Produced on 06/11/2020 with Xpress Selection V9.0.1 - database DIL 16.0.

Project name OFICINAS LIB


Project address Peru
Reference A
Client name AP
Revision A

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Type Model Name Qty Description
Outdoor unit RXYQ144TATJU 1 Heat pump VRV IV 220V(TATJU)
RXYQ168TATJU 3 Heat pump VRV IV 220V(TATJU)
Indoor unit FXMQ100PAVE 7 VRV M-PA - Ceiling Mounted Duct
FXMQ125PAVE 6 VRV M-PA - Ceiling Mounted Duct
FXMQ140PAVE 1 VRV M-PA - Ceiling Mounted Duct
FXMQ63PAVE 2 VRV M-PA - Ceiling Mounted Duct
FXMQ80PAVE 3 VRV M-PA - Ceiling Mounted Duct
Branch unit KHRP26A22T 2 Refnet branch piping kit
KHRP26A33T 6 Refnet branch piping kit
KHRP26M72TU 7 Refnet branch piping kit
KHRP26M73TU 1 Refnet branch piping kit
Option or add-on BRC1E63 19 Wired Remote Controller (Navigation Remote Controller)
BHFP22P100U 1 Outdoor unit multi connection piping kit
Refrigerant R410A 38.2kg Extra refrigerant charge
Copper pipe Piping ⅜" 40.1m Soft copper pipe
Piping ½" 10.1m Soft copper pipe
Piping ⅝" 71.9m Soft copper pipe
Piping ¾" 39.4m Hard copper pipe
Piping ⅞" 7.9m Hard copper pipe
Piping 1⅛" 54.3m Hard copper pipe
Piping 1⅜" 35.0m Hard copper pipe

2. Indoor Unit Details


2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / RH)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tmp H Indoor temperature in heating

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1
Rq HC Required heating capacity
Max HC Available heating capacity
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

2.2. Out 1 - RXYQ168TATJU


Capacity data at conditions and connection ratio (114%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C BTU/h BTU/h cfm
OF-1-01 FXMQ100PAVE 23.0 / 55% 32025 33124 n/a 23936 6.0 23.0 n/a 38557 1130
OF-1-02 FXMQ140PAVE 23.0 / 55% 44753 47398 n/a 33975 6.0 23.0 n/a 55447 1624
OF-1-03 FXMQ100PAVE 23.0 / 55% 27909 33124 n/a 23936 6.0 23.0 n/a 38557 1130
OF-1-04A FXMQ80PAVE 23.0 / 55% 24444 26499 n/a 19862 6.0 23.0 n/a 30880 883
OF-1-04B FXMQ80PAVE 23.0 / 55% 24444 26499 n/a 19862 6.0 23.0 n/a 30880 883

Required cooling capacity towards the outdoor unit: 153575BTU/h.


The sum of the required indoor unit capacities is 153575BTU/h for cooling and 0BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 138217BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
OF-1-01 39-43 220V 1ph 2.9 1400×300×700 45
OF-1-02 43-46 220V 1ph 3.4 1400×300×700 46
OF-1-03 39-43 220V 1ph 2.9 1400×300×700 45
OF-1-04A 39-43 220V 1ph 2.3 1000×300×700 35
OF-1-04B 39-43 220V 1ph 2.3 1000×300×700 35

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2
2.3. Out 2 - RXYQ312TATJU
Capacity data at conditions and connection ratio (117%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C BTU/h BTU/h cfm
OF-X-01A FXMQ100PAVE 23.0 / 55% 26852 33124 n/a 23936 6.0 23.0 n/a 38557 1130
OF-X-02 FXMQ80PAVE 23.0 / 55% 22932 26499 n/a 19862 6.0 23.0 n/a 30880 883
OF-X-03 FXMQ100PAVE 23.0 / 55% 28322 33124 n/a 23936 6.0 23.0 n/a 38557 1130
OF-X-04A FXMQ100PAVE 23.0 / 55% 29085 33124 n/a 23936 6.0 23.0 n/a 38557 1130
OF-X-05 FXMQ125PAVE 23.0 / 55% 35415 41455 n/a 29948 6.0 23.0 n/a 49305 1377
OF-X-06 FXMQ63PAVE 23.0 / 55% 20454 20898 n/a 15747 6.0 23.0 n/a 24738 689
OF-X-07 FXMQ63PAVE 23.0 / 55% 17010 20898 n/a 15747 6.0 23.0 n/a 24738 689
OF-X-08 FXMQ125PAVE 23.0 / 55% 36975 41455 n/a 29948 6.0 23.0 n/a 49305 1377
OF-X-01B FXMQ100PAVE 23.0 / 55% 26852 33124 n/a 23936 6.0 23.0 n/a 38557 1130
OF-X-04B FXMQ100PAVE 23.0 / 55% 29085 33124 n/a 23936 6.0 23.0 n/a 38557 1130

Required cooling capacity towards the outdoor unit: 272982BTU/h.


