You are on page 1of 6

Main Contractor: Owner: Consultant: Project Name:

Toshka 3 (220/66/22 KV) GIS S/S


Date: Page:
SEP, 2021 1 of 6
Vendor: Document Number:
Sieyuan

Title.

CT INSULATION RESISTANCE TEST

Test Report

for

66 KV GIS CT TEST

Company MADKOUR WITNESSED BY (EETC)


Name
Signature
Date
Main Contractor: Owner: Consultant: Project Name:
Toshka 3 (220/66/22 KV) GIS S/S
Date: Page:
SEP, 2021 2 of 6
Vendor: Document Number:
Sieyuan

Title.

CT INSULATION RESISTANCE TEST

 CT DATA
Bay No.: D07 No. of cores: 4 Manufacturer: Sieyuan

Core 1 Ratio: 1000-2000/1 Class: 5P30


Core 2 Ratio: 1000-2000/1 Class: 5P30
Core 3 Ratio: 1000-2000/1 Class: CLX
Core 4 Ratio: 1000-2000/1 Class: 0.5M5

Insulation ResistanceTest:

Test procedure:
* APPLIED VOLTAGE 5 KV (PRIM – E).
* APPLIED VOLTAGE 2.5 KV (PRIM – SEC).
* APPLIED VOLTAGE 1 KV (SEC – E) and (SEC TO SEC).
The test done according to the FAT procedure and results referred to the FAT criteria

A) CORE IT SELF:

R S T
CORES
Pri -Sec Sec - E Pri -Sec Sec - E Pri -Sec Sec - E
CORE 1
CORE 2
CORE 3

Company MADKOUR WITNESSED BY (EETC)


Name
Signature
Date
Main Contractor: Owner: Consultant: Project Name:
Toshka 3 (220/66/22 KV) GIS S/S
Date: Page:
SEP, 2021 3 of 6
Vendor: Document Number:
Sieyuan

Title.

CT INSULATION RESISTANCE TEST

B) SEC TO SEC:

Phase
R S T
Core
CORE 1 -CORE 2
CORE 2 - CORE 3
CORE 3 - CORE 1

C) PRIM TO EARTH:

R -E S-E T-E

CT Analyzer Test:

Test Procedure:
Company MADKOUR WITNESSED BY (EETC)
Name
Signature
Date
Main Contractor: Owner: Consultant: Project Name:
Toshka 3 (220/66/22 KV) GIS S/S
Date: Page:
SEP, 2021 4 of 6
Vendor: Document Number:
Sieyuan

Title.

CT INSULATION RESISTANCE TEST

 The CT will be completely tested by CT analyzer.


 Connect the CT to the testing kit (primary and secondary)
 Choose the below mentioned tests.
 Winding resistance
 Turns ratio
 Excitation curve
 Polarity
 Burden
 Run the test and print the test report from the testing kit.

1.1.WINDING RESISTANCE:
Ambient temp: o
C

Primary Winding
Phase
at C
o
at 75 oC
N

Secondary Winding 1
Phase
at o
C at 75 oC
n
R75 = Rt (234.5 +75) / (234.5 + t)
Where,
t is ambient temp,
Rt is resistance at ambient temp
Criteria:

1.2.POLARITY TEST:
Phase N
Core 1S1 - 1S2
  

Company MADKOUR WITNESSED BY (EETC)


Name
Signature
Date
Main Contractor: Owner: Consultant: Project Name:
Toshka 3 (220/66/22 KV) GIS S/S
Date: Page:
SEP, 2021 5 of 6
Vendor: Document Number:
Sieyuan

Title.

CT INSULATION RESISTANCE TEST

1.3.RATIO TEST :

Core Primary current (A) Secondary current (A) Expected current % error
S1 – S2

Criteria:
2. SINGLE POINT EARTH TEST:

Core no Function T.b.no Single point earthing check

S1 – s2

3. CHECK SHORT & ISOLATED LINK FOR PROPER FUNCTION:

Core no Function Confirm test for short and isolated check


S1 – s2

4. MAG - CURVE:

Locatio
Function:       CT#  
n
Make:   Phase     Ratio  
V kp:   SL #     Class  

Company MADKOUR WITNESSED BY (EETC)


Name
Signature
Date
Main Contractor: Owner: Consultant: Project Name:
Toshka 3 (220/66/22 KV) GIS S/S
Date: Page:
SEP, 2021 6 of 6
Vendor: Document Number:
Sieyuan

Title.

CT INSULATION RESISTANCE TEST

I mag   SL #     Burden  
Earthed   SL #     R ct  

Ter.    

Sl.# V I mA  
1      
2      
V volts

3      
4      
5      
6      
7      
8     I mA
 
Vkp      
 
Criteria:

Company MADKOUR WITNESSED BY (EETC)