presented data doesn't
motor data declared in terms of usable kW is less
match project power supply
than the tested values Agreed
characteristics kindly refer to page 2
19. in motor cooling design section). (because the supplier (Regal) tests in ambient air
and the motors are finally cooled by refrigerant
without external power supply or any external
chilled water connection)
Chiller shall be able to operate at an ambient of
Control panel ambient temperature
50°C for a couple of hours during startup.
rating is to be coordinated with
design ambient limits/ratings for the For sustained operation, please refer to IOM
chiller hall. (IOM mentions 40°C as max ambient operation)
Agreed
20. The chiller hall is air conditioned @ 35 ° C.
Moreover, as per Contract, all electrical
equipment installed inside the building shall be
selected to operate at 35°C and therefore, the
control panel is suitable for operation under the
above ambient condition.

Hinged marine box for both sides of Hinged marine box is considered as per
condenser and evaporator and Contractual project scope document (App 7).
21. marine water boxes sand tube sheets Please note that ceramic coating is not required
Ceramic Coating for Condenser is
plates shall be factory applied as per Contractual project scope document and
required.
ceramic coating. hence not considered.
22. Part load testing as per specification is
Part load testing shall be as per the
confirmed.
specification (constant entering

Form No.: 67084-A-40SN-0000-0001 KFUPM District Cooling


Rev. No.: 00 Plant
Date: 06/02/2020 Page 4 of 7
DISTRICT COOLING SCHEME FOR KFUPM BUSINESS PARK

REVIEW COMMENTS SHEET

DVCC COMMENTS SLA REPLY DVCC COMMENTS SLA REPLY STATUS


ITEM Rev.-- date by 20th Apr 2020 Rev.---- date by ----- 2020
Rev.00 date by 15th Mar-2020 Rev.01 date by 29th Mar- 2020 (Open /
No. Letter No.: DVCC-SLA-016 Letter No.: 667084-CA-------
Letter No.: DVCC-SLA-009 Letter No.: 667084-CA-1000 Closed)
Please note that Zero tolerance is only applicable All Part Load Testing shall be done at
temp.), tolerance is not acceptable as
at 100% chiller load on capacity and power. Zero Tolerance
proposed.
Other than 100% load points, the AHRI tolerance
shall be applicable as per industry practice and
as per all previous projects executed for Saudi
Tabreed.
NPLV Value = 0.5622 kW/TR as indicated in
The NPLV@ Zero tolerance (0.8297
attached selection sheet "Annexure 3" however
kW/Tr) is very high. Daikin to confirm
0.8297 kW/TR is the performance
the NPLV@ Zero tolerance.
at 4 points when keeping Constant condenser
water temperature through all the four points. As per Appendix.3 NPLV Value of
23. 0.5622 kW/TR is at AHRI Tolerance
Please note that NPLV plays a significant role not at Zero Tolerance
when the part load design condition is not known
and chiller is selected based on unknown part
load operating scenario.

This request is not part of Contract.


Daikin to provide HFO refrigerant
24. option.
Noted

This request is not part of Contract.


Daikin to advise on the impact of
25. chiller capacity and efficiency
Noted
should the chiller be replaced with
possible HFO refrigerant in future.
@75%: 43.1 deg F
The minimum acceptable chilled
@50%: 41.9 deg F
water temp. Mentioned is 50.5 deg F
26. @25%: 40.7 deg F Agreed
@ full load. Daikin confirm the
minimum acceptable chilled temp. At
75%, 50% at 25% load.
As per Contractual vendor list the motor from
27. Country of origin of Motor shall be
China is acceptable and considered accordingly. Agreed
Europe or USA.
As per data sheet, the motor power factor at
Motor Power factor 0.96 to be
100% load is 0.891. The power factor will be
28. complied with the specifications.
improved to 0.94 (as per Contract) using Power Shall be as per the contract
Factor Correction Capacitors.

29. Comply Noted


Number of thermal sensors for motors

Form No.: 67084-A-40SN-0000-0001 KFUPM District Cooling


Rev. No.: 00 Plant
Date: 06/02/2020 Page 5 of 7
DISTRICT COOLING SCHEME FOR KFUPM BUSINESS PARK

REVIEW COMMENTS SHEET

DVCC COMMENTS SLA REPLY DVCC COMMENTS SLA REPLY STATUS


ITEM Rev.-- date by 20th Apr 2020 Rev.---- date by ----- 2020
Rev.00 date by 15th Mar-2020 Rev.01 date by 29th Mar- 2020 (Open /
No. Letter No.: DVCC-SLA-016 Letter No.: 667084-CA-------
Letter No.: DVCC-SLA-009 Letter No.: 667084-CA-1000 Closed)

shall be 6 nos. (2 per phase).


Proposed 3 nos. not acceptable.
Customized chiller has been selected to meet
Chiller selection data sheet shall be
project requirements rated in accordance with the
with AHRI authentication with
30. AHRI Standard. Third party shall be appointed by
date/time and version number of the
Daikin to verify the Performance
software.

Oil filter differential pressure switch


Comply with oil pressure regulation valve Agreed
31. shall be factory installed.

The service factor is not applicable for the


Motor service factor shall be
Hermetic motors. However Please refer to the
preferably 1.15 or minimum 1.10.
material submittal section C, Motor datasheet Agreed. The compliance statement
32. and Curve, letter from Daikin dated 24th Sept confirming SF of 1.15 shall be
2019, confirming the service factor of the motor amended
as 1.15.

Please refer to the section B and C of the


All electrical supply shall be 60 Hz as
material submittal for specific chiller datasheet
33. per the local regulation.
and motor datasheet, it is clearly mentioned 60 Agreed
Hz as per project requirements.

Performance testing procedures will be submitted


Daikin's procedure for shipment and
34. prior to performance testing stage. Noted
field performance testing shall be
submitted
Low net oil pressure alarm (feed pressure – the
Oil flow indicator is required.
35. sump pressure) are provided to ensure oil
movement. Agreed

Refer to MOS for vibration test "Annexure 6".


36. Vibration test shall be as per
Noted
specifications.
37. @ 96 °F : Maximum Capacity will be =
Daikin to advise the impact of
2228/Chiller
elevated CWET on the chiller
@ 96.5 °F : Maximum Capacity will be =
performance.
2210.8/Chiller. Noted
@ 97.5 °F : Maximum Capacity will be =
2175/Chiller.

Form No.: 67084-A-40SN-0000-0001 KFUPM District Cooling


Rev. No.: 00 Plant
Date: 06/02/2020 Page 6 of 7
DISTRICT COOLING SCHEME FOR KFUPM BUSINESS PARK

REVIEW COMMENTS SHEET

DVCC COMMENTS SLA REPLY DVCC COMMENTS SLA REPLY STATUS


ITEM Rev.-- date by 20th Apr 2020 Rev.---- date by ----- 2020
Rev.00 date by 15th Mar-2020 Rev.01 date by 29th Mar- 2020 (Open /
No. Letter No.: DVCC-SLA-016 Letter No.: 667084-CA-------
Letter No.: DVCC-SLA-009 Letter No.: 667084-CA-1000 Closed)

Warranty shall be in accordance with the 5-years warranty to be provided


38. Warranty Period 5 years for full
requirement of the Contract. from the startup date
chiller
Number of attendees for any Factory witnessed Factory Test to be witnessed by 6
Factory Test to be witnessed by 6
39. test shall be in accordance with the Contract. persons
people

Form No.: 67084-A-40SN-0000-0001 KFUPM District Cooling


Rev. No.: 00 Plant
Date: 06/02/2020 Page 7 of 7

You might also like