The sum of the required indoor unit capacities is 272982BTU/h for cooling and 0BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 245684BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
OF-X-01A 39-43 220V 1ph 2.9 1400×300×700 45
OF-X-02 39-43 220V 1ph 2.3 1000×300×700 35
OF-X-03 39-43 220V 1ph 2.9 1400×300×700 45
OF-X-04A 39-43 220V 1ph 2.9 1400×300×700 45
OF-X-05 40-44 220V 1ph 3.4 1400×300×700 45
OF-X-06 38-42 220V 1ph 1.8 1000×300×700 35
OF-X-07 38-42 220V 1ph 1.8 1000×300×700 35
OF-X-08 40-44 220V 1ph 3.4 1400×300×700 45
OF-X-01B 39-43 220V 1ph 2.9 1400×300×700 45
OF-X-04B 39-43 220V 1ph 2.9 1400×300×700 45

Outdoor unit placed 50.0m above the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3
2.4. Out 3 - RXYQ168TATJU
Capacity data at conditions and connection ratio (114%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C BTU/h BTU/h cfm
LOCAL 1 A FXMQ125PAVE 23.0 / 55% 38110 41455 n/a 29948 6.0 23.0 n/a 49305 1377
LOCAL 1B FXMQ125PAVE 23.0 / 55% 38110 41455 n/a 29948 6.0 23.0 n/a 49305 1377
LOCAL 2A FXMQ125PAVE 23.0 / 55% 34356 41455 n/a 29948 6.0 23.0 n/a 49305 1377
LOCAL 2B FXMQ125PAVE 23.0 / 55% 34356 41455 n/a 29948 6.0 23.0 n/a 49305 1377

Required cooling capacity towards the outdoor unit: 144932BTU/h.


The sum of the required indoor unit capacities is 144932BTU/h for cooling and 0BTU/h for heating.
However, the outdoor unit selection uses reduced load values for cooling of 130439BTU/h (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
LOCAL 1 A 40-44 220V 1ph 3.4 1400×300×700 45
LOCAL 1B 40-44 220V 1ph 3.4 1400×300×700 45
LOCAL 2A 40-44 220V 1ph 3.4 1400×300×700 45
LOCAL 2B 40-44 220V 1ph 3.4 1400×300×700 45

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
EER EER at nominal conditions for standard efficiency series (nominal temperatures, 100% connection ratio and
without considering pipe length corrections)
Tmp H Outdoor conditions in heating (dry bulb temp. / RH)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
COP COP at nominal conditions for standard efficiency series (nominal temperatures, 100% connection ratio and
without considering pipe length corrections)
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 5
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC EER (*) Tmp H HC Rq HC COP (*)
% °C BTU/h BTU/h BTU/h/W °C BTU/h BTU/h W/W
Out 1 RXYQ168TATJU 114 30.0 145664 138217 12.8 0.0 / 50% 121533 4.5
Out 2 RXYQ312TATJU 117 30.0 272110 245684 13.5 0.0 / 50% 231503 4.6
Out 3 RXYQ168TATJU 114 30.0 159559 130439 12.8 0.0 / 50% 125669 4.5

(*) The EER and COP values are calculated at nominal conditions: nominal temperatures, 100% connection ratio
and without considering pipe length corrections.

Name Model Piping Refrigerant


m Type Bse Refr Ex Refr
kg kg
Out 1 RXYQ168TATJU 51.2 R410A 7.8 14.8
Out 2 RXYQ312TATJU 52.5 R410A 16.0 23.4
Out 3 RXYQ168TATJU 7.5 R410A 7.8 n/a

Name Model PS MCA WxHxD Wght


A mm kg
Out 1 RXYQ168TATJU 230V 3ph 55.1 1242×1694×767 315
Out 2 RXYQ312TATJU 230V 3ph
× RXYQ168TATJU 55.1 1242×1694×767 315
× RXYQ144TATJU 55.1 1242×1694×767 315
Out 3 RXYQ168TATJU 230V 3ph 55.1 1242×1694×767 315

Sufficient distance should be respected between the modules according to the service & operation space rules as
mentioned in the databook.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 6
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

4.1. Piping Out 1


Out 1
RXYQ168TATJU

42.0m 2.0m 1.2m 4.5m


⅝"×1⅛" ½"×1⅛" ⅜"×⅞" ⅜"×⅝"
KHRP26M72TU KHRP26M72TU KHRP26A33T

OF-1-01
FXMQ100PAVE
1.9m
⅜"×⅝"

OF-1-02
FXMQ140PAVE
1.5m
⅜"×⅝"

OF-1-03
FXMQ100PAVE
2.5m 2.5m
⅜"×¾" ⅜"×⅝"
KHRP26A22T

OF-1-04A
FXMQ80PAVE
2.5m
⅜"×⅝"

OF-1-04B
FXMQ80PAVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 7
4.2. Piping Out 2
Out 2
RXYQ312TATJU
RXYQ168TATJU RXYQ144TATJU

⅝"×1⅛" ½"×1⅛"

BHFP22P100U

35.0m 1.0m 1.7m 1.3m 1.3m


¾"×1⅜" ½"×1⅛" ⅜"×⅞" ⅜"×⅞" ⅜"×⅝"
KHRP26M73TU KHRP26M72TU KHRP26A33T KHRP26A33T

OF-X-01A
FXMQ100PAVE
1.3m
⅜"×⅝"

OF-X-01B
FXMQ100PAVE
1.3m
⅜"×⅝"

OF-X-02
FXMQ80PAVE
1.5m
⅜"×⅝"

OF-X-03
FXMQ100PAVE
2.2m 1.6m 1.6m
⅝"×1⅛" ⅜"×⅞" ⅜"×⅝"
KHRP26M72TU KHRP26A33T

OF-X-04A
FXMQ100PAVE
1.6m
⅜"×⅝"

OF-X-04B
FXMQ100PAVE
7.1m 2.0m
½"×1⅛" ⅜"×⅝"
KHRP26M72TU

OF-X-05
FXMQ125PAVE
2.1m 1.3m
⅜"×⅞" ⅜"×⅝"
KHRP26A33T

OF-X-06
FXMQ63PAVE
1.9m 1.3m
⅜"×¾" ⅜"×⅝"
KHRP26A22T

OF-X-07
FXMQ63PAVE
1.7m
⅜"×⅝"

OF-X-08
FXMQ125PAVE

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 8
4.3. Piping Out 3
Out 3
RXYQ168TATJU

⅝"×1⅛" ⅜"×⅝"
KHRP26M72TU

LOCAL 1 A
FXMQ125PAVE

½"×1⅛" ⅜"×⅝"
KHRP26M72TU

LOCAL 1B
FXMQ125PAVE

⅜"×⅞" ⅜"×⅝"
KHRP26A33T

LOCAL 2A
FXMQ125PAVE

⅜"×⅝"

LOCAL 2B
FXMQ125PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 9
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

5.1. Wiring Out 1


P1,P2
Out 1 OF-1-01 BRC1E63
RXYQ168TATJU FXMQ100PAVE
IN F1,F2 F1,F2
L1,L2,L3 55.1A 3ph L, N 2.9A 1ph
P1,P2
OF-1-02 BRC1E63
FXMQ140PAVE
F1,F2
L, N 3.4A 1ph
P1,P2
OF-1-03 BRC1E63
FXMQ100PAVE
F1,F2
L, N 2.9A 1ph
P1,P2
OF-1-04A BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph
P1,P2
OF-1-04B BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 10
5.2. Wiring Out 2
P1,P2
Out 2 BRC1E63
OF-X-01A
RXYQ312TATJU
FXMQ100PAVE
IN F1,F2 F1,F2
RXYQ168TATJU L, N 2.9A 1ph
Q1,Q2 L1,L2,L3 P1,P2
55.1A 3ph OF-X-01B BRC1E63
FXMQ100PAVE
RXYQ144TATJU F1,F2
Q1,Q2 L1,L2,L3 L, N 2.9A 1ph
55.1A 3ph P1,P2
OF-X-02 BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph
P1,P2
OF-X-03 BRC1E63
FXMQ100PAVE
F1,F2
L, N 2.9A 1ph
P1,P2
OF-X-04A BRC1E63
FXMQ100PAVE
F1,F2
L, N 2.9A 1ph
P1,P2
OF-X-04B BRC1E63
FXMQ100PAVE
F1,F2
L, N 2.9A 1ph
P1,P2
OF-X-05 BRC1E63
FXMQ125PAVE
F1,F2
L, N 3.4A 1ph
P1,P2
OF-X-06 BRC1E63
FXMQ63PAVE
F1,F2
L, N 1.8A 1ph
P1,P2
OF-X-07 BRC1E63
FXMQ63PAVE
F1,F2
L, N 1.8A 1ph
P1,P2
OF-X-08 BRC1E63
FXMQ125PAVE
F1,F2
L, N 3.4A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 11
5.3. Wiring Out 3
P1,P2
Out 3 LOCAL 1 A BRC1E63
RXYQ168TATJU FXMQ125PAVE
IN F1,F2 F1,F2
L1,L2,L3 55.1A 3ph L, N 3.4A 1ph
P1,P2
LOCAL 1B BRC1E63
FXMQ125PAVE
F1,F2
L, N 3.4A 1ph
P1,P2
LOCAL 2A BRC1E63
FXMQ125PAVE
F1,F2
L, N 3.4A 1ph
P1,P2
LOCAL 2B BRC1E63
FXMQ125PAVE
F1,F2
L, N 3.4A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 12
6. Device Options
6.1. Outdoor Unit Options
Model Description Used by
BHFP22P100U Outdoor unit multi connection piping kit Out 2 [RXYQ312TATJU]

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 